HOJA DE GANANCIAS DE CALOR CALCULO DE CARGA TERMICA

ESPACIO USADO PARA: HALL y RECEPCION PRIMER PISO INSTALADOR WILLIAM BELTRAN
LARGO 7.3 ML SUPERFICIE 32.12 M2 BY-PASS 0.2 %
ANCHO 4.4 ML VOLUMEN 80.3 M3 CLIENTE LICOSINU
ALTO 2.5 ML FECHA 4/7/2011 HORA LOCAL:13:00 HORA PICO
GANANCIA SOLAR POR CRISTALES CARGA MAXIMA:13:00
ORIENTACION ( M2) GANANCIA FACTORES KCAL/H CONDICIONES TEMP B.S TEMP. BH GRM/KG %HR
E CRISTAL: 8.4 X 447 X 0.54 X 1 = 2027.59 INTERIORES 27 22 12 55
SE CRISTAL: 0 X 38 X 0.56 X 1 = 0.00 EXTERIORES 33 28 23.5 75
S CRISTAL: 0 X 442 X 0.6 X 1 = 0.00 DIFERENCIAS 6 11.5
SO CRISTAL: 0 X 157 X 0.56 X 1 = 0.00 INFILTRACION Y VENTILACION
O CRISTAL: 6.7 X 447 X 0.51 X 1 = 1527.40 6 PERSONAS X 11 M3/H x PERS. = 66 M3/H
NO CRISTAL: 0 X 124 X 0.56 X 1 = 0.00 80.3 M 3
X 1.5 M3/H = 120 M3/H
N CRISTAL: 0 X 54 X 0.83 X 1 = 0.00 0 M2 PUERT. X 540 M3/H x PUERT = 0 M3/H
NE CRISTAL: 0 X 38 X 0.56 X 1 = 0.00 0 M VENTAN. X 540 M /H x VENT
2 3
= 0 M3/H
GANANCIA SOLAR Y TRANSMISIÓN PAREDES Y TEJ. 17 INFILTRAC. X 12 M3/H x INFILT = 204 M3/H
ORIENTACION ( M2) DIF.TEMP ºC FACTORES KCAL/H M3/H DE AIRE EXTERIOR = 204 M3/H
E PARED 0 X 6 X 1.66 X 1 = 0.00 PTO DE ROCIO DEL APARATO (ADP)
SE PARED 0 X 14.4 X 1.66 X 1 = 0.00
CSEL
S PARED 6.6 X 6 X 1.66 X 1 = 65.74 FCS  ; FCS  0.8
SO PARED 0 X 4.4 X 1.66 X 1 = 0.00 CSEL  CLEL
O PARED 6.6 X 6 X 1.66 X 1 = 65.74 DIF.TEMP=24ºC - ºC ADP ELEGIDO X (1- BP)= 9.6 ºC
NO PARED 0 X 3.3 X 1.66 X 1 = 0.00 ADP SELECCIÓN. 7 ºC ADP ELEGIDO 12 ºC
N PARED 0 X 6 X 1.66 X 1 = 0.00 IMPULSION DE AIRE
NE PARED 0 X 8.3 X 1.66 X 1 = 0.00 M3 CSEL
= ; 1,944.3 M3/H
TEJ. SOL 0 X 6 X 1.66 X 1 = 0.00 H 0 .3 X ( DIF TEMP ) ºC
TRANSMISION EXCEPTO PAREDES Y TECHO CONDICIONES DE ENTRADA Y SALIDA
CONCEPTO ( M2) DIF TEMP ºC FACTORES KCAL/H
TABIQUES
TECHO
0
0
X
X
6
6
X
X
2
1.4
X
X
1
1
=
=
0.00
0.00
24+ [ AIRE EXTERIOR
AIRE IMPULSION
* ( DIF. TEMP. BS ) ] 24.6 ºC TMP

