Documentos de Académico
Documentos de Profesional
Documentos de Cultura
This article reviews a series of scientific articles written by the authors, where the following topics
were investigated in relation to non-unidirectional airflow cleanrooms.
(1) The air supply rate required to obtain a specified concentration of airborne contamination.
(2) The calculation of concentrations of airborne contaminants in different ventilation and dispersion
of contamination situations.
(3) The decay of airborne contamination
(a) during the ‘clean up’ test described in Annex 1 of the EU Guidelines to Good Manufacturing
Practice (2008);
(b) during the recovery rate test described in Annex B12 of ISO 14644-3 (2005);
(c) associated with clean areas, such as airlocks, to reduce airborne contamination before a door
into a cleanroom is opened.
Worked examples are provided to demonstrate the calculation methods to provide solutions to the
above topics.
Key words: Air supply rates, airborne concentration, airborne contamination, particles, MCPs,
cleanrooms, ventilation equations, decay of contamination.
relationships that govern the decay of airborne contamination in the ‘build-up’, ‘steady-state’ and ‘decay’
contamination in enclosed spaces, such as cleanrooms. conditions. These equations are discussed in Article I,
which reports their modification for use in cleanrooms.
The equations only apply to non-UDAF cleanrooms, as
The build-up, steady-state, and decay of the derivation of the equations is based on the assumption
airborne contamination that room air is well mixed, and this assumption does not
To provide solutions to the situations outlined above, it is apply to UDAF conditions, where contamination is
necessary to understand the three ventilation conditions displaced by a piston of contamination-free air.
that determine the concentration of particles and microbe-
carrying particles (MCPs) in cleanroom air. If a cleanroom Steady-state equations
is in the ‘at rest’ state with no personnel present and no Equation 1 is a simple dilution equation used to estimate
machinery working, there will be no airborne the airborne concentration of contaminants in a non-
contamination dispersed. As the air supply to the UDAF cleanroom in the ‘steady-state’ condition, when the
cleanroom is filtered and essentially free of air supply rate to the cleanroom and dispersion rate of
contamination, and the cleanroom pressurised to prevent airborne contamination are known. It is applied in this
contamination entering from adjacent areas, the article to the most common sizes of airborne particles used
concentration of airborne contamination in such a to classify and monitor cleanrooms, i.e. ≥0.3 µm, ≥0.5 µm
cleanroom should be close to zero. However, when and ≥5 µm, as well as to MCPs.
personnel enter and operations start, the dispersion of
airborne particles and MCPs causes their concentration to Equation 1
‘build up’ to a plateau, or ‘steady-state’ condition. In the
D
‘steady-state’ condition, the contamination dispersed into C=1
air equals that removed by ventilation, and the Q
concentration remains relatively steady. When
contamination-generating activities cease, or decrease, the Where,
airborne concentration of contamination will ‘decay’. The C = concentration of airborne contamination
three conditions of ‘build-up’, ‘steady-state’ and ‘decay’ D = dispersion rate of airborne contamination
are illustrated in Figure 1. Q = air supply rate into cleanroom
Calculation of the ‘build-up’ of airborne contamination
is of limited use in cleanrooms, but knowledge of ‘steady- Alternatively, the air supply rate into a cleanroom (Q)
state’ and ‘decay’ concentrations is useful; particularly the required for a specified concentration of airborne
‘steady-state’, which determines the average airborne contamination can be calculated by Equation 2.
concentration during operation and, therefore, the amount
that may deposit onto a product. The concentrations of
airborne contamination in the steady-state and decay Equation 2
conditions can be calculated by equations described in the
D
next section. Q=1
C
The ventilation equations
Equations 1 and 2 do not include several factors present in
Equations are used in conventional mechanically cleanrooms that are likely to affect the calculations. These
ventilated rooms, such as offices, to predict toxic gaseous are discussed in Article IV, and are as follows.
1. The ventilation effectiveness in a non-UDAF cleanroom If the airborne concentration of contamination has to be
may vary across a cleanroom, and give locations with calculated, then Equation 5 can be used.
higher than average concentrations of contamination. To
compensate for this, the increase of the air supply rate is Equation 5
calculated by the use of a ventilation effectiveness index
(ε), as shown in Equation 3. D
C = 11111111
ε(Q + βQD – VDa)
D Equation 6
Q = 1 – βQD – V D a
εC C = Co . e– n t
Where,
Where C = concentration of contamination after time t
Q = required air supply rate (m3/s) Co = initial concentration
D = average value of dispersion rate (no./s) n = air change rate in the cleanroom
ε = ventilation effectiveness index t = elapsed time
C = concentration of airborne contamination (no./m3)
β = ventilation efficiency coefficient of clean air It should be noted that Equation 6 shows that the decay
device rate is dependent on the air change rate, and not the air
QD = air supply rate passing through clean air device volume supply rate. Although the air supply rate must be
(m3/s) used to calculate the airborne concentration of
VD = deposition velocity of MCPs and particles passing contamination in the steady-state condition, the air change
through air and onto a surface (m/s) rate must be used to calculate decays of airborne
a = surface area of a cleanroom where deposition contamination associated with recovery rates for
occurs – usually equivalent to the floor area (m2) cleanrooms, or clean areas such as airlocks.
