CORRIENTE DE LOS MOTORES M1, M2 Y M3 70HP.

70HP = 70HP*745.7 = 52.199KW


52.199KW
Ialim = = 𝟖𝟕. 𝟓𝟖𝟕𝟒𝐀
√3(460)(0.88)(0.85)
CALCULO DEL RELÉ TÉRMICO.

R TERMICO = In(1.15) = (87.5874)(1.15) = 𝟏𝟎𝟎. 𝟕𝟐𝟓𝟓𝐀


R TERMICO = 𝟏𝟎𝟎. 𝟕𝟐𝟓𝟓𝐀
CALCULO DEL INTERRUPTOR TERMOMAGNÉTICO.

ITERMOMAGNETICO = In(1.5) = (87.74)(1.50) = 1𝟑𝟏. 𝟑𝟖𝟏𝟏𝐀


ITERMOMAGNETICO. = 𝟏𝟑𝟏. 𝟑𝟖𝟏𝟏 𝑨

CORRIENTE DEL MOTOR M4 75HP.


75HP = 75HP*745.7 = 55.9275KW
55.9275KW
Ialim = = 𝟖𝟔. 𝟔𝟔𝟎𝟔𝐀
√3(460)(0.90)(0.90)
CALCULO DEL RELÉ TÉRMICO.

R TERMICO = In(1.15) = (86.6606)(1.15) = 𝟗𝟗. 𝟔𝟓𝟗𝟔𝐀


R TERMICO = 𝟗𝟗. 𝟔𝟓𝟗𝟔𝐀
CALCULO DEL INTERRUPTOR TERMOMAGNÉTICO.

ITERMOMAGNETICO = In(1.5) = (86.6606)(1.50) = 𝟏𝟐𝟗. 𝟗𝟗𝟎𝟗𝐀


ITERMOMAGNETICO. = 𝟏𝟐𝟗. 𝟗𝟗𝟎𝟗 𝑨

CORRIENTE DEL ALIMENTADOR ES LA SUMA DE LOS MOTORES M1, M2,


M3, Y M4.

Iprinc = (87.5874 ∗ 3) = 262.7622 + 86.6606 = 𝟑𝟒𝟗. 𝟒𝟐𝟐𝟖𝑨


RELE TERMICO GENERAL.
𝑅𝑇𝐺𝐸𝑁𝐸 = (349.4228)(1.15) = 401.8362𝐴

INTERRUPTOR TERMOMAGENTICO GENERAL.


𝐼𝑁𝑇𝐺𝐸𝑁𝐸 = (349.4228)(1.50) = 524.1342𝐴.

PASO2.-
PARA HACER EL CÁLCULO DEL TRANSFORMADOR.

KVA = √3(349.4228 A)(460V)(0.9) = 𝟐𝟓𝟎. 𝟓𝟔𝟎𝟐𝐊𝐕𝐀


PASO3.-
CONDUCTOR LADO PRIMARIO DEL TRANSFORMADOR.
250.5602KVA
Iprim = = 𝟏𝟏. 𝟔𝟒𝟕𝟒𝐀
√3(13800 V)(0.9)
PASO4.-
CALIBRE DEL CONDUCTOR DEL PRIMARIO DEL TRANSFORMADOR.

Icond. = (11.6474A)(1.25) = 𝟏𝟒. 𝟓𝟓𝟗𝟐𝐀


PASO5.-
CALIBRE DEL SECUNDARIO DEL TRANSFORMADOR AL DRIVE.

Icond. = (𝟑𝟒𝟗. 𝟒𝟐𝟐𝟖𝑨A)(1.25) = 436.7785𝐀


PASO6.-
CALCULO DE REACTOR DE LÍNEA.
(0.03)V (0.03)(460V)
L= L= = 𝟔𝟎. 𝟒𝟖𝟏𝟗𝐦𝐇
√3 I 37 √3(349.4228)(377)
PASO7.-
CALCULO DEL REACTOR DE CARGA.
(0.03)V (0.03)(460V)
L= L= = 𝟔𝟎. 𝟒𝟖𝟏𝟗𝐦𝐇
√3 I 37 √3(349.4228)(377)
CALIBRE DEL MOTOR M1, M2 Y M3.
# 6 THW 75C.
CALIBRE DEL MOTOR M4.
# 6 THW 75C.

CALIBRE DEL INTERRUPTOR TERMOMAGNETICO.


# 4 THW 75C.
CALIBRE DEL RELEVADOR TERMICO.
# 4 THW 75C.