PISO 32.12 X 6 X 1.4 X 1 = 269.81 10ºC BY-PASS x 25 ºC TMP -- (ADP)= 12.9 ºC


CRISTAL 15.1 X 6 X 5.5 X 1 = 498.30
INFILTRACION 17 X 6 X 0.3 X = 331.50
CALOR INTERNO
NUMEROS DE PERSONAS 6 PERSONAS X 60 = 360.00
POT. APAR. ELECTRICOS 200 WATIOS X 0.86 = 172.80
ALUMBRADO DEL LOCAL 192 WATIOS X 1.08 = 207.36
OTROS CONSUMOS ELECT 0 WATIOS X = 0.00
CALOR SENSIBLE LOCAL (CSL) 5526.23
BY-PASS DE AIRE EXTERIOR
AIRE EXTERIOR M3/H x 6 ºC x 0,2 BP x 0,3 = 73.44
CALOR SENSIBLE EFECTIVO DEL LOCAL (CSEL) 5599.67
CALOR LATENTE
NUMEROS DE PERSONAS 6 PERSONAS X 50 = 300.00
DISTINTAS FUENTES GENERADORAS DEVAPOR O FUENTE 1120.00
CALOR LATENTE DEL LOCAL (CLL) 1420.00
BY-PASS DE AIRE EXTERIOR
AIRE EXTERIOR M3/H x 8,5 GR/KG x 0,2 BPx 0.72 = 337.82
CALOR LATENTE EFECTIVO LOCAL 1757.82
CALOR TOTAL EFECTIVO LOCAL (CLEL) 7357.50
CALOR AIRE EXTERIOR
SENSIBLE M3/Hx 6 ºC x( 1- 0,2 BP) x 0.3 = 293.76
LATENTE M /H x 8,5GR/KG x (1- 0,2 BP)x 0.72 =
3
1351.30
GRAN CALOR TOTAL 9002.55

GRAN CALOR CON MARGEN DE SEGURIDAD 9902.806


CAPACIDAD DEL EQUIPO EN TR 3.3
HOJA DE GANANCIAS DE CALOR CALCULO DE CARGA TERMICA
ESPACIO USADO PARA: OFICINA DE PUBLICIDAD PRIMER PISO INSTALADOR WILLIAM BELTRAN
LARGO 8.9 ML SUPERFICIE 69.42 M2 BY-PASS 0.2 %
ANCHO 7.8 ML VOLUMEN 174 M3 CLIENTE LICOSINU
ALTO 2.5 ML FECHA 4/7/2011 HORA LOCAL:13:00 HORA PICO
GANANCIA SOLAR POR CRISTALES CARGA MAXIMA:13:00
ORIENTACION ( M2) GANANCIA FACTORES KCAL/H CONDICIONES TEMP B.S TEMP. BH GRM/KG %HR
E CRISTAL: 0 X 447 X 0.54 X 1 = 0.00 INTERIORES 27 22 12 55
SE CRISTAL: 0 X 38 X 0.56 X 1 = 0.00 EXTERIORES 33 28 23.5 75
S CRISTAL: 4.9 X 442 X 0.6 X 1 = 1299.48 DIFERENCIAS 6 11.5
SO CRISTAL: 0 X 157 X 0.56 X 1 = 0.00 INFILTRACION Y VENTILACION
O CRISTAL: 10 X 447 X 0.51 X 1 = 2279.70 20 PERSONAS X 11 M3/H x PERS. = 220 M3/H
NO CRISTAL: 0 X 124 X 0.56 X 1 = 0.00 174 M 3
X 1.5 M3/H = 260 M3/H
N CRISTAL: 0 X 54 X 0.83 X 1 = 0.00 0 M2 PUERT. X 540 M3/H x PUERT = 0 M3/H
NE CRISTAL: 0 X 38 X 0.56 X 1 = 0.00 0 M VENTAN. X 540 M /H x VENT
2 3
= 0 M3/H
GANANCIA SOLAR Y TRANSMISIÓN PAREDES Y TEJ. 17 INFILTRAC. X 12 M3/H x INFILT = 204 M3/H
ORIENTACION ( M2) DIF.TEMP ºC FACTORES KCAL/H M3/H DE AIRE EXTERIOR = 260 M3/H
E PARED 23.4 X 6 X 1.66 X 1 = 233.06 PTO DE ROCIO DEL APARATO (ADP)
SE PARED 0 X 14.4 X 1.66 X 1 = 0.00
CSEL
S PARED 21.45 X 6 X 1.66 X 1 = 213.64 FCS  ; FCS  0.8
SO PARED 0 X 4.4 X 1.66 X 1 = 0.00 CSEL  CLEL
O PARED 13.2 X 6 X 1.66 X 1 = 131.47 DIF.TEMP=24ºC - ºC ADP ELEGIDO X (1- BP)= 9.6 ºC
NO PARED 0 X 3.3 X 1.66 X 1 = 0.00 ADP SELECCIÓN. 7 ºC ADP ELEGIDO 12 ºC
N PARED 26.7 X 6 X 1.66 X 1 = 265.93 IMPULSION DE AIRE
NE PARED 0 X 8.3 X 1.66 X 1 = 0.00 M3 CSEL
= ; 2,987.3 M3/H
TEJ. SOL 69.42 X 6 X 1.66 X 1 = 691.42 H 0 .3 X ( DIF TEMP ) ºC
TRANSMISION EXCEPTO PAREDES Y TECHO CONDICIONES DE ENTRADA Y SALIDA
CONCEPTO ( M2) DIF TEMP ºC FACTORES KCAL/H
TABIQUES
TECHO
0
0
X
X
6
6
X
X
2
1.4
X
X
1
1
=
=
0.00
0.00
24+ [ AIRE EXTERIOR
AIRE IMPULSION
* ( DIF. TEMP. BS ) ] 24.5 ºC TMP