CalCulation of air SuPPly ratES anD ConCEntrationS of airbornE Contamination in non-uDaf ClEanroomS 129
Figure 2. Decay of airborne contamination in cleanrooms with different air change rates.
Application of the decay equation The cleanliness recovery test described in ISO 14644-3
(2005)11 fails to suggest what recovery rate results are
The application of the decay Equation 6 is considered in
acceptable, or not. However, if the air change rate at a
Article II, where it is explained that Equation 6 can be
location obtained from measuring the recovery rate is
rewritten so that the air change rate (n) at a location can be
compared with the average air change rate of the entire
obtained from the rate of decay of airborne contamination.
cleanroom, a ventilation effectiveness index known as the
This equation can be given in natural logarithms, or
Air Change Effectiveness (ACE) is obtained by Equation
logarithms to the base 10, and is as follows.
8. If the ACE index is calculated, then a useful numerical
result will be obtained to establish whether the recovery
Equation 7 rate at the measuring location is higher or lower than
average. Further information about the ACE index is
1 C 1 C given in the Ventilation effectiveness section.
n = – 1 ln 1 = –2.3 × 1 log10 1
t C0 t C0 Equation 8
The cleanroom standard, ISO 14644-3 (2005)11 contains a Ventilation effectiveness index (ACE)
test that is used to obtain the cleanliness ‘recovery rate’
and calculated by Equation B12 that is given in the air change rate at measuring location
standard, and is as follows. = 1111111111111111
average air change rate in cleanroom
1 C1
n = –2.3 × 1 log10 1 Articles II and III discuss the EU GGMP Annex 1 (2005)2
t1 C0 ‘clean-up’ test required in pharmaceutical cleanrooms to
demonstrate that when production ceases the particle
Where, concentration quickly decays to the ‘at rest’ condition. By
n = recovery rate use of the decay equation, the number of air changes
t1 = time elapsed between the first and second required to ensure that a non-UDAF cleanroom complies
measurement with the ‘clean-up’ test requirements can be obtained.
C0 = initial concentration This calculation is discussed in more depth in Article
C1 = concentration after time t1 VIII, and applied in the Worked examples of the
calculation of air supply rates or airborne concentrations
If the measurement units are the same, e.g. number of air in a non-uDaf cleanroom section. Finally, in the design
changes/hour, it is seen that the right-hand side of of air locks, suitable air change rates and time delays
Equation B12 is the same as the right-hand side of before doors are opened can be calculated, so that
Equation 7 and, therefore, the ‘recovery rate (n)’ is the undesirable transfer of airborne contamination across the
same as the ‘air change rate (n)’, when measured at the airlock is minimised; this information is included in
same location. Article II.
130 W WhytE, t Eaton, Wm WhytE, n lEnEgan, S WarD, K agriCola
Information required for the calculation dispersion rate, as much of the person’s contamination is
of air supply rates and airborne dispersed from under the gown and into the cleanroom air
concentrations and, therefore, their dispersion rate can be assumed to be
similar to normal indoor clothing.
To calculate either the air supply rate, or concentration of Article IV gives further information on dispersion rates
contaminants in a non-UDAF cleanroom, Equations 1 to 5
from personnel exercising in a dispersion chamber when
can be used. However, values of the equation variables are
wearing more effective cleanroom clothing made from a
required, and these are now considered.
tighter-woven polyester fabric with a pore diameter of 12
µm. It can be seen in Table 2 that much lower dispersion
Dispersion rates from personnel and machinery
rates are obtained from the better clothing. When wearing
To calculate the required air supply rate, or the airborne
the same clothing within an operational cleanroom, where
concentration in a non-UDAF cleanroom, the dispersion
personnel activity was lower than exercising in a
rates of airborne contamination from sources such as
dispersion chamber, the lower activity gave even lower
personnel and machines is required. All individual
dispersion rates.
dispersion rates should be added together to obtain the
Shown in Table 3 is information given in Article IV of
total dispersion rate.
emission rates of particles from various types of
If required, the dispersion rates can be obtained in a
machinery.
cleanroom or test chamber containing the active source,
using a method similar to that suggested in Annex B4 of
Ventilation effectiveness
ISO 14644-1413. The test space should be supplied with a
When filtered air is supplied to a non-UDAF cleanroom,
known rate of particle-free air, which pressurises the test
the air movement pattern in the room may result in less
space against the ingress of contamination from adjacent
clean air than the average reaching a critical location. To
areas. If the average concentration of airborne
compensate for this, an increase in the air supply is
contamination is measured in the steady-state condition,
required, and this can be calculated by use of a ventilation
the dispersion rate can be calculated as follows.
effectiveness index and Equations 3 or 4.
