Está en la página 1de 2

4) 1400/480 V, Y-∆, 3∆ DE 100 KVA

Prueba C.A↓: (∆)

5.5 A
|Yex|= =0.025 v
220

14400 v 2
Zbase,p= =6 9 1.2 Ω
300 KVA

277 2
Zbase,s= =0.767 Ω
100 KVA

3600 w
θ=−cos −1
( 3
220∗5.51 )
=−7.37 °
→Yex=0.025-3.21*10-3j

1
Rn= =40 Ω→Rn,pu=40/0.767=52.15 pu
0.025
1
Xm= =311.53 Ω →Xm,pu=311.53/0.767=406.17 pu
3.21∗10−3
Prueba C.C ↑(Y):

3 0 00 w
|Zeq|: 510/12.6=40.48Ω;
θ=−cos−1 ( 3
510∗12.6 )=81.05 °
→Zeq=6.29+39.98j

Req=6.29Ω→Req,pu=6.29/691.2=0.0091 pu

Xeq=39.98→Xeq,pu=39.98/691.2=0.0578 pu

PU con FP=0.8(-) θ=−36.87

Req=0.0091 Xeq=0.0578j2

Rn=52.15 Xm=406.17

a) Vp= 1∟0º + (1∟-36.87)(0.0091+0.578j)


Vp=1.043∟2.24
b) RV=(1.043-1)/1=4.3%
c) Pout= (1)(1)(0.8)=0.8
Pout= (1)(1)(0.8)(0.5)=0.4
Pout= (1)(1)(0.8)(0.75)=0.6
Pout= (1)(1)(0.8)(1.25)=1
Pcu=12*0.0091=0.0091
Pcore=1.0432/52.15=0.021

N=Pout/R*100
N1=0.8/0.8701=96.37%
N2=0.4/0.4304=93%
N3=0.6/0.6301=95.12%
d) Ref. al lado de alta

Req=6.29 Xeq=39.45j

Rn=35.58 Xm=280.74 K

Ref. a lado de baja

Req=0.007 Xeq=0.0443j

Rn=39.23 Xeq=311.53j

También podría gustarte