MURO DE CONTENCION EN VOLADIZO CON ANG CR13 CLEMER

DATOS:
H(m) 5.35 A(m) 0.25
B(m) 1.75 a(m) 0.25
h(m) 0.6
p(m) 0.25
DATOS BASICOS RADIANES
relleno: PE (kg/m3) 2141.37 angulo de f 40 0.698131701
factor seg volteo 1.8
suelo base
PE (kg/m3) 1700 angulo de f 30 0.523598776
factor seg deslizamiento 1.8 cap portante 3
otros
fc(kg/cm2) 210 PE C° 2400
fy(kg/cm2) 4200 beta 15 0.261799388
r(cm) 6

calculo de Ka y Pa
ka 0.2346280366
pa (KG) 7190.3360605671 sobrecarga 0 pa=
CALCULO DE CARGAS VERTICALES - HORIZONTALES Y LOS MMENTOS ESTABILIZANTES - VOLTEO K EFECTUA E
Ph(kg) 6945.3313005994
Pv(kg) 1860.9959131622
analisis vertical

CARGA CALCULO DE PESO PESO (kg) braso momento


w1 2850 0.375 1068.75
w2 2520 0.875 2205
w3 1425 0.5833325 831.2488125
w4 1271.4384375 0.666666675 847.6256356
w5 10171.5075 1.25 12714.38438
w6 448.2643454658 1.33333375 597.6859807

pav 1860.9959131622 0.6666666667 1240.663942


sum F(vert) 20547.206196128 sum(mest) 19505.35875
x 0.1666666667

analisis horizntal

CARGA CALCULO DE PESO PESO (kg) braso momento


pah calculado 6945.3313005994 1.7833333333 12385.84082

sum F(horiz) 6945.3313005994 sum F(Mvol) 12385.84082

estabilidad por volteo


sum(Mesta/sumFhor) > FS
1.5748110306 > 1.8 ok
ESTABILIDAD DE DESLIZAMIENTO

f= 0.5196152423
1.5372400629 > 1.8 error

2.3 cmprobacion de la resultante en la base


x(m)= 0.3464956675
e(m)= 0.5285043325 0.5
2.4 comprobacion de la capacidad del suelo
cap del suelo > qmax
3 > 3.1869136141
kg/cm2 kg/cm2
2.5 calculo de esrzos cortantes y momentos
calculo de esfuerzo en talon
W1+W2= 11068.036191

-8386.6147739298 26118.3145816671 14616.671463


40255.750914863

0.25 0.25 0.25 1


1.75
talon
11068.0361909316
+
14616.6714631348 -8386.614774

=
-3548.6352722032 19454.650965

1
analisis de la pantalla
3.166666667
4.75
1.583333333
0.6

2.6 analisis de cortantes


vc 6.5283652242
punta talon pantalla
v kg 7248.431340325 7953.0078463291 5667.9869811
b (cm) 100 100 100
d (cm) 54 54 17
va 1.3423021001 1.4727792308 3.3341099889
ok ok ok
2.7 analisis de momentos y aceros
punta talon pantalla
M (kg-m) 936.0061131618 5893.4444429199 8974.3127201
Mu (kg-cm) 93600.6113161808 589344.444291994 897431.27201
b (cm) 100 100 100
d (cm) 54 54 45
fc (kg/cm2) 210 210 210
fy (kg/cm2) 4200 4200 4200
ku 0.0015285226 0.0096241499 0.021103616
w 0.0017000637 0.010761832 0.0237821611
p 8.500318486551E-05 0.0005380916 0.0011891081
As 0.4590171983 2.9056946274 5.3509862392
As min 8.1
As min 13.0422390716 13.0422390716 4.1058900781
CLEMER

r op 5 50

COS^2 COS SEN tang


0.586824089 0.766044443

0.577350269

0.933012702 0.965925826 0.258819045 0.267949192

7190.336061
NTES - VOLTEO K EFECTUA EL MURO

0.334936491
w6
W4 3.566666667

5.35 W3
w1 W5 4.75 1.783333333
w2 0.6
0.25 0.25 0.25 1
1.75
2.7m
qmax 31869.13614 kg/m -8386.61477 qmin

q= 896.5286909

q= 10171.5075

-8386.61477

1.5

punta

31869.13614 26118.31458

0.25

2.375 v relleno 5667.986981


2.375 v s/c 0
60
0.423333333