Equation 9 A large number of types of ventilation effectiveness
indexes exist, and the most commonly-known are: air
Dispersion rate (no./s) = air volume supply to test space change effectiveness, air change efficiency, and
(m3/s) × average concentration in test space (no./m3) contamination removal effectiveness. It is considered that
the ACE index is most appropriate for the design of
Information on typical dispersion rates of personnel is cleanrooms18 and also has the advantage of being obtained
discussed in Article IV, and shown in Table 1 is the from the results of tests that are routinely carried out in
average dispersion rate of 55 different personnel when cleanrooms (see application of the decay equation
exercising in a dispersion chamber. The beneficial effect section).
of cleanroom garments made from a woven, reusable, The ACE index is commonly used in ordinary
polyester fabric with a pore diameter14 of 28 µm is shown ventilated rooms, such as offices, and described in
in comparison to normal indoor clothing. It was also ANSI/ASHRAE standard 129-1997 (RA 2002)12. The air
reported that gowns (smocks) do little to reduce the change efficiency index is described in the REHVA
Table 1. Average dispersion rate of particles and MCPs from people exercising in a test chamber.
Particles MCPs
≥0.5 μm ≥5 μm
Table 2. Average dispersion rate of particles and MCPs from people exercising in a test chamber, or working in an
operational cleanroom.
≥0.5 μm ≥5 μm MCPs
Ventilation Effectiveness Guidebook No 218 and is very measurement as the overall air change rate. The overall air
similar to the ACE index, but gives results that are half the change rate can be obtained in the routine way from
value. The Contamination Removal Effectiveness index18 knowledge of the air supply rate and the cleanroom’s
measures the effectiveness of removal of contamination volume. Alternatively, the overall air change rate can be
and is the ratio of the concentration of contamination at determined by measuring the decay of airborne particles at
the exhaust compared to the average in the cleanroom. each of the room’s exhausts, and obtaining an average that
However, it may not be the best indication of the required is weighted by the air volume rate through the exhausts.
increase of air supply when the critical location is situated As deduced from Equation 11, if the air mixing in the
between source and extract. cleanroom is perfect, the ACE index will be 1. If less clean
The ACE index can be measured at one or more air than average reaches the measuring location, the ACE
locations in a room, and the main location suggested in the index will be below 1, and if more air reaches the location
ANSI/ASHRAE standard is where a person breathes. it will be above 1.
However, in a cleanroom, it is best measured at a critical An experimental study of a non-UDAF cleanroom, and
location, such as where product is exposed to airborne field tests of another 23 non-UDAF cleanrooms, were
contamination. carried out to determine their ACE indexes, and reported
The method of calculation given in the ASHRAE in Article III. The article explains the method to obtain
standard is as follows. ACE indexes in cleanrooms, and reports that good air
mixing cannot be assumed in non-UDAF cleanrooms. It
Equation 10 also contains information on how poor mixing and low
ventilation effectiveness can be minimised. The tests
τn showed that when cleanrooms use efficient air supply
aCE = 1
ai diffusers and low-level extracts, the supply air will mix
effectively with room air, and the ACE index is unlikely to
Where, be below 0.7, and may be close to 1; a value of 0.7 is a
τn = nominal time constant reasonable design choice.
ai = age of air at location, i It should be noted that the ACE index can be measured
at one or more locations. Using one location will be
Both the ‘age of air’ and ‘nominal time constant’ are terms satisfactory if airborne contamination mainly occurs at
unlikely to be familiar to cleanroom designers and users, that location, but if contamination occurs at several
but it has been demonstrated in the annex of Article III that locations, it may be necessary to determine the lowest
the ACE index can be calculated by the alternative ACE index.
Equation 11.
Contribution of additional clean air from clean air
Equation 11 devices
If a clean air device is installed in a non-UDAF
air change rate at measuring location cleanroom, then the device’s air will enter the cleanroom
ACE index = 111111111111111
overall air change of cleanroom and a proportion will mix with the room air and reduce the
airborne contamination. This is discussed in Article IV.
