TABLA 4 - XVI

CAPACIDAD DE CORRIENTE PARA UN SISTEMA DE CABLES


UNIPOLARES CON AISLAMIENTO TERMOPLASTICO

Por ejemplo : NYY, NYSY

TABLA A1 - CAPACIDAD DE CORRIENTE PARA UN SISTEMA DE CAB


UNIPOLARES CON AISLAMIENTO TERMOPLASTICO
Temperatura Ambiente Corriente Alterna
Temperatura Admisibl cable sin armadura
SECCIÓN EN TUBO A LA VISTA
NOMINAL
NYY THW THW-90 TW N2XH NH-80 NH-90 NYY THW-90 TW
(mm2) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)

1.5
2.5 19.5 20 27 18 38 32 37
4 26 27 34 25 55 31 34 43 45 37
6 35 38 44 35 68 39 44 54 61 52
10 46 50 62 46 95 51 62 74 88 78
16 63 75 85 62 125 68 85 98 124 105
25 87 95 107 80 160 88 107 130 158 140
35 113 120 135 100 195 110 135 161 197 175
50 138 145 160 125 230 138 160 196 245 220
70 168 180 203 150 275 165 203 250 307 270
95 213 215 242 180 330 198 242 306 375 330
120 258 245 279 210 380 231 279 356 437 380
150 299 285 318 240 410 264 318 408 501 445
185 344 320 361 275 450 303 361 470 586 515
240 392 375 406 320 525 352 406 562 654 595
300 461 420 462 355 600 391 462 646 767 690
400 523 490 541 430 680 778 908 825
500 626 580 603 490 700 895 1037 950

LSOH-80 <> NH-80


D DE CORRIENTE PARA UN SISTEMA DE CABLES
CON AISLAMIENTO TERMOPLASTICO
Corriente Alterna
cable sin armadura
A LA VISTA 2 cond. 3 y 4 cond.
(Bipolar) (Tripolar)
N2XH NH-80 NH-90
(Tetrapolar)
(A) (A) (A) (A) (A)

19.5 17.5
38 26 24
55 35 45 35 32
65 50 61
90 74 88 46 41
125 99 124 63 57
160 132 158 85 76
200 165 197
240 204 245 112 101
305 253 307 138 125
375 303 375 168 151
435 352 437
510 413 501 213 192
575 473 586 258 232
690 528 654 299 269
790 633 767
955 344 309
1100 392 353
TABLA 3 - X

CONDUCTOR DE PUESTA A TIERRA PARA SISTEMAS DE


CORRIENTE ALTERNA

SECCION NOMINAL DEL CONDUCTOR SECCION NOMINAL DEL MAXIMA


MAYOR DE LA ACOMETIDA O SU CONDUCTOR DE CAPACIDAD DE
EQUIVALENTE PARA CONDUCTORES PUESTA A TIERRA CORRIENTE
EN PARALELO (mm2) (COBRE) mm2 (A)

35 ó menor sección 10 138


50 16 168
70 25 213
95 a 185 35 392
240 a 300 50 523
400 a 500 70 713
Más de 500 95

CODIGO NACIONAL DE ELECTRICIDAD SISTEMA DE


UTILIZACION - TOMO V
LISTA DE INTERRUPTORES
COMERCIALES

I diseño Interrrup.
(A) I (A)
0.1 20
20.2 32
32.2 40
40.5 50
52 63
65 80
83 100
103 125
128 150
152 160
162 175
178 200
203 250
255 300
305 400
405 630
640 800
810 1000
1020 1250
1270 1600
1620 2000
2050 2500
2550 3200
3250 4000
MOTORES TRIFASICOS

IT KW CosØ Eficiencia
%
1 0.25 0.25 0.7 62
2 0.35 0.35 0.72 64
3 0.55 0.55 0.75 69
4 0.75 0.75 0.8 74
5 1.1 1.1 0.83 77
6 1.5 1.5 0.83 78
7 2.2 2.2 0.83 81
8 3 3 0.84 81
9 4 4 0.84 82
10 5.5 5.5 0.85 83
11 7.5 7.5 0.86 85
12 11 11 0.86 87
13 15 15 0.86 87
14 18.5 18.5 0.86 88
15 22 22 0.87 89
16 30 30 0.87 90
17 37 37 0.87 90
18 45 45 0.88 91
19 60 60 0.88 91
20 75 75 0.88 91
21 90 90 0.88 92
22 110 110 0.88 92
23 132 132 0.88 92
24 160 160 0.88 93
25 200 200 0.88 93
26 250 250 0.88 93
27 315 315 0.88 93
28 400 400 0.89 96
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)

TABLERO FUERZA TLC-S.1 / NIVEL -12.5 NPT


C-1 BANCO 1 380 3Ø 110 100 11.0 1.00 11.0 0.80 20.9 26.1 3x
C-2 BANCO 2 380 3Ø 102 100 10.2 1.00 10.2 0.80 19.4 24.2 3x
C-3 BANCO 3 380 3Ø 174 100 17.4 1.00 17.4 0.80 33.0 41.3 3x
C-4 BANCO 4 380 3Ø 163 100 16.3 1.00 16.3 0.80 31.0 38.7 3x
54.9 54.9

TABLERO FUERZA TLC-S.2 / NIVEL -12.5 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)


C-1 LS-01 380 1Ø 17.6 50 0.9 1.00 0.9 0.80 2.9 3.6 1x
C-2 LS-02 380 1Ø 15.1 50 0.8 1.00 0.8 0.80 2.5 3.1 1x
C-3 LS-03 380 1Ø 33 50 1.7 1.00 1.7 0.80 5.4 6.8 1x
C-4 LS-04 380 1Ø 33.6 50 1.7 1.00 1.7 0.80 5.5 6.9 1x
C-5 LS-05 380 3Ø 146.6 50 7.3 1.00 7.3 0.80 13.9 17.4 3x
C-6 LS-06 380 1Ø 54.5 50 2.7 1.00 2.7 0.80 9.0 11.2 1x
C-7 LS-07 380 1Ø 35.6 50 1.8 1.00 1.8 0.80 5.9 7.3 1x
C-8 LS-08 380 1Ø 48.7 50 2.4 1.00 2.4 0.80 8.0 10.0 1x
C-9 LS-09 380 1Ø 12 50 0.6 1.00 0.6 0.80 2.0 2.5 1x
19.8 19.8

TABLERO FUERZA TLC-1.1 / NIVEL -12.5 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)


C-1 L101 380 1Ø 42 50 2.1 1.00 2.1 0.80 6.9 8.6 1x
C-2 L102 380 1Ø 36 50 1.8 1.00 1.8 0.80 5.9 7.4 1x
C-3 L103 380 3Ø 114 50 5.7 1.00 5.7 0.80 10.8 13.5 3x
C-4 L104 380 1Ø 12.3 50 0.6 1.00 0.6 0.80 2.0 2.5 1x
C-5 L1 380 3Ø 340 50 17.0 1.00 17.0 0.80 32.3 40.4 3x
C-6 L105 380 1Ø 35 50 1.8 1.00 1.8 0.80 5.8 7.2 1x
C-7 L106 380 3Ø 92 50 4.6 1.00 4.6 0.80 8.7 10.9 3x
C-8 L107 380 3Ø 77 50 3.9 1.00 3.9 0.80 7.3 9.1 3x
C-9 L117 380 3Ø 130 50 6.5 1.00 6.5 0.80 12.3 15.4 3x
C-10 L118 380 3Ø 104 50 5.2 1.00 5.2 0.80 9.9 12.3 3x
C-11 L119 380 3Ø 67.4 50 3.4 1.00 3.4 0.80 6.4 8.0 3x
C-12 L120 380 3Ø 67.1 50 3.4 1.00 3.4 0.80 6.4 8.0 3x
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)


C-13 L121 380 3Ø 189 50 9.5 1.00 9.5 0.80 17.9 22.4 3x
C-14 L122 380 3Ø 137.4 50 6.9 1.00 6.9 0.80 13.0 16.3 3x
C-15 L123 380 1Ø 53.8 50 2.7 1.00 2.7 0.80 8.8 11.1 1x
74.9 74.9
TABLERO FUERZA TLC-1.2 / NIVEL -12.5 NPT
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)


C-1 L109 380 3Ø 126 50 6.3 1.00 6.3 0.80 12.0 15.0 3x
C-2 L110 380 1Ø 55 50 2.8 1.00 2.8 0.80 9.0 11.3 1x
C-3 L111 380 1Ø 45 50 2.3 1.00 2.3 0.80 7.4 9.3 1x
C-4 L112 380 1Ø 47 50 2.4 1.00 2.4 0.80 7.7 9.7 1x
C-5 L113 380 3Ø 62 50 3.1 1.00 3.1 0.80 5.9 7.4 3x
C-6 L114 380 3Ø 58 50 2.9 1.00 2.9 0.80 5.5 6.9 3x
C-7 L116 380 3Ø 405 50 20.3 1.00 20.3 0.80 38.5 48.1 3x
C-8 L124 380 3Ø 70.3 50 3.5 1.00 3.5 0.80 6.7 8.3 3x
C-9 L125 380 3Ø 127 50 6.4 1.00 6.4 0.80 12.1 15.1 3x
C-10 L126 380 3Ø 59 50 3.0 1.00 3.0 0.80 5.6 7.0 3x
C-11 L127 380 3Ø 98 50 4.9 1.00 4.9 0.80 9.3 11.6 3x
C-12 L128 380 3Ø 152 50 7.6 1.00 7.6 0.80 14.4 18.0 3x
C-13 L129 380 3Ø 85 50 4.3 1.00 4.3 0.80 8.1 10.1 3x
C-14 L130 380 1Ø 37 50 1.9 1.00 1.9 0.80 6.1 7.6 1x
71.3 71.3
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)

TABLERO FUERZA TLC-1.3 / NIVEL -6.00 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)


C-1 Rest 1 380 3Ø 168 180 30.2 1.00 30.2 0.80 57.4 71.8 3x
C-2 Rest 2 380 3Ø 352 180 63.4 1.00 63.4 0.80 120.3 150.4 3x
C-3 Rest 3 380 3Ø 170 180 30.6 1.00 30.6 0.80 58.1 72.6 3x
C-4 Rest 4 380 3Ø 182 180 32.8 1.00 32.8 0.80 62.2 77.8 3x
C-5 Rest 5 380 3Ø 196 180 35.3 1.00 35.3 0.80 67.0 83.8 3x
192.2 192.2

TABLERO FUERZA TLC-2.1 / NIVEL 0.00 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)


C-1 L 201 380 3Ø 179 50 9.0 1.00 9.0 0.80 17.0 21.2 3x
C-2 L 202 220 1Ø 77 50 3.9 1.00 3.9 0.80 21.9 27.3 1x
C-3 L 203 220 1Ø 54 50 2.7 1.00 2.7 0.80 15.3 19.2 1x
C-4 L 204 220 1Ø 50 50 2.5 1.00 2.5 0.80 14.2 17.8 1x
C-5 L 205 380 3Ø 86 50 4.3 1.00 4.3 0.80 8.2 10.2 3x
C-6 L 206 220 1Ø 30 50 1.5 1.00 1.5 0.80 8.5 10.7 1x
C-7 L 207 220 1Ø 33 50 1.7 1.00 1.7 0.80 9.4 11.7 1x
C-8 L 208 380 3Ø 166 50 8.3 1.00 8.3 0.80 15.8 19.7 3x
C-9 L 209 380 3Ø 187 50 9.4 1.00 9.4 0.80 17.8 22.2 3x
C-10 L 210 220 1Ø 93 50 4.7 1.00 4.7 0.80 26.4 33.0 1x
C-11 L 211 380 3Ø 91 50 4.6 1.00 4.6 0.80 8.6 10.8 3x
C-12 L 220 380 3Ø 140 50 7.0 1.00 7.0 0.80 13.3 16.6 3x
C-13 L 221 380 3Ø 123 50 6.2 1.00 6.2 0.80 11.7 14.6 3x
C-14 L 222 380 3Ø 85 50 4.3 1.00 4.3 0.80 8.1 10.1 3x
C-15 L 223 380 3Ø 130 50 6.5 1.00 6.5 0.80 12.3 15.4 3x
C-16 L 224 380 3Ø 72 50 3.6 1.00 3.6 0.80 6.8 8.5 3x
C-17 L 225 380 3Ø 130 50 6.5 1.00 6.5 0.80 12.3 15.4 3x
C-18 L 226 380 3Ø 245 50 12.3 1.00 12.3 0.80 23.3 29.1 3x
C-19 L227 380 3Ø 125 50 6.3 1.00 6.3 0.80 11.9 14.8
104.8
TABLERO FUERZA TLC-2.2 / NIVEL 0.00 NPT
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)


C-1 L 212 380 1Ø 47 50 2.4 1.00 2.4 0.80 7.7 9.7 1x
C-2 L 213 380 1Ø 53 50 2.7 1.00 2.7 0.80 8.7 10.9 1x
C-3 L 214 380 1Ø 50 50 2.5 1.00 2.5 0.80 8.2 10.3 1x
C-4 L 215 380 1Ø 33 50 1.7 1.00 1.7 0.80 5.4 6.8 1x
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)


C-5 L 216 380 1Ø 46 50 2.3 1.00 2.3 0.80 7.6 9.5 1x
C-6 L 217 380 3Ø 38 50 1.9 1.00 1.9 0.80 3.6 4.5 3x
C-7 L 218 380 3Ø 84 50 4.2 1.00 4.2 0.80 8.0 10.0 3x
C-8 L 219 380 3Ø 83 50 4.2 1.00 4.2 0.80 7.9 9.9 3x
C-9 L 228 380 3Ø 111 50 5.6 1.00 5.6 0.80 10.5 13.2 3x
C-10 L 229 380 3Ø 107 50 5.4 1.00 5.4 0.80 10.2 12.7 3x
C-11 L 230 380 1Ø 79 50 4.0 1.00 4.0 0.80 13.0 16.2 1x
C-12 L 231 380 3Ø 201 50 10.1 1.00 10.1 0.80 19.1 23.9 3x
C-13 L 232 380 3Ø 160 50 8.0 1.00 8.0 0.80 15.2 19.0 3x
C-14 L 233 380 3Ø 130 50 6.5 1.00 6.5 0.80 12.3 15.4 3x
C-15 L 234 380 3Ø 59 50 3.0 1.00 3.0 0.80 5.6 7.0 3x
C-16 L 235 380 1Ø 48 50 2.4 1.00 2.4 0.80 7.9 9.9 1x
C-17 L 236 380 1Ø 47 50 2.4 1.00 2.4 0.80 7.7 9.7 1x
C-18 L 237 380 1Ø 33 50 1.7 1.00 1.7 0.80 5.4 6.8 1x
C-19 L 238 380 1Ø 25 50 1.3 1.00 1.3 0.80 4.1 5.1 1x
71.7

TABLERO FUERZA TLC-2.3 / NIVEL 0.00 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup.

N° (V) (m2) (W/m²) (kW) (kW) (A) (A) No x I (A)


C-1 FC-01 380 3Ø 65 180 11.7 1.00 11.7 0.80 22.2 27.8 3x
C-2 FC-02 380 3Ø 57 180 10.3 1.00 10.3 0.80 19.5 24.4 3x
C-3 FC-03 380 3Ø 53 180 9.5 1.00 9.5 0.80 18.1 22.6 3x
C-4 FC-04 380 3Ø 47 180 8.5 1.00 8.5 0.80 16.1 20.1 3x
C-5 FC-05 380 3Ø 59 180 10.6 1.00 10.6 0.80 20.2 25.2 3x
C-6 FC-06 380 3Ø 66 180 11.9 1.00 11.9 0.80 22.6 28.2 3x
C-7 FC-07 380 3Ø 83 180 14.9 1.00 14.9 0.80 28.4 35.5 3x
C-8 FC-08 380 3Ø 90 180 16.2 1.00 16.2 0.80 30.8 38.5 3x
93.6
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)

.
30 62 16 1.663 0.112 3.13 0.82 0.82%
30 67 16 1.663 0.112 3.14 0.83 0.83%
50 80 25 0.928 0.106 3.69 0.97 0.97%
40 96 25 0.928 0.106 4.15 1.09 1.09%

.
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)

15 158 6 4.122 0.142 3.09 0.81 1.41%


15 156 6 4.122 0.142 2.62 0.69 1.19%
15 137 10 2.644 0.131 3.26 0.86 1.49%
15 145 10 2.644 0.131 3.52 0.93 1.60%
20 148 16 1.663 0.112 4.99 1.31 1.31%
15 150 16 1.663 0.112 3.76 0.99 1.71%
15 145 16 1.663 0.112 2.37 0.62 1.08%
15 145 16 1.663 0.112 3.25 0.85 1.48%
15 167 6 4.122 0.142 2.23 0.59 1.02%
.

.
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)

15 158 16 1.663 0.112 3.05 0.80 1.39%


15 156 16 1.663 0.112 2.58 0.68 1.18%
15 137 16 1.663 0.112 3.59 0.94 0.94%
15 145 6 4.122 0.142 1.98 0.52 0.90%
40 75 16 1.663 0.112 5.86 1.54 1.54%
15 148 16 1.663 0.112 2.38 0.63 1.09%
15 150 10 2.644 0.131 4.98 1.31 1.31%
15 145 10 2.644 0.131 4.03 1.06 1.06%
15 145 10 2.644 0.131 6.80 1.79 1.79%
15 167 10 2.644 0.131 6.27 1.65 1.65%
15 160 6 4.122 0.142 6.00 1.58 1.58%
15 160 6 4.122 0.142 5.97 1.57 1.57%
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)

20 160 16 1.663 0.112 6.95 1.83 1.83%


20 166 16 1.663 0.112 5.24 1.38 1.38%
20 167 16 1.663 0.112 4.13 1.09 1.88%
.
.
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)

15 89 10 2.644 0.131 4.05 1.06 1.06%


15 62 10 2.644 0.131 2.46 0.65 1.12%
15 158 16 1.663 0.112 3.27 0.86 1.49%
15 156 16 1.663 0.112 3.37 0.89 1.54%
15 137 6 4.122 0.142 4.73 1.24 1.24%
15 145 6 4.122 0.142 4.68 1.23 1.23%
50 148 35 0.671 0.107 5.92 1.56 1.56%
15 150 10 2.644 0.131 3.81 1.00 1.00%
15 145 10 2.644 0.131 6.64 1.75 1.75%
20 145 6 4.122 0.142 4.76 1.25 1.25%
20 167 16 1.663 0.112 3.76 0.99 0.99%
15 160 16 1.663 0.112 5.59 1.47 1.47%
15 160 10 2.644 0.131 4.91 1.29 1.29%
15 160 16 1.663 0.112 2.72 0.72 1.24%
.
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)

.
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)

80 90 25 0.928 0.106 7.22 1.90 1.90%


150 45 50 0.435 0.105 3.85 1.01 1.01%
80 35 25 0.928 0.106 2.84 0.75 0.75%
80 30 25 0.928 0.106 2.61 0.69 0.69%
80 25 25 0.928 0.106 2.34 0.62 0.62%
.

