Está en la página 1de 6

RISH Master 3430

Digital Multifunction Instrument with onsite pluggable output options

Application :
RISH Master 3430 measures important electrical parameters in
3 phase and single phase Network & replaces the multiple
analog panel meters. It measures electrical parameters like
AC current, Voltage, frequency, Power, Energy (Active/
Reactive/Apparent), Harmonic Distortion. The instrument has
optional output as one pulse output or two pulse output for
energy measurement.
Product Features: %THD

On site programmable PT/CT ratios:


It is possible to program primary of external potential
Transformer (PT), primary of external Current Transformer (CT)
on site via front panel keys by entering into Programming mode.

User selectable CT Secondary 5A/1A


The secondary of external Current Transformer (CT) can be
Total Harmonic Distortion (THD):
programmed on site to either 5A or 1A using front panel keys.
The instrument can measures per phase THD of voltage and
User selectable 3 phase 3W or 4W THD of current.
User can program on site the network connection as either 3 Programmable Energy format & Energy rollover count:
Phase 3 Wire or 4 Wire using front panel keys. For single phase
Customer can assign the format for energy display on MODBUS
applications, single phase version is available.
(RS485) in terms of W, kW or MW. Additional to this, customer
Low back depth: can also set a rollover count from 7 to 14 digits (for W), 7 to 12
digits (for kW) & 7 to 9 digits (for MW), after which the energy will
The instrument has very low back depth (behind the panel) of roll back to zero. The above settings are applicable for all types
less than 80 mm in spite of optional features like pulse output of energy.
Onsite selection of Auto scroll / Fixed Screen Energy Count storage:
User can set the display in auto scrolling mode or fixed screen In case of power failure, the instrument memorizes the last
mode using front panel keys. energy count. Every 40 sec, the instrument updates the energy
counter in the non-volatile memory.
Energy measurement (Import and Export):
Active energy (kWhr), Reactive energy (kVArhr) and Apparent Min Max storage of parameters possible
energy ( kVAhr). Any of the parameters can be freely assigned to
2 optional pulse outputs. The instrument stores minimum and maximum values for
System Voltage and System Current. Every 40 sec minimum
Energy Update Rate ( 3 Phase only): and maximum readings are updated.
This updates the energy values in the registers depending on the Optional MODBUS (RS485) Output (With Optical Isolation)
energy rate selected by the user. Energy update rate can be set
The optional ModBus output enables the instrument to transmit
from 1 min. to 60 min.
all the measured parameters over standard MODBUS (RS485 ).
True RMS measurement Ethernet Interface (Modbus TCP/IP Protocol)
The instrument measures distorted waveform up to 15th The optional Ethernet Interface output transmit all the measured
Harmonic. parameters on Modbus TCP/IP. Also user can configure their
instrument via Ethernet Interface.
High brightness 3 line 4 digits LED display:
Simultaneous display of 3 Parameters Optional Pulse Output ( 1 or 2 Relay output)
The optional pulse output is a potential free, very fast acting relay
Number of parameters measured: up to 48 contact which can be used to drive an external mechanical
The instrument measures 48 electrical parameters of 3 Phase counter for energy measurement.
network.
Optional Analog Outputs
Parameter Screen recall: (2 Outputs – 4-20mA or 0 -1 mA): 2 Analog outputs can be
In case of power failure, the instrument memorizes the last programmed from a list of input parameters.
displayed screen. The displayed screen will get memorized only Enclosure Protection for dust and water:
if user keeps this screen for minimum 40 sec duration before conforms to IP 54 (front face) as per IEC60529
power failure for fixed screen mod.
Compliance to International Safety standards
Compliance to International Safety standard IEC 61010-1- 2001
User selectable Low Current suppression (below 30 mA)
User can suppress the readings below 30 mA in the current EMC Compatibility
measurement by onsite programming if required. Compliance to International standard IEC 61326
RISHABH INSTRUMENTS PVT.LTD.
F-31, MIDC, Satpur, Nashik-422 007,India.
Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064
E-mail : India :- marketing@rishabh.co.in
International :- exp.marketing@rishabh.co.in
www.rishabh.co.in
Rev : I 06/15
Page 1/6
RISH Master 3430
Digital Multifunction Instrument with onsite pluggable output options