The air change rate at the measuring location can be Figure 3 shows a computational fluid dynamics (CFD)
measured by the decay of airborne contamination and use analysis of airflow in a non-UDAF cleanroom that
of Equation 7. However, as shown in the application of contains a free-standing vertical UDAF workstation. It
the decay equation section, the air change rate at a can be seen that a proportion of the air from the UDAF
location has the exact same value as the ‘recovery rate’ workstation returns to the device’s air intake in the
test described in ISO 14644-3 and, therefore, the recovery cleanroom and, as it does, it mixes well with the
rate can be used as long as it uses the same units of cleanroom air. However, a proportion exits through the
132 W WhytE, t Eaton, Wm WhytE, n lEnEgan, S WarD, K agriCola
cleanroom’s low-level extracts without effectively mixing concentration (C) in different cleanliness conditions by
with room air. Article IV discusses the proportion of air the following equation (converted to SI units).
(β) from clean air devices that effectively mixes with
room air, with about 0.5 in the situation shown in Figure PDR ≥5µm (no./m2/s) = 0.0226 ×C 0.773
3, about 0.2 when the same type of workstation is supplied
from the air handling plant that also supplies the However, it is known that
cleanroom, and about 0.8 from small clean air devices. If
the amount of air passing through the device is QD and the PDr
ventilation effectiveness coefficient is β, then the air VD = 111
supply from the air handling plant to the cleanroom can be C
reduced by βQD. It should be noted that the presence of a
clean air device is likely to influence the ventilation Therefore,
effectiveness index, and may give an index different from
that reported in Article III for non-UDAF cleanrooms with
no clean air device. This situation is discussed in the Equation 12
Worked examples of the calculation of air supply rates or
airborne concentrations in a non-uDaf cleanroom 0.0226 × C 0.773
VD (m/s) = 1111111
section. C
Surface deposition of particles and MCPs Because of the difficulty in accurately measuring low
The air supply rate required for a non-UDAF cleanroom airborne concentrations of particles ≥5 µm, the class limits
can be calculated by Equation 4, and the airborne
for that size of particle are only specified in Classes 6, 7, 8
concentration of particles and MCPs by Equation 5. Both
and 9 of ISO 14644-1 (2015)1. The deposition velocities
equations incorporate the effect of surface deposition and,
for particles ≥5 µm, calculated by means of Equation 12,
to obtain this, the deposition velocity is required.
are given in Table 4 for these classes.
Deposition velocities of a range of cumulative particle
It has been additionally reported in Article V that the
sizes have been reported in Article VI, where it is also
reported that the deposition velocity may increase as the deposition velocities of MCPs are related to the airborne
airborne concentration decreases. Small particles ≥0.3 µm concentration, and the microbial deposition rate (MDR)
and ≥0.5 µm were shown to have deposition velocities of given by the following equation.
2.8 x 10-5 m/s and 6.4 x 10-5 m/s, repectively, and the
surface deposition over a range of air cleanliness is very MDR (no./m2/s) = 0.0161 × C 0.6571
low, and it is unnecessary to include their deposition in
these calculations. However, particles ≥5 µm have greater Using the same approach as described above for particles
deposition rates, and their deposition should be included. ≥5 µm, the deposition velocities expected in the different
In Article VI, Hamberg’s research in cleanrooms is Grades of cleanrooms specified in Annex 1 of EU GGMP2
discussed19, which shows that for particles ≥5 µm, the are given in Table 5. Additonal depositon velocities for
particle deposition rate (PDR) is related to the airborne other airborne concentrations are reported in Article V.
CalCulation of air SuPPly ratES anD ConCEntrationS of airbornE Contamination in non-uDaf ClEanroomS 133
ISO 14644-1 Class1 Class limit for particles ≥5 µm/m3 Deposition velocity (m/s)
6 293 0.0062
7 2930 0.0037
8 29,300 0.0022
9 293,000 0.0013
Calculation of the increase of air supply airborne counts are from the average, and is the ratio of
rate to ensure the airborne standard deviation to the mean of the counts. Values of CV
concentration limit is rarely exceeded found in cleanrooms are given in Article IV and are
normally between 0.5 and 2, and a value of 1 is a
The dispersion rates of particles and MCPs from sources reasonable choice. The percentage of counts below the
will vary in a cleanroom over time and are normally class limits can be chosen as 95% as this is a reasonable
reported as an average number per second and, therefore, choice for two reasons. Firstly, ISO 14644-1 (2015)
the calculated air supply rate gives an average airborne selects the number of sampling locations to give a 95%
concentration (number/m3), where half the counts will be chance that 90% of the count will be below the class
above the average concentration. However, ISO 14644-11 limit. Secondly, ISO 14644-1 (2015) allows a second
requires the particle concentration not to exceed the class chance of sampling a location when a count is over the
limit, and a cleanroom with an airborne concentration class limit, although this is only allowed when there is an
whose limit is exceeded about half the time, would be abnormal occurrence. However, in most situations there
generally unacceptable. It is almost impossible to design a is enough uncertainty to accept the likelihood of an
cleanroom that will never exceed the class limit, as abnormal occurrence. As 95% is a proportion of 0.05, the
airborne counts conform to a statistical distribution, with chance that two consecutive counts will be above the
counts distributed around the average and a number of limit is 0.05 x 0.05 = 2.5 in 1000. Although 95% seems a
outlying high counts. By increasing the air volume supply reasonable level, there may be situations where higher
rate, the percentage of airborne counts above the class percentages of counts (and values of CV) may be
limit will decrease, and the increase in air supply to ensure desirable, and the increases in air supply required in such
that an ISO class limit is rarely exceeded can be calculated conditions are available in Article IV.
