SmartLock Installation Instructions

The SmartLock improves the security of ACTSmart2 installations by allowing the installer to
locate the lock control relay inside a secure area. The SmartLock learns an ID code from the
ACTSmart2 and only operates its' relay when a valid card or PIN is presented to the ACTSmart2.
Since the SmartLock is inside a secure area, an attacker has no access to the lock control relay.

Installation
The normally open door release button should be connected to the SmartLock. When the
input is activated, the door will open for the Door Relay Time programmed into the ACTSmart.
ACT recommends installing the SmartLock inside the Power Supply Unit. Some PSUs can accomodate
the Smartlock directly, otherwise drill holes to suit the SmartLock, (5mm drill bit required).
For a Maglock, two fused outputs are required - one fused output for the ACTSmart2 and another for the
Smartlock and Maglock. This prevents a short from +12V to 0V on the ACTSmart2 side of the door from
deenergising the Maglock. Ensure that the Door Release wires are not accessible to an attacker.
The Data line from the SmartLock to the ACTSmart2 must be less than 30m.

Programming
1. Connect the ACTSmart2 and the SmartLock as in the diagram below and power up.
2. The red LED on the SmartLock will be on steady.
3. Program one of the AUX I/Os on the Smart2 for SmartLock operation. For AUX I/O 2 enter
followed by the programming code (default code is 9999) and 5211 . PO O
4. The red LED on the SmartLock flashes every second.
5. Press and hold the Programming button until the LED flashes rapidly. The SmartLock is now
programmed.
6. Remember to change the other AUX I/O and the Programmable Input from Door Release Button.
To set the Programmable Input to Door Contact enter
To set AUX I/O 1 to Door Alarm enter O
followed by the programming code and 5108 O
then the programming code and 500
.
.
PO PO
7. If the ACTSmart2 unit is ever replaced or defaulted, then repeat this procedure.
Power
ACTSmart2 Unit Supply Unit
Red LED Programming
Button
+12V Fuse 1 0V

+12V Fuse 2
125V
+

1A
RO
N

5A
5A
O
RN
OM
12-24V DC/AC
B
5A/250V ~AC
12V = DC

0V
A
Aux I/O 2 N/O
Programmable Input
COMM 12-24V DC/AC
Aux I/O 1 N/C
Tamper 0V
Push Button
N/O
Door
5A/250V ~AC

0V COMM
12V = DC

Contact Max. 30m


Data N/C

SmartLock
Door Release Button
This illustration shows wiring Important!
for a normally energised lock (eg. maglock). Always Place Varistor
If a normally de-energised lock (doorstrike) is Across Lock Terminals
required, use the N/O relay contact.

Note: A Break-Glass Unit (not shown) is required for Maglock installations.

Unit 8, UTallaght
nit 8 IDA BBusiness
us ines s Park,Centre, Whitestown,
W hites town, Tallaght,
T allaght, Dublin Dublin 24, Ireland.
24, Ireland.
Telephone: 353 1 462 2585. Telefax: 353 1 462 2587. E-mail: sales@accesscontrol.ie Web: www.accesscontrol.ie
T elephone: 353 1 462 2585. T elefax: 353 1 462 2587. E -m ail: s ales @ actrl.com W eb: www.actrl.com

30-00030

También podría gustarte