.
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)


15 103 10 2.644 0.131 6.65 1.75 1.75%
20 80 16 1.663 0.112 4.89 2.22 3.85%
15 78 10 2.644 0.131 5.25 2.39 4.13%
15 65 10 2.644 0.131 4.05 1.84 3.19%
15 65 6 4.122 0.142 3.11 0.82 0.82%
15 55 6 4.122 0.142 3.17 1.44 2.50%
15 69 6 4.122 0.142 4.38 1.99 3.45%
40 91 25 0.928 0.106 2.00 0.53 0.53%
15 93 10 2.644 0.131 6.28 1.65 1.65%
15 96 10 2.644 0.131 11.13 5.06 8.76%
15 110 10 2.644 0.131 3.61 0.95 0.95%
20 61 16 1.663 0.112 1.96 0.52 0.52%
20 57 16 1.663 0.112 1.61 0.42 0.42%
15 24 6 4.122 0.142 1.14 0.30 0.30%
20 66 6 4.122 0.142 4.77 1.26 1.26%
15 73 6 4.122 0.142 2.92 0.77 0.77%
15 74 6 4.122 0.142 5.35 1.41 1.41%
15 85 6 4.122 0.142 11.59 3.05 3.05%

.
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)


15 50 6 4.122 0.142 2.62 0.69 1.19%
15 40 6 4.122 0.142 2.36 0.62 1.08%
15 43 6 4.122 0.142 2.39 0.63 1.09%
15 45 6 4.122 0.142 1.65 0.43 0.75%
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)


15 53 6 4.122 0.142 2.71 0.71 1.24%
15 114 6 4.122 0.142 2.41 0.63 0.63%
15 115 6 4.122 0.142 5.38 1.41 1.41%
120 0.00 0.00 0.00%
20 114 10 2.644 0.131 4.57 1.20 1.20%
20 98 10 2.644 0.131 3.78 1.00 1.00%
15 105 10 2.644 0.131 5.99 1.58 2.73%
20 126 16 1.663 0.112 5.82 1.53 1.53%
20 127 10 2.644 0.131 7.33 1.93 1.93%
20 129 6 4.122 0.142 9.33 2.46 2.46%
20 132 6 4.122 0.142 4.33 1.14 1.14%
20 139 10 2.644 0.131 4.82 1.27 2.19%
20 140 10 2.644 0.131 4.75 1.25 2.16%
20 153 10 2.644 0.131 3.64 0.96 1.66%
20 154 10 2.644 0.131 2.78 0.73 1.27%

.
Interrrup. L S R X Caida Ten. D V* D V*

No x I (A) (m) (mm²) (Ohms/Km) (Ohms/Km) (V) (%) (%)


25 83 10 2.644 0.131 7.01 1.84 1.84%
20 80 10 2.644 0.131 5.92 1.56 1.56%
20 66 10 2.644 0.131 4.54 1.20 1.20%
20 64 10 2.644 0.131 3.91 1.03 1.03%
25 53 10 2.644 0.131 4.06 1.07 1.07%
25 51 10 2.644 0.131 4.37 1.15 1.15%
30 40 10 2.644 0.131 4.31 1.13 1.13%
40 40 10 2.644 0.131 4.68 1.23 1.23%
CIRC. DESCRIPCION TENSION FASE C.I. F.D.D. M.D. F. P. I nom. I diseño Interrrup. L S

N° (V) (kW) (kW) (A) (A) No x I (A) (m) (mm²)

TABLERO FUERZA TLCE-S.1 / NIVEL -12.5 NPT .


C-1 BANCO 1 380 3Ø 3.3 1.00 3.3 0.80 6.3 7.8 3x 10 62 6
C-2 BANCO 2 380 3Ø 3.1 1.00 3.1 0.80 5.8 7.3 3x 10 67 6
C-3 BANCO 3 380 3Ø 5.2 1.00 5.2 0.80 9.9 12.4 3x 10 80 10
C-4 BANCO 4 380 3Ø 4.9 1.00 4.9 0.80 9.3 11.6 3x 10 96 10
16.5 16.5

TABLERO FUERZA TLCE-S.2 / NIVEL -12.5 NPT .


C-1 LS-01 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 158 6
C-2 LS-02 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 156 6
C-3 LS-03 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 137 6
C-4 LS-04 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 145 6
C-5 LS-05 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 148 6
C-6 LS-06 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 150 6
C-7 LS-07 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 145 6
C-8 LS-08 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 145 6
C-9 LS-09 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 167 6
9.0 9.0 .
.

TABLERO FUERZA TLCE-1.1 / NIVEL -12.5 NPT .


C-1 L101 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 158 6
C-2 L102 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 156 6
C-3 L103 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 137 6
C-4 L104 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 145 6
C-5 L1 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 10 75 16
C-6 L105 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 148 10
C-7 L106 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 150 6
C-8 L107 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 145 6
C-9 L117 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 145 10
C-10 L118 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 167 10
C-11 L119 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 160 6
C-12 L120 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 160 6
C-13 L121 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 160 16
C-14 L122 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 166 16
C-15 L123 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 167 6
17.0 17.0 .
.
.

TABLERO FUERZA TLCE-1.2 / NIVEL -12.5 NPT .


C-1 L109 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 89 6
C-2 L110 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 62 6
C-3 L111 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 158 6
C-4 L112 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 156 6
C-5 L113 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 137 6
C-6 L114 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 145 6
C-7 L116 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 148 10
C-8 L124 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 150 10
C-9 L125 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 145 6
C-10 L126 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 145 6
C-11 L127 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 167 6
C-12 L128 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 160 6
C-13 L129 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 160 6
C-14 L130 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 160 6
14.0 14.0 .
.

TABLERO FUERZA TLCE-1.3 / NIVEL -12.5 NPT .


C-1 Rest 1 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 158 16
C-2 Rest 2 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 156 16
C-3 Rest 3 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 137 16
C-4 Rest 4 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 145 16
C-5 Rest 5 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 148 16
15.0 15.0 .

TABLERO FUERZA TLCE-2.1 / NIVEL NPT .


C-1 L 201 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 103 6
C-2 L 202 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 80 6
C-3 L 203 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 78 6
C-4 L 204 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 65 6
C-5 L 205 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 65 6
C-6 L 206 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 55 6
C-7 L 207 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 69 6
C-8 L 208 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 91 6
C-9 L 209 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 93 6
C-10 L 210 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 96 6
C-11 L 211 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 110 6
C-12 L 220 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 61 6
C-13 L 221 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 57 6
C-14 L 222 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 24 6
C-15 L 223 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 66 6
C-16 L 224 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 73 6
C-17 L 225 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 74 6
C-18 L 226 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 85 6
18.0

TABLERO FUERZA TLCE-2.2 / NIVEL NPT .


C-1 L 212 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 50 6
C-2 L 213 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 40 6
C-3 L 214 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 43 6
C-4 L 215 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 45 6
C-5 L 216 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 53 6
C-6 L 217 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 114 6
C-7 L 218 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 115 6
C-8 L 219 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10
C-9 L 227 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 114 6
C-10 L 228 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 98 6
C-11 L 229 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 105 10
C-12 L 230 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 126 6
C-13 L 231 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 127 6
C-14 L 232 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 129 6
C-15 L 233 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 135 6
C-16 L 234 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 139 6
C-17 L 235 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 140 6
C-18 L 236 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 153 6
C-19 L 237 380 1Ø 1.0 1.00 1.0 0.80 3.3 4.1 1x 10 154 6
19.0

TABLERO FUERZA TLCE-2.3 / NIVEL NPT .


C-1 FC-01 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 83 10
C-2 FC-02 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 80 10
C-3 FC-03 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 66 10
C-4 FC-04 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 64 10
C-5 FC-05 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 53 6
C-6 FC-06 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 51 6
C-7 FC-07 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 40 6
C-8 FC-08 380 1Ø 3.0 1.00 3.0 0.80 9.9 12.3 1x 15 40 6
24.0
R X Caida Ten. D V* D V*

(Ohms/Km) (Ohms/Km) (V) (%) (%)

4.122 0.142 2.28 0.60 0.60%


4.122 0.142 2.28 0.60 0.60%
2.644 0.131 3.01 0.79 0.79%
2.644 0.131 3.39 0.89 0.89%

4.122 0.142 3.52 0.93 1.60%


4.122 0.142 3.47 0.91 1.58%
4.122 0.142 3.05 0.80 1.39%
4.122 0.142 3.23 0.85 1.47%
4.122 0.142 3.29 0.87 1.50%
4.122 0.142 3.34 0.88 1.52%
4.122 0.142 3.23 0.85 1.47%
4.122 0.142 3.23 0.85 1.47%
4.122 0.142 3.72 0.98 1.69%

4.122 0.142 3.52 0.93 1.60%


4.122 0.142 3.47 0.91 1.58%
4.122 0.142 3.05 0.80 1.39%
4.122 0.142 3.23 0.85 1.47%
1.663 0.112 2.07 0.54 0.94%
2.644 0.131 2.14 0.56 0.97%
4.122 0.142 3.34 0.88 1.52%
4.122 0.142 3.23 0.85 1.47%
2.644 0.131 2.09 0.55 0.95%
2.644 0.131 2.41 0.63 1.10%
4.122 0.142 3.56 0.94 1.62%
4.122 0.142 3.56 0.94 1.62%
1.663 0.112 1.47 0.39 0.67%
1.663 0.112 1.53 0.40 0.70%
4.122 0.142 3.72 0.98 1.69%
4.122 0.142 1.98 0.52 0.90%
4.122 0.142 1.38 0.36 0.63%
4.122 0.142 3.52 0.93 1.60%
4.122 0.142 3.47 0.91 1.58%
4.122 0.142 3.05 0.80 1.39%
4.122 0.142 3.23 0.85 1.47%
2.644 0.131 2.14 0.56 0.97%
2.644 0.131 2.17 0.57 0.99%
4.122 0.142 3.23 0.85 1.47%
4.122 0.142 3.23 0.85 1.47%
4.122 0.142 3.72 0.98 1.69%
4.122 0.142 3.56 0.94 1.62%
4.122 0.142 3.56 0.94 1.62%
4.122 0.142 3.56 0.94 1.62%

1.663 0.112 4.36 1.15 1.99%


1.663 0.112 4.30 1.13 1.96%
1.663 0.112 3.78 0.99 1.72%
1.663 0.112 4.00 1.05 1.82%
1.663 0.112 4.08 1.07 1.86%

4.122 0.142 2.29 0.60 1.04%


4.122 0.142 1.78 0.47 0.81%
4.122 0.142 1.74 0.46 0.79%
4.122 0.142 1.45 0.38 0.66%
4.122 0.142 1.45 0.38 0.66%
4.122 0.142 1.22 0.32 0.56%
4.122 0.142 1.54 0.40 0.70%
4.122 0.142 2.03 0.53 0.92%
4.122 0.142 2.07 0.54 0.94%
4.122 0.142 2.14 0.56 0.97%
4.122 0.142 2.45 0.64 1.12%
4.122 0.142 1.36 0.36 0.62%
4.122 0.142 1.27 0.33 0.58%
4.122 0.142 0.53 0.14 0.24%
4.122 0.142 1.47 0.39 0.67%
4.122 0.142 1.62 0.43 0.74%
4.122 0.142 1.65 0.43 0.75%
4.122 0.142 1.89 0.50 0.86%

4.122 0.142 1.11 0.29 0.51%


4.122 0.142 0.89 0.23 0.41%
4.122 0.142 0.96 0.25 0.44%
4.122 0.142 1.00 0.26 0.46%
4.122 0.142 1.18 0.31 0.54%
4.122 0.142 2.54 0.67 1.16%
4.122 0.142 2.56 0.67 1.17%
0.00 0.00 0.00%
4.122 0.142 2.54 0.67 1.16%
4.122 0.142 2.18 0.57 0.99%
2.644 0.131 1.52 0.40 0.69%
4.122 0.142 2.80 0.74 1.28%
4.122 0.142 2.83 0.74 1.29%
4.122 0.142 2.87 0.76 1.31%
4.122 0.142 3.00 0.79 1.37%
4.122 0.142 3.09 0.81 1.41%
4.122 0.142 3.12 0.82 1.42%
4.122 0.142 3.41 0.90 1.55%
4.122 0.142 3.43 0.90 1.56%

2.644 0.131 3.59 0.95 1.64%


2.644 0.131 3.46 0.91 1.58%
2.644 0.131 2.86 0.75 1.30%
2.644 0.131 2.77 0.73 1.26%
4.122 0.142 3.54 0.93 1.61%
4.122 0.142 3.41 0.90 1.55%
4.122 0.142 2.67 0.70 1.22%
4.122 0.142 2.67 0.70 1.22%
CALCULO JUSTIFICATIVO DE DEMANDA MAXIMA TABLERO TGN-L
1.0 TABLERO FUERZA TLC-S.1 / NIVEL -12.5 NPT
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. FDD M.D.
N° (V) (m2) (W/m²) (kW) (kW)
C-1 BANCO 1 380 3Ø 110 100 11.0 1.00 11.0
C-2 BANCO 2 380 3Ø 102 100 10.2 1.00 10.2
C-3 BANCO 3 380 3Ø 174 100 17.4 1.00 17.4
C-4 BANCO 4 380 3Ø 163 100 16.3 1.00 16.3
SUBTOTAL = 54.9 54.9

2.0 TABLERO FUERZA TLC-S.2 / NIVEL -12.5 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. FDD M.D.
N° (V) (m2) (W/m²) (kW) (kW)
C-1 LS-01 380 1Ø 17.6 50 0.9 1.00 0.9
C-2 LS-02 380 1Ø 15.1 50 0.8 1.00 0.8
C-3 LS-03 380 1Ø 33 50 1.7 1.00 1.7
C-4 LS-04 380 1Ø 33.6 50 1.7 1.00 1.7
C-5 LS-05 380 3Ø 146.6 50 7.3 1.00 7.3
C-6 LS-06 380 1Ø 54.5 50 2.7 1.00 2.7
C-7 LS-07 380 1Ø 35.6 50 1.8 1.00 1.8
C-8 LS-08 380 1Ø 48.7 50 2.4 1.00 2.4
C-9 LS-09 380 1Ø 12 50 0.6 1.00 0.6
SUBTOTAL = 19.8 19.8

3.0 TABLERO FUERZA TLC-1.1 / NIVEL -12.5 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D.
N° (V) (m2) (W/m²) (kW) (kW)
C-1 L101 380 1Ø 42 50 2.1 1.00 2.1
C-2 L102 380 1Ø 36 50 1.8 1.00 1.8
C-3 L103 380 3Ø 114 50 5.7 1.00 5.7
C-4 L104 380 1Ø 12.3 50 0.6 1.00 0.6
C-5 L1 380 3Ø 340 50 17.0 1.00 17.0
C-6 L105 380 1Ø 35 50 1.8 1.00 1.8
C-7 L106 380 3Ø 92 50 4.6 1.00 4.6
C-8 L107 380 3Ø 77 50 3.9 1.00 3.9
C-9 L117 380 3Ø 130 50 6.5 1.00 6.5
C-10 L118 380 3Ø 104 50 5.2 1.00 5.2
C-11 L119 380 3Ø 67.4 50 3.4 1.00 3.4
C-12 L120 380 3Ø 67.1 50 3.4 1.00 3.4
C-13 L121 380 3Ø 189 50 9.5 1.00 9.5
C-14 L122 380 3Ø 137.4 50 6.9 1.00 6.9
C-15 L123 380 1Ø 53.8 50 2.7 1.00 2.7
SUBTOTAL = 74.9 74.9

4.0 TABLERO FUERZA TLC-1.2 / NIVEL -12.5 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D.
N° (V) (m2) (W/m²) (kW) (kW)
C-1 L109 380 3Ø 126 50 6.3 1.00 6.3
C-2 L110 380 1Ø 55 50 2.8 1.00 2.8
C-3 L111 380 1Ø 45 50 2.3 1.00 2.3
C-4 L112 380 1Ø 47 50 2.4 1.00 2.4
C-5 L113 380 3Ø 62 50 3.1 1.00 3.1
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. FDD M.D.
N° (V) (m2) (W/m²) (kW) (kW)
C-6 L114 380 3Ø 58 50 2.9 1.00 2.9
C-7 L116 380 3Ø 405 50 20.3 1.00 20.3
C-8 L124 380 3Ø 70.3 50 3.5 1.00 3.5
C-9 L125 380 3Ø 127 50 6.4 1.00 6.4
C-10 L126 380 3Ø 59 50 3.0 1.00 3.0
C-11 L127 380 3Ø 98 50 4.9 1.00 4.9
C-12 L128 380 3Ø 152 50 7.6 1.00 7.6
C-13 L129 380 3Ø 85 50 4.3 1.00 4.3
C-14 L130 380 1Ø 37 50 1.9 1.00 1.9
C-15 L131 380 1Ø 33 50 1.7 1.00 1.7
SUBTOTAL = 73.0 73.0
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. FDD M.D.
N° (V) (m2) (W/m²) (kW) (kW)

5.0 TABLERO FUERZA TLC-1.3 / NIVEL -6.00 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D.
N° (V) (m2) (W/m²) (kW) (kW)
C-1 Rest 1 380 3Ø 168 180 30.2 1.00 30.2
C-2 Rest 2 380 3Ø 352 180 63.4 1.00 63.4
C-3 Rest 3 380 3Ø 170 180 30.6 1.00 30.6
C-4 Rest 4 380 3Ø 182 180 32.8 1.00 32.8
C-5 Rest 5 380 3Ø 196 180 35.3 1.00 35.3
SUBTOTAL = 192.2 192.2

6.0 TABLERO FUERZA TLC-2.1 / NIVEL 0.00 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D.
N° (V) (m2) (W/m²) (kW) (kW)
C-1 L 201 380 3Ø 179 50 9.0 1.00 9.0
C-2 L 202 220 1Ø 77 50 3.9 1.00 3.9
C-3 L 203 220 1Ø 54 50 2.7 1.00 2.7
C-4 L 204 220 1Ø 50 50 2.5 1.00 2.5
C-5 L 205 380 3Ø 86 50 4.3 1.00 4.3
C-6 L 206 220 1Ø 30 50 1.5 1.00 1.5
C-7 L 207 220 1Ø 33 50 1.7 1.00 1.7
C-8 L 208 380 3Ø 166 50 8.3 1.00 8.3
C-9 L 209 380 3Ø 187 50 9.4 1.00 9.4
C-10 L 210 220 1Ø 93 50 4.7 1.00 4.7
C-11 L 211 380 3Ø 91 50 4.6 1.00 4.6
C-12 L 220 380 3Ø 140 50 7.0 1.00 7.0
C-13 L 221 380 3Ø 123 50 6.2 1.00 6.2
C-14 L 222 380 3Ø 85 50 4.3 1.00 4.3
C-15 L 223 380 3Ø 130 50 6.5 1.00 6.5
C-16 L 224 380 3Ø 72 50 3.6 1.00 3.6
C-17 L 225 380 3Ø 130 50 6.5 1.00 6.5
C-18 L 226 380 3Ø 245 50 12.3 1.00 12.3
SUBTOTAL = 104.8 104.8