PISO 69.42 X 6 X 1.4 X 1 = 583.13 10ºC BY-PASS x 25 ºC TMP -- (ADP)= 12.9 ºC


CRISTAL 10 X 6 X 5.5 X 1 = 330.00
INFILTRACION 4.9 X 6 X 0.3 X = 331.50
CALOR INTERNO
NUMEROS DE PERSONAS 20 PERSONAS X 60 = 1200.00
POT. APAR. ELECTRICOS 600 WATIOS X 0.86 = 518.40
ALUMBRADO DEL LOCAL 400 WATIOS X 1.08 = 432.00
OTROS CONSUMOS ELECT 0 WATIOS X = 0.00
CALOR SENSIBLE LOCAL (CSL) 8509.74
BY-PASS DE AIRE EXTERIOR
AIRE EXTERIOR M3/H x 6 ºC x 0,2 BP x 0,3 = 93.72
CALOR SENSIBLE EFECTIVO DEL LOCAL (CSEL) 8603.46
CALOR LATENTE
NUMEROS DE PERSONAS 20 PERSONAS X 50 = 1000.00
DISTINTAS FUENTES GENERADORAS DEVAPOR O FUENTE 1120.00
CALOR LATENTE DEL LOCAL (CLL) 2120.00
BY-PASS DE AIRE EXTERIOR
AIRE EXTERIOR M3/H x 8,5 GR/KG x 0,2 BPx 0.72 = 431.10
CALOR LATENTE EFECTIVO LOCAL 2551.10
CALOR TOTAL EFECTIVO LOCAL (CLEL) 11154.56
CALOR AIRE EXTERIOR
SENSIBLE M3/Hx 6 ºC x( 1- 0,2 BP) x 0.3 = 374.87
LATENTE M /H x 8,5GR/KG x (1- 0,2 BP)x 0.72 =
3
1724.39
GRAN CALOR TOTAL 13253.82

