Application :
RISH Master 3430 measures important electrical parameters in
3 phase and single phase Network & replaces the multiple
analog panel meters. It measures electrical parameters like
AC current, Voltage, frequency, Power, Energy (Active/
Reactive/Apparent), Harmonic Distortion. The instrument has
optional output as one pulse output or two pulse output for
energy measurement.
Product Features: %THD
Technical Specifications:
Input Voltage:
Nominal input voltage (AC RMS) Phase –Neutral 63.5 / 133 / 239.6 / 254VL-N
Line-Line 110 / 230 / 415 / 440 VL-L
System PT primary values 100VLL to 692kVLL programmable on site.
Max continuous input voltage 120% of rated value
Input Current:
Nominal input current 5A AC RMS.
System CT secondary values 1A & 5A programmable on site.
System CT primary values From 1A up to 9999A (for 1 or 5 Amp )
Max continuous input current 120% of rated value
Auxiliary Supply:
AC Auxiliary Supply 110 V AC -15% / +20%
230 V AC -15% / +20%
380 VAC-15% / +20
AC /DC Auxiliary Supply 100 – 250 VAC /DC +/- 10%
DC Auxiliary Supply 12…..48 VDC +/- 10%
AC Auxiliary supply frequency range 45 to 66 Hz
VA Burden:
Nominal input voltage burden < 0.2 VA approx. per phase
Nominal input current burden < 0.6 VA approx. per phase
Auxillary Supply burden < 4 VA approx OR < 5VA approx with 4-20mA analog output option
Overload Withstand:
Voltage 2 x rated value for 1 second, repeated 10 times at 10 second intervals
Current 20x for 1 second, repeated 5 times at 5 min
Technical Specifications:
Accuracy:
Accuracy 1.0 (Standard) Accuracy 0.5 (on request) Accuracy 0.2 (on request)
Voltage ± 0.5% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Current ± 0.5% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Frequency ± 0.15% of mid frequency ± 0.15% of mid frequency ± 0.15% of mid frequency
Active Power ± 0.5% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Re-Active Power ± 0.5% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Apparent Power ± 0.5% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Active energy (kWh) ± 1.0% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Re Active energy (kVArh) ± 1.0% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Apparent energy (kVAh) ± 1.0% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Accuracy of Analog Output 1 % of Output end value 1 % of Output end value 1 % of Output end value
Power Factor ±1% of Unity ±1% of Unity ±1.0% of Unity
Angle ±1% of range ±1% of range ±1% of range
Total Harmonic Distortion ±1% ±1% ±1%
Measurement error is normally much less than the error specified above. Variation due to influence quantity is less than twice the error allowed for reference condition
Influence of Variations:
Temperature coefficient :(for rated value 0.05%/°C for Voltage (50... 120% of rated value) and
range of use (0…50°C)) 0.05%/°C for Current (10... 120% of rated value)
Applicable Standards:
EMC IEC 61326
Immunity IEC 61000-4-3. 10V/m min – Level 3 industrial low level
Safety IEC 61010-1-2001 , Permanently connected use
IP for water & dust IEC60529
Pollution degree: 2
Installation category: III
High Voltage Test 2.2 kV AC, 50Hz for 1 minute between all electrical circuits
Environmental
Operating temperature -10 to +55°C
Storage temperature -20 to +65°C
Relative humidity 0... 90% non condensing
Warm up time Minimum 3 minute
Shock 15g in 3 planes
Vibration 10... 55 Hz, 0.15mm amplitude
Enclosure IP54 (front face only)
Electrical Connections:
For 3 Phase 4 Wire Unbalanced Load
2 5 8 11 1 3 4 6 7 9 13 14
L N
+ -
AUX
SUPPLY
L1
L2
L3
N
L N
+ -
AUX
SUPPLY
L1
L2
L3
L N
+ -
AUX
SUPPLY
L1
L2
L3
N
It is recommended that the wires used for connections to the instrument should have lugs soldered at the end. That is, the connections
should be made with Lugged wires for secure connections. The Maximum diameter of the lug should be 7.0 mm and maximum thickness
3.5 mm. Permissible cross section of the connection wires: <= 4.0 mm2 single wire or 2 × 2.5 mm2 fine wire.
Dimensions
96 mm 80 mm 92mm+0.8
Display Area
96 mm 92mm+0.8
Panel Cutout
Order Code:
Ordering information Ordering Code RISH Master 3430
Accuracy Class
Accuracy 1.0% (Standard) 1.0
Accuracy 0.5% (on request) 0.5
Accuracy 0.2% (on request) 0.2
System Type (Connection network)
3 Phase (programmable as 4 Wire or 3 Wire on site) 3
1 Phase 1
Input Voltage
110V L-L (63.5V L-N) 110
230V L-L (133V L-N) 230
415V L-L (239.6V L-N) 415
440V L-L (254V L-N) 440
AC Auxiliary Voltage
110 V AC -15% / +20% L
230 V AC -15% / +20% M
380 VAC-15% / +20 % H
AC/DC Auxiliary Supply Voltage
100 – 250V AC/DC +/- 10% AD
12V… 48V V DC +/- 10 % D
Communication Interface (Optional):
MODBUS (RS485) output R
Ethernet (Modbus TCP/IP) output E
Communication Option not used Z
Optional: Pulse Output for energy measurement
1 Pulse output S
2 Pulse output D
Pulse Output option not used Z
Optional: Analog Outputs
2 outputs ( 0 – 1mA ) 1
2 outputs ( 4 – 20 mA ) 2
Analog Outputs option not used Z