7.0 TABLERO FUERZA TLC-2.2 / NIVEL 0.00 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D.
N° (V) (m2) (W/m²) (kW) (kW)
C-1 L 212 380 1Ø 47 50 2.4 1.00 2.4
C-2 L 213 380 1Ø 53 50 2.7 1.00 2.7
C-3 L 214 380 1Ø 50 50 2.5 1.00 2.5
C-4 L 215 380 1Ø 33 50 1.7 1.00 1.7
C-5 L 216 380 1Ø 46 50 2.3 1.00 2.3
C-6 L 217 380 3Ø 38 50 1.9 1.00 1.9
C-7 L 218 380 3Ø 84 50 4.2 1.00 4.2
C-8 L 219 380 3Ø 83 50 4.2 1.00 4.2
C-9 L 227 380 3Ø 125 50 6.3 1.00 6.3
C-10 L 228 380 3Ø 111 50 5.6 1.00 5.6
C-11 L 229 380 3Ø 107 50 5.4 1.00 5.4
C-12 L 230 380 1Ø 79 50 4.0 1.00 4.0
C-13 L 231 380 3Ø 201 50 10.1 1.00 10.1
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. FDD M.D.
N° (V) (m2) (W/m²) (kW) (kW)
C-14 L 232 380 3Ø 160 50 8.0 1.00 8.0
C-15 L 233 380 3Ø 130 50 6.5 1.00 6.5
C-16 L 234 380 3Ø 59 50 3.0 1.00 3.0
C-17 L 235 380 1Ø 48 50 2.4 1.00 2.4
C-18 L 236 380 1Ø 47 50 2.4 1.00 2.4
C-19 L 237 380 1Ø 33 50 1.7 1.00 1.7
SUBTOTAL = 76.7 76.7
CIRC. DESCRIPCION TENSION FASE Area Carga C.I. FDD M.D.
N° (V) (m2) (W/m²) (kW) (kW)

8.0 TABLERO FUERZA TLC-2.3 / NIVEL 0.00 NPT


CIRC. DESCRIPCION TENSION FASE Area Carga C.I. F.D.D. M.D.
N° (V) (m2) (W/m²) (kW) (kW)
C-1 FC-01 380 3Ø 65 180 11.7 1.00 11.7
C-2 FC-02 380 3Ø 57 180 10.3 1.00 10.3
C-3 FC-03 380 3Ø 53 180 9.5 1.00 9.5
C-4 FC-04 380 3Ø 47 180 8.5 1.00 8.5
C-5 FC-05 380 3Ø 59 180 10.6 1.00 10.6
C-6 FC-06 380 3Ø 66 180 11.9 1.00 11.9
C-7 FC-07 380 3Ø 83 180 14.9 1.00 14.9
C-8 FC-08 380 3Ø 90 180 16.2 1.00 16.2
SUBTOTAL = 93.6 93.6

RESUMEN TABLERO TGN-L


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CGNL-1 TLC-S.1 380 3Ø 54.90 54.90
CGNL-2 TLC-S.2 380 3Ø 19.84 19.84
CGNL-3 TLC-1.1 380 3Ø 74.85 74.85
CGNL-4 TLC-1.2 380 3Ø 72.97 72.97
CGNL-5 TLC-2.1 380 3Ø 104.80 104.80
CGNL-6 TLC-2.2 380 3Ø 76.70 76.70
CGNL-7 TLC-2.3 380 3Ø 93.60 93.60
SUBTOTAL = 492.65 492.65

NOTA: NO INCLUYE EL TABLERO TLC-1.3


CALCULO JUSTIFICATIVO DE DEMANDA MAXIMA TABLERO TGE-L
1.0 TABLERO FUERZA TLCE-S.1 / NIVEL -12.5 NPT
CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CE-1 BANCO 1 380 3Ø 3.30 1.00 3.30
CE-2 BANCO 2 380 3Ø 3.06 1.00 3.06
CE-3 BANCO 3 380 3Ø 5.22 1.00 5.22
CE-4 BANCO 4 380 3Ø 4.89 1.00 4.89
SUBTOTAL = 16.47 16.47

2.0 TABLERO FUERZA TLCE-S.2 / NIVEL -12.5 NPT


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CE-1 LS-01 380 1Ø 1.0 1.00 1.00
CE-2 LS-02 380 1Ø 1.0 1.00 1.00
CE-3 LS-03 380 1Ø 1.0 1.00 1.00
CE-4 LS-04 380 1Ø 1.00 1.00 1.00
CE-5 LS-05 380 1Ø 1.00 1.00 1.00
CE-6 LS-06 380 1Ø 1.00 1.00 1.00
CE-7 LS-07 380 1Ø 1.00 1.00 1.00
CE-8 LS-08 380 1Ø 1.00 1.00 1.00
CE-9 LS-09 380 1Ø 1.00 1.00 1.00
SUBTOTAL = 9.00 9.00

3.0 TABLERO FUERZA TLCE-1.1 / NIVEL -12.5 NPT


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CE-1 L101 380 1Ø 1.00 1.00 1.00
CE-2 L102 380 1Ø 1.00 1.00 1.00
CE-3 L103 380 1Ø 1.00 1.00 1.00
CE-4 L104 380 1Ø 1.00 1.00 1.00
CE-5 L1 380 1Ø 3.00 1.00 3.00
CE-6 L105 380 1Ø 1.00 1.00 1.00
CE-7 L106 380 1Ø 1.00 1.00 1.00
CE-8 L107 380 1Ø 1.00 1.00 1.00
CE-9 L117 380 1Ø 1.00 1.00 1.00
CE-10 L118 380 1Ø 1.00 1.00 1.00
CE-11 L119 380 1Ø 1.00 1.00 1.00
CE-12 L120 380 1Ø 1.00 1.00 1.00
CE-13 L121 380 1Ø 1.00 1.00 1.00
CE-14 L122 380 1Ø 1.00 1.00 1.00
CE-15 L123 380 1Ø 1.00 1.00 1.00
SUBTOTAL = 17.00 17.00

4.0 TABLERO FUERZA TLCE-1.2 / NIVEL -12.5 NPT


CE-1 L109 380 1Ø 1.00 1.00 1.00
CE-2 L110 380 1Ø 1.00 1.00 1.00
CE-3 L111 380 1Ø 1.00 1.00 1.00
CE-4 L112 380 1Ø 1.00 1.00 1.00
CE-5 L113 380 1Ø 1.00 1.00 1.00
CE-6 L114 380 1Ø 1.00 1.00 1.00
CE-7 L116 380 1Ø 1.00 1.00 1.00
CE-8 L124 380 1Ø 1.00 1.00 1.00
CE-9 L125 380 1Ø 1.00 1.00 1.00
CE-10 L126 380 1Ø 1.00 1.00 1.00
CE-11 L127 380 1Ø 1.00 1.00 1.00
CE-12 L128 380 1Ø 1.00 1.00 1.00
CE-13 L129 380 1Ø 1.00 1.00 1.00
CE-14 L130 380 1Ø 1.00 1.00 1.00
SUBTOTAL = 14.00 14.00
5.0 TABLERO FUERZA TLCE-1.3 / NIVEL -12.5 NPT
CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CE-1 Rest 1 380 1Ø 3.00 1.00 3.00
CE-2 Rest 2 380 1Ø 3.00 1.00 3.00
CE-3 Rest 3 380 1Ø 3.00 1.00 3.00
CE-4 Rest 4 380 1Ø 3.00 1.00 3.00
CE-5 Rest 5 380 1Ø 3.00 1.00 3.00
SUBTOTAL = 15.00 15.00

6.0 TABLERO FUERZA TLCE-2.1 / NIVEL NPT


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CE-1 L 201 380 1Ø 1.00 1.00 1.00
CE-2 L 202 380 1Ø 1.00 1.00 1.00
CE-3 L 203 380 1Ø 1.00 1.00 1.00
CE-4 L 204 380 1Ø 1.00 1.00 1.00
CE-5 L 205 380 1Ø 1.00 1.00 1.00
CE-6 L 206 380 1Ø 1.00 1.00 1.00
CE-7 L 207 380 1Ø 1.00 1.00 1.00
CE-8 L 208 380 1Ø 1.00 1.00 1.00
CE-9 L 209 380 1Ø 1.00 1.00 1.00
CE-10 L 210 380 1Ø 1.00 1.00 1.00
CE-11 L 211 380 1Ø 1.00 1.00 1.00
CE-12 L 220 380 1Ø 1.00 1.00 1.00
CE-13 L 221 380 1Ø 1.00 1.00 1.00
CE-14 L 222 380 1Ø 1.00 1.00 1.00
CE-15 L 223 380 1Ø 1.00 1.00 1.00
CE-16 L 224 380 1Ø 1.00 1.00 1.00
CE-17 L 225 380 1Ø 1.00 1.00 1.00
CE-18 L 226 380 1Ø 1.00 1.00 1.00
SUBTOTAL = 18.00 18.00

7.0 TABLERO FUERZA TLCE-2.2 / NIVEL NPT


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CE-1 L 212 380 1Ø 1.00 1.00 1.00
CE-2 L 213 380 1Ø 1.00 1.00 1.00
CE-3 L 214 380 1Ø 1.00 1.00 1.00
CE-4 L 215 380 1Ø 1.00 1.00 1.00
CE-5 L 216 380 1Ø 1.00 1.00 1.00
CE-6 L 217 380 1Ø 1.00 1.00 1.00
CE-7 L 218 380 1Ø 1.00 1.00 1.00
CE-8 L 219 380 1Ø 1.00 1.00 1.00
CE-9 L 227 380 1Ø 1.00 1.00 1.00
CE-10 L 228 380 1Ø 1.00 1.00 1.00
CE-11 L 229 380 1Ø 1.00 1.00 1.00
CE-12 L 230 380 1Ø 1.00 1.00 1.00
CE-13 L 231 380 1Ø 1.00 1.00 1.00
CE-14 L 232 380 1Ø 1.00 1.00 1.00
CE-15 L 233 380 1Ø 1.00 1.00 1.00
CE-16 L 234 380 1Ø 1.00 1.00 1.00
CE-17 L 235 380 1Ø 1.00 1.00 1.00
CE-18 L 236 380 1Ø 1.00 1.00 1.00
CE-19 L 237 380 1Ø 1.00 1.00 1.00
SUBTOTAL = 19.00 19.00
8.0 TABLERO FUERZA TLCE-2.3 / NIVEL NPT
CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CE-1 FC-01 380 1Ø 3.00 1.00 3.00
CE-2 FC-02 380 1Ø 3.00 1.00 3.00
CE-3 FC-03 380 1Ø 3.00 1.00 3.00
CE-4 FC-04 380 1Ø 3.00 1.00 3.00
CE-5 FC-05 380 1Ø 3.00 1.00 3.00
CE-6 FC-06 380 1Ø 3.00 1.00 3.00
CE-7 FC-07 380 1Ø 3.00 1.00 3.00
CE-8 FC-08 380 1Ø 3.00 1.00 3.00
SUBTOTAL = 24.00 24.00

RESUMEN TABLERO TGE-L


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CGEL-1 TLCE-S.1 380 3Ø 16.47 16.47
CGEL-2 TLCE-S.2 380 3Ø 9.00 9.00
CGEL-3 TLCE-1.1 380 3Ø 17.00 17.00
CGEL-4 TLCE-1.2 380 3Ø 14.00 14.00
CGEL-5 TLCE-2.1 380 3Ø 18.00 18.00
CGEL-6 TLCE-2.2 380 3Ø 19.00 19.00
CGEL-7 TLCE-2.3 380 3Ø 24.00 24.00
SUBTOTAL = 117.47 117.47

NOTA: NO INCLUYE EL TABLERO TLCE-1.3


CALCULO JUSTIFICATIVO DE DEMANDA MAXIMA DEL TABLERO GENERAL TGD-ESG

1.0 TABLERO TGE-SG / Nivel -9.25m


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CGE-SG-1 TF-EX 380 3Ø 71.25 71.25
CGE-SG-2 TF-BO 380 3Ø 33.57 33.57
CGE-SG-3 TB-BS-3 380 3Ø 4.47 1.0 4.47
CGE-SG-4 TB-BS-4 380 3Ø 4.47 1.0 4.47
SUBTOTAL = 113.76 113.76
SUBTABLERO TF-EX
CF-EX-1 TC-EX-1 380 3Ø 18.75 1.0 18.75
CF-EX-2 TC-EX-2 380 3Ø 18.75 1.0 18.75
CF-EX-3 TC-EX-3 380 3Ø 18.75 1.0 18.75
CF-EX-4 TC-EX-4 380 3Ø 15.00 1.0 15.00
SUBTOTAL = 71.25 71.25

2.0 TABLERO TASC-SG / Nivel -9.25 m


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CAE-SG-1 ASCENSOR N° 01 380 3Ø 15.00 1.0 15.00
CAE-SG-2 ASCENSOR N° 02 380 3Ø 15.00 1.0 15.00
CAE-SG-3 ASCENSOR N° 03 380 3Ø 15.00 1.0 15.00
CAE-SG-4 ASCENSOR N° 04 380 3Ø 15.00 1.0 15.00
CAE-SG-5 ASCENSOR N° 05 380 3Ø 15.00 1.0 15.00
CAE-SG-6 TSGE-5.4 380 3Ø 26.32 26.32
SUBTOTAL = 101.32 101.32

3.0 TABLERO TEM-SG / Nivel -9.25 m


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CEM-SG-1 TF-EM-3 380 3Ø 45.00 45.00
CEM-SG-2 TF-EM-4 380 3Ø 45.00 45.00
CEM-SG-3 ESCALERA 7 380 3Ø 15.00 1.0 15.00
CEM-SG-4 ESCALERA 9 380 3Ø 15.00 1.0 15.00
CEM-SG-5 ESCALERA 11 380 3Ø 15.00 1.0 15.00
CEM-SG-6 ESCALERA 19 380 3Ø 15.00 1.0 15.00
SUBTOTAL = 150.00 150.00
SUBTABLERO TF-EM-3
CEM-3-1 ESC. MECA 1 380 3Ø 15.00 1.0 15.00
CEM-3-2 ESC. MECA 3 380 3Ø 15.00 1.0 15.00
CEM-3-3 ESC. MECA 5 380 3Ø 15.00 1.0 15.00
SUBTOTAL = 45.00 45.00
SUBTABLERO TF-EM-4
CEM-4-1 ESC. MECA 13 380 3Ø 15.00 1.0 15.00
CEM-4-2 ESC. MECA 15 380 3Ø 15.00 1.0 15.00
CEM-4-3 ESC. MECA 17 380 3Ø 15.00 1.0 15.00
SUBTOTAL = 45.00 45.00
4.0 TABLERO STE-SGS / NIVEL -9.25 m
CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CTE-SG-1 TDE-1 380 3Ø 17.58 15.04
CTE-SG-2 TSGE-1.4 380 3Ø 4.31 4.03
CTE-SG-3 TDE-2 380 3Ø 19.46 17.97
CTE-SG-4 TDE-3 380 3Ø 26.31 24.90
CTE-SG-5 TSGE-3.4 380 3Ø 18.57 16.86
SUBTOTAL = 86.23 78.80
SUBTABLERO TDE-1
SGE-1.1 TSGE-1.1 380 3Ø 4.01 3.61
SGE-1.2 TSGE-1.2 380 3Ø 4.62 4.16
SGE-1.3 TSGE-1.3 380 3Ø 8.95 7.28
SUBTOTAL = 17.58 15.04
SUBTABLERO TDE-2
SGE-2.1 TSGE-2.1 380 3Ø 3.06 2.75
SGE-2.2 TSGE-2.2 380 3Ø 3.27 2.95
SGE-2.3 TSGE-2.3 380 3Ø 13.13 12.27
SUBTOTAL = 19.46 17.97
SUBTABLERO TDE-3
SGE-3.1 TSGE-3.1 380 3Ø 16.89 16.20
SGE-3.2 TSGE-3.2 380 3Ø 2.75 2.47
SGE-3.3 TSGE-3.3 380 3Ø 6.68 6.23
SUBTOTAL = 26.31 24.90

5.0 TABLERO STE-SGG / NIVEL -9.25 m


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CT-SG-1 TDE-4 380 3Ø 49.14 45.44
CT-SG-2 TE-AD 380 3Ø 15.78 15.78
CT-SG-3 TDE-5 380 3Ø 38.70 35.71
CT-SG-4 TSGE-3.5 380 3Ø 9.52 8.93
SUBTOTAL = 113.14 105.85
SUBTABLERO TDE-4
SGE-4.1 TSGE-4.1 380 3Ø 18.49 17.04
SGE-4.2 TSGE-4.2 380 3Ø 14.00 12.96
SGE-4.3 TSGE-4.3 380 3Ø 16.65 15.43
SUBTOTAL = 49.14 45.44
SUBTABLERO TDE-5
SGE-5.1 TSGE-5.1 380 3Ø 15.60 14.44
SGE-5.2 TSGE-5.2 380 3Ø 13.73 12.72
SGE-5.3 TSGE-5.3 380 3Ø 9.38 8.55
SUBTOTAL = 38.70 35.71
6.0 TABLERO TE-SEG / NIVEL -9.25 m
CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CTE-SG-1 TC-PE-1 380 3Ø 5.60 1.0 5.60
CTE-SG-2 TC-PE-2 380 3Ø 5.60 1.0 5.60
CTE-SG-3 TC-PE-3 380 3Ø 5.60 1.0 5.60
CTE-SG-4 TC-PE-4 380 3Ø 5.60 1.0 5.60
CTE-SG-5 TC-PE-5 380 3Ø 5.60 1.0 5.60
CTE-SG-6 TC-PE-6 380 3Ø 5.60 1.0 5.60
CTE-SG-7 TC-PE-7 380 3Ø 5.60 1.0 5.60
CTE-SG-8 TC-PE-8 380 3Ø 5.60 1.0 5.60
CTE-SG-9 TA-SEG 380 3Ø 4.10 4.10
CTE-SG-10 TF-ACI 380 3Ø 1.60 1.60
SUBTOTAL = 50.46 50.46

7.0 TABLERO STE-SEG / NIVEL -9.25 m


CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CSS-1 TS-E 380 3Ø 4.80 1.0 4.80
SUBTOTAL = 4.80 4.80

RESUMEN TABLERO GENERAL TGN-SG


ITEM DESCRIPCION TENSION FASE POTENCIA FDD M.D.
(V) (kW) (kW)

01 TABLERO TGE-SG 380 3Ø 113.76 113.76


02 TABLERO TASC-SG 380 3Ø 101.32 101.32
03 TABLERO TEM-SG 380 3Ø 150.00 150.00
04 TABLERO STE-SGS 380 3Ø 86.23 78.80
05 TABLERO STE-SGG 380 3Ø 113.14 105.85
06 TABLERO TE-SEG 380 3Ø 50.46 50.46
07 TABLERO STE-SEG 380 3Ø 4.80 4.80

