WSterlite Power
STER-TACSR™
Sterlite* Thermal-resistant Aluminium-alloy Conductor, Steel Reinforced (TACSR) conductors are high ampacity
conductors, wherein the inner core is composed of galvanized steel and the outer layers are composed of
thermal-resistant aluminium-alloy.
Thermal Aluminum APPLICATION
Alloy wire
TACSR conductors are recommended for new
lines for high power transfer requirements.
Wire-Galvanized
steel
BENEFITS,
New aluminium alloys having high thermal resistance ean cary 50%-60% more current than ACSR of the same
ize, while maximum sag and maximum working tension remains almost the same as that of ACSR.
‘Can carry 50%-60% more current than ACSR of the same size,
+ Higher capacity new lines can be built to deal with future demands,
TECHNICAL SPECIFICATIONS
ee Pet as
Cote EQUIVALENT) remy)
‘Typical factors s53mm [01378 in| 318mm —|o1252in | 300mm | ONTBT In
Reference specifications | IEC 62004 1EC 62004 tec 62004
Total cross section area | 596.99 mm'|0.9253 in’ | 484.25 mm'| 0.7506 in’ | 26150 mmv | 0.4054 int
Conductive wire ANZ ATT Zr ATT Alzratt
core wire Galvanized Stee! Galvanized Stee! Galvanized Stee!
Conductor diameter | 177mm [1.2508 im | 28.62mm |rr268in | 2.00mm | 08268 in
went 2004 13456 | 1621 ‘oss3 | 972 532
kava | tbs/mite | ko/km | Ibs/mile | ka/km —_| Ibs/mile
ease | 3028954 | 14407 | si7ei96 | 10119 22308 55
Ultimate tensile streneth | [64 ie i my i 22s
DE resistance at (006 08 007 on ona 022
20°C temperature vam aimie | a/km | /mile | A/km afmile
Maximum operating 150°C 302°F 150°C 302°F 150°C 302°F
‘Current canying capacity
at maximum operating | 1508 Amp 1302 Amp, 831 Amp
temperature
Assumptions: Ampacity is caleulated based on, 45°C (TSF) ambient temperature, Q6 mys wind velocity. 05 as coefficient of
solar absorption, 06 as coefficient of emmisivty and 1200 wi/sam coefficient for solar radiation, at sea level.
12 SPTL