Technical Specifications:
Input Voltage:
Nominal input voltage (AC RMS) Phase –Neutral 63.5 / 133 / 239.6 / 254VL-N
Line-Line 110 / 230 / 415 / 440 VL-L
System PT primary values 100VLL to 692kVLL programmable on site.
Max continuous input voltage 120% of rated value

Input Current:
Nominal input current 5A AC RMS.
System CT secondary values 1A & 5A programmable on site.
System CT primary values From 1A up to 9999A (for 1 or 5 Amp )
Max continuous input current 120% of rated value

Auxiliary Supply:
AC Auxiliary Supply 110 V AC -15% / +20%
230 V AC -15% / +20%
380 VAC-15% / +20
AC /DC Auxiliary Supply 100 – 250 VAC /DC +/- 10%
DC Auxiliary Supply 12…..48 VDC +/- 10%
AC Auxiliary supply frequency range 45 to 66 Hz

VA Burden:
Nominal input voltage burden < 0.2 VA approx. per phase
Nominal input current burden < 0.6 VA approx. per phase
Auxillary Supply burden < 4 VA approx OR < 5VA approx with 4-20mA analog output option

Overload Withstand:
Voltage 2 x rated value for 1 second, repeated 10 times at 10 second intervals
Current 20x for 1 second, repeated 5 times at 5 min

Operating Measuring Ranges


Voltage 10… 120% of rated value
Current 5 … 120% of rated value
Frequency 40…70 Hz
Power Factor 0.5 Lag ... 1... 0.5 Lead

Reference conditions for Accuracy:


Reference temperature 23°C +/- 2°C
Input waveform Sinusoidal (distortion factor 0.005)
Input frequency 50 or 60 Hz ±2%
Auxiliary supply voltage Rated Value ±1%
Auxiliary supply frequency Rated Value ±1%
Voltage Range 50... 100% of Nominal Value.
60... 100% of Nominal Value for THD.
Current Range 10... 100% of Nominal Value.
20... 100% of Nominal Value for THD.
Power Cos phi / sin phi = 1 for Active / Reactive Power & Energy.
10... 100% of Nominal Current &
50... 100% of Nominal Voltage.
Power Factor / Phase Angle 40... 100% of Nominal Current &
50... 100% of Nominal Voltage.

RISHABH INSTRUMENTS PVT.LTD.


F-31, MIDC, Satpur, Nashik-422 007,India.
Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064
E-mail : India :- marketing@rishabh.co.in
International :- exp.marketing@rishabh.co.in
www.rishabh.co.in
Rev : I 06/15
Page 2/6
RISH Master 3430
Digital Multifunction Instrument with onsite pluggable output options

Technical Specifications:
Accuracy:
Accuracy 1.0 (Standard) Accuracy 0.5 (on request) Accuracy 0.2 (on request)
Voltage ± 0.5% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Current ± 0.5% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Frequency ± 0.15% of mid frequency ± 0.15% of mid frequency ± 0.15% of mid frequency
Active Power ± 0.5% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Re-Active Power ± 0.5% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Apparent Power ± 0.5% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Active energy (kWh) ± 1.0% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Re Active energy (kVArh) ± 1.0% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Apparent energy (kVAh) ± 1.0% of Nominal value ± 0.5% of Nominal value ± 0.2% of Nominal value
Accuracy of Analog Output 1 % of Output end value 1 % of Output end value 1 % of Output end value
Power Factor ±1% of Unity ±1% of Unity ±1.0% of Unity
Angle ±1% of range ±1% of range ±1% of range
Total Harmonic Distortion ±1% ±1% ±1%
Measurement error is normally much less than the error specified above. Variation due to influence quantity is less than twice the error allowed for reference condition

Influence of Variations:
Temperature coefficient :(for rated value 0.05%/°C for Voltage (50... 120% of rated value) and
range of use (0…50°C)) 0.05%/°C for Current (10... 120% of rated value)

Display update rate:


Response time to step input 1 sec approx.