TOTAL 619.71 605.00

DEMANDA ESTIMADA (KW) 605.00


FACTOR DE SIMULTANEIDAD 0.9
MAXIMA DEMANDA (KW) 544.50

POTENCIA INSTALADA = 619.71


MAXIMA DEMANDA = 544.50
CALCULO JUSTIFICATIVO DE DEMANDA MAXIMA DEL TABLERO GENERAL TGN-SG
1.0 TABLERO TGN-SG / Nivel -9.25m
CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD M.D.
N° (V) (kW) (kW)
CGN-SG-1 TDN-SG1 380 3Ø 18.30 13.70
CGN-SG-2 TSGN-1.4 380 3Ø 2.60 1.87
CGN-SG-3 TDN-SG2 380 3Ø 17.08 12.38
CGN-SG-4 TDN-SG3 380 3Ø 13.99 10.63
CGN-SG-5 TSGN-3.4 380 3Ø 3.07 2.76
CGN-SG-6 TDN-SG4 380 3Ø 39.39 28.49
CGN-SG-7 TN-AD 380 3Ø 11.39 9.97
CGN-SG-8 TF-EM-1 380 3Ø 45.00 45.00
CGN-SG-9 TF-EM-2 380 3Ø 45.00 45.00
CGN-SG-10 ESC. MECA 8 380 3Ø 15.00 1.0 15.00
CGN-SG-11 ESC. MECA 10 380 3Ø 15.00 1.0 15.00
CGN-SG-12 ESC. MECA 12 380 3Ø 15.00 1.0 15.00
CGN-SG-13 ESC. MECA 14 380 3Ø 15.00 1.0 15.00
SUBTOTAL = 255.81 229.80
SUBTABLERO TDN-SG1
SGN-1.1 TSGN-1.1 380 3Ø 6.19 4.42
SGN-1.2 TSGN-1.2 380 3Ø 9.09 7.10
SGN-1.3 TSGN-1.3 380 3Ø 3.02 2.18
SUBTOTAL = 18.30 13.70
SUBTABLERO TDN-SG2
SGN-2.1 TSGN-2.1 380 3Ø 6.15 4.52
SGN-2.2 TSGN-2.2 380 3Ø 8.41 6.08
SGN-2.3 TSGN-2.3 380 3Ø 2.52 1.78
SUBTOTAL = 17.08 12.38
SUBTABLERO TDN-SG3
SGN-3.1 TSGN-3.1 380 3Ø 6.93 5.22
SGN-3.2 TSGN-3.2 380 3Ø 2.91 2.07
SGN-3.3 TSGN-3.3 380 3Ø 4.15 3.33
SUBTOTAL = 13.99 10.63
SUBTABLERO TDN-SG4
SGN-4.1 TSGN-4.1 380 3Ø 4.02 2.68
SGN-4.2 TSGN-4.2 380 3Ø 5.19 3.53
SGN-4.3 TSGN-4.3 380 3Ø 5.13 3.40
SGN-4.4 TSGN-5.1 380 3Ø 10.82 8.52
SGN-4.5 TSGN-5.2 380 3Ø 6.39 4.40
SGN-4.6 TSGN-5.3 380 3Ø 7.84 5.96
SUBTOTAL = 39.39 28.49
SUBTABLERO TF-EM-1
CEM-1-1 ESC. MECA 16 380 3Ø 15.00 1.0 15.00
CEM-1-2 ESC. MECA 18 380 3Ø 15.00 1.0 15.00
CEM-1-3 ESC. MECA 20 380 3Ø 15.00 1.0 15.00
SUBTOTAL = 45.00 45.00
SUBTABLERO TF-EM-2
CEM-2-1 ESC. MECA 2 380 3Ø 15.00 1.0 15.00
CEM-2-2 ESC. MECA 4 380 3Ø 15.00 1.0 15.00
CEM-2-3 ESC. MECA 6 380 3Ø 15.00 1.0 15.00
SUBTOTAL = 45.00 45.00
TABLERO TGN-L / NIVEL -12.5 NPT LOCALES COMERCIALES - NORMALES
CIRC. DESCRIPCION TENSION FASE M.D. F. P. I nom. I diseño Interrrup. L S
N° (V) (kW) (A) (A) No x I (A) (m) (mm²)

CGNL-1 TLC-S.1 380 3Ø 54.9 0.80 104.3 130.3 3x 150 214 150

CGNL-2 TLC-S.2 380 3Ø 19.8 0.80 37.7 47.1 3x 60 44 16

CGNL-3 TLC-1.1 380 3Ø 74.9 0.80 142.2 177.7 3x 200 206 185

CGNL-4 TLC-1.2 380 3Ø 71.3 0.80 135.4 169.3 3x 200 96 70

CGNL-5 TLC-2.1 380 3Ø 104.8 0.80 199.0 248.8 3x 250 214 240

CGNL-6 TLC-2.2 380 3Ø 71.7 0.80 136.2 170.2 3x 150 46 50

CGNL-7 TLC-2.3 380 3Ø 93.6 0.80 177.8 222.2 3x 250 104 120

220.9

TABLERO TGE-L / NIVEL -12.5 NPT LOCALES COMERCIALES - EMERGENCIA


CIRC. DESCRIPCION TENSION FASE M.D. F. P. I nom. I diseño Interrrup. L S
N° (V) (kW) (A) (A) No x I (A) (m) (mm²)
CGNL-1 TLCE-S.1 380 3Ø 16.5 0.80 31.3 39.1 3x 60 214 50
CGNL-2 TLCE-S.2 380 3Ø 9.0 0.80 17.1 21.4 3x 80 44 25
CGNL-3 TLCE-1.1 380 3Ø 17.0 0.80 32.3 40.4 3x 50 206 50
CGNL-4 TLCE-1.2 380 3Ø 14.0 0.80 26.6 33.2 3x 40 96 25
CGNL-5 TLCE-2.1 380 3Ø 18.0 0.80 34.2 42.7 3x 50 214 50
CGNL-6 TLCE-2.2 380 3Ø 19.0 0.80 36.1 45.1 3x 50 46 25
CGNL-7 TLCE-2.3 380 3Ø 24.0 0.80 45.6 57.0 3x 60 104 25
56.5

TABLERO TGN-FCB / NIVEL -9.25 NPT LOCALES COMERCIALES-NORMALES


CIRC. DESCRIPCION TENSION FASE M.D. F. P. I nom. I diseño Interrrup. L S
N° (V) (kW) (A) (A) No x I (A) (m) (mm²)
CGNL-1 TLC-1.3 380 3Ø 192.2 0.80 365.1 456.4 3x 60 36 50
CGNL-2 REST-5 380 3Ø 37.6 0.80 71.4 89.3 3x 80 206 95
CGNL-3 REST-6 380 3Ø 32.4 0.80 61.5 76.9 3x 70 96 50
CGNL-4 REST-7 380 3Ø 37.6 0.80 71.4 89.3 3x 80 214 95
CGNL-5 REST-8 380 3Ø 29.3 0.80 55.7 69.7 3x 70 46 25
CGNL-6 CONEY PARK 380 3Ø 58.7 0.80 111.4 139.2 3x 70 330 185
CGNL-7 JUEGOS 380 3Ø 85.2 0.80 161.8 202.3 3x 200 60 95
CGNL-8 CASINO 380 3Ø 104.0 0.80 197.5 246.9 3x 200 195 185
CGNL-9 CITY TOYS 380 3Ø 78.1 0.80 148.4 185.5 3x 175 350 185
CGNL-10 INTERM. 2 380 3Ø 48.7 0.80 92.5 115.6 3x 50 145 150
299.9

TABLERO TGE-FCB / NIVEL -9.25 NPT LOCALES COMERCIALES - EMERGENCIA


CIRC. DESCRIPCION TENSION FASE M.D. F. P. I nom. I diseño Interrrup. L S
N° (V) (kW) (A) (A) No x I (A) (m) (mm²)
CGEFCB-1 TLCE-1.3 380 3Ø 24.0 0.80 45.6 57.0 3x 36 10
CGEFCB-2 REST-5 380 3Ø 3.0 0.80 5.7 7.1 3x 206 10
REST-
CGEFCB-3 6/CASINO/INTER 380 3Ø 9.0 0.80 17.1 21.4 3x 96 10
2
CGEFCB-4 REST-7 380 3Ø 3.0 0.80 5.7 7.1 3x 214 10
CGEFCB-5 REST-8 380 3Ø 3.0 0.80 5.7 7.1 3x 46 10
42.0

TABLERO TGN-SG / NIVEL -9.25 NPT NORMAL-SERVICIOS GENERALES


CIRC. DESCRIPCION TENSION FASE M.D. F. P. I nom. I diseño Interrrup. L S
N° (V) (kW) (A) (A) No x I (A) (m) (mm²)
CGN-SG-1 TSGN-1.1 380 3Ø 4.42 0.80 8.4 10.5 3x 15 155 6
CGN-SG-2 TSGN-1.2 380 3Ø 7.18 0.80 13.6 17.0 3x 15 53 6
CGN-SG-3 TSGN-1.3 380 3Ø 2.23 0.80 4.2 5.3 3x 15 128 6
CGN-SG-4 TSGN-1.4 380 3Ø 2.18 0.80 4.1 5.2 3x 15 145 6
CGN-SG-5 TSGN-2.1 380 3Ø 4.52 0.80 8.6 10.7 3x 15 148 6
CGN-SG-6 TSGN-2.2 380 3Ø 8.00 0.80 15.2 19.0 3x 15 158 10
CGN-SG-7 TSGN-2.3 380 3Ø 1.71 0.80 3.2 4.1 3x 15 44 6
CGN-SG-8 TSGN-3.1 380 3Ø 5.11 0.80 9.7 12.1 3x 15 145 6
CGN-SG-9 TSGN-3.2 380 3Ø 2.40 0.80 4.6 5.7 3x 15 155 6
CGN-SG-10 TSGN-3.3 380 3Ø 3.60 0.80 6.8 8.5 3x 15 45 6
CGN-SG-11 TSGN-3.4 380 3Ø 0.80 0.0 0.0 3x 15 161 6
CGN-SG-12 TSGN-4.1 380 3Ø 2.81 0.80 5.3 6.7 3x 15 140 6
CGN-SG-13 TSGN-4.2 380 3Ø 2.35 0.80 4.5 5.6 3x 15 37 6
CGN-SG-14 TSGN-4.3 380 3Ø 8.28 0.80 15.7 19.7 3x 15 297 16
CGN-SG-15 TSGN-5.1 380 3Ø 3.83 0.80 7.3 9.1 3x 15 100 6
CGN-SG-16 TSGN-5.2 380 3Ø 2.69 0.80 5.1 6.4 3x 15 37 6
CGN-SG-17 TSGN-5.3 380 3Ø 9.88 0.80 18.8 23.5 3x 15 290 16
CGN-SG-18 TN-AD 380 3Ø 0.80 0.0 0.0 3x 15 290 16
16.0
TABLERO TGE-SG / NIVEL -9.25 NPT EMERGENCIA-SERVICIOS GENERALES
CIRC. DESCRIPCION TENSION FASE M.D. F. P. I nom. I diseño Interrrup. L S
N° (V) (kW) (A) (A) No x I (A) (m) (mm²)
CGE-SG-1 EXTRACTOR 1 380 3Ø 18.75 0.80 35.6 44.5 3x 60 82 25
CGE-SG-2 EXTRACTOR 2 380 3Ø 18.75 0.80 35.6 44.5 3x 60 151 35
CGE-SG-3 EXTRACTOR 3 380 3Ø 18.75 0.80 35.6 44.5 3x 60 153 35
CGE-SG-4 EXTRACTOR 4 380 3Ø 15.00 0.80 28.5 35.6 3x 60 155 35
CGE-SG-5 TF-BO 380 3Ø 33.57 0.80 63.8 79.7 3x 70 91 35
CGE-SG-6 TB-BS-3 380 3Ø 4.47 0.80 8.5 10.6 3x 15 38 6
CGE-SG-7 TB-BS-4 380 3Ø 4.47 0.80 8.5 10.6 3x 15 223 10
CGE-SG-18 ASCENSOR 1 380 3Ø 15.00 0.80 28.5 35.6 3x 40 184 25
CGE-SG-19 ASCENSOR 2 380 3Ø 15.00 0.80 28.5 35.6 3x 40 50 10
CGE-SG-20 ASCENSOR 3 380 3Ø 15.00 0.80 28.5 35.6 3x 40 180 25
CGE-SG-21 ASCENSOR 4 380 3Ø 15.00 0.80 28.5 35.6 3x 40 52 25
CGE-SG-22 ASCENSOR 5 380 3Ø 15.00 0.80 28.5 35.6 3x 40 52 25
CGE-SG-24 ASCENSOR 6 380 3Ø 15.00 0.80 28.5 35.6 3x 40 236 50
71.3

TABLERO TEM-SG / NIVEL -9.25 NPT EMERGENCIA-SERVICIOS GENERALES-ESCALERAS M


CIRC. DESCRIPCION TENSION FASE M.D. F. P. I nom. I diseño Interrrup. L S
N° (V) (kW) (A) (A) No x I (A) (m) (mm²)
CEM-SG-1 ESC. MECA 1 380 3Ø 15.00 0.80 28.5 35.6 3x 40 127 25
CEM-SG-2 ESC. MECA 2 380 3Ø 15.00 0.80 28.5 35.6 3x 40 127 25
CEM-SG-3 ESC. MECA 3 380 3Ø 15.00 0.80 28.5 35.6 3x 40 112 25
CEM-SG-4 ESC. MECA 4 380 3Ø 15.00 0.80 28.5 35.6 3x 40 112 25
CEM-SG-5 ESC. MECA 5 380 3Ø 15.00 0.80 28.5 35.6 3x 40 122 25
CEM-SG-6 ESC. MECA 6 380 3Ø 15.00 0.80 28.5 35.6 3x 40 122 25
CEM-SG-7 ESC. MECA 7 380 3Ø 15.00 0.80 28.5 35.6 3x 40 130 25
CEM-SG-8 ESC. MECA 8 380 3Ø 15.00 0.80 28.5 35.6 3x 40 130 25
CEM-SG-9 ESC. MECA 9 380 3Ø 15.00 0.80 28.5 35.6 3x 40 110 25
CEM-SG-10 ESC. MECA 10 380 3Ø 15.00 0.80 28.5 35.6 3x 40 110 25
CEM-SG-11 ESC. MECA 11 380 3Ø 15.00 0.80 28.5 35.6 3x 40 158 25
CEM-SG-12 ESC. MECA 12 380 3Ø 15.00 0.80 28.5 35.6 3x 40 158 25
CEM-SG-13 ESC. MECA 13 380 3Ø 15.00 0.80 28.5 35.6 3x 40 189 25
CEM-SG-14 ESC. MECA 14 380 3Ø 15.00 0.80 28.5 35.6 3x 40 189 25
CEM-SG-15 ESC. MECA 15 380 3Ø 15.00 0.80 28.5 35.6 3x 40 101 25
CEM-SG-16 ESC. MECA 16 380 3Ø 15.00 0.80 28.5 35.6 3x 40 142 25
CEM-SG-17 ESC. MECA 17 380 3Ø 15.00 0.80 28.5 35.6 3x 40 204 35
CEM-SG-18 ESC. MECA 18 380 3Ø 15.00 0.80 28.5 35.6 3x 40 204 35
CEM-SG-19 ESC. MECA 19 380 3Ø 15.00 0.80 28.5 35.6 3x 40 25
CEM-SG-20 ESC. MECA 20 380 3Ø 15.00 0.80 28.5 35.6 3x 40 25
300.00

TABLERO STE-SG / NIVEL -9.25 NPT EMERGENCIA-SERVICIOS GENERALES


CIRC. DESCRIPCION TENSION FASE M.D. F. P. I nom. I diseño Interrrup. L S
N° (V) (kW) (A) (A) No x I (A) (m) (mm²)
CTE-SG-1 TSGE-1.1 380 3Ø 4.04 0.80 7.7 9.6 3x 20 155 6
CTE-SG-2 TSGE-1.2 380 3Ø 3.82 0.80 7.3 9.1 3x 20 53 6
CTE-SG-3 TSGE-1.3 380 3Ø 9.08 0.80 17.2 21.5 3x 20 128 6
CTE-SG-4 TSGE-1.4 380 3Ø 5.24 0.80 10.0 12.4 3x 20 145 6
CTE-SG-5 TSGE-2.1 380 3Ø 3.67 0.80 7.0 8.7 3x 20 148 6
CTE-SG-6 TSGE-2.2 380 3Ø 3.58 0.80 6.8 8.5 3x 20 158 6
CTE-SG-7 TSGE-2.3 380 3Ø 1.88 0.80 3.6 4.5 3x 20 44 6
CTE-SG-8 TSGE-3.1 380 3Ø 10.14 0.80 19.2 24.1 3x 20 145 6
CTE-SG-9 TSGE-3.2 380 3Ø 3.60 0.80 6.8 8.5 3x 20 155 6
CTE-SG-10 TSGE-3.3 380 3Ø 3.28 0.80 6.2 7.8 3x 20 45 6
CTE-SG-11 TSGE-3.4 380 3Ø 18.57 0.80 35.3 44.1 3x 20 161 6
CTE-SG-12 TSGE-4.1 380 3Ø 15.96 0.80 30.3 37.9 3x 20 140 16
CTE-SG-13 TSGE-4.2 380 3Ø 9.05 0.80 17.2 21.5 3x 20 37 6
CTE-SG-14 TSGE-4.3 380 3Ø 11.06 0.80 21.0 26.2 3x 20 297 35
CTE-SG-15 TE-AD 380 3Ø 0.80 0.0 0.0 3x 20
CTE-SG-16 TSGE-5.1 380 3Ø 11.18 0.80 21.2 26.5 3x 20 100 16
CTE-SG-17 TSGE-5.2 380 3Ø 13.78 0.80 26.2 32.7 3x 20 37 6
CTE-SG-18 TSGE-5.3 380 3Ø 11.78 0.80 22.4 28.0 3x 20 290 25
CTE-SG-19 TSGE-3.5 380 3Ø 0.80 0.0 0.0 3x 20
139.7

TABLERO TE-SEG / NIVEL -9.25 NPT EMERGENCIA-SERVICIOS GENERALES


CIRC. DESCRIPCION TENSION FASE M.D. F. P. I nom. I diseño Interrrup. L S
N° (V) (kW) (A) (A) No x I (A) (m) (mm²)
CE-SEG-1 PRESURIZ 1 380 3Ø 5.60 0.80 10.6 13.3 3x 40 184 16
CE-SEG-2 PRESURIZ 2 380 3Ø 5.60 0.80 10.6 13.3 3x 40 184 16
CE-SEG-3 PRESURIZ 3 380 3Ø 5.60 0.80 10.6 13.3 3x 40 302 25
CE-SEG-4 PRESURIZ 4 380 3Ø 5.60 0.80 10.6 13.3 3x 40 50 10
CE-SEG-5 PRESURIZ 5 380 3Ø 5.60 0.80 10.6 13.3 3x 40 55 10
CE-SEG-6 PRESURIZ 6 380 3Ø 5.60 0.80 10.6 13.3 3x 40 55 10
CE-SEG-7 PRESURIZ 7 380 3Ø 5.60 0.80 10.6 13.3 3x 40 236 16
CE-SEG-8 PRESURIZ 8 380 3Ø 5.60 0.80 10.6 13.3 3x 40 236 16
CE-SEG-9 T-SEG 380 3Ø 6.50 0.80 12.3 15.4 3x 40
CE-SEG-10 TF-ACI 380 3Ø 3.00 0.80 5.7 7.1 3x 40 94 10
22.4
R X Caida Ten. D V* D V*
(Ohms/Km) (Ohms/Km) (V) (%) (%)

