Está en la página 1de 129

E.N.G.I.N.E.E.R., Inc.

ELECTRICAL CODE &


ELECTRICAL PLANNING
DESIGN
William J. Juan, pee,rmp,mepf
0915 292 8668/0943 0616 215/0919 605 4873

Facebook Pages Administered:


ESEA Advocates / SOLARSAFE PHILIPPINES/ MEPF ENGINEERS../ E.N.G.I.N.E.E.R. Group
NAMPAP-PSUMP-PIPES Groups / ATTEMP/ STOP FLOODING… /
TALAKAYANG PINOY/ PUGAD LAWIN INTERNATIONAL
January 2017
Invocation
• Amang Banal, pinupuri Ka namin at
pinsasalamatan sa mga biyaya at sa tuloy-tuloy
mong paggabay sa amin, Maraming salamat
po sa pagkakataon na makapaglingkod sa
aming mga kapatid at sa aming Bayan, Sana po
ang gawaing ito ay magdudulot ng positibong
resulta na magbibigay ng dagdag na kaalaman,
kakayahan at kaunlaran ng bawat isa at para sa
aming Bayan, Lahat pong ito ay aming itinataas
sa Iyo Dakilang Ama sa Pangalan ng Inyong
Anak na si Jesus, Amen…
Short Resume of Speaker/Lecturer
• Engr. William Jacinto Juan, pee,rmp,mepf,ma
0915 292 8668 / 0943 0616 215 / 0919 605 4873

PEE-Top 1 (Oct.1980)/ Asso.EE-Top 3 (Sept.1979) / Asst.EE-Top 8 (Aug.1976) /


RMP-Top 5 (Sept.1989) / Amateur Radio License DU1-ICH (94.5% rating)
BSEE 1976 - NU/ BSME 1987 – NU
Admin/Founder – SOLARSAFE PHILIPPINES, a FB Group
Dep.Gen.Sec/Co-Founder – E.N.G.I.N.E.E.R., Inc.
Training Director/Co-Founder – MEPF Engineers Co.
Gen.Manager/Proprietor of FEMP Safety Engineering Construction, 2013-present
President/CEO/Founder of Versatech Consultants & Mngt.Corp., 1985-present
President, Phil.Integrated Plumbing Engineers Society (PIPES), 2014-present
Founding President, Phil. Society of United Master Plumbers (PSUMP), 2013
National President, Pro-Change NAMPAP, 2012-present
Former IIEE Nat’l Treasurer/ Nat’l Auditor/ Governor-at-Large
Former Chairmen, IIEE Balik Liwanag Committee & Electrical Safety Committee
Was Electrical Consultant/ Designer for PICOP/ SMC/ Parsons Int’l/ AEP Int’l/
Caltex/ Petron/ Coca Cola/ Selecta/ Avida / DMCI-UPDI/ Motolite Projects
Former EE Professor @ National U, 1979-1991
National President - Pugad Lawin Philippines, Inc., 2009,2010,2011
President – Rotary Club of Pasig North, RID3800, 2005-2006
Broadcaster – Talakayang Pinoy, DWAD 1098Khz
Electrical Engineering Design
• Electrical Engineering Design is the engineering
practice of providing for a safe and optimum
electrical scheme/s for buildings/plants/facilities,
including its power distribution system, standby
power generator system, uninterruptible power
supply (UPS) system, solar power system,
telecommunication system, fire detection & alarm
system (FDAS), signalization, grounding system,
lightning protection, building automation system
(BAS), as well as lighting and small power system.
1.0 The Philippine Electrical Code
• The PEC has two parts, namely:
• PEC Part I - Electrical installation inside
buildings.
• PEC Part II - Electrical installation outside
buildings.
• The PEC consists of rules which
are intended to make the use of electricity
safe for persons and property.
1.1 Categories of PEC Rules
• Two (2) categories of PEC rules:
• 1. Mandatory Rules -
• characterized by the use of the word “SHALL’’.

