3.

Calcular los TAP y considerar que las protecciones diferenciales ubicadas en los
transformadores y en la barra 3 no operan en condiciones normales.
 Para el Transformador 1

S 100 MVA 900


IP= = =836,7395 A=¿=¿
√ 3∗V √3∗69 kV 5

S 100 MVA
I S= = =418,3697 A
√ 3∗V √ 3∗138 kV
√ 3∗836,7395 = 418,3697
900 X
5 5

√ 3∗4183,6975 = 2091,8485
900 X

3 00
X =259,8075=¿=¿
5

418,3697
I P= =6,9728
3 00
5

836,7395
I S= =4,6985
9 00
5

6,9728 Y
=
4,6985 5

6,9728∗5
Y=
4,6985

Y =7,4202
Derivación (5−7,4202 ) ≈5−8
Datos:
900
TC A =
5
3 00
TC B=
5
m=35 %
I arranque=0 , 3

Lado de baja
418,3697∗5
I B=
3 00
I B=6,9728 A
Ia=6,9728 ∠ 150° A−6,9728∠270 ° A
Ia=12,0772∠120 ° A
Ib=6,9728 ∠ 30° A−6,9728∠ 150 ° A
Ib=12,0772∠0 ° A
Ic=6,9728 ∠270 ° A−6,9728 ∠ 150 ° A
Ic=12,0772 ∠−60° A
Lado de alta
836,7395∗5
I A=
900
I =4,6485 A

IA=4,6485∠−30 ° A+ ∠150° A
IA=4,6485∠120 ° A
IB=4,6485 ∠−150° A+∠ 150 ° A
IB=4,6485 ∠ 0 ° A

IC=4,6485∠ 90° A +∠150 ° A


IC=4 , 6485 ∠−60 ° A

Calculo del TAP

12,0772−→5
4,6485−→ X
4,6485∗5
x=
12,0772
x=1,924 4
TAP TC=1−2

Usamos el TAP=1
12,0772∗1
Id=¿ 4,6485∠120 ° A− ∠ 120 ° A∨¿
5
Id=2,2330 A
12,0772∗1
4,6485∠ 120 ° A + ∠120 ° A
5
I res =
2
I res =3,5319 A
Id min=m∗I res + I arr
Id min=¿
Id min=1,5361 A
Id > Id min
2,2330>1,5361=¿=¿ Opera
 Para el Transformador 2

S 100 MVA 5 00
IP= = =418,3697 A=¿=¿
√ 3∗V √3∗138 kV 5

S 100 MVA
I S= = =836,7395 A
√ 3∗V √ 3∗138 kV
√ 3∗418,3697 = 836,7395
5 00 X
5 5

√ 3∗2091,8485 = 4183,6975
5 00 X

6 00
X =577,3503=¿=¿
5
418,3697
I P= =4,1836
5 00
5
836,7395
I S= =6,9728
6 00
5

6,9728 Y
=
4,1836 5
6,9728∗5
Y=
4,1836
Y =8,3334
Derivación (5−8,3334 ) ≈ 5−9
Datos:
5 00
TC A =
5
6 00
TC B=
5
m=35 %
I arranque=0 , 3

Lado de baja
836,7395∗5
I B=
6 00
I B=6,9728 A

Ia=6,9728 ∠ 150° A−6,9728∠270 ° A


Ia=12,0772∠120 ° A
Ib=6,9728 ∠ 30° A−6,9728∠ 150 ° A
Ib=12,0772∠0 ° A
Ic=6,9728 ∠270 ° A−6,9728 ∠ 150 ° A
Ic=12,0772 ∠−60° A

Lado de alta
4,1836∗5
I A=
5 00
I =4,1836 A

IA=4,1836∠−30 ° A +∠150° A
IA=4,1836∠ 120 ° A
IB=4,1836 ∠−150 ° A+∠150 ° A
IB=4,1836 ∠ 0 ° A

IC=4,1836∠ 90° A+∠150 ° A


IC=4,1836∠−60 ° A

Calculo del TAP


12,0772−→5
4,1836−→ X
4,1836∗5
X=
12,0772
X =1,7320
TAP TC=1−2

Usamos el TAP=1
12,0772∗1
Id=¿ 4,1836 ∠ 120° A− ∠ 120° A∨¿
5
Id=1,7681 A
12,0772∗1
4,1836 ∠120 ° A + ∠ 120 ° A
5
I res =
2
I res =3,2995 A
Id min=m∗I res + I arr
Id min=¿
Id min=1,4548 A
Id > Id min
1,7681>1,4548=¿=¿ Opera

 Para el Transformador 3

Ya que tiene los mismos datos del transformador 2


Vp=138 kV
Vs=69 kV
S=100 MVA
El resultado es igual al del transformador 2