using the method explained in Article IV. Given in Table 6
are the number of times the air supply rate should be
increased to ensure that 95% or 99% of the counts are
Effect of different types of air supply
below the class limit.
distribution systems
The increases of air supply given in Table 6 are based Equations 1 to 5 have been derived to calculate the
on the coefficient of variation (CV) and the percentage of airborne concentration of contamination, or the air supply
particle counts required to be below the class limit. The rate needed for a specified concentration of
coefficient of variation shows how widely spread contamination. However, there are variables not included
EU GGMP Annex 12 cleanroom grades Airborne MCP concentration/m3 Deposition velocity (cm/s)
A 1 0.016
B 10 0.0073
C 100 0.0033
95% 1 2.7
99% 1 3.5
134 W WhytE, t Eaton, Wm WhytE, n lEnEgan, S WarD, K agriCola
in these equations that might affect the results, namely, other cleanrooms may be required to meet a recovery rate
requirement according to ISO 14644-3: 20051. Both
(a) the design of the air conditioning plant with respect to ‘clean up’ and ‘recovery rate’ tests measure the particle
the mixing of recirculated and fresh air, and the decay rate which, as previously discussed, is dependent on
number, placement and combinations of air filters; the cleanroom’s air change rate.
(b) removal efficiency of the air filters; Article VIII describes a method to calculate the air
(c) concentration of contamination in the outside air; change rates needed to achieve the ‘clean up’
(d) percentage of fresh make-up air in total air supply. requirements of the EU GGMP. The method takes account
of the ventilation effectiveness of the airflow in the
To investigate the significance of these additional cleanroom. If the ACE index is assumed to be no poorer
variables, equations were derived in Article VII that than 0.7, then, if the most stringent requirements are
included these variables, in addition to the already applied to Grade B cleanrooms of a 100-fold drop in
established variables of airborne dispersion rate and particle concentration from the ‘in operation’ to ‘at rest’
surface deposition. Equations were derived for the steady- state, in 15 minutes, the required air changes per hour is
state condition in three common layouts of air handling 26. For Grade C cleanrooms that require a 10-fold drop in
plants, when an additional secondary air filter was 15 minutes, 13 air changes per hour are required. Other air
installed, or not. The importance of all equation variables change rates can be calculated for different conditions.
was then investigated in Article IX. Knowing the volume of the cleanroom, the air supply
In Article IX, the concentration of particles ≥0.5 µm rate calculated by the method described in the previous
and MCPs in the air of a typical non-UDAF cleanroom sections should be converted to the room’s air change rate.
was calculated for various designs of ventilation plants, This air change rate should be the same as, or greater than,
using different placements and combinations of air filters. the air change required for the EU GGMP ‘clean up’
Filter standards EN 1822-1:200920 and ISO 29463- requirements.
1:200921 classify high efficiency filters by their removal The same calculation method used for the EU GGMP
efficiency against the most penetrating particle size ‘clean up’ requirement can also be used to check that the
(MPPS). It was found that a primary/secondary/terminal air supply rate (converted to an air change rate) will
combination of air filters with removal efficiencies of achieve the required recovery rate according to ISO
85/99.95/99.995% (a E10/H13/H14 filter combination 14644-311, for any drop in particle concentration, time
according to EN 1822), provided no contribution of requirement, or ventilation effectiveness index.