• 2. Advisory Rules -
• characterized by the use of the word “SHOULD”
or are stated as recommendations of that which
is advised but not required.
1.2 Objectives of the PEC
• a) Safe Use of Electricity- to establish basic
materials quality and electrical work standards
for the safe use of electricity for light, heat,
power, communications, signaling and for other
purposes.
• b) Adequacy - Strict compliance with the
provisions of the PEC will ensure safety in
electrical installations and construction, but not
necessarily efficient, convenient, or adequate
for good service or for future expansion of
electrical use.
1.3 Republic Act 7920
• The use of the PEC is mandated by the R.A. 7920,
(formerly the R.A. 184 which was enacted in 1947). The
R.A. 7920 (which repealed R.A. 184 in 1995) is also
known as the New Electrical Engineering Law.
• R.A. 7920 - is an act providing for a more responsive
and comprehensive regulation for the practice, licensing,
and registration of electrical engineers and electricians.
• Likewise, referral codes are also used which are
mandated by their corresponding laws.
• 1. P.D. 1096 - National Building Code of the Philippines
• 2. R.A. 9514 – New Fire Code of the Philippines (2008)
• 3. National Structural Code of the Philippines (2010)
1.4 Government Authorities which
Implement the PEC

• 1. Office of the Building Official (OBO)


• 2. Office of the City Electrician ( City
Electrical Supervising Engineer )
• 3. Office of the Municipal Electrician
(Municipal Electrical Supervising
Engineer)
• 4. Regional Office of the DOLE
1.5 Scope of the PEC
• The PEC covers electric conductors including optical fiber cable and
installed within or on, to or from:
• 1. Public and private buildings 2. Electrical generating plants
• 3. Temporary & permanent substations
• 4. Industrial plants 5. Transformer stations
• 6. Railway switchyards 7. Yards, carnival, parking, etc.
• 8. Watercraft 9. Dockyards
• 10. Airfields 11. Quarries and mines
• 12. Mobile homes, travel trailers & recreational vehicles
• 13. Offshore facilities
• 14. Other premises which requires electrical installation except to those
which are done in; a) Aircrafts
b) motor vehicles
c) railway rolling stocks
1.6 PERMITS & INSPECTION
CERTIFICATES
• An Electrical Permit is required before undertaking any
electrical installation. An inspection is also required after
which certificate of electrical inspection (CEI) is issued
by the authority.
• *EXCEPTIONS* A permit is not required for;
• 1. The installation of electrical portable equipment rated
not more than 1,200 VA.
• 2. Reconnection of disconnected service due to non-
payment of electric bill or change of occupants for a
period of one year.
1.7 CODE RULES

• CLASSIFICATION OF CODE RULES


• 1.Wiring Design Rules
• 2.Installation Rules
• 3.Manufacturing Rules
1.7.1 Wiring Design Rules
Wiring design rules are used to determine sizes
and rating of circuit conductors and devices.
• Example:
• 1. Branch circuit conductors supplying a single
motor shall have an ampacity not less than
125% of the full-load current. Section 4.30.2.2
• 2. The disconnecting means for motor circuits
shall have an ampere rating of at least 115% of
the full-load current rating of the motor.
Section 4.30.10.10(a)
1.7.2 Installation Rules
• Installation rules
• Example:
• 1.A disconnecting means shall be located within
sight from the motor controller. Section 4.30.102
• 2.In class II Division I Locations, motors,
generators, and other rotating electric
machinery shall be dust ignition proof or totally
enclosed pipe ventilated and shall be approved
for class II locations. Sections 5.02.8
1.7.3 Manufacturing Rules
• Manufacturing rules
• Example:
• Section 4.30.1.7
• A motor shall be marked with the following
information:
• 1) Manufacturer’s Name
• 2) Rated Volts and Full-load Amperes
• 3) Rated Frequency and Number of Phases, if
• an alternating current motor, etc.
• 4) Rated full-load speed
1.8 Editions of the PEC
• The following are the editions of the PEC:
• 1962; 1969; 1973; 1980; 1985; 1992; 2000;
2009, the Latest
• Why do Code Rules Change?
• – Existing provisions become unsafe
• – New technologies
• – New products
• – New methods or techniques
1.8.1 Why do Code Rules Change?
– Existing Provisions Become Unsafe