GRAN CALOR CON MARGEN DE SEGURIDAD 14579.2


CAPACIDAD DEL EQUIPO EN TR 4.8
HOJA DE GANANCIAS DE CALOR CALCULO DE CARGA TERMICA
ESPACIO USADO PARA: VENTAS, SUBGERENCIA ,SISTEMAS - P1 INSTALADOR WILLIAM BELTRAN
LARGO 13.2 ML SUPERFICIE 103 M2 BY-PASS 0.2 %
ANCHO 7.8 ML VOLUMEN 257.4 M3 CLIENTE LICOSINU
ALTO 2.5 ML FECHA 4/7/2011 HORA LOCAL:13:00 HORA PICO
GANANCIA SOLAR POR CRISTALES CARGA MAXIMA:13:00
ORIENTACION ( M2) GANANCIA FACTORES KCAL/H CONDICIONES TEMP B.S TEMP. BH GRM/KG %HR
E CRISTAL: 8.4 X 447 X 0.54 X 1 = 2027.59 INTERIORES 27 22 12 55
SE CRISTAL: 0 X 38 X 0.56 X 1 = 0.00 EXTERIORES 33 28 23.5 75
S CRISTAL: 13.2 X 442 X 0.6 X 1 = 3500.64 DIFERENCIAS 6 11.5
SO CRISTAL: 0 X 157 X 0.56 X 1 = 0.00 INFILTRACION Y VENTILACION
O CRISTAL: 10 X 447 X 0.51 X 1 = 2279.70 10 PERSONAS X 11 M3/H x PERS. = 110 M3/H
NO CRISTAL: 0 X 124 X 0.56 X 1 = 0.00 257 M 3
X 1.5 M3/H = 386 M3/H
N CRISTAL: 13.2 X 54 X 0.83 X 1 = 591.62 0 M2 PUERT. X 540 M3/H x PUERT = 0 M3/H
NE CRISTAL: 0 X 38 X 0.56 X 1 = 0.00 0 M VENTAN. X 540 M /H x VENT
2 3
= 0 M3/H
GANANCIA SOLAR Y TRANSMISIÓN PAREDES Y TEJ. 17 INFILTRAC. X 12 M3/H x INFILT = 204 M3/H
ORIENTACION ( M2) DIF.TEMP ºC FACTORES KCAL/H M3/H DE AIRE EXTERIOR = 386 M3/H
E PARED 13.2 X 6 X 1.66 X 1 = 131.47 PTO DE ROCIO DEL APARATO (ADP)
SE PARED 0 X 14.4 X 1.66 X 1 = 0.00
CSEL
S PARED 26.7 X 6 X 1.66 X 1 = 265.93 FCS  ; FCS  0.9
SO PARED 0 X 4.4 X 1.66 X 1 = 0.00 CSEL  CLEL
O PARED 13.2 X 6 X 1.66 X 1 = 131.47 DIF.TEMP=24ºC - ºC ADP ELEGIDO X (1- BP)= 9.6 ºC
NO PARED 0 X 3.3 X 1.66 X 1 = 0.00 ADP SELECCIÓN. 7 ºC ADP ELEGIDO 12 ºC
N PARED 6.7 X 6 X 1.66 X 1 = 66.73 IMPULSION DE AIRE
NE PARED 0 X 8.3 X 1.66 X 1 = 0.00 M3 CSEL
= ; 4,950.3 M3/H
TEJ. SOL 0 X 6 X 1.66 X 1 = 0.00 H 0 .3 X ( DIF TEMP ) ºC
TRANSMISION EXCEPTO PAREDES Y TECHO CONDICIONES DE ENTRADA Y SALIDA
CONCEPTO ( M2) DIF TEMP ºC FACTORES KCAL/H
TABIQUES
TECHO
0
0
X
X
6
6
X
X
2
1.4
X
X
1
1
=
=
0.00
0.00
24+ [ AIRE EXTERIOR
AIRE IMPULSION
* ( DIF. TEMP. BS ) ] 24.5 ºC TMP

PISO 102.96 X 6 X 1.4 X 1 = 864.86 10ºC BY-PASS x 24 ºC TMP -- (ADP)= 12.9 ºC


CRISTAL 44.8 X 6 X 5.5 X 1 = 1478.40
INFILTRACION 17 X 6 X 0.3 X = 331.50
CALOR INTERNO
NUMEROS DE PERSONAS 10 PERSONAS X 60 = 600.00
POT. APAR. ELECTRICOS 600 WATIOS X 0.86 = 518.40
ALUMBRADO DEL LOCAL 768 WATIOS X 1.08 = 829.44
OTROS CONSUMOS ELECT 0 WATIOS X = 500.00
CALOR SENSIBLE LOCAL (CSL) 14117.77
BY-PASS DE AIRE EXTERIOR
AIRE EXTERIOR M3/H x 6 ºC x 0,2 BP x 0,3 = 139.00
CALOR SENSIBLE EFECTIVO DEL LOCAL (CSEL) 14256.76
CALOR LATENTE
NUMEROS DE PERSONAS 10 PERSONAS X 50 = 500.00
DISTINTAS FUENTES GENERADORAS DEVAPOR O FUENTE 0.00
CALOR LATENTE DEL LOCAL (CLL) 500.00
BY-PASS DE AIRE EXTERIOR
AIRE EXTERIOR M3/H x 8,5 GR/KG x 0,2 BPx 0.72 = 639.38
CALOR LATENTE EFECTIVO LOCAL 1139.38
CALOR TOTAL EFECTIVO LOCAL (CLEL) 15396.15
CALOR AIRE EXTERIOR
SENSIBLE M3/Hx 6 ºC x( 1- 0,2 BP) x 0.3 = 555.98
LATENTE M /H x 8,5GR/KG x (1- 0,2 BP)x 0.72 =
3
2557.53
GRAN CALOR TOTAL 18509.66

