MATERIAL : AAAC
TEMPERATURA °C : 40
FRECUENCIA Hz : 60
a °C/°C : 0.0036
CONSTANTE DE INDUCCIÓN (mo) H/Km : 0.00126
PERMEABILIDAD MAGNÉTICA RELATIVA AL CONDUC. : 1
DISTANCIA MEDIA GEOMÉTRICA m : 0.5040 :
RADIO EQUIVALENTE DEL CONDUC. : 0.0033
CALCULO ELECTRICO
CONDUCTOR AAAC IMPEDANCIA DE LA SECUENCIA POSITIVA IMPEDANCIA DE LA SECUENCIA
SECCIÓN DIÁM. K' R20°C R(T) X(+) Z(+) R20°C
mm2 mm. W/ K W/K m W/K m W/ K m W/ K m
16 5.10 0.726 m
1.80 1.932 0.389 1.971 1.80
25 6.42 0.726 1.18 1.266 0.372 1.319 1.18
35 7.56 0.726 0.83 0.892 0.359 0.962 0.83
50 8.90 0.757 0.60 0.638 0.344 0.725 0.60
70 10.70 0.757 0.60 0.638 0.330 0.718 0.60
95 12.60 0.757 0.31 0.331 0.318 0.459 0.31
120 14.25 0.788 0.25 0.264 0.305 0.404 0.25
150 15.75 0.788 0.20 0.210 0.298 0.365 0.20
185 17.64 0.788 0.16 0.170 0.289 0.336 0.16
240 20.25 0.819 0.12 0.128 0.276 0.304 0.12
300 22.68 0.819 0.10 0.104 0.268 0.287 0.10
MPEDANCIA DE LA SECUENCIA NEGATIVA IMPEDANCIA DE LA SECUENCIA CERO
R(T) X(+) Z(+) R20°C R(T) X(o) Z(o)
W/K m W/K m W/K m W/K m W/K m W/K m W/ K m
1.932 0.39 1.971 1.80 1.932 1.46 2.419
1.266 0.37 1.320 1.18 1.266 1.40 1.891
0.892 0.360 0.962 0.83 0.892 1.37 1.633
0.638 0.34 0.725 0.60 0.638 1.33 1.476
0.638 0.33 0.718 0.60 0.638 1.29 1.439
0.331 0.32 0.459 0.31 0.331 1.25 1.296
0.264 0.31 0.404 0.25 0.264 1.23 1.254
0.210 0.30 0.365 0.20 0.210 1.20 1.221
0.170 0.29 0.336 0.16 0.170 1.18 1.190
0.128 0.28 0.304 0.12 0.129 1.15 1.154
0.104 0.27 0.287 0.10 0.104 1.12 1.127
TABLA DE TEMPLADO
Proyecto : EQUIPAMIENTO DE LA LÍNEA DE TRANSMISIÓN EN 33 KV TRAMO "S.E. POLOBAYA - S.E.
PUQUINA - S.E. OMATE - S.E. UBINAS" Y LINEA PRIMARIA EN 22.9 KV TRAMO "OMATE -
CALACOA - TITIRE - ARUNTAYA" "UBINAS - ICHUÑA", PROVINCIA GENERAL SANCHEZ
CERRO, REGION MOQUEGUA
Descripción : LINEA DE TRANSMISION POLOBAYA DESDE LA EST. Nº01 HASTA EST. Nº11
Conductor : AAAC. 120 mm².
FLECHA EN METROS
Longitud del Temp. (ºC.) 0 5 10 15 20 25 30
Vano en (m.) s (Kg/mm².) 9.2630 8.7364 8.0515 8.7364 8.7364 6.0069 8.0515
438 f(m) 14.4328 15.3027 16.6045 15.3027 15.3027 22.2563 16.6045
270 f(m) 5.4844 5.8150 16.6045 5.8150 5.8150 8.4573 6.3096
470 f(m) 16.6187 17.6204 16.6045 17.6204 17.6204 25.6271 19.1194
186 f(m) 2.6027 2.7596 16.6045 2.7596 2.7596 4.0136 2.9944
222 f(m) 3.7077 3.9312 16.6045 3.9312 3.9312 5.7176 4.2656
140 f(m) 1.4745 1.5634 16.6045 1.5634 1.5634 2.2738 1.6964
236 f(m) 4.1901 4.4427 16.6045 4.4427 4.4427 6.4614 4.8206
194 f(m) 2.8314 3.0021 16.6045 3.0021 3.0021 4.3662 3.2575
206 f(m) 3.1925 3.3850 16.6045 3.3850 3.3850 4.9231 3.6729
196 f(m) 2.8901 3.0643 16.6045 3.0643 3.0643 4.4567 3.3250
CIMENTACIÓN DE ESTRUCTURAS
POSTE SIN RETENIDA
ESPECIFICACIONES Dp
Tipo 13/300
FE
Longitud total L = 13.00 m
Diámetro en la punta Dp = 0.18 m
Diámetro en la base Db = 0.380 m
Diámetro de empotramiento De = 0.35 m
Profundidad de cimentación he = 1.80 m
Longitud Libre del poste hl = 11.20 m
Punto aplicación de fuerza equivalente Lo = 11.10 m
hl Lo
Fuerza Horizontal
(considerando la Roruta del Conductor 35 mm2) Fe = 7,000.00 N L
Peso del poste Wp = 9,310.00 N
Peso Total de Conductores Wc = 1507 N
Peso extra We = 980.00 N
da
db
Fc
F
L
l
Fpv
Z
Ht
SELECCIÓN DE POSTES DIAGRAMA DE LONGITUDES
He
CALCULO DE RESISTENCIA DE PUESTA A TIERRA CON CEMENTO CONDUCTIVO
Resultados
0.0663
140.82
0.244
0.1697
9.34 Ω