Applicable Standards:
EMC IEC 61326
Immunity IEC 61000-4-3. 10V/m min – Level 3 industrial low level
Safety IEC 61010-1-2001 , Permanently connected use
IP for water & dust IEC60529
Pollution degree: 2
Installation category: III
High Voltage Test 2.2 kV AC, 50Hz for 1 minute between all electrical circuits

Environmental
Operating temperature -10 to +55°C
Storage temperature -20 to +65°C
Relative humidity 0... 90% non condensing
Warm up time Minimum 3 minute
Shock 15g in 3 planes
Vibration 10... 55 Hz, 0.15mm amplitude
Enclosure IP54 (front face only)

Energy Pulsed Output Option :


Relay contact 1 NO + 1 NC
Switching Voltage & Current for Relay 240 VDC ,5 A
Default pulse rate divisor 1 per Wh (up to 3600W), 1 per kWh (up to 3600kW), 1 per MWh (above 3600 kWh)
Other Pulse rate divisors (applicable only when Energy on RS485 is in W)
10 1 per 10 Wh (up to 3600W), 1 per 10kWh (up to 3600kW), 1 per 10MWh (above 3600 kWh)
100 1 per 100Wh (up to 3600W), 1 per 100kWh (up to 3600kW), 1 per 100MWh (above 3600 kWh)
1000 1 per 1000Wh (up to 3600W), 1 per 1000kWh (up to 3600kW), 1 per 1000MWh (above 3600 kWh)
Pulse duration 60 ms, 100 ms or 200 ms
Note : Above conditions are also applicable for Reactive and Apparent Energy .
RISHABH INSTRUMENTS PVT.LTD.
F-31, MIDC, Satpur, Nashik-422 007,India.
Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064
E-mail : India :- marketing@rishabh.co.in
International :- exp.marketing@rishabh.co.in
www.rishabh.co.in
Rev : I 06/15
Page 3/6
RISH Master 3430
Digital Multifunction Instrument with onsite pluggable output options

Parameter Measurement and Display:

Sr No Parameter 3 PH 4W 3PH 3W 1PH 2W


1. System Volts   
2. System Current   
3. Volts L1 – N   
4. Volts L2 – N   
5. Volts L3 – N   
6. Volts L1 – L2   
7. Volts L2 – L3   
8. Volts L3 – L1   
9. Current L1   
10. Current L2   
11. Current L3   
12. Neutral Current   
13. Frequency   
14. System Active Power (kW)   
15. Active Power L1 (kW)   
16. Active Power L2 (kW)   
17. Active Power L3 (kW)   
18. System Re-active Power (kVAr)   
19. Re-active Power L1 (kVAr)   
20. Re-active Power L2 (kVAr)   
21. Re-active Power L3 (kVAr)   
22. System Apparent Power (kVA)   
23. Apparent Power L1 (kVA)   
24. Apparent Power L2 (kVA)   
25. Apparent Power L3 (kVA)   
26. System Power Factor   
27. Power Factor L1   
28. Power Factor L2   
29. Power Factor L3   
30. Phase Angle L1   
31. Phase Angle L2   
32. Phase Angle L3   
33. Import kWh (8 digit resolution)   
34. Export kWh (8 digit resolution)   
35. Import kVArh (8 digit resolution)   
36. Export kVArh (8 digit resolution)   
37. kVAh (8 digit resolution)   
38. THD Volts L1-N   
39. THD Volts L2-N   
40. THD Volts L3-N   
41. THD Volts L1-L2   
42. THD Volts L2-L3   
43. THD Volts L3-L1   
44. THD Current L1   
45. THD Current L2   
46. THD Current L3   
47. THD Voltage Mean   
48. THD Current Mean   

RISHABH INSTRUMENTS PVT.LTD.