GRAN CALOR CON MARGEN DE SEGURIDAD 20360.62


CAPACIDAD DEL EQUIPO EN TR 6.7
HOJA DE GANANCIAS DE CALOR CALCULO DE CARGA TERMICA
ESPACIO USADO PARA: SALA DE JUNTAS, GERENCIA (P2) INSTALADOR WILLIAM BELTRAN
LARGO 12.1 ML SUPERFICIE 60.5 M2 BY-PASS 0.2 %
ANCHO 5 ML VOLUMEN 151 M3 CLIENTE LICOSINU
ALTO 2.5 ML FECHA 4/7/2011 HORA LOCAL:13:00 HORA PICO
GANANCIA SOLAR POR CRISTALES CARGA MAXIMA:13:00
ORIENTACION ( M2) GANANCIA FACTORES KCAL/H CONDICIONES TEMP B.S TEMP. BH GRM/KG %HR
E CRISTAL: 10 X 447 X 0.54 X 1 = 2413.80 INTERIORES 27 22 12 55
SE CRISTAL: 0 X 38 X 0.56 X 1 = 0.00 EXTERIORES 33 28 23.5 75
S CRISTAL: 8.4 X 442 X 0.6 X 1 = 2227.68 DIFERENCIAS 6 11.5
SO CRISTAL: 0 X 157 X 0.56 X 1 = 0.00 INFILTRACION Y VENTILACION
O CRISTAL: 10 X 447 X 0.51 X 1 = 2279.70 10 PERSONAS X 11 M3/H x PERS. = 110 M3/H
NO CRISTAL: 0 X 124 X 0.56 X 1 = 0.00 151 M 3
X 1.5 M3/H = 227 M3/H
N CRISTAL: 0 X 54 X 0.83 X 1 = 0.00 0 M2 PUERT. X 540 M3/H x PUERT = 0 M3/H
NE CRISTAL: 0 X 38 X 0.56 X 1 = 0.00 0 M VENTAN. X 540 M /H x VENT
2 3
= 0 M3/H
GANANCIA SOLAR Y TRANSMISIÓN PAREDES Y TEJ. 17 INFILTRAC. X 12 M3/H x INFILT = 204 M3/H
ORIENTACION ( M2) DIF.TEMP ºC FACTORES KCAL/H M3/H DE AIRE EXTERIOR = 227 M3/H
E PARED 3.3 X 6 X 1.66 X 1 = 32.87 PTO DE ROCIO DEL APARATO (ADP)
SE PARED 0 X 14.4 X 1.66 X 1 = 0.00
CSEL
S PARED 23.4 X 6 X 1.66 X 1 = 233.06 FCS  ; FCS  0.9
SO PARED 0 X 4.4 X 1.66 X 1 = 0.00 CSEL  CLEL
O PARED 5 X 6 X 1.66 X 1 = 49.80 DIF.TEMP=24ºC - ºC ADP ELEGIDO X (1- BP)= 9.6 ºC
NO PARED 0 X 3.3 X 1.66 X 1 = 0.00 ADP SELECCIÓN. 7 ºC ADP ELEGIDO 12 ºC
N PARED 0 X 6 X 1.66 X 1 = 0.00 IMPULSION DE AIRE
NE PARED 0 X 8.3 X 1.66 X 1 = 0.00 M3 CSEL
= ; 3,980.6 M3/H
TEJ. SOL 0 X 6 X 1.66 X 1 = 0.00 H 0 .3 X ( DIF TEMP ) ºC
TRANSMISION EXCEPTO PAREDES Y TECHO CONDICIONES DE ENTRADA Y SALIDA
CONCEPTO ( M2) DIF TEMP ºC FACTORES KCAL/H
TABIQUES
TECHO
0
60.5
X
X
6
6
X
X
2
1.4
X
X
1
1
=
=
0.00
508.20
24+ [ AIRE EXTERIOR
AIRE IMPULSION
* ( DIF. TEMP. BS ) ] 24.3 ºC TMP