0.161 0.095 7.18 1.89 1.89%

1.663 0.112 4.01 1.06 1.06%

0.130 0.095 8.17 2.15 2.15%

0.343 0.101 7.54 1.99 1.99%

0.100 0.093 10.02 2.64 2.64%

0.435 0.105 4.46 1.17 1.17%

0.197 0.096 6.89 1.81 1.81%

R X Caida Ten. D V* D V*
(Ohms/Km) (Ohms/Km) (V) (%) (%)
0.435 0.105 4.77 1.25 1.25%
0.928 0.106 1.05 0.28 0.28%
0.435 0.105 4.73 1.25 1.25%
0.928 0.106 3.56 0.94 0.94%
0.435 0.105 5.21 1.37 1.37%
0.928 0.106 2.32 0.61 0.61%
0.928 0.106 6.62 1.74 1.74%

R X Caida Ten. D V* D V*
(Ohms/Km) (Ohms/Km) (V) (%) (%)
0.435 0.105 9.36 2.46 2.46%
0.248 0.098 6.56 1.73 1.73%
0.435 0.105 4.21 1.11 1.11%
0.248 0.098 6.81 1.79 1.79%
0.928 0.106 3.58 0.94 0.94%
0.130 0.095 10.25 2.70 2.70%
0.248 0.098 4.33 1.14 1.14%
0.130 0.095 10.74 2.83 2.83%
0.130 0.095 14.48 3.81 3.81%
0.161 0.095 4.32 1.14 1.14%

R X Caida Ten. D V* D V*
(Ohms/Km) (Ohms/Km) (V) (%) (%)
2.644 0.131 6.24 1.64 1.64%
2.644 0.131 4.46 1.17 1.17%

2.644 0.131 6.24 1.64 1.64%


2.644 0.131 4.63 1.22 1.22%
2.644 0.131 1.00 0.26 0.26%

R X Caida Ten. D V* D V*
(Ohms/Km) (Ohms/Km) (V) (%) (%)
4.122 0.142 7.63 2.01 2.01%
4.122 0.142 4.24 1.11 1.11%
4.122 0.142 3.17 0.84 0.84%
4.122 0.142 3.51 0.92 0.92%
4.122 0.142 7.45 1.96 1.96%
2.644 0.131 9.12 2.40 2.40%
4.122 0.142 0.84 0.22 0.22%
4.122 0.142 8.24 2.17 2.17%
4.122 0.142 4.15 1.09 1.09%
4.122 0.142 1.80 0.47 0.47%
4.122 0.142 0.00 0.00 0.00%
4.122 0.142 4.38 1.15 1.15%
4.122 0.142 0.97 0.26 0.26%
1.663 0.112 11.31 2.98 2.98%
4.122 0.142 4.26 1.12 1.12%
4.122 0.142 1.11 0.29 0.29%
1.663 0.112 13.17 3.47 3.47%
1.663 0.112 0.00 0.00 0.00%
R X Caida Ten. D V* D V*
(Ohms/Km) (Ohms/Km) (V) (%) (%)
0.928 0.106 4.08 1.07 1.07%
0.671 0.107 5.60 1.47 1.47%
0.671 0.107 5.67 1.49 1.49%
0.671 0.107 4.60 1.21 1.21%
0.671 0.107 6.04 1.59 1.59%
4.122 0.142 1.89 0.50 0.50%
2.644 0.131 7.19 1.89 1.89%
0.928 0.106 7.32 1.93 1.93%
2.644 0.131 5.41 1.42 1.42%
0.928 0.106 7.16 1.88 1.88%
0.928 0.106 2.07 0.54 0.54%
0.928 0.106 2.07 0.54 0.54%
0.435 0.105 4.79 1.26 1.26%

S-ESCALERAS MECANICAS
R X Caida Ten. D V* D V*
(Ohms/Km) (Ohms/Km) (V) (%) (%)
0.928 0.106 5.05 1.33 1.33%
0.928 0.106 5.05 1.33 1.33%
0.928 0.106 4.45 1.17 1.17%
0.928 0.106 4.45 1.17 1.17%
0.928 0.106 4.85 1.28 1.28%
0.928 0.106 4.85 1.28 1.28%
0.928 0.106 5.17 1.36 1.36%
0.928 0.106 5.17 1.36 1.36%
0.928 0.106 4.37 1.15 1.15%
0.928 0.106 4.37 1.15 1.15%
0.928 0.106 6.28 1.65 1.65%
0.928 0.106 6.28 1.65 1.65%
0.928 0.106 7.52 1.98 1.98%
0.928 0.106 7.52 1.98 1.98%
0.928 0.106 4.02 1.06 1.06%
0.928 0.106 5.65 1.49 1.49%
0.671 0.107 6.05 1.59 1.59%
0.671 0.107 6.05 1.59 1.59%
0.928 0.106 0.00 0.00 0.00%
0.928 0.106 0.00 0.00 0.00%

R X Caida Ten. D V* D V*
(Ohms/Km) (Ohms/Km) (V) (%) (%)
4.122 0.142 6.97 1.83 1.83%
4.122 0.142 2.25 0.59 0.59%
4.122 0.142 12.93 3.40 3.40%
4.122 0.142 8.46 2.23 2.23%
4.122 0.142 6.05 1.59 1.59%
4.122 0.142 6.30 1.66 1.66%
4.122 0.142 0.92 0.24 0.24%
4.122 0.142 16.36 4.30 4.30%
4.122 0.142 6.21 1.63 1.63%
4.122 0.142 1.64 0.43 0.43%
4.122 0.142 33.27 8.76 8.76%
1.663 0.112 10.27 2.70 2.70%
4.122 0.142 3.73 0.98 0.98%
0.671 0.107 6.49 1.71 1.71%
0.00 0.00 0.00%
1.663 0.112 5.14 1.35 1.35%
4.122 0.142 5.67 1.49 1.49%
0.928 0.106 9.05 2.38 2.38%
0.00 0.00 0.00%

R X Caida Ten. D V* D V*
(Ohms/Km) (Ohms/Km) (V) (%) (%)
1.663 0.112 4.73 1.25 1.25%
1.663 0.112 4.73 1.25 1.25%
0.928 0.106 4.48 1.18 1.18%
2.644 0.131 2.02 0.53 0.53%
2.644 0.131 2.22 0.58 0.58%
2.644 0.131 2.22 0.58 0.58%
1.663 0.112 6.07 1.60 1.60%
1.663 0.112 6.07 1.60 1.60%
0.00 0.00 0.00%
2.644 0.131 2.04 0.54 0.54%
CALCULO JUSTIFICATIVO DE DEMANDA MAXIMA DEL TABLERO GENERAL STE-SG

CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD


N° (V) (W)

1.0 TABLERO TSGE-1.1


CE-1 ALUMBRADO 220 1Ø 449
CE-2 ALUMBRADO 220 1Ø 520
CE-3 ALUMBRADO 220 1Ø 1240
CE-4 ALUMBRADO 220 1Ø 1300
CE-5 ALUMB. EMERG. 220 1Ø 500 0.90
SUBTOTAL = 4009

2.0 TABLERO TSGE-1.2 / Nivel -15.50m


CE-1 ALUMBRADO 220 1Ø 1690
CE-2 ALUMBRADO 220 1Ø 780
CE-3 ALUMBRADO 220 1Ø 1040
CE-4 ALUMBRADO 220 1Ø 310
CE-5 ALUMBRADO 220 1Ø 450
CE-6 ALUMBRADO 220 1Ø 350 0.90
SUBTOTAL = 4620
3.0 TABLERO TSGE-1.3
CN-1 ALUMBRADO 220 1Ø 1742
CN-2 ALUMBRADO 220 1Ø 520
CN-3 ALUMBRADO 220 1Ø 1022
CN-4 ALUMBRADO 220 1Ø 688
CN-5 ALUMBRADO 220 1Ø 2408
CN-6 ALUMBRADO 220 1Ø 1356
CN-8 ALUMBRADO EMERG. 220 1Ø 350 0.90
CN-7 TE-CA-1 220 1Ø 868
SUBTOTAL = 8954
4.0 TABLERO TSGE-1.4
CE-1 ALUMBRADO 220 1Ø 694
CE-2 ALUMBRADO 220 1Ø 806
ALUMBRADO 220 1Ø 868
CE-3 ALUMB. EMERG. 220 1Ø 450 0.90
CE-4 EXTRACTOR EN SSHH 220 3Ø 1492 1.0
SUBTOTAL = 4310
5.0 TABLERO TSGE-2.1 / Nivel -12.50m
CE-1 ALUMBRADO 220 1Ø 817
CE-2 ALUMBRADO 220 1Ø 980
CE-3 ALUMBRADO 220 1Ø 558
CE-4 ALUMBRADO 220 1Ø 700 0.90
SUBTOTAL = 3055
6.0 TABLERO TSGE-2.2 / Nivel -12.50m
CE-1 ALUMBRADO 220 1Ø 780
CE-2 ALUMBRADO 220 1Ø 644
CE-3 ALUMBRADO 220 1Ø 650
CE-4 ALUMB. EMERG. 220 1Ø 750
CE-5 ALUMB. EMERG. 220 1Ø 450 0.90
SUBTOTAL = 3274
7.0 TABLERO TSGE-2.3
CE-1 ALUMBRADO 220 1Ø 898
CE-2 ALUMBRADO 220 1Ø 1028 0.90
CE-3 TOMACORRIENTE 220 1Ø 1200 0.45
CE-6 TSH 1,2,3 220 3Ø 10000
SUBTOTAL = 13126
8.0 TABLERO TSGE-3.1 / Nivel -9.25m
CE-1 ALUMBRADO 220 1Ø 480
CE-2 ALUMBRADO 220 1Ø 480
CE-3 ALUMBRADO 220 1Ø 780
CE-4 ALUMBRADO 220 1Ø 384
CE-5 ALUMBRADO 220 1Ø 352
CE-6 ALUMBRADO 220 1Ø 1300
CE-7 ALUMBRADO 220 1Ø 980
CE-8 ALUMBRADO 220 1Ø 1300
CE-9 RESERVA 220 1Ø -
CE-10 RESERVA 220 1Ø -
CE-11 ALUMBRADO 220 1Ø 180
CE-12 ALUMBRADO 220 1Ø 550
CE-13 ALUMBRADO 220 1Ø 100 0.90
CE-14 TE-CA 220 3Ø 10000
SUBTOTAL = 16886
9.0 TABLERO TSGE-3.2 / Nivel -9.25m
CE-1 ALUMBRADO 220 1Ø 910
CE-2 ALUMBRADO 220 1Ø 780
CE-3 RESERVA 220 1Ø -
CE-4 ALUMBRADO 220 1Ø 180
CE-5 ALUMBRADO EMERG. 220 1Ø 300
CE-6 ALUMBRADO EMERG. 220 1Ø 450
CE-7 ALUMBRADO 220 1Ø 128 0.90
SUBTOTAL = 2748
10.0 TABLERO TSGE-3.3 / Nivel -9.25m
CE-1 ALUMBRADO 220 1Ø 1300
CE-2 ALUMBRADO 220 1Ø 780
CE-3 ALUMBRADO 220 1Ø 813
CE-4 ALUMBRADO 220 1Ø 1094
CE-5 ALUMBRADO 220 1Ø 450 0.90
CE-6 EXTRACTOR EN SSHH 220 3Ø 746 1.0
CE-7 EXTRACTOR EN SSHH 220 3Ø 746 1.0
CE-7 FUERZA 220 3Ø 373 1.0
CE-7 FUERZA 220 3Ø 373 1.0
SUBTOTAL = 6675
11.0 TABLERO TSGE-3.4 / Nivel -9.25m
CE-1 ALUMBRADO 220 1Ø 1170
CE-2 ALUMBRADO 220 1Ø 650
CE-3 ALUMBRADO 220 1Ø 930
CE-4 ALUMBRADO 220 1Ø 496
CE-5 ALUMBRADO 220 1Ø 992
CE-6 ALUMBRADO 220 1Ø 620
CE-7 ALUMBRADO 220 1Ø 880
CE-8 ALUMBRADO 220 1Ø 1690
CE-9 ALUMBRADO 220 1Ø 2408
CE-10 ALUMBRADO 220 1Ø 860
CE-11 ALUMBRADO 220 1Ø 688
CE-12 ALUMBRADO 220 1Ø 860
CE-13 ALUMBRADO 220 1Ø 1300
CE-14 ALUMBRADO 220 1Ø 780
CE-15 ALUMBRADO 220 1Ø 940
CE-16 ALUMBRADO 220 1Ø 1313
CE-17 ALUMBRADO 220 1Ø 500 0.90
CE-18 EXTRACTOR EN SSHH 220 3Ø 746 1.0
CE-19 EXTRACTOR EN SSHH 220 3Ø 746 1.0
SUBTOTAL = 18569
12.0 TABLERO TSGE-3.5 / Nivel -9.25m
CE-1 ALUMBRADO 220 1Ø 372
CE-2 ALUMBRADO 220 1Ø 240
CE-3 ALUMBRADO 220 1Ø 400 0.90
CE-4 TABLERO TE-GE 220 1Ø 5000 1.0
CE-5 EXTRACTOR DE AIRE 220 3Ø 2611 1.0
CE-6 TOMACORRIENTE 220 1Ø 900 0.45
SUBTOTAL = 9523
13.0 TABLERO TSGE-4.1
CE-1 ALUMBRADO 220 1Ø 1720
CE-2 ALUMBRADO 220 1Ø 1892
CE-3 ALUMBRADO 220 1Ø 1720
CE-4 ALUMBRADO 220 1Ø 2408
CE-5 ALUMBRADO 220 1Ø 860
CE-6 ALUMBRADO 220 1Ø 1120
CE-7 ALUMBRADO 220 1Ø 560
CE-8 ALUMBRADO 220 1Ø 79.2
CE-9 ALUMBRADO 220 1Ø 860
CE-10 ALUMBRADO 220 1Ø 1095
CE-11 ALUMBRADO 220 1Ø 660
CE-12 ALUMBRADO 220 1Ø 1467 0.90
CE-13 EXTRACTOR EN SSHH 220 3Ø 746 1.0
CE-14 EQUIPO A/A, 2 kW 220 1Ø 2000 1.0
CE-15 EQUIPO A/A, 1.3kW 220 1Ø 1300 1.0
SUBTOTAL = 18487.2 1.0
14.0 TABLERO TSGE-4.2
CE-1 ALUMBRADO 220 1Ø 1920
CE-2 ALUMBRADO 220 1Ø 3956
CE-3 RESERVA 220 1Ø -
CE-4 ALUMBRADO 220 1Ø 480
CE-5 ALUMBRADO 220 1Ø 1874
CE-6 ALUMBRADO 220 1Ø 960
CE-7 ALUMBRADO 220 1Ø 582
CE-8 RESERVA 220 1Ø -
CE-9 ALUMBRADO EMERG. 220 1Ø 550 0.90
CE-10 EXTRACTOR EN SSHH 220 3Ø 373 1.0
CE-11 EQUIPO A/A, 2 kW 220 1Ø 2000 1.0
CE-12 EQUIPO A/A, 1.3kW 220 1Ø 1300 1.0
SUBTOTAL = 13995 1.0
15.0 TABLERO TSGE-4.3
CE-1 ALUMBRADO 220 1Ø 1720
CE-2 ALUMBRADO 220 1Ø 1720
CE-3 ALUMBRADO 220 1Ø 720
CE-4 ALUMBRADO 220 1Ø 880
CE-5 ALUMBRADO 220 1Ø 2236
CE-6 ALUMBRADO 220 1Ø 640
CE-7 RESERVA 220 1Ø -
CE-8 RESERVA 220 1Ø -
CE-9 ALUMBRADO 220 1Ø 1204
CE-10 ALUMBRADO 220 1Ø 480
CE-11 ALUMBRADO 220 1Ø 900
CE-12 ALUMBRADO 220 1Ø 734
CE-13 ALUMBRADO 220 1Ø 500
CE-14 ALUMBRADO 220 1Ø 500 0.90
CE-15 EXTRACTOR EN SSHH 220 3Ø 1119 1.0
CE-16 EQUIPO A/A, 2 kW 220 1Ø 2000 1.0
CE-17 EQUIPO A/A, 1.3kW 220 1Ø 1300 1.0
SUBTOTAL = 16653 1.0
16.0 TABLERO TSGE-5.1
CE-1 ALUMBRADO 220 1Ø 2236
CE-2 ALUMBRADO 220 1Ø 2064
CE-3 ALUMBRADO 220 1Ø 1376
CE-4 ALUMBRADO 220 1Ø 2752
CE-5 ALUMBRADO 220 1Ø 30
CE-6 ALUMBRADO 220 1Ø 1026
CE-7 ALUMBRADO 220 1Ø 255
CE-8 ALUMBRADO 220 1Ø 660
CE-9 ALUMBRADO 220 1Ø 650
CE-10 ALUMBRADO 220 1Ø 500 0.90
CE-11 EXTRACTOR EN SSHH 220 3Ø 746 1.0
CE-12 EQUIPO A/A, 2 kW 220 1Ø 2000 1.0
CE-13 EQUIPO A/A, 1.3kW 220 1Ø 1300 1.0
SUBTOTAL = 15595 1.0
17.0 TABLERO TSGE-5.2
CE-1 ALUMBRADO 220 1Ø 860
CE-2 ALUMBRADO 220 1Ø 805
CE-3 ALUMBRADO 220 1Ø 1032
CE-4 RESERVA 220 1Ø -
CE-5 ALUMBRADO 220 1Ø 970
CE-6 ALUMBRADO 220 1Ø 776
CE-7 ALUMBRADO 220 1Ø 582
CE-8 ALUMBRADO 220 1Ø 480
CE-9 ALUMBRADO 220 1Ø 744
CE-10 ALUMBRADO 220 1Ø 1020
CE-11 ALUMBRADO 220 1Ø 240
CE-12 ALUMBRADO 220 1Ø 1632
CE-13 ALUMBRADO 220 1Ø 500
CE-14 ALUMBRADO 220 1Ø 450 0.90
CE-15 EXTRACTOR 220 3Ø 559.5 1
CE-16 EXTRACTOR 220 3Ø 895.2 1
CE-17 ALUMBRADO 220 1Ø 1930 1
CE-18 ALUMBRADO 220 1Ø 250 1
SUBTOTAL = 13725.7
18.0 TABLERO TSGE-5.3
CE-1 ALUMBRADO 220 1Ø 172
CE-2 ALUMBRADO 220 1Ø 1376
CE-3 ALUMBRADO 220 1Ø 1892
CE-4 ALUMBRADO 220 1Ø 1892
CE-5 ALUMBRADO 220 1Ø 24
CE-6 RESERVA 220 1Ø -
CE-7 RESERVA 220 1Ø -
CE-8 ALUMBRADO 220 1Ø 900
CE-9 ALUMBRADO 220 1Ø 434
CE-10 ALUMBRADO 220 1Ø 420
CE-11 ALUMBRADO 220 1Ø 600
CE-12 ALUMBRADO 220 1Ø 550 0.90
CE-13 EXTRACTOR 220 3Ø 559.5 1
CE-14 EXTRACTOR 220 3Ø 559.5 1
SUBTOTAL = 9379
19.0 TABLERO TSGE-5.4
CE-1 ALUMBRADO 220 1Ø 240 1
CE-2 ALUMBRADO 220 1Ø 400 1
CE-3 RESERVA 220 1Ø -
CE-4 RESERVA 220 1Ø -
CE-5 FUERZA 220 1Ø 15000 1
CE-6 ALUMBRADO 220 1Ø 120 1
CE-7 ALUMBRADO 220 1Ø 10000 1
CE-8 RESERVA 220 1Ø -
CE-9 EXTRACTOR 220 3Ø 559.5 1
SUBTOTAL = 26319.5
20.0 TABLERO TE-AD
CE-1 ALUMBRADO 220 1Ø 840 1
CE-2 TRAFO 220 1Ø 6400 1
CE-3 ALUMB. EMERG. 220 3Ø 3000 1
CE-4 ALUMBRADO 220 1Ø 1892 1
CE-5 EQUIPO A/A 220 1Ø 1300 1
CE-6 EQUIPO A/A 220 1Ø 2000 1
CE-7 ALUMBRADO EMERG. 220 1Ø 350 1
SUBTOTAL = 15782 1.0