- Some existing provisions of


the Code become unsafe now.
1.8.2 Why do Code Rules Change?
– New Technologies
• PVC –Polyvinyl Chloride Conduit
• - Non-metallic Conduit
• »continuous or interconnected equipment
grounding conductors is required.
• 400/230 Volts 3-Phase 4-Wire + Ground
System
• - In lieu of the 230V 3-Ph 3-W + G System
• »Neutral wire must be sized similar to the
phase conductors.
1.8.3 Why do Code Rules Change?
– New products

Example: GFCIs
1. Bathrooms
2. Garages
3. Outdoors
4. Crawl spaces at or
below grade level
5. Unfinished basements
6. Kitchens for
countertop appliances
7. Wet bar sink
1.8.4 Why do Code Rules Change?
– New Methods or Techniques
Grid-tie Solar Power Systems
1.9 Type of Changes

• 1.New Definitions
• 2.New Provisions
• 3.Revision
• 4.Relocated
• 5.Reorganization
• 6.Universal Change
• 7.Deletion (310.5)
1.9.1 New Definitions

• AHJ –Authority Having Jurisdiction


• Bonding Jumper, System
• Coordination (Selective)
• Guest Rooms
• Guest Suite
• Handhole Enclosure
1.9.2 New Provisions

New Provision, example:

2.10.1.8(b)(2) – GFCI
Protection Other than
Dwelling.
Commercial and

the purposes of this


section, a kitchen is an
area with a sink and
permanent facilities for
food preparation and
cooking. (Culinary Schools)
1.9.3 Revisions
• Revised -definition
• Dwelling Unit –one or more rooms for the use of
one or more persons as a housekeeping unit with
space for eating, living, sleeping, and permanent
provisions for cooking and sanitation. (PEC 2000)
• Dwelling Unit –a single unit, providing complete
and independent living facilities for one or more
persons, including permanent provisions for
living, sleeping, cooking, and sanitation. (PEC
2009)
1.9.4 Relocated

• Relocated

• Solidly Grounded – PEC 2000

• Grounded, Solidly – PEC 2009


1.9.5 Re-organization
• Reorganization –Article 2.20 Branch-Circuit, Feeder, and Service Calculations
• 2000 2009
• Article 2.20 Article 2.20
• Part, Sections Part, Sections
• I. General, 2.20.1.1-4 I. General, 2.20.1.1 -5
• II. Feeders and Services, II. Branch Circuit Load Calculations,
• 2.20.2.1-14 2.20.2.1 -7
• III. Optional Calculations for III. Feeder and Service Load
• Computing Feeder & Service Loads, Calculations
• 2.20.3.1 -7 2.20.3.1 -23
• IV. Method for Computing Farm IV. Optional Feeder & Service
Loads, 2.20.4.1 -2 Load Calculations, 2.20.4.1 -9
• ----- V. Farm Calculation, 2.20.5.1-4
1.9.6 Universal Change

• A universal change throughout the Code is the


replacement of “computed load” and “demand
load” with “calculated load.” For example, the
term demand load is being replaced with
calculated load to improve clarity and to reduce
confusion, especially when related to
“calculated load” and “ demand factor.” The
term calculated load includes demand factor,
the concepts of diversity, and historical data.
1.10 Qualified Person
• 2.0 CODE HIGHLIGHTS
2.1 Code Highlights
2.2 Code Highlights
2.3 Code Highlights
2.4 Code Highlights
2.5 Code Highlights
Service Entrance
Conductors –
The conductors from the
service point to the service
disconnecting means.
Service Drop –The
overhead service
conductors from the last
pole or other aerial
support to and including
the splices, if any,
connecting to the service-
entrance conductors at the
building or other structure.
2.6 Code Highlights
Boundary: PEC I and PEC II
2.7 Code Highlights
2.8 Code Highlights
2.9 Code Highlights
2.10 Code Highlights
2.11 Code Highlights
INTEGRITY OF ELEC’L EQUIPMENT
DETERIORATING AGENTS
Short-Circuit Current Rating
Short-Circuit Current Rating
Conductor Termination
Conductor Termination
Conductor Termination
Conductor Termination
Integrity of Elec’l Equipment
Overhead Clearance of S.E.
Illegal Support for Other Purposes
Recommended Wiring Installation
Extension Cords
Extension Cords
Extension Cords
Line-to-Ground System
Fixture Wires as Branch Circuit
Lamps in Clothes Closets
Luminaire Can’t Be Used as Raceway!
Lampholder Only!
Luminaire Mounting
Luminaire Mounting
Decorative Lighting
… must
Indicate
“Indoor” or
“Outdoor”
purpose..
.. a major
cause of
electrical
fires..
Panels/CBs Never in Bathrooms!
CBs in Vertical Mounting
Illegal Wirings!

