PASO3.- CONDUCTOR LADO PRIMARIO DEL TRANSFORMADOR. 250.5602KVA Iprim = = 𝟏𝟏. 𝟔𝟒𝟕𝟒𝐀 √3(13800 V)(0.9) PASO4.- CALIBRE DEL CONDUCTOR DEL PRIMARIO DEL TRANSFORMADOR.
Icond. = (11.6474A)(1.25) = 𝟏𝟒. 𝟓𝟓𝟗𝟐𝐀
PASO5.- CALIBRE DEL SECUNDARIO DEL TRANSFORMADOR AL DRIVE.
Icond. = (𝟑𝟒𝟗. 𝟒𝟐𝟐𝟖𝑨A)(1.25) = 436.7785𝐀
PASO6.- CALCULO DE REACTOR DE LÍNEA. (0.03)V (0.03)(460V) L= L= = 𝟔𝟎. 𝟒𝟖𝟏𝟗𝐦𝐇 √3 I 37 √3(349.4228)(377) PASO7.- CALCULO DEL REACTOR DE CARGA. (0.03)V (0.03)(460V) L= L= = 𝟔𝟎. 𝟒𝟖𝟏𝟗𝐦𝐇 √3 I 37 √3(349.4228)(377) CALIBRE DEL MOTOR M1, M2 Y M3. # 6 THW 75C. CALIBRE DEL MOTOR M4. # 6 THW 75C.
CALIBRE DEL INTERRUPTOR TERMOMAGNETICO.
# 4 THW 75C. CALIBRE DEL RELEVADOR TERMICO. # 4 THW 75C. CA