RESUMEN TABLERO GENERAL STE-SG


ITEM DESCRIPCION TENSION FASE POTENCIA FDD
(V) (kW)

1 TSGE-1.1 380 3Ø 4.01


2 TSGE-1.2 380 3Ø 4.62
3 TSGE-1.3 380 3Ø 8.95
4 TSGE-1.4 380 3Ø 4.31
5 TSGE-2.1 380 3Ø 3.06
6 TSGE-2.2 380 3Ø 3.27
7 TSGE-2.3 380 3Ø 13.13
8 TSGE-3.1 380 3Ø 16.89
9 TSGE-3.2 380 3Ø 2.75
10 TSGE-3.3 380 3Ø 6.68
11 TSGE-3.4 380 3Ø 18.57
12 TSGE-3.5 380 3Ø 9.52
13 TSGE-4.1 380 3Ø 18.49
14 TSGE-4.2 380 3Ø 14.00
15 TSGE-4.3 380 3Ø 16.65
16 TSGE-5.1 380 3Ø 15.60
17 TSGE-5.2 380 3Ø 13.73
18 TSGE-5.3 380 3Ø 9.38
19 TSGE-5.4 380 3Ø 26.32
20 TE-AD 380 3Ø 15.78

TOTAL 225.69

DEMANDA ESTIMADA (KW) 210.98


FACTOR DE SIMULTANEIDAD 0.9
MAXIMA DEMANDA (KW) 189.88

POTENCIA INSTALADA = 225.69


MAXIMA DEMANDA = 189.88
MANDA MAXIMA DEL TABLERO GENERAL STE-SG

M.D.
(W)

3608.1
3608.1

4158
4158

7277.4
0
7277.4

2536.2
1492
4028.2

2749.5
2749.5

2946.6
2946.6
1733.4
540
10000
12273

6197.4
10000
16197
2473.2
2473.2

3993.3
746
746
373
373
6231.3

15369
746
746
16861

910.8
5000
2611
405
8926.8
12997
746
2000
1300
17043
9289.8
373
2000
1300
12963

11011
1119
2000
1300
15430

10394
746
2000
1300
14440
9081.9
559.5
895.2
1930
250
12717
7434
559.5
559.5
8553

240
400

15000
120
10000

559.5
26320

840
6400
3000
1892
1300
2000
350
15782

AL STE-SG
M.D.
(kW)

3.61
4.16
7.28
4.03
2.75
2.95
12.27
16.20
2.47
6.23
16.86
8.93
17.04
12.96
15.43
14.44
12.72
8.55
26.32
15.78

210.98
CALCULO JUSTIFICATIVO DE DEMANDA MAXIMA DEL TABLERO GENERAL TGN-SG

CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD


N° (V) (W)

1.0 TABLERO TSGN-1.1


CN-1 ALUMBRADO 220 1Ø 1040
CN-2 ALUMBRADO 220 1Ø 1300
CN-3 ALUMBRADO 220 1Ø 1300 0.90
CN-4 TOMACORRIENTE 220 1Ø 1200
CN-5 TOMACORRIENTE 220 1Ø 1350 0.45
SUBTOTAL = 6190

2.0 TABLERO TSGN-1.2 / Nivel -15.50m


CN-1 ALUMBRADO 220 1Ø 780
CN-2 ALUMBRADO 220 1Ø 910
CN-3 ALUMBRADO 220 1Ø 1040
CN-4 ALUMBRADO 220 1Ø 2012
CN-5 ALUMBRADO 220 1Ø 1950 0.90
CN-6 TOMACORRIENTE 220 1Ø 1500
CN-7 TOMACORRIENTE 220 1Ø 900 0.45
SUBTOTAL = 9092

3.0 TABLERO TSGN-1.3


CN-1 ALUMBRADO 220 1Ø 1170
CN-2 ALUMBRADO 220 1Ø 650 0.90
CN-3 TOMACORRIENTE 220 1Ø 1200 0.45
SUBTOTAL = 3020
TABLERO TE-CA-1
CA-1 C. TELEF 220 1Ø 400
CA-2 P. CONTROL ACCESO 220 1Ø 300
CA-3 TRANQUERA 220 1Ø 100
CA-4 TRANQUERA 220 1Ø 100
CA-5 TRANQUERA + ACCESO+TELEF. 220 1Ø 800
CA-6 TRANQUERA 220 1Ø 100 0.90
SUBTOTAL = 1800

4.0 TABLERO TSGN-1.4 / Nivel -15.50m


CN-1 ALUMBRADO 220 1Ø 496
CN-2 ALUMBRADO 220 1Ø 620
CN-3 ALUMBRADO 220 1Ø 434 0.90
CN-4 TOMAC. SERVICIOS 220 1Ø 1050
CN-6 RESERVA 220 1Ø - 0.45
SUBTOTAL = 2600

5.0 TABLERO TSGN-2.1 / Nivel -12.50m


CN-1 ALUMBRADO 220 1Ø 1560
CN-2 ALUMBRADO 220 1Ø 1300
CN-3 ALUMBRADO 220 1Ø 1040 0.90
CN-4 TOMAC. SERVICIOS 220 1Ø 900
CN-5 TOMAC. SERVICIOS 220 1Ø 1350 0.45
SUBTOTAL = 6150
CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD
N° (V) (W)

6.0 TABLERO TSGN-2.2 / Nivel -12.50m


CN-1 ALUMBRADO 220 1Ø 1040
CN-2 ALUMBRADO 220 1Ø 1170
CN-3 ALUMBRADO 220 1Ø 650
CN-4 ALUMBRADO 220 1Ø 1560
CN-5 ALUMBRADO 220 1Ø 688 0.90
CN-6 TOMACORRIENTE 220 1Ø 1350
CN-7 TOMACORRIENTE 220 1Ø 600
CN-8 TOMACORRIENTE 220 1Ø 1350 0.45
SUBTOTAL = 8408

7.0 TABLERO TSGN-2.3


CN-1 ALUMBRADO 220 1Ø 1170 1.00
CN-2 TOMACORRIENTE 220 1Ø 900
CN-3 TOMACORRIENTE 220 1Ø 450 0.45
SUBTOTAL = 2520

8.0 TABLERO TSGN-3.1 / Nivel -9.25m


CN-1 ALUMBRADO 220 1Ø 1170
CN-2 ALUMBRADO 220 1Ø 1300
CN-3 ALUMBRADO 220 1Ø 910
CN-4 ALUMBRADO 220 1Ø 1300
CN-5 ALUMBRADO 220 1Ø 0.90
CN-6 TOMACORRIENTE 220 1Ø 1350
CN-7 TOMACORRIENTE 220 1Ø 900 0.45
SUBTOTAL = 6930

9.0 TABLERO TSGN-3.2 / Nivel -9.25m


CN-1 ALUMBRADO 220 1Ø 1430
CN-2 ALUMBRADO 220 1Ø 260
CN-3 ALUMBRADO 220 1Ø 15 0.90
CN-4 TOMACORRIENTE 220 1Ø 1200 0.45
SUBTOTAL = 2905

10.0 TABLERO TSGN-3.3 / Nivel -9.25m


CN-1 ALUMBRADO 220 1Ø 780
CN-2 ALUMBRADO 220 1Ø 1430
CN-3 ALUMBRADO 220 1Ø 1040 0.90
CN-4 TOMACORRIENTE 220 1Ø 900 0.45
SUBTOTAL = 4150

11.0 TABLERO TSGN-3.4 / Nivel -9.25m


CN-1 ALUMBRADO 220 1Ø 780
CN-2 ALUMBRADO 220 1Ø 650
CN-3 ALUMBRADO 220 1Ø 750
CN-4 ALUMBRADO 220 1Ø 402
CN-5 ALUMBRADO 220 1Ø 396
CN-6 ALUMBRADO 220 1Ø 90 0.90
SUBTOTAL = 3068

12.0 TABLERO TSGN-4.1


CN-1 ALUMBRADO 220 1Ø 475.2
CN-2 ALUMBRADO 220 1Ø 79.2
CN-3 ALUMBRADO 220 1Ø 1204
CN-4 ALUMBRADO 220 1Ø 165 0.90
CN-5 TOMACORRIENTE 220 1Ø 1050
CN-6 TOMACORRIENTE 220 1Ø 1050 0.45
SUBTOTAL = 4023.4
CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD
N° (V) (W)

13.0 TABLERO TSGN-4.2


CN-1 ALUMBRADO 220 1Ø 554.4
CN-2 ALUMBRADO 220 1Ø 132
CN-3 RESERVA 220 1Ø -
CN-4 RESERVA 220 1Ø 480
CN-5 ALUMBRADO 220 1Ø 1477 0.90
CN-6 TOMACORRIENTE 220 1Ø 1050
CN-7 TOMACORRIENTE 220 1Ø 1500 0.45
SUBTOTAL = 5193.4
14.0 TABLERO TSGN-4.3
CN-1 ALUMBRADO 220 1Ø 330
CN-2 ALUMBRADO 220 1Ø 482.4
CN-3 ALUMBRADO 220 1Ø 702
CN-4 ALUMBRADO 220 1Ø 30
CN-5 ALUMBRADO 220 1Ø 33
CN-6 ALUMBRADO 220 1Ø 480
CN-7 ALUMBRADO 220 1Ø 372 0.90
CN-8 TOMACORRIENTE 220 1Ø 1050
CN-9 TOMACORRIENTE 220 1Ø 1650 0.45
SUBTOTAL = 5129.4
15.0 TABLERO TSGN-5.1
CN-1 ALUMBRADO 220 1Ø 396
CN-2 ALUMBRADO 220 1Ø 429
CN-3 ALUMBRADO 220 1Ø 108
CN-4 ALUMBRADO 220 1Ø 450
CN-5 ALUMBRADO 220 1Ø 528
CN-6 ALUMBRADO 220 1Ø 384
CN-7 ALUMBRADO 220 1Ø 1548
CN-8 ALUMBRADO 220 1Ø 1376
CN-9 ALUMBRADO 220 1Ø 924
CN-10 ALUMBRADO 220 1Ø 1176
CN-11 ALUMBRADO 220 1Ø 400
CN-12 ALUMBRADO 220 1Ø 400 0.90
CN-13 TOMACORRIENTE 220 1Ø 2100
CN-14 TOMACORRIENTE 220 1Ø 600 0.45
SUBTOTAL = 10819
16.0 TABLERO TSGN-5.2
CN-1 ALUMBRADO 220 1Ø 429
CN-2 ALUMBRADO 220 1Ø 150
CN-3 ALUMBRADO 220 1Ø 1548
CN-4 ALUMBRADO 220 1Ø 1020
CN-5 ALUMBRADO 220 1Ø 240 0.90
CN-6 TOMACORRIENTE 220 1Ø 1200
CN-7 TOMACORRIENTE 220 1Ø 1800 0.45
SUBTOTAL = 6387
17.0 TABLERO TSGN-5.3
CN-1 ALUMBRADO 220 1Ø 561
CN-2 ALUMBRADO 220 1Ø 528
CN-3 ALUMBRADO 220 1Ø 198
CN-4 ALUMBRADO 220 1Ø 1032
CN-5 ALUMBRADO 220 1Ø 860
CN-6 ALUMBRADO 220 1Ø 320
CN-7 ALUMBRADO 220 1Ø -
CN-8 ALUMBRADO 220 1Ø -
CN-9 ALUMBRADO 220 1Ø 420 0.90
CN-10 TOMACORRIENTE 220 1Ø 1350
CN-11 TOMACORRIENTE 220 1Ø 1350 0.45
CN-12 ALUMBRADO 220 1Ø 420 1.0
CN-13 ALUMBRADO 220 1Ø 420 1.0
CN-14 ALUMBRADO 220 1Ø 380 1.0
SUBTOTAL = 7839
CIRCUITO DESCRIPCION TENSION FASE POTENCIA FDD
N° (V) (W)

18.0 TABLERO TN-AD


CN-1 ALUMBRADO 220 1Ø 1720
CN-2 ALUMBRADO 220 1Ø 1720 0.90
CN-3 TOMACORRIENTE 220 1Ø 1200
CN-4 TOMACORRIENTE 220 1Ø 750 0.45
CN-5 EQUIPO A/A, 3 kW 220 1Ø 3000 1.0
CN-6 EQUIPO A/A, 3 kW 220 1Ø 3000 1.0
SUBTOTAL = 11390
19.0 TABLERO TF-BO
CN-1 TC-BAF 380 3Ø 23872 1.0
CN-2 TC-BS1 380 3Ø 2238 1.0
CN-3 TC-BS2 380 3Ø 7460 1.0
SUBTOTAL = 33570
20.0 TABLERO TF-ACI
CN-1 TC-BJ 220 1Ø 800 1.0
CN-2 TC-BAF 220 1Ø 800 1.0
SUBTOTAL = 1600
21.0 TABLERO TA-SEG
CN-1 PANEL ACI 220 1Ø 800 1.0
CN-2 PANEL CONTROL ACCESO 220 1Ø 800 1.0
CN-3 CCTV 220 1Ø 1000 1.0
CN-4 SISTEMA PERIFONEO 220 1Ø 1000 1.0
CN-5 MONITOREO 220 1Ø 500 1.0
SUBTOTAL = 4100

RESUMEN TABLERO GENERAL TGN-SG


ITEM DESCRIPCION TENSION FASE POTENCIA FDD
(V) (kW)

1 TSGN-1.1 380 3Ø 6.19


2 TSGN-1.2 380 3Ø 9.09
3 TSGN-1.3 380 3Ø 3.02
4 TSGN-1.4 380 3Ø 2.60
5 TSGN-2.1 380 3Ø 6.15
6 TSGN-2.2 380 3Ø 8.41
7 TSGN-2.3 380 3Ø 2.52
8 TSGN-3.1 380 3Ø 6.93
9 TSGN-3.2 380 3Ø 2.91
10 TSGN-3.3 380 3Ø 4.15
11 TSGN-3.4 380 3Ø 3.07
12 TSGN-4.1 380 3Ø 4.02
13 TSGN-4.2 380 3Ø 5.19
14 TSGN-4.3 380 3Ø 5.13
15 TSGN-5.1 380 3Ø 10.82
16 TSGN-5.2 380 3Ø 6.39
17 TSGN-5.3 380 3Ø 7.84
18 TN-AD 380 3Ø 11.39
19 TE-CA-1 380 3Ø 1.80

TOTAL 107.61

DEMANDA ESTIMADA (KW) 81.42


FACTOR DE SIMULTANEIDAD 0.9
MAXIMA DEMANDA (KW) 73.28

POTENCIA INSTALADA = 107.61


MAXIMA DEMANDA = 73.28
EMANDA MAXIMA DEL TABLERO GENERAL TGN-SG

M.D.
(W)

3276

1147.5
4423.5

6022.8

1080
7102.8

1638
540
2178

1620
1620

1395

472.5
1867.5

3510

1012.5
4522.5
M.D.
(W)

4597.2

1485
6082.2

1170

607.5
1777.5

4212

1012.5
5224.5

1534.5
540
2074.5

2925
405
3330

2761.2
2761.2

1731.1
945
2676.1
M.D.
(W)

2379.1

1147.5
3526.6

2186.5

1215
3401.5

7307.1

1215
8522.1

3048.3

1350
4398.3
3527.1

1215
420
420
380
5962.1
M.D.
(W)

3096

877.5
3000
3000
9973.5

23872
2238
7460
33570

800
800
1600

800
800
1000
1000
500
4100

AL TGN-SG
M.D.
(kW)

4.42
7.10
2.18
1.87
4.52
6.08
1.78
5.22
2.07
3.33
2.76
2.68
3.53
3.40
8.52
4.40
5.96
9.97
1.62

81.42
SISTEMA METRICO
DATOS CONSTRUCTIVOS - TW DATO
Sección Numero Espesor de Diámetro Peso Sección
Nominal de Hilos la Aislación Exterior Kg/Km Nominal
mm² N° mm mm mm²
Conductor Solido
1.5 1 0.75 0 3 20 1.5
2.5 1 0.75 3.2 3.5 30 2.5
4 1 0.75 3.7 4 45 4
6 1 0.75 4.2 4.5 65 6
10 1 1.15 5 6 115 10
Conductor Cableado
2.5 7 0.75 0 4 35 2.5
4 7 0.75 4.1 4.5 50 4
6 7 0.75 4.6 5 70 6
10 7 1.15 5.4 6.5 120 10
16 7 1.5 7.2 8.5 195 16
25 7 1.5 8.8 9.5 290 25
35 7 1.5 9.9 11 390 35
50 19 2 11.5 13 530 50
70 19 2 13.5 15 750 70
95 19 2 15.5 17 1000 95
120 37 2.4 18 20 1280 120
150 37 2.4 20.3 21 1550 150
185 37 2.4 21.5 23 1910 185
240 61 2.4 24 26 2460 240
300 61 2.8 27 29 3100 300
400 61 2.8 30 32 3920 400
500 61 2.8 33 35 4890 500
SISTEMA METRICO
DATOS CONSTRUCTIVOS - THW
Numero Espesor de Diámetro Peso
de Hilos Aislación Exterior Kg/Km
N° mm mm
Conductor Solido
1 1.15 4 30
1 1.15 4.5 40
1 1.15 5 55
1 1.15 5.5 75
1 1.5 7 125
Conductor Cableado
7 1.15 4.5 40
7 1.15 5 60
7 1.15 5.5 80
7 1.5 7.5 130
7 1.5 8.5 195
7 1.5 9.5 290
7 1.5 11 390
19 2 13 530
19 2 15 750
19 2 17 1000
37 2.4 20 1280
37 2.4 21 1550
37 2.4 23 1900
61 2.4 26 2460
61 2.8 29 3100
61 2.8 32 3920
61 2.8 35 4890
CUADRO DE MAXIMA DEMANDA - CC LA CURVA
SUBESTACIONES ELECTRICAS

SUMIN. SUB
N° DESCRIPCION
ESTACION

MT-1.1 SE "A" TR-1

MT-1.2 SE "A" TR-2


MT-1.3 SE "B" TR-3
RESUMEN CUADRO DE CARGAS

DESCRIPCION C.I. M.D.