BUNDLED/ NON-
CONDUITEDWIRES ON A
STEEL TRUSSES
Ungrounded Metal Casings
G F C I or E L C B
G F C I or E L C B
Code Highlights…
Code Highlights…
Code Highlights…
Code Highlights…
Code Highlights…
Code Highlights…
Code Highlights…
Code Highlights…
Code Highlights…
Neutral Wires

• Insulated grounded conductor larger than 6


AWG or 14 mm2to be identified by the one of the
following methods: PEC 2.1.1.6(b)

• 1. By a white or gray outer finish


• 2. By three continuous white stripes, on other than
green insulation, running along the entire length of
conductor
• 3. By a distinctive white marking ,encircling the
conductor, placed there at the time of installation, and
the identifying the grounded conductor at each
termination (The identification may be by tagging,
marking, painting or other effective means)
Code Highlights… Neutral Wires
Code Highlights… Neutral Wires
• 3.0 ELECTRICAL PLANNING
DESIGN
3.0 ELECTRICAL DESIGN
• REQUIREMENTS:
• 3.1 LIGHTING SYSTEM
• 3.2 SMALL POWER LOADS (CONVENIENCE OUTLETS)
• 3.3 AIRCONDITIONING LOADS
• 3.4 WATER HEATER LOADS
• 3.5 PUMP LOADS – DOMESTIC WATER SUPPLY, SUMP PUMP
• 3.6 FIRE PUMP & JOCKEY PUMP
• 3.7 STAIRWELL PRESSURIZATION LOADS
• 3.8 ELEVATOR LOADS
• 3.9 LOAD SCHEDULES & DESIGN COMPUTATIONS
• 3.10 FIRE DETECTION & ALARM SYSTEM (FDAS)
• 3.11 GROUNDING SYSTEM & LIGHTNING PROTECTION SYSTEM
• 3.12 AUXILIARY SYSTEMS -TELEPHONE/ INTERCOM/ CCTV/CATV/
PUBLIC ADDRESS
3.01 BASIC RULE ON BRANCH CIRCUITS