PISO 60.5 X 6 X 1.4 X 1 = 508.20 10ºC BY-PASS x 24 ºC TMP -- (ADP)= 12.9 ºC


CRISTAL 28.4 X 6 X 5.5 X 1 = 937.20
INFILTRACION 17 X 6 X 0.3 X = 331.50
CALOR INTERNO
NUMEROS DE PERSONAS 10 PERSONAS X 60 = 600.00
POT. APAR. ELECTRICOS 400 WATIOS X 0.86 = 345.60
ALUMBRADO DEL LOCAL 384 WATIOS X 1.08 = 414.72
OTROS CONSUMOS ELECT 0 WATIOS X = 500.00
CALOR SENSIBLE LOCAL (CSL) 11382.33
BY-PASS DE AIRE EXTERIOR
AIRE EXTERIOR M3/H x 6 ºC x 0,2 BP x 0,3 = 81.68
CALOR SENSIBLE EFECTIVO DEL LOCAL (CSEL) 11464.01
CALOR LATENTE
NUMEROS DE PERSONAS 10 PERSONAS X 50 = 500.00
DISTINTAS FUENTES GENERADORAS DEVAPOR O FUENTE 1120.00
CALOR LATENTE DEL LOCAL (CLL) 1620.00
BY-PASS DE AIRE EXTERIOR
AIRE EXTERIOR M3/H x 8,5 GR/KG x 0,2 BPx 0.72 = 375.71
CALOR LATENTE EFECTIVO LOCAL 1995.71
CALOR TOTAL EFECTIVO LOCAL (CLEL) 13459.71
CALOR AIRE EXTERIOR
SENSIBLE M3/Hx 6 ºC x( 1- 0,2 BP) x 0.3 = 326.70
LATENTE M /H x 8,5GR/KG x (1- 0,2 BP)x 0.72 =
3
1502.82
GRAN CALOR TOTAL 15289.23