(kW) (kW)

SUBESTACION "A" TR-1 #REF! #REF!

SUBESTACION "A" TR-2 #REF! #REF!

SUBESTACION "B" TR-3 #REF! #REF!

SUBTOTAL #REF! #REF!


FACTOR DE SIMULTANEIDAD = 0.65
POTENCIA SIMULTANEA = #REF!
1 2 3 6 7 8 ###

MEMORIA DE CALCULO - SUBESTACION ELECTRICA "A"

###
### #REF!
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D.

N° (V) (kW) (kW)


#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!

SUBTOTAL 380 3Ø #REF! #REF! ###

### #REF!
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D.

N° (V) (kW) (kW)


#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! 1.00 #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###

SUBTOTAL 380 3Ø #REF! #REF! ###

CARGA INSTALADA SE "A" TR-1 = #REF!


MAXIMA DEMANDA SE "A" TR-1 = #REF!

TR-1 : TRANSFORMADOR LOCALES COMERCIALES


TOTAL MAXIMA DEMANDA (kW) #REF!
FACTOR DE SIMULTANEIDAD 0.80
CARGA ELECTRICA SIMULTANEA ( kW) #REF!
FACTOR DE POTENCIA 0.85
POTENCIA APARENTE TOTAL (KVA) #REF!
RESERVA 10%
POTENCIA TOTAL (KVA) #REF!

POTENCIA DEL TRANSFORMADOR 1,000 kVA


###
### #REF!
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D.

N° (V) (kW) (kW)


#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF!

SUBTOTAL 380 3Ø #REF! #REF! ###

### #REF!
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D.

N° (V) (kW) (kW)


#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF! ###
#REF! #REF! #REF! #REF! #REF! #REF! #REF!

SUBTOTAL 380 3Ø #REF! #REF! ###

CARGA INSTALADA SE "A" TR-2 = #REF!


MAXIMA DEMANDA SE "A" TR-2 = #REF!

TR-2 : TRANSFORMADOR LOCALES Y SERVICIOS


TOTAL MAXIMA DEMANDA (kW) #REF!
FACTOR DE SIMULTANEIDAD 0.85
CARGA ELECTRICA SIMULTANEA ( kW) #REF!
FACTOR DE POTENCIA 0.85
POTENCIA APARENTE TOTAL (KVA) #REF!
RESERVA 15%
POTENCIA TOTAL (KVA) #REF!

POTENCIA DEL TRANSFORMADOR 1,000 kVA

B.1. SELECCIÓN DEL GRUPO ELECTROGENO


MAXIMA DEMANDA TGE-A1 (kW) : #REF!
MAXIMA DEMANDA TGE-A2 (kW) : #REF!
MAXIMA DEMANDA EMERG. TOTAL (kW) #REF!
FACTOR DE SIMULTANEIDAD 0.85
CARGA SIMULTANEA EN EMERGENCIA #REF!
RESERVA 20%
POTENCIA TOTAL (kW) #REF!

POTENCIA GRUPO ELECTROGENO 450 kW


MEMORIA DE CALCULO - SUBESTACION ELECTRICA "A"

A. TRANSFORMADOR TR-2
1.0 TABLERO TGN-A2
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. I nom. I diseño Interrrup. L S D V*

N° (V) (kW) (kW) (A) (A) Calculado (m) (mm²) (%)


GNA2-1 TLCN-B-P4 380 3Ø #REF! #REF! #REF! #REF! 3x ### 30 ### #REF!
GNA2-2 TD-SGN-SEB 380 3Ø 24.80 1.00 24.80 47.1 58.9 3x 63 15 16 0.45
GNA2-3 TM-1 380 3Ø 126.2 0.80 100.97 191.8 239.7 3x 250 93 185 1.42
GNA2-4 TM-2 380 3Ø 91.0 0.80 72.79 138.2 172.8 3x 175 93 120 1.33
GNA2-5 GYM 380 3Ø 100.9 0.80 80.71 153.3 191.6 3x 200 112 240 1.15
GNA2-6 JUEGOS 380 3Ø 69.6 0.90 62.63 118.9 148.7 3x 150 87 70 1.96
GNA2-7 TG-OESCHLE 380 3Ø 362.0 0.80 289.60 550.0 687.5 3x 800 87 240 1.60

SUBTOTAL 380 3Ø #REF! #REF! #REF! #REF! 3x ### 5 ### #REF!

B. TRANSFORMADOR TR-1
1.0 TABLERO TGN-A1
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. I nom. I diseño Interrrup. L S D V*

N° (V) (kW) (kW) (A) (A) Calculado (m) (mm²) (%)


GNA1-1 TLC-A-S1 380 3Ø #REF! #REF! #REF! #REF! 3x ### 78 240 #REF!
GNA1-2 TLC-A-P1 380 3Ø #REF! #REF! #REF! #REF! 3x 500 75 120 #REF!
GNA1-3 TLC-A-P3 380 3Ø #REF! #REF! #REF! #REF! 3x ### 80 ### #REF!
GNA1-4 TD-SGN-SEA 380 3Ø 70.5 0.85 59.9 113.8 142.3 3x 150 20 70 0.43
GNA1-5 TNF-EM 380 3Ø 36.0 0.85 30.6 58.1 72.6 3x 100 138 70 1.52
SUBTOTAL 380 3Ø #REF! #REF! #REF! #REF! 3x ### 5 240 #REF!
2.0 TABLERO TGE-A1
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. I nom. I diseño Interrrup. L S D V*

N° (V) (kW) (kW) (A) (A) Calculado (m) (mm²) (%)


GEA1-1 TF-BCI 380 3Ø 12.00 0.85 10.20 19.4 24.2 3x 32 130 16 1.60
GEA1-2 TD-SGE-SEA 380 3Ø 46.40 0.85 39.44 74.9 93.6 3x 100 20 35 0.39
GEA1-3 TF-BAF 380 3Ø 40.10 0.85 34.09 64.7 80.9 3x 100 130 50 1.97
GEA1-4 TEF-EM 380 3Ø 36.00 0.85 30.60 58.1 72.6 3x 100 138 50 1.88
GEA1-5 T-ADM 380 3Ø 30.00 1.00 30.00 57.0 71.2 3x 100 50 35 0.73

SUBTOTAL 380 3Ø 164.5 144.3 274.1 334.4 3x 400 10 300 0.15

TR-1 : TRANSFORMADOR LOCALES COMERCIALES


TOTAL MAXIMA DEMANDA (kW) #REF!
FACTOR DE SIMULTANEIDAD 0.80
CARGA ELECTRICA SIMULTANEA ( kW) #REF!
FACTOR DE POTENCIA 0.80
POTENCIA APARENTE TOTAL (KVA) #REF!
RESERVA 5%
POTENCIA TOTAL (KVA) #REF!

POTENCIA DEL TRANSFORMADOR 2,000 kVA

B.1. SELECCIÓN DEL GRUPO ELECTROGENO


MAXIMA DEMANDA EMERG. SE A (kW) : 144.3
MAXIMA DEMANDA EMERG. SE B (kW) : #REF!
MAXIMA DEMANDA EMERG. TOTAL (kW) : #REF!
FACTOR DE SIMULTANEIDAD 0.85
CARGA SIMULTANEA EN EMERGENCIA (kW #REF!
RESERVA 20%
POTENCIA TOTAL (kW) #REF!
POTENCIA GRUPO ELECTROGENO 350 kW
ALIMENTADOR

#REF!
N2XH 3-1x16mm² +1x16mm²(N)+1x10mm²(T)-40mmØ EMT
N2XH 3-1x185mm² +1x185mm²(N)+1x35mm²(T)-100mmØ EMT
N2XH 3-1x120mm² +1x120mm²(N)+1x35mm²(T)-90mmØ EMT
N2XH 3-1x240mm² +1x240mm²(N)+1x50mm²(T)-100mmØ EMT
N2XH 3-1x70mm² +1x70mm²(N)+1x25mm²(T)-80mmØ EMT
N2XH 2(3-1x240mm² +1x240mm²(N)-100mmØ EMT) +1x70mm²(T)

#REF!

ALIMENTADOR

#REF!
#REF!
#REF!
N2XH 3-1x70mm² +1x70mm²(N)+1x25mm²(T)-80mmØ EMT
N2XH 3-1x70mm² +1x70mm²(N)+1x25mm²(T)-80mmØ EMT
#REF!
ALIMENTADOR

N2XH 3-1x16mm² +1x16mm²(N)+1x10mm²(T)-40mmØ EMT


N2XH 3-1x35mm² +1x35mm²(N)+1x10mm²(T)-50mmØ EMT
N2XH 3-1x50mm² +1x50mm²(N)+1x16mm²(T)-65mmØ EMT
N2XH 3-1x50mm² +1x50mm²(N)+1x16mm²(T)-65mmØ EMT
N2XH 3-1x35mm² +1x35mm²(N)+1x10mm²(T)-50mmØ EMT

N2XH 3-1x300mm² +1x300mm²(N)+1x50mm²(T)-130mmØ EMT


MEMORIA DE CALCULO -SERVICIOS
1.0 TABLERO T-LAB
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CLAB-1 ALUMBRADO 220 1Ø 1.08 0.90 0.97 0.80 5.5 1x 20 10
CLAB-2 ALUMBRADO 220 1Ø 1.02 0.90 0.92 0.80 5.2 1x 20 25
CLAB-3 ALUMBRADO 220 1Ø 0.48 0.90 0.43 0.80 2.5 1x 20 8
CLAB-4 ALUMBRADO 220 1Ø 1.20 0.90 1.08 0.80 6.1 1x 20 16
CLAB-5 ALUMBRADO 220 1Ø 1.20 0.90 1.08 0.80 6.1 1x 20 20
CLAB-6 ALUMBRADO 220 1Ø 0.72 0.90 0.65 0.80 3.7 1x 20 18
CLAB-7 ALUMBRADO 220 1Ø 0.72 0.90 0.65 0.80 3.7 1x 20 24
CLAB-8 ALUMBRADO 220 1Ø 0.42 0.90 0.38 0.80 2.1 1x 20 30
CLAB-9 ALUMBRADO EXTERIOR 220 1Ø 0.40 0.90 0.36 0.80 2.0 1x 20 55
CLAB-10 TOMACORRIENTE 220 1Ø 0.90 0.50 0.45 0.80 2.6 1x 20 15
CLAB-11 TOMACORRIENTE 220 1Ø 0.90 0.50 0.45 0.80 2.6 1x 20 18
CLAB-12 TOMACORRIENTE 220 1Ø 0.90 0.50 0.45 0.80 2.6 1x 20 20
CLAB-13 TOMACORRIENTE 220 1Ø 0.90 0.50 0.45 0.80 2.6 1x 20 22
CLAB-14 TOMACORRIENTE 220 1Ø 0.90 0.50 0.45 0.80 2.6 1x 20 21
CLAB-15 TOMACORRIENTE 220 1Ø 0.90 0.50 0.45 0.80 2.6 1x 20 23
CLAB-16 REFRIGERADORA 1 220 1Ø 0.90 0.80 0.72 0.80 4.1 1x 20 12
CLAB-17 REFRIGERADORA 2 220 1Ø 0.90 0.80 0.72 0.80 4.1 1x 20 13
CLAB-18 REFRIGERADORA 3 220 1Ø 0.90 0.80 0.72 0.80 4.1 1x 20 16
CLAB-19 REFRIGERADORAS 4 220 1Ø 0.90 0.80 0.72 0.80 4.1 1x 20 21
CLAB-20 TABLERO TFAA-2 380 3Ø 27.90 0.90 25.11 0.80 47.7 3x 63 28
CLAB-21 UE-18 220 1Ø 1.52 1.00 1.52 0.80 8.6 1x 20 12
CLAB-22 UE-19 220 1Ø 0.53 1.00 0.53 0.80 3.0 1x 20 8
CLAB-23 UE-20 220 1Ø 0.53 1.00 0.53 0.80 3.0 1x 20 15
CLAB-24 UE-21 220 1Ø 1.52 1.00 1.52 0.80 8.6 1x 20 24
CLAB-25 UE.22 220 1Ø 0.57 1.00 0.57 0.80 3.3 1x 20 26
CLAB-26 UE-23 220 1Ø 1.52 1.00 1.52 0.80 8.6 1x 20 32
CLAB-27 UE-24 220 1Ø 0.45 1.00 0.45 0.80 2.6 1x 20 36
CLAB-28 V-5 220 1Ø 0.38 1.00 0.38 0.80 2.1 1x 20 6
CLAB-29 E-17 220 1Ø 0.45 1.00 0.45 0.80 2.6 1x 20 38
CLAB-30 TF-ACI 380 3Ø 4.00 0.90 3.60 0.80 6.8 3x 20 22
CLAB-31 CAMARA BIOSEGURIDAD 1 220 1Ø 1.50 1.00 1.50 0.80 8.5 1x 20 15
CLAB-32 CAMARA BIOSEGURIDAD 2 220 1Ø 1.50 1.00 1.50 0.80 8.5 1x 20 18
CLAB-33 AUTOCLAVE 1 220 1Ø 3.50 0.80 2.80 0.80 15.9 1x 20 20
CLAB-34 AUTOCLAVE2 220 1Ø 3.50 0.80 2.80 0.80 15.9 1x 20 22
CLAB-35 AUTOCLAVE 3 380 3Ø 3.50 0.80 2.80 0.80 5.3 3x 20 20
CLAB-36 BOMBA DE VACIO 220 1Ø 0.55 1.00 0.55 0.80 3.1 1x 20 18
CLAB-37 BOMBA PERISTALTICA 380 3Ø 0.70 1.00 0.70 0.80 1.3 3x 20 19
CLAB-38 ELECTROBOMBA A. FRIA 380 3Ø 2.00 1.00 2.00 0.80 3.8 3x 20 140

SUBTOTAL 72.3 62.9


2.0 TABLERO T-ECH
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CECH-1 ALUMBRADO 220 1Ø 0.44 0.90 0.4 0.80 2.3 1x 20 8
CECH-2 TOMACORRIENTE 220 1Ø 0.90 0.50 0.5 0.80 2.6 1x 20 6
CECH-3 AA UCD-3 220 1Ø 2.85 0.90 2.6 0.80 14.6 1x 20 10
CECH-4 ELECTROBOMBA A. FRIA 220 1Ø 1.13 1.00 1.1 0.80 6.4 1x 20 12

SUBTOTAL 380 3Ø 5.3 4.5


3.0 TABLERO ST-SEG
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CSEG-1 ALUMBRADO 220 1Ø 0.71 1.00 0.7 0.80 4.0 1x 20 14
CSEG-2 ALUMBRADO 220 1Ø 0.41 1.00 0.4 0.80 2.3 1x 20 16
CSEG-3 ALUMBRADO EXTERIOR 220 1Ø 0.24 1.00 0.2 0.80 1.4 1x 20 30
CSEG-4 TOMACORRIENTES 220 1Ø 1.20 1.00 1.2 0.80 6.8 1x 20 16
CSEG-5 TOMACORRIENTES 220 1Ø 0.75 1.00 0.8 0.80 4.3 1x 20 14
CSEG-6 COCINILLA ELECTRICA 220 1Ø 2.00 1.00 2.0 0.80 11.4 1x 20 8
CSEG-7 MICROONDAS 220 1Ø 1.50 1.00 1.5 0.80 8.5 1x 20 10
CSEG-8 REFRIGERADOR 220 1Ø 0.60 1.00 0.6 0.80 3.4 1x 20 12
CSEG-9 EQUIPOS DE COCINA 220 1Ø 0.53 1.00 0.5 0.80 3.0 1x 20 12
CSEG-10 UCD-04 220 1Ø 2.60 1.00 2.6 0.80 14.8 1x 20 25
CSEG-11 CALENTADOR ELECTRICO 220 1Ø 2.00 0.60 1.2 0.80 6.8 1x 20 26
CSEG-12 UE 220 1Ø 0.70 0.60 0.4 0.80 2.4 1x 20 12
CSEG-13 UE 220 1Ø 0.90 0.60 0.5 0.80 3.1 1x 20 18
CSEG-14 E-19, V-13 220 1Ø 0.55 1.00 0.6 0.80 3.1 1x 20 21
CSEG-15 V-4, E-16, E5 220 1Ø 0.60 1.00 0.6 0.80 3.4 1x 20 22

SUBTOTAL 380 3Ø 15.3 13.8


4.0 TABLERO T-SEG
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CS-1 SUBTABLERO ST-SEG 380 3Ø 15.30 1.00 13.8 0.80 26.2 3x 40 14
CS-2 EQUIPO UC-2 380 3Ø 8.10 1.00 8.1 0.80 15.4 3x 20 8
CS-3 T-UPS 220 1Ø 5.00 0.85 4.3 0.80 24.1 1x 32 3
CS-4 ELECROBOMBA A. FRIA 380 3Ø 2.00 1.00 2.0 0.80 3.8 3x 20 35