• NO BRANCH CIRCUIT SHALL BE LOADED IN EXCESS OF


80% OF ITS AMPACITY.
• EXAMPLE 1 FOR A 20-AMPERE CIRCUIT:
• IF THE COMPUTED LOAD CURRENT OF A BRANCH
CIRCUIT IS 16.8 AMPERES, THEN THE NEXT LARGER
SIZE OF WIRE MUST BE USED, EX. 30-AMPERE
• EXAMPLE 2 FOR A 30-AMPERE BRANCH CIRCUIT: THE
MAXIMUM LOAD IS 24 AMPERES..
• EXAMPLE 3 FOR A 15-AMPERE CIRCUIT: THE
MAXIMUM LOAD IS 12 AMPERES..
3.02 PEC-1
ALLOWABLE
AMPACITIES
OF INSULATED
WIRES,
60º C TO 90ºC,
NOT MORE
THAN 3 WIRES
IN CONDUIT,
AMBIENT
TEMP. OF 30ºC
3.03 PEC-1
For Optional
Calculations –
Demand
Factors for 3
or more
Multifamily
Dwellings
3.1 LIGHTING SYSTEM-1
• PER AREA METHOD
• USE 24 VOLT-AMPERE (VA) PER SQUARE METER
• EXAMPLE 1: A 12M X 8M OFFICE AREA, THE VOLT-AMPERE
LOAD IS,
• VA= 12M X 8M X 24 VA/ SQ. MTR
• VA= 2,304 VA
• THE LOAD CURRENT IS,
• I = VOLT-AMPERE / VOLTAGE
• I = 2,304 VA / 230 VOLTS
• I = 10.01 AMPERES
• USE A MINIMUM OF ONE 15-AMPERE BRANCH CIRCUIT
• USE 2 – 2.0MM2 THHN W/ 15AT CIRCUIT BREAKER PROTECTION FOR THE
BRANCH CIRCUIT
3.1 LIGHTING SYSTEM-2
• PER AREA METHOD
• USE 24 VOLT-AMPERE (VA) PER SQUARE METER
• EXAMPLE 2: A 24M X 6M OFFICE AREA, THE VOLT-AMPERE LOAD IS,
• VA= 24M X 6M X 24 VA/ SQ. MTR
• VA= 3,456 VA
• THE LOAD CURRENT IS,
• I = VOLT-AMPERE / VOLTAGE
• I = 3,456 VA / 230 VOLTS
• I = 15.02 AMPERES
• USE A MINIMUM OF ONE 20-AMPERE BRANCH CIRCUIT
• USE 2 – 2.0MM2 THHN W/ 20AT CIRCUIT BREAKER PROTECTION FOR THE
BRANCH CIRCUIT
3.1 LIGHTING SYSTEM-3
• PER AREA METHOD
• USE 24 VOLT-AMPERE (VA) PER SQUARE METER
• EXAMPLE 3: A 30M X 8M OFFICE AREA, THE VOLT-AMPERE LOAD IS,
• VA= 30M X 8M X 24 VA/ SQ. MTR
• VA= 5,760 VA
• THE LOAD CURRENT IS,
• I = VOLT-AMPERE / VOLTAGE
• I = 5,760 VA / 230 VOLTS
• I = 25.04 AMPERES
• USE A MINIMUM OF TWO 15-AMPERE BRANCH CIRCUITS
• USE 2 – 2.0MM2 THHN W/ 15AT CIRCUIT BREAKER PROTECTION
FOR EACH BRANCH CIRCUIT
3.2 SMALL POWER LOADS
(CONVENIENCE OUTLETS) - 1
• DEPENDING ON THE LAYOUT PLAN, CONVENIENCE OUTLETS SHOULD
BE SPACED AT A MAXIMUM OF 2.4 METERS. THE PEC SPECIFIES 180
VOLT-AMPERE LOAD RATING PER OUTLET.
• EXAMPLE 1: A 12M X 8M OFFICE AREA, THE MAX. NUMBER OF COs
IS,
• = (12M + 8M) 2 / 2.4M = 16.6, SAY 17 Cos, DUPLEX
• THE TOTAL CO VA LOAD IS,
• VA = 17 DUPLEX COs X 180VA X 2 = 6,120 VA
• THE TOTAL LOAD CURRENT IS,
• I = 6120VA / 230 VOLTS = 26.7 AMPERES
• NO. OF CO CIRCUITS = 26.7 / 16 = 1.67, SAY 2 CIRCUITS
• USE 2 CO BRANCH CIRCUITS W/ A 20-AMPERE RATING PER CIRCUIT, 1
CO CIRCUIT WILL HAVE 8 COs AND THE OTHER CIRCUIT WILL HAVE 9
Cos, FOR THE 17 TOTAL COs..
3.2 SMALL POWER LOADS
(CONVENIENCE OUTLETS) - 2
• EXAMPLE 2: A 20M X 20M OFFICE AREA, THE MAX.
NUMBER OF COs IS,
• = (20M + 20M) 2 / 2.4M = 33.3, SAY 33 COs, DUPLEX
• THE TOTAL CO VA LOAD IS,
• VA = 33 DUPLEX COs X 180VA X 2 = 11,880 VA
• THE TOTAL LOAD CURRENT IS,
• I = 11,880VA / 230 VOLTS = 51.65 AMPERES
• NO. OF CO CIRCUITS = 51.65 / 16 = 3.23, SAY 4 CIRCUITS
• USE 4 CO BRANCH CIRCUITS W/ A 20-AMPERE RATING PER
CIRCUIT, 1 CO CIRCUIT WILL HAVE 9 COs AND THE OTHER 3
CIRCUITs WILL HAVE 8 COs, FOR THE 33 TOTAL COs..
3.3.1 AIRCONDITIONING LOAD - 1
• EXAMPLE 1:
• FOR A 1 UNIT OF 2.5 HP WINDOW TYPE ACU
2.5HP X 746 W
I = __________________
230V/ 0.8 PF / 0.9 EFF’Y
• I = 11.26 AMPERES
• Iw = 11.26 X 125% = 14.08 AMPERES
• USE: 2 – 2.0mm2 THHN + 2.0mm2 TW GROUND WIRE
20AT/60AF/2P 230V CIRCUIT BREAKER PROTECTION
• AMPACITY = 25 AMPERES
3.3.2 AIRCONDITIONING LOAD - 2
• EXAMPLE 2:
• FOR A 1 UNIT OF 3-TONNER SPLIT TYPE ACU
3 TONS X 1.2HP/TON X 746 W
• I = __________________________
230V X 0.8 PF X 0.9 EFF’Y
• I = 16.2 AMPERES
• Iw = 16.2 X 125% = 20.3 AMPERES
• USE: 2 – 3.5mm2 THHN + 2.0mm2 TW GROUND WIRE
30AT/60AF/2P 230V CIRCUIT BREAKER PROTECTION
• AMPACITY = 30 AMPERES
3.3.3 AIRCONDITIONING LOAD - 3
• EXAMPLE 3:
• FOR A 1 UNIT OF 5-TONNER SPLIT TYPE ACU
5 TONS X 1.2HP/TON X 746 W
• I = __________________________
230V X 0.8 PF X 0.9 EFF’Y
• I = 27.03 AMPERES
• Iw = 27.03 X 125% = 33.8 AMPERES
• USE: 2 – 5.5mm2 THHN + 2.0mm2 TW GROUND WIRE
30AT/60AF/2P 230V CIRCUIT BREAKER PROTECTION
• AMPACITY = 40 AMPERES
3.4.1 WATER HEATER LOADS - 1
• EXAMPLE: FOR A 3,600 WATT 230V HEATER 1-PHASE
• FOR THE LOAD CURRENT, I = POWER / VOLTAGE
• I = 3,600W / 23OV = 15.65 AMPERES