GRAN CALOR CON MARGEN DE SEGURIDAD 16818.16


CAPACIDAD DEL EQUIPO EN TR 5.6
HOJA DE GANANCIAS DE CALOR CALCULO DE CARGA TERMICA
ESPACIO USADO PARA: HALL, RECEPCION (P2) INSTALADOR WILLIAM BELTRAN
LARGO 8.9 ML SUPERFICIE 69.42 M2 BY-PASS 0.2 %
ANCHO 7.8 ML VOLUMEN 174 M3 CLIENTE LICOSINU
ALTO 2.5 ML FECHA 4/7/2011 HORA LOCAL:13:00 HORA PICO
GANANCIA SOLAR POR CRISTALES CARGA MAXIMA:13:00
ORIENTACION ( M2) GANANCIA FACTORES KCAL/H CONDICIONES TEMP B.S TEMP. BH GRM/KG %HR
E CRISTAL: 16.5 X 447 X 0.54 X 1 = 3982.77 INTERIORES 27 22 12 55
SE CRISTAL: 0 X 38 X 0.56 X 1 = 0.00 EXTERIORES 33 28 23.5 75
S CRISTAL: 0 X 442 X 0.6 X 1 = 0.00 DIFERENCIAS 6 11.5
SO CRISTAL: 0 X 157 X 0.56 X 1 = 0.00 INFILTRACION Y VENTILACION
O CRISTAL: 13.2 X 447 X 0.51 X 1 = 3009.20 6 PERSONAS X 11 M3/H x PERS. = 66 M3/H
NO CRISTAL: 0 X 124 X 0.56 X 1 = 0.00 174 M 3
X 1.5 M3/H = 260 M3/H
N CRISTAL: 0 X 54 X 0.83 X 1 = 0.00 0 M2 PUERT. X 540 M3/H x PUERT = 0 M3/H
NE CRISTAL: 0 X 38 X 0.56 X 1 = 0.00 0 M VENTAN. X 540 M /H x VENT
2 3
= 0 M3/H
GANANCIA SOLAR Y TRANSMISIÓN PAREDES Y TEJ. 17 INFILTRAC. X 12 M3/H x INFILT = 204 M3/H
ORIENTACION ( M2) DIF.TEMP ºC FACTORES KCAL/H M3/H DE AIRE EXTERIOR = 260 M3/H
E PARED 6.7 X 6 X 1.66 X 1 = 66.73 PTO DE ROCIO DEL APARATO (ADP)
SE PARED 0 X 14.4 X 1.66 X 1 = 0.00
CSEL
S PARED 0 X 6 X 1.66 X 1 = 0.00 FCS  ; FCS  0.9
SO PARED 0 X 4.4 X 1.66 X 1 = 0.00 CSEL  CLEL
O PARED 10 X 6 X 1.66 X 1 = 99.60 DIF.TEMP=24ºC - ºC ADP ELEGIDO X (1- BP)= 9.6 ºC
NO PARED 0 X 3.3 X 1.66 X 1 = 0.00 ADP SELECCIÓN. 7 ºC ADP ELEGIDO 12 ºC
N PARED 21.5 X 6 X 1.66 X 1 = 214.14 IMPULSION DE AIRE
NE PARED 0 X 8.3 X 1.66 X 1 = 0.00 M3 CSEL
= ; 4,051.4 M3/H
TEJ. SOL 0 X 6 X 1.66 X 1 = 0.00 H 0 .3 X ( DIF TEMP ) ºC
TRANSMISION EXCEPTO PAREDES Y TECHO CONDICIONES DE ENTRADA Y SALIDA
CONCEPTO ( M2) DIF TEMP ºC FACTORES KCAL/H
TABIQUES
TECHO
0
69.42
X
X
6
6
X
X
2
1.4
X
X
1
1
=
=
0.00
583.13
24+ [ AIRE EXTERIOR
AIRE IMPULSION
* ( DIF. TEMP. BS ) ] 24.4 ºC TMP

PISO 69.42 X 6 X 1.4 X 1 = 583.13 10ºC BY-PASS x 24 ºC TMP -- (ADP)= 12.9 ºC


CRISTAL 29.7 X 6 X 5.5 X 1 = 980.10
INFILTRACION 17 X 6 X 0.3 X = 331.50
CALOR INTERNO
NUMEROS DE PERSONAS 6 PERSONAS X 60 = 360.00
POT. APAR. ELECTRICOS 400 WATIOS X 0.86 = 345.60
ALUMBRADO DEL LOCAL 480 WATIOS X 1.08 = 518.40
OTROS CONSUMOS ELECT 0 WATIOS X = 500.00
CALOR SENSIBLE LOCAL (CSL) 11574.30
BY-PASS DE AIRE EXTERIOR
AIRE EXTERIOR M3/H x 6 ºC x 0,2 BP x 0,3 = 93.72
CALOR SENSIBLE EFECTIVO DEL LOCAL (CSEL) 11668.02
CALOR LATENTE
NUMEROS DE PERSONAS 6 PERSONAS X 50 = 300.00
DISTINTAS FUENTES GENERADORAS DEVAPOR O FUENTE 1120.00
CALOR LATENTE DEL LOCAL (CLL) 1420.00
BY-PASS DE AIRE EXTERIOR
AIRE EXTERIOR M3/H x 8,5 GR/KG x 0,2 BPx 0.72 = 431.10
CALOR LATENTE EFECTIVO LOCAL 1851.10
CALOR TOTAL EFECTIVO LOCAL (CLEL) 13519.12
CALOR AIRE EXTERIOR
SENSIBLE M3/Hx 6 ºC x( 1- 0,2 BP) x 0.3 = 374.87
LATENTE M /H x 8,5GR/KG x (1- 0,2 BP)x 0.72 =
3
1724.39
GRAN CALOR TOTAL 15618.38

GRAN CALOR CON MARGEN DE SEGURIDAD 17180.22


CAPACIDAD DEL EQUIPO EN TR 5.7