particles ≥0.5 µm in the supply air. If a secondary filter is
not installed, a few particles were supplied to the
Worked examples of the calculation of
cleanroom. This filter combination appeared to be
air supply rates or airborne
satisfactory, especially as the post-installation leak test to
concentrations in a non-UDAF
demonstrate that terminal filters are free of leaks, requires
cleanroom
the penetration of test particles to be less than 0.01%. To
ensure this, the filter’s local penetration should be close to
99.99%, i.e. the terminal filter is not less efficient than a Calculation of the air supply rate
H14 filter. However, should other combinations of filters It is assumed that air supply rates required to satisfy the
be considered, the equations derived in Article VII will temperature, humidity, and other ventilation requirements
establish their effectiveness in removing particles and of a cleanroom, will be separately calculated. This section
MCPs from the air supply. only considers the air supply rate to provide a specified
If the installed air filters ensure that the contamination airborne concentration of particle and MCP
in the supply air is practically zero, the most important contamination. The method is demonstrated by a worked
determinants of airborne concentration in a cleanroom example of a non-UDAF cleanroom that has to conform to
were demonstrated in Article IX to be the air supply rate a cleanliness standard of ISO 14644-1 Class 7 at particle
and dispersion rate of contamination, with a lesser effect sizes of ≥0.5 µm (352,000/m3) and ≥5 µm (2930/m3), and
from surface deposition. The additional variables listed at an MCP limit of 10/m3. It also has to comply with the
the start of this section were shown to be of little practical ‘clean-up’ requirement of the EU GGMP (2008) for a
importance when effective air filters, typical of the type Grade B cleanroom.
installed in current designs of cleanrooms, are installed. The combination of filters to be installed are chosen to
The previously quoted Equations 4 and 5 were, therefore, ensure that the air supply contributes little, or no, airborne
shown to be suitable equations for the calculation of the contamination to the cleanroom and, to achieve this,
air supply rate, or airborne concentration in non-UDAF reference should be made to the Effect of different types of
cleanrooms. air supply distribution systems section and Articles VII
and IX. When the number, placement and removal
efficiency of the filters has been established, the air supply
Ensuring air supply rates comply with rate can be calculated by means of Equation 4.
EU GGMP (2008)2 and ISO 14644-3: 20051
recovery rate requirements D
Pharmaceutical cleanrooms should meet the ‘clean up’ Q = 11 – βQD – VDa
εC
requirements given in Annex 1 of EU GGMP (2008)2, and
CalCulation of air SuPPly ratES anD ConCEntrationS of airbornE Contamination in non-uDaf ClEanroomS 135
When there are no clean air devices, the second term can 500/s of particles ≥0.5 µm, and 100/s of particles ≥5 µm,
be removed from the equation, and if surface deposition is but no MCPs. The total sum of the dispersion rates (D) is
not included, the third term can be removed. In this given in Table 7.
example, deposition is included, and the calculation is Step 2 establishes the value of the ventilation
firstly carried out with no clean air device present, and effectiveness index (ε), and reference should be made to
when one is installed. the Ventilation effectiveness section for further
Step 1 in calculating the air supply rate is to obtain the information on this topic. It was decided to avoid uneven
dispersion rate of airborne contamination in the concentrations of contamination around the cleanroom in
cleanroom. In this example, dispersion comes from two order to minimise the need for extra air to compensate for
people working in the cleanroom, and machinery. If the the higher concentrations of contamination that might
new cleanroom will have the same production method as occur. Therefore, effective air diffusers were used to
an existing cleanroom, then the dispersion rate can be supply and mix the filtered air, with low-level extracts
obtained from the existing room by the method described around the periphery of the cleanroom. This should give a
in the Dispersion rates from personnel and machinery ventilation effectiveness index close to 1 but, to add a
section. However, the cleanroom was required for a new safety margin, a value of 0.7 was assumed.
production method, and the dispersion rate can be Step 3 establishes the floor area (a) and particle
obtained by simulating the new production method in a deposition velocities (DV) that are needed to calculate the
cleanroom, and using the method given in the Dispersion reduction of the airborne concentration owing to surface
rates from personnel and machinery section. If no deposition losses. The total horizontal surface area of the
experimental information on dispersion rates is available, cleanroom is assumed to be the same as the floor area of
then it can be estimated from data similar to that given in 50 m2. The deposition velocities of particles ≥5 µm and
the Dispersion rates from personnel and machinery MCPs are given in Tables 4 and 5. The deposition velocity
section. The two people working in the cleanroom will of particles ≥0.5 µm was not included, as the deposition
wear one-piece polyester coveralls with hood and was known to be insignificant (see the Surface deposition
overboots, and will be active most of the time. It was of particles and mCPs section).
decided that the average dispersion rates in Table 1 would Step 4 calculates the initial value of the air supply rate.
be used, and for two people it was 34,000/s for particles It was firstly assumed that no clean air device was
≥0.5 µm, 1200/s for particles ≥5 µm, and 6/s for MCPs. installed, and Equation 4 without the clean air device term
The manufacturer reported that the machinery dispersed was used to calculate the air supply rate.
