Valve data
Tag no. farris demo 7 Serial no.
Make Process fluid
Type ?Orifice
Rating class (in-out) Notes
Material
Size
Test parameters
?Expected set pressure 10.0 bar Tollerance as per ASME sec. 1
?Line pressure 8.0 bar Load cell serial O00895
Load cell calibration date 23-10-2018
Test results
Average found set pressure 10.1 bar
remark
Inspected by Tested by
?Name ?Name
Date Date
Signature Signature
Test 1
Found set pressure 10.2 bar
Pulling force 126 N
?Line pressure 8.0 bar
[%] [bar] [mm] [N]
100 10 1.0 200
90 9 0.9 180
80 8 0.8 160
70 7 0.7 140
60 6 0.6 120
50 5 0.5 100
40 4 0.4 80
30 3 0.3 60
20 2 0.2 40
10 1 0.1 20
0 0 0.0 0
Test 2
Found set pressure 10.0 bar
Pulling force 118 N
?Line pressure 8.0 bar
[%] [bar] [mm] [N]
100 10 1.0 200
90 9 0.9 180
80 8 0.8 160
70 7 0.7 140
60 6 0.6 120
50 5 0.5 100
40 4 0.4 80
30 3 0.3 60
20 2 0.2 40
10 1 0.1 20
0 0 0.0 0
Test 3
Found set pressure 10.0 bar
Pulling force 117 N