F-31, MIDC, Satpur, Nashik-422 007,India.
Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064
E-mail : India :- marketing@rishabh.co.in
International :- exp.marketing@rishabh.co.in
www.rishabh.co.in
Rev : I 06/15
Page 4/6
RISH Master 3430
Digital Multifunction Instrument with onsite pluggable output options

Electrical Connections:
For 3 Phase 4 Wire Unbalanced Load

2 5 8 11 1 3 4 6 7 9 13 14

L N
+ -
AUX
SUPPLY
L1
L2
L3
N

For 3 Phase 3 Wire Unbalanced Load


2 5 8 1 3 7 9 13 14

L N
+ -
AUX
SUPPLY
L1
L2
L3

For Single Phase


2 11 1 3 13 14

L N
+ -
AUX
SUPPLY
L1
L2
L3
N

It is recommended that the wires used for connections to the instrument should have lugs soldered at the end. That is, the connections
should be made with Lugged wires for secure connections. The Maximum diameter of the lug should be 7.0 mm and maximum thickness
3.5 mm. Permissible cross section of the connection wires: <= 4.0 mm2 single wire or 2 × 2.5 mm2 fine wire.

Dimensions

96 mm 80 mm 92mm+0.8

Display Area
96 mm 92mm+0.8

Panel Cutout

RISHABH INSTRUMENTS PVT.LTD.


F-31, MIDC, Satpur, Nashik-422 007,India.
Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064
E-mail : India :- marketing@rishabh.co.in
International :- exp.marketing@rishabh.co.in
www.rishabh.co.in
Rev : I 06/15
Page 5/6
RISH Master 3430
Digital Multifunction Instrument with onsite pluggable output options

Order Code:
Ordering information Ordering Code RISH Master 3430
Accuracy Class
Accuracy 1.0% (Standard) 1.0
Accuracy 0.5% (on request) 0.5
Accuracy 0.2% (on request) 0.2
System Type (Connection network)
3 Phase (programmable as 4 Wire or 3 Wire on site) 3
1 Phase 1
Input Voltage
110V L-L (63.5V L-N) 110
230V L-L (133V L-N) 230
415V L-L (239.6V L-N) 415
440V L-L (254V L-N) 440
AC Auxiliary Voltage
110 V AC -15% / +20% L
230 V AC -15% / +20% M
380 VAC-15% / +20 % H
AC/DC Auxiliary Supply Voltage
100 – 250V AC/DC +/- 10% AD
12V… 48V V DC +/- 10 % D
Communication Interface (Optional):
MODBUS (RS485) output R
Ethernet (Modbus TCP/IP) output E
Communication Option not used Z
Optional: Pulse Output for energy measurement
1 Pulse output S
2 Pulse output D
Pulse Output option not used Z
Optional: Analog Outputs
2 outputs ( 0 – 1mA ) 1
2 outputs ( 4 – 20 mA ) 2
Analog Outputs option not used Z

Order Code Example:


RISH Master 3430 0.2– 3– 415-AD-R-S-2
RISH Master 3430, Accuracy 0.2% , 3 phase( programmable onsite as 4 wire or 3 Wire), 415L-L nominal voltage, 100-250V AC/DC Auxiliary
supply, with ModBus (RS485),with 1 pulse output and 2 Analog Outputs ( 4 -20 mA ) . (No need to specify CT secondary as 5 A or 1 A is
programmable on site.)

Types AC Aux 100...250VACDC 12…48 VDC


(110V, 230V, 380V) Aux Aux
3430
3430 + 1pulse (1 Limit)   
3430 + 2pulse (2 Limit)   
3430 + Rs485   
3430 + 2 Analog Output   
3430 + 1pulse (1 Limit) +Rs485   
3430 + 1pulse (1 Limit)+ 2 Analog Output   
3430 + 2pulse (2 Limit)+ Rs485   
3430 + RS485+ 2 Analog Output   
3430 + RS485+1pulse (1 Limit) )+ 2 Analog Output   
3440 + Ethernet Interface (Modbus TCP/IP)   
Rishabh Instruments always tries for Improvement and therefore product specifications are subject to change without notice
RISHABH INSTRUMENTS PVT.LTD.
F-31, MIDC, Satpur, Nashik-422 007,India.
Tel.: +91 253 2202160, 2202202 Fax : +91 253 2351064
E-mail : India :- marketing@rishabh.co.in
International :- exp.marketing@rishabh.co.in
www.rishabh.co.in
Rev : I 06/15
Page 6/6

También podría gustarte