Table 8. Calculation of airborne contaminants in a non-UDAF cleanroom without clean air device.
without a clean air device, and based on the highest air contamination. The EU GGMP ‘clean up’ test was also
supply rate needed to ensure that MCPs (and hence the considered, and a method devised for calculating the air
two other types of contamination) achieve the specified change rate needed to achieve the desired ‘clean-up’
airborne concentration. This air supply rate does not requirements.
include an uplift of the air supply. The results of the To calculate the air supply rate, or concentrations of
calculation of the expected airborne concentrations of the airborne contamination, it is necessary to obtain values of
three contaminants are given in Table 8. the equation variables, and these are provided in this
article and in Article IV. If this information is accurate
then so will the results, but there may be uncertainty in
Discussion
some of the values. However, the calculation method
This article reviews scientific articles published by the includes a requirement to increase the air supply rate by
authors to provide methods for calculating in non-UDAF several-fold to ensure that counts rarely exceed the class
cleanrooms, either the airborne concentrations of particles limit and this provides a margin of safety.
and MCPs, or the air supply rate required to achieve The success of these calculations has been assessed in
specified concentrations of airborne contamination. These Article IV by comparing airborne concentrations with the
are calculated for the steady-state condition, which is the concentration calculated from the actual air supply in a
condition where the contamination of product or non-UDAF cleanroom, as well as similar unpublished
production process may occur. In that condition, the observations carried out by authors of this article, and
contribution of various combinations of air filters were good correlation has been found. When compared to the
investigated, and it was shown that air filters of the type method commonly used at present to design a non-UDAF
routinely installed in cleanrooms ensure that there is little, cleanroom, which is mainly based on experience, the
or no, contribution to the airborne contamination from the analytical methods in this article provide a useful step
air supply (assuming no leakage from the filter system) to forward.
non-UDAF cleanrooms. In this situation, the airborne
concentration in a non-UDAF cleanroom, or the air supply
rate, can be calculated by Equations 1 to 5 using
Main articles
combinations of air supply rate, concentration of airborne I. Whyte W, Whyte WM and Eaton T. The application of the
contamination, dispersion rate of contamination, ventilation equations to cleanrooms Part 1: The equations. Clean
air and Containment review 2012;Issue 12:4–8. Available at:
ventilation effectiveness index and, when installed, the http://eprints.gla.ac.uk/84186/1/84186.pdf
contribution of clean air devices. Should lower removal II. Whyte W, Whyte WM and Eaton T. The application of the
efficiency air filters be utilised, or other design decisions ventilation equations to cleanrooms Part 2: Decay of
contamination. Clean air and Containment review 2014;Issue
made that might allow particles to enter in the supply air, 20:4–9. Available at: http://eprints.gla.ac.uk/100820/1/100820.pdf
then Articles VII and IX give equations that can be used to III. Whyte W, Ward S, Whyte WM and Eaton T. Decay of airborne
calculate the outcome of these design decisions. The effect contamination and ventilation effectiveness of cleanrooms.
international Journal of Ventilation 2014;13(3):211–219. Available
of particle deposition should be included in the at: http://eprints.gla.ac.uk/100819/1/100819i.pdf
calculations involving MCPs and particles ≥5 µm, but can IV. Whyte W, Whyte WM, Eaton T and Lenegan N. Calculation of air
be ignored for particles ≥0.3 µm and ≥0.5 µm. Worked supply rates for non-unidirectional airflow cleanrooms. European
Journal of Parenteral and Pharmaceutical Sciences
examples are provided to demonstrate calculations of air 2014;19(4):121–129. Available at: http://eprints.gla.ac.uk/104331/
supply rate and particle concentration. 1/104331.pdf
Also discussed in this article is the decay of particles in V. Whyte W and Eaton T. Deposition velocities of airborne microbe-
carrying particles. European Journal of Parenteral and
a cleanroom, which is determined by the room’s air Pharmaceutical Sciences 2016;21(2):45–49. Available at:
change rate. Extending the ISO 14644-3 recovery rate test http://eprints.gla.ac.uk/121686/1/121686.pdf
method allows an ACE ventilation effectiveness index to VI. Whyte W, Agricola K and Derks M. Airborne particle deposition in
cleanrooms: relationship between deposition rate and airborne
be obtained that gives a numerical result of the concentration. Clean air and Containment review 2016;Issue
cleanroom’s effectiveness of removing airborne 25:4–10. Available at: http://eprints.gla.ac.uk/119091/1/119091.pdf
138 W WhytE, t Eaton, Wm WhytE, n lEnEgan, S WarD, K agriCola
VII. Whyte W, Lenegan N and Eaton T. Equations for predicting airborne 9. Camfil Farr. Clean room Design Standards and Energy
cleanliness in non-unidirectional airflow cleanrooms. European optimisation. Stockholm, Sweden: Camfil Farr; 2012.