SUBTOTAL 380 3Ø 30.4


5.0 TABLERO T-OFI
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


COFI-1 ALUM. 220 1Ø 0.54 1.00 0.5 0.80 3.1 1x 20 50
COF-2 ALUM. 220 1Ø 0.42 1.00 0.4 0.80 2.4 1x 20 50
COFI-3 ALUM. 220 1Ø 0.48 1.00 0.5 0.80 2.8 1x 20 50
COFI-4 ALUM. 220 1Ø 0.67 1.00 0.7 0.80 3.8 1x 20 50
COFI-5 ALUM. 220 1Ø 0.30 1.00 0.3 0.80 1.7 1x 20 50
COFI-6 ALUM. 220 1Ø 0.54 1.00 0.5 0.80 3.1 1x 20 50
COFI-7 ALUM. EXTERIORES 220 1Ø 0.30 1.00 0.3 0.80 1.7 1x 20 50
COFI-8 TOMACORRIENTES 220 1Ø 0.30 1.00 0.3 0.80 1.7 1x 20 50
COFI-9 TOMACORRIENTES 220 1Ø 0.30 1.00 0.3 0.80 1.7 1x 20 50
COF-10 TOMACORRIENTES 220 1Ø 0.26 1.00 0.3 0.80 1.5 1x 20 50
COF-11 TABOLA 220 1Ø 0.53 1.00 0.5 0.80 3.0 1x 20 50
COFI-12 FRIO 220 1Ø 0.30 1.00 0.3 0.80 1.7 1x 20 50
COFI-13 REFRIGERADORA 220 1Ø 0.30 1.00 0.3 0.80 1.7 1x 20 50
COF-14 MICROONDAS 220 1Ø 0.30 1.00 0.3 0.80 1.7 1x 20 50
COFI-15 EQUIPOS DE COCINA 220 1Ø 0.83 1.00 0.8 0.80 4.7 1x 20 50
COF-16 SECADORA DE MANOS 220 1Ø 1.20 1.00 1.2 0.80 6.8 1x 20 50
COF-17 SECADORA DE MANOS 220 1Ø 1.20 1.00 1.2 0.80 6.8 1x 20 50
COFI-18 SECADORA DE MANOS 220 1Ø 1.20 1.00 1.2 0.80 6.8 1x 20 50
COFI-19 SECADORA DE MANOS 220 1Ø 1.20 1.00 1.2 0.80 6.8 1x 20 50
COFI-20 T.EST 220 1Ø 3.80 1.00 3.8 0.80 21.6 1x 32 50
COFI-21 TF-AA 220 1Ø 27.90 1.00 27.9 0.80 158.5 1x 200 50
COFI-22 UE-1 220 1Ø 1.21 1.00 1.2 0.80 6.9 1x 20 50
COFI-23 UE-2 220 1Ø 0.45 1.00 0.5 0.80 2.6 1x 20 50
COFI-24 UE-9 220 1Ø 0.90 1.00 0.9 0.80 5.1 1x 20 50
COFI-25 UE-8 220 1Ø 0.60 1.00 0.6 0.80 3.4 1x 20 50
COFI-26 UE-11 220 1Ø 1.52 1.00 1.5 0.80 8.6 1x 20 50
COFI-27 UE-12 220 1Ø 1.52 1.00 1.5 0.80 8.6 1x 20 50
COFI-28 UE-13 220 1Ø 0.41 1.00 0.4 0.80 2.3 1x 20 50
COFI-29 E-9 220 1Ø 0.59 0.60 0.4 0.80 2.0 1x 20 50
COFI-30 E-10 220 1Ø 0.65 0.60 0.4 0.80 2.2 1x 20 50
COFI-31 ELECTROBOMBA AGUA FRIA 220 1Ø 3.21 0.50 1.6 0.80 9.1 1x 20 50
COFI-32 CALENTADOR ELECTRICO 220 1Ø 2.00 1.00 2.0 0.80 11.4 1x 20 50

SUBTOTAL 380 3Ø 56.0 53.9


6.0 TABLERO T-MAE
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CMAE-1 ALUMBRADO 220 1Ø 1.02 0.90 0.9 0.80 5.2 1x 20 15
CMAE-2 TOMACORRIENTES 220 1Ø 0.90 0.50 0.5 0.80 2.6 1x 20 20
CMAE-3 TOMACORRIENTES 220 1Ø 0.60 0.50 0.3 0.80 1.7 1x 20 18
CMAE-4 ELEVADOR 1 380 3Ø 2.20 1.00 2.2 0.80 4.2 3x 20 15
CMAE-5 ELEVADOR 2 380 3Ø 2.20 1.00 2.2 0.80 4.2 3x 20 15
CMAE-6 MAQUINA DE SOLDAR 380 3Ø 5.00 1.00 5.0 0.80 9.5 3x 20 16
CMAE-7 ELECROBOMBA DE AGUA FRIA 220 1Ø 0.75 1.00 0.8 0.80 4.3 1x 20 14

SUBTOTAL 380 3Ø 12.7 11.8


7.0 TABLERO T-VIG 1
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CVIG1-1 ALUMBRADO 220 1Ø 0.28 0.90 0.3 0.80 1.5 1x 20 6
CVIG1-2 TOMACORRIENTES 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 5
CVIG1-3 TRANQUERA 1 220 1Ø 0.38 1.00 0.4 0.80 2.1 1x 20 16
CVIG1-4 TRANQUERA 2 220 1Ø 0.38 1.00 0.4 0.80 2.1 1x 20 18
CVIG1-5 TRANQUERA 3 220 1Ø 0.38 1.00 0.4 0.80 2.1 1x 20 20
CVIG1-6 TRANQUERA 4 220 1Ø 0.38 1.00 0.4 0.80 2.1 1x 20 34
CVIG1-7 EQUIPO AA 220 1Ø 2.85 0.90 2.6 0.80 14.6 1x 20 16
CVIG1-8 ELECTROBOMBA A. FRIA 380 3Ø 2.20 1.00 2.2 0.80 4.2 3x 20 22
CVIG1-9 ANTENA 220 1Ø 0.15 1.00 0.2 0.80 0.9 1x 20 5
CVIG1-10 CONTROLADOR 220 1Ø 0.20 1.00 0.2 0.80 1.1 1x 20 4
CVIG1-11 COMPUTADORAS 220 1Ø 0.50 0.85 0.4 0.80 2.4 1x 20 6

SUBTOTAL 380 3Ø 8.1 7.5


8.0 TABLERO T-VIG 2
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CVIG2-1 ALUMBRADO 220 1Ø 0.90 0.90 0.8 0.80 4.6 1x 20 6
CVIG2-2 TOMACORRIENTES 220 1Ø 0.50 0.50 0.3 0.80 1.4 1x 20 5
CVIG2-3 EQUIPO AA 380 3Ø 0.90 0.90 0.8 0.80 1.5 3x 20 20
CVIG2-4 ELECTROBOMBA A.FRIA 380 3Ø 0.75 1.00 0.8 0.80 1.4 3x 20 18
CVIG2-5 SEMAFORO 220 1Ø 0.20 1.00 0.2 0.80 1.1 1x 20 25
CVIG2-6 BALANZA 1 380 3Ø 0.75 1.00 0.8 0.80 1.4 3x 20 33
CVIG2-7 BALANZA 2 380 3Ø 0.75 1.00 0.8 0.80 1.4 3x 20 35
CVIG2-8 ANTENA 220 1Ø 0.15 1.00 0.2 0.80 0.9 1x 20 8
CVIG2-9 COMPUTADORAS 220 1Ø 0.50 0.85 0.4 0.80 2.4 1x 20 13

SUBTOTAL 380 3Ø 5.4 4.9

9.0 TABLERO T-TOR1


CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CTOR1-1 ALUMBRADO 220 1Ø 0.35 0.90 0.3 0.80 1.8 1x 20 50
CTOR1-2 ALUMBRADO 220 1Ø 0.40 0.90 0.4 0.80 2.0 1x 20 50
CTOR1-3 ALUMBRADO EXTERIORES 220 1Ø 0.16 1.00 0.2 0.80 0.9 1x 20 50
CTOR1-4 ELECTROBOMBA AGUA FRIA 220 1Ø 1.50 0.50 0.8 0.80 4.3 1x 20 50
CTOR1-5 TOMACORRIENTES 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 50
CTOR1-6 TOMACORRIENTES 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 50
CTOR1-7 T-UPS 220 1Ø 4.60 0.85 3.9 0.80 22.2 1x 32 50
CTOR1-8 UCD 380 3Ø 6.50 1.00 6.5 0.80 12.3 3x 20 50

SUBTOTAL 380 3Ø 14.4 12.4


10.0 TABLERO T-TOR 2
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CTOR2-1 ALUMBRADO 220 1Ø 0.35 0.90 0.3 0.80 1.8 1x 20 50
CTOR2-2 ALUMBRADO 220 1Ø 0.40 0.90 0.4 0.80 2.0 1x 20 50
CTOR2-3 ALUMBRADO EXTERIORES 220 1Ø 0.16 1.00 0.2 0.80 0.9 1x 20 50
CTOR2-4 ELECTROBOMBA AGUA FRIA 220 1Ø 1.50 0.50 0.8 0.80 4.3 1x 20 50
CTOR2-5 TOMACORRIENTES 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 50
CTOR2-6 TOMACORRIENTES 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 50
CTOR2-7 T-UPS 220 1Ø 4.60 0.85 3.9 0.80 22.2 1x 32 50
CTOR2-8 UCD 380 3Ø 6.50 1.00 6.5 0.80 12.3 3x 20 50

SUBTOTAL 380 3Ø 14.4 12.4


11.0 TABLERO T-TOR-3
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CTOR3-1 ALUMBRADO 220 1Ø 0.35 0.90 0.3 0.80 1.8 1x 20 50
CTOR3-2 ALUMBRADO 220 1Ø 0.40 0.90 0.4 0.80 2.0 1x 20 50
CTOR3-3 ALUMBRADO EXTERIORES 220 1Ø 0.16 1.00 0.2 0.80 0.9 1x 20 50
CTOR3-4 ELECTROBOMBA AGUA FRIA 220 1Ø 1.50 0.50 0.8 0.80 4.3 1x 20 50
CTOR3-5 TOMACORRIENTES 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 50
CTOR3-6 TOMACORRIENTES 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 50
CTOR3-7 T-UPS 220 1Ø 4.60 0.85 3.9 0.80 22.2 1x 32 50
CTOR3-8 UCD 380 3Ø 6.50 1.00 6.5 0.80 12.3 3x 20 50

SUBTOTAL 380 3Ø 14.4 12.4

12.0 TABLERO T-TOR 4


CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CTOR4-1 ALUMBRADO 220 1Ø 0.35 0.90 0.3 0.80 1.8 1x 20 50
CTOR4-2 ALUMBRADO 220 1Ø 0.40 0.90 0.4 0.80 2.0 1x 20 50
CTOR4-3 ALUMBRADO EXTERIORES 220 1Ø 0.16 1.00 0.2 0.80 0.9 1x 20 50
CTOR4-4 ELECTROBOMBA AGUA FRIA 220 1Ø 1.50 0.50 0.8 0.80 4.3 1x 20 50
CTOR4-5 TOMACORRIENTES 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 50
CTOR4-6 TOMACORRIENTES 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 50
CTOR4-7 T-UPS 220 1Ø 4.60 0.85 3.9 0.80 22.2 1x 32 50
CTOR4-8 UCD 380 3Ø 6.50 1.00 6.5 0.80 12.3 3x 20 50

SUBTOTAL 380 3Ø 14.4 12.4

13.0 TABLERO TD-RIP 4


CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CTOR4-1 ALUMBRADO 220 1Ø 0.65 0.90 0.6 0.80 3.3 1x 20 8
CTOR4-2 TOMACORRIENTES 220 1Ø 0.40 0.90 0.4 0.80 2.0 1x 20 12
CTOR4-3 RECTIFICADOR 220 1Ø 0.16 1.00 0.2 0.80 0.9 1x 20 6
CTOR4-4 ET-2 3 HP 380 3Ø 2.25 1.00 2.3 0.80 4.3 3x 20 15
CTOR4-5 VT-1 7.5 HP 380 3Ø 5.63 1.00 5.6 0.80 10.7 3x 20 14
CTOR4-6 ET-3 0.5 HP 220 1Ø 0.38 1.00 0.4 0.80 2.1 1x 20 16
CTOR4-7 VT-2 1 HP 220 1Ø 0.75 1.00 0.8 0.80 4.3 1x 20 14
CTOR4-8 EQUIPO DE SOLDAR 380 3Ø 6.00 1.00 6.0 0.80 11.4 3x 20 55

SUBTOTAL 380 3Ø 16.2 16.1

12.0 TABLERO TD-RIP 1, 2, 3


CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. Interrrup. L

N° (V) (kW) (kW) (A) Calculado (m)


CTOR4-1 ALUMBRADO 220 1Ø 0.48 0.90 0.4 0.80 2.5 1x 20 50
CTOR4-2 TOMACORRIENTES 220 1Ø 0.40 0.90 0.4 0.80 2.0 1x 20 50
CTOR4-3 RECTIFICADOR 220 1Ø 0.16 1.00 0.2 0.80 0.9 1x 20 50
CTOR4-4 ET-4 2HP 220 1Ø 1.50 0.50 0.8 0.80 4.3 1x 20 50
CTOR4-5 VT-3 5 HP 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 50
CTOR4-6 VT-4 220 1Ø 0.45 0.50 0.2 0.80 1.3 1x 20 50
CTOR4-7 ET-5 1/2 HP 220 1Ø 4.60 0.85 3.9 0.80 22.2 1x 32 50
CTOR4-8 EQUIPO DE SOLDAR 380 3Ø 6.50 1.00 6.5 0.80 12.3 3x 20 50

SUBTOTAL 380 3Ø 14.5 12.6


S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.60 0.27 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.41 0.64 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.21 0.10 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.06 0.48 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.32 0.60 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.71 0.32 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.95 0.43 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.69 0.32 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.21 0.55 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.41 0.19 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.50 0.23 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.55 0.25 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.61 0.28 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.58 0.26 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.63 0.29 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.53 0.24 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.57 0.26 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.71 0.32 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.93 0.42 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

16 1.663 0.112 3.23 0.85 NH-90 3-1x16mm² +1x16mm²(N)+1x10mm²(T)-40mmØ EMT

4 6.697 0.058 1.11 0.51 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.26 0.12 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.49 0.22 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


4 6.697 0.058 2.23 1.01 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.91 0.41 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 2.97 1.35 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.99 0.45 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.14 0.06 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.05 0.48 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

6 4.122 0.142 0.88 0.23 NH-90 3-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

4 6.697 0.058 1.38 0.63 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

6 4.122 0.142 1.04 0.47 NH-90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

6 4.122 0.142 2.15 0.98 NH-90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

6 4.122 0.142 2.37 1.08 NH-90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

10 2.644 0.131 0.40 0.11 NH-90 3-1x10mm² +1x10mm²(N)+1x10mm²(T)-35mmØ EMT

6 4.122 0.142 0.38 0.17 NH-90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

10 2.644 0.131 0.10 0.03 NH-90 3-1x10mm² +1x10mm²(N)+1x10mm²(T)-35mmØ EMT

4 6.697 0.058 4.97 1.31 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.19 0.09 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.17 0.08 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.57 0.71 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.83 0.38 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.61 0.28 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.40 0.18 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.44 0.20 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.18 0.53 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.64 0.29 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.98 0.45 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.92 0.42 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.44 0.20 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.39 0.18 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 3.98 1.81 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.91 0.87 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.31 0.14 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.60 0.27 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.71 0.32 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.81 0.37 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


16 1.663 0.112 0.89 0.23 NH-90 3-1x16mm² +1x16mm²(N)+1x10mm²(T)-40mmØ EMT

4 6.697 0.058 1.15 0.30 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

6 4.122 0.142 0.49 0.22 NH-90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

4 6.697 0.058 1.24 0.33 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 1.67 0.76 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.30 0.59 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.48 0.67 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 2.04 0.93 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.93 0.42 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.67 0.76 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.93 0.42 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.93 0.42 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.93 0.42 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.81 0.37 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.62 0.74 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.93 0.42 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.93 0.42 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.93 0.42 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 2.55 1.16 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 3.68 1.67 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 3.68 1.67 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 3.68 1.67 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 3.68 1.67 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

6 4.122 0.142 7.30 3.32 NH-90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

95 0.272 0.089 4.29 1.95 NH-90 1-1x95mm² +1x95mm²(N)+1x35mm²(T)-90mmØ EMT

4 6.697 0.058 3.70 1.68 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.38 0.63 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 2.76 1.25 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.84 0.84 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 4.64 2.11 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 4.64 2.11 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


4 6.697 0.058 1.26 0.57 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.08 0.49 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.19 0.54 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 4.92 2.24 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 6.13 2.79 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.84 0.38 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.55 0.25 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.33 0.15 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.59 0.15 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.59 0.15 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.42 0.37 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.64 0.29 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.09 0.04 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.07 0.03 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.37 0.17 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.41 0.19 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.46 0.21 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.78 0.36 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 2.51 1.14 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.86 0.23 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.05 0.02 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.05 0.02 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.16 0.07 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.30 0.14 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.08 0.03 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.29 0.08 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.24 0.06 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.31 0.14 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.44 0.12 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.47 0.12 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.07 0.03 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.34 0.15 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.97 0.44 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.10 0.50 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.49 0.22 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 2.30 1.04 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.69 0.31 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.69 0.31 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

6 4.122 0.142 7.52 3.42 NH-90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

4 6.697 0.058 5.76 1.52 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.97 0.44 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.10 0.50 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.49 0.22 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 2.30 1.04 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.69 0.31 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.69 0.31 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

6 4.122 0.142 7.52 3.42 NH-90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

4 6.697 0.058 5.76 1.52 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT


S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.97 0.44 NH90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.10 0.50 NH90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.49 0.22 NH90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 2.30 1.04 NH90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.69 0.31 NH90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.69 0.31 NH90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

6 4.122 0.142 7.52 3.42 NH90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

4 6.697 0.058 5.76 1.52 NH90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.97 0.44 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 1.10 0.50 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.49 0.22 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 2.30 1.04 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.69 0.31 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

4 6.697 0.058 0.69 0.31 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

6 4.122 0.142 7.52 3.42 NH-90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT

4 6.697 0.058 5.76 1.52 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT

S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 0.29 0.13 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 0.26 0.12 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 0.06 0.03 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 0.60 0.16 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 1.40 0.37 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 0.37 0.17 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 0.64 0.29 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
10 2.644 0.131 2.38 0.63 NH-90 3-1x10mm² +1x10mm²(N)+1x10mm²(T)-35mmØ EMT

S R X Caida Ten. D V* ALIMENTADOR

(mm²) (Ohms/Km) (Ohms/Km) (V) (%)


4 6.697 0.058 1.32 0.60 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 1.10 0.50 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 0.49 0.22 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 2.30 1.04 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 0.69 0.31 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
4 6.697 0.058 0.69 0.31 NH-90 1-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
6 4.122 0.142 7.52 3.42 NH-90 1-1x6mm² +1x6mm²(N)+1x6mm²(T)-25mmØ EMT
4 6.697 0.058 5.76 1.52 NH-90 3-1x4mm² +1x4mm²(N)+1x4mm²(T)-20mmØ EMT
1.0 TABLERO TEF-PE
CIRC. DESCRIPCION TENSION FASE C.I. FDD M.D. F. P. I nom. I diseño Interrrup. L S D V*

N° (V) (kW) (kW) (A) (A) Calculado (m) (mm²) (%)


C-1 CPEN-1 380 3Ø 14.9 1.0 14.9 0.80 28.3 48.2 3x 50 45 16 0.81
C-2 CPEN-2 380 3Ø 14.9 1.0 14.9 0.80 28.3 48.2 3x 50 135 25 1.71
C-3 CPEN-3 380 3Ø 14.9 1.0 14.9 0.80 28.3 48.2 3x 50 135 25 1.71
C-4 CPEN-4 380 3Ø 14.9 1.0 14.9 0.80 28.3 48.2 3x 50 135 25 1.71
C-5 CPEN-5 380 3Ø 14.9 1.0 14.9 0.80 28.3 48.2 3x 50 110 25 1.39

SUBTOTAL 380 3Ø 74.6 1.0 74.6


ALIMENTADOR

N2XH 3-1x16mm² +1x16mm²(N)+1x10mm²(T)-40mmØ EMT


N2XH 3-1x25mm² +1x25mm²(N)+1x10mm²(T)-50mmØ EMT
N2XH 3-1x25mm² +1x25mm²(N)+1x10mm²(T)-50mmØ EMT
N2XH 3-1x25mm² +1x25mm²(N)+1x10mm²(T)-50mmØ EMT
N2XH 3-1x25mm² +1x25mm²(N)+1x10mm²(T)-50mmØ EMT

También podría gustarte