Journal of Parenteral and Pharmaceutical Sciences 2016;21(2):38– 10. Fedotov A. Air change rate for cleanrooms with non-unidirectional
43. Available at: http://eprints.gla.ac.uk/121682/1/121682.pdf airflow. Clean air and Containment review 2016;Issue 26:12–20.
VIII. Whyte W, Lenegan N and Eaton T. Ensuring the air supply rate to a 11. International Organization for Standardization. iSo 14644-3.
cleanroom complies with the EU GGMP and ISO 14644-3 recovery Cleanrooms and associated Controlled Environments. Part 3: test
rate requirements. Clean air and Containment review 2016;Issue methods. Geneva, Switzerland: ISO; 2005.
26:22–24. Available at: http://eprints.gla.ac.uk/119087/1/119087.pdf 12. American National Standards Institute. anSi/aShraE Standard
IX. Whyte W, Lenegan N and Eaton T. Calculation of airborne 129-1997 (ra 2002). measuring air-Change Effectiveness.
cleanliness and air supply rate for non-unidirectional airflow Washington, DC, USA: ANSI; 1997.
cleanrooms. European Journal of Parenteral and Pharmaceutical 13. International Organization for Standardization. iSo 14644-14.
Sciences 2016;21(3):79–88. Available at: http://eprints.gla.ac.uk/ assessment of Suitability of Equipment and materials for
130348/1/130348.pdf Cleanrooms. Geneva, Switzerland: ISO; 2017.
14. Institute of Environmental Science and Technology. iESt-rP-
CC003: garment System Considerations for Cleanrooms and other
Additional references Controlled Environments. Schaumburg, IL, USA: IEST; 2011.
15. Hejab M. Prediction of airborne contamination in conventionally
1. International Organization for Standardization. iSo 14644-1. ventilated cleanrooms. PhD Thesis, University of Glasgow,
Cleanrooms and associated Controlled Environments. Part 1: Scotland; 1992.
Classification of air Cleanliness by Particle Concentration. 16. Sundstrom S, Ljungqvist B and Reinmuller B. Some observations
Geneva, Switzerland: ISO; 2015. on airborne particles in blow-fill-seal filling rooms. PDa Journal of
2. European Commission. Eudralex. the rules governing medicinal Pharmaceutical Science and technology 2007;61(3):147–153.
Products in the European union. Volume 4: Eu guidelines to good 17. Hnatek ER. integrated Circuit Quality and reliability, Second
manufacturing Practice – medicinal Products for human and edition. Boca Raton, FL, USA: CRC Press; 1995.
Veterinary use. annex 1 – manufacture of Sterile medicinal 18. Mundt E (Ed.), Mathisen HM, Nielsen PV and Moser A. guidebook
Products. Brussels, Belgium: European Commission; 2008. no. 2 – Ventilation Effectiveness. Brussels, Belgium: REHVA
3. Food and Drug Administration. guidance for industry. Sterile Drug (Federation of European Heating and Ventilation and Air-
Products Produced by aseptic Processing – Current good Conditioning Association); 2004.
manufacturing Practice. Silver Spring, MD, USA: FDA; 2004 19. Hamberg O. Particle fallout predictions for clean rooms. the
4. Morrison PW. Environmental Control in Electronic manufacturing. Journal of Environmental Sciences 1982;25:15–20.
New York, NY, USA: Van Nostrand; 1973. ISBN: 0442255640. 20. European Committee for Standardization. En 1822-1. high
5. Brown WK and Lynn CA. Fundamental clean room concepts. Efficiency air filters (EPa, hEPa and ulPa). Classification,
aShraE transactions 1986;92(1):272–288. Performance, testing, marking. Brussels, Belgium: European
6. Gustavsson J. Calculating cleanroom cleanliness. Cleanroom Committee for Standardization; 2009.
technology 1999;5(1):24–25. 21. International Organization for Standardization. iSo 29463-1. high-
7. Jaisinghani RA. Energy efficient low operating cost cleanroom Efficiency filters and filter media for removing Particles in air.
airflow design. Presentation at Institute of Environmental Science Part 1: Classification, Performance testing and marking. Geneva,
and Technology Estech Conference, Phoenix, AZ, USA; 2003. Switzerland: ISO; 2011.
8. Sun W, Mitchell J, Flyzik K, Shih-Cheng H, Junjie L, Vijayakumar
R and Fukuda H. Development of cleanroom required airflow rate
model based on establishment of theoretical basis and lab validation.
aShraE transactions 2010;116:87–97.