• FOR THE CIRCUIT HOMERUN


• = 15.65 AMPERES X 125% = 19.56 AMPERES

• USE A MINIMUM OF 20-AMPERE CIRCUIT


• WIRES: 2 – 3.5sq.mm THHN COPPER (30A AMPACITY)
+ 2.0 sq.mm GREEN GROUND WIRE
• PROTECTION: 30-AMPERE TRIP/ 2-POLE 220V CIRCUIT
BREAKER
3.4.2 WATER HEATER LOADS - 2
• EXAMPLE: FOR A 5,000 WATT 230V HEATER 1-PHASE
• FOR THE LOAD CURRENT, I = POWER / VOLTAGE
• I = 5,000W / 23OV = 21.74 AMPERES

• FOR THE CIRCUIT HOMERUN


• = 21.74 AMPERES X 125% = 27.17 AMPERES
• USE A 30-AMPERE CIRCUIT
• WIRES: 2 – 3.5sq.mm THHN COPPER (30A AMPACITY)
+ 2.0 sq.mm GREEN GROUND WIRE
• PROTECTION: 30-AMPERE TRIP/ 2-POLE 220V CIRCUIT
BREAKER
3.4.3 WATER HEATER LOADS - 3
• EXAMPLE: FOR A 6,000 WATT 230V HEATER 1-PHASE
• FOR THE LOAD CURRENT, I = POWER / VOLTAGE
• I = 6,000W / 23OV = 26.08 AMPERES

• FOR THE CIRCUIT HOMERUN


• = 26.08 AMPERES X 125% = 32.60 AMPERES

• USE A MINIMUM OF 40-AMPERE CIRCUIT


• WIRES: 2 – 5.5sq.mm THHN COPPER (40A AMPACITY)
+ 3.5 sq.mm GREEN GROUND WIRE
• PROTECTION: 40-AMPERE TRIP/ 2-POLE 220V CIRCUIT
BREAKER
3.4.4 WATER HEATER LOADS - 4
• EXAMPLE: FOR A 7,500 WATT 230V HEATER 3-PHASE
• FOR THE LOAD CURRENT, I = POWER / VOLTAGE /1.732
• I = 7,500W / 23OV / 1.732 = 18.83 AMPERES

• FOR THE CIRCUIT HOMERUN


• = 18.83 AMPERES X 125% = 23.54 AMPERES

• USE A MINIMUM OF 30-AMPERE CIRCUIT


• WIRES: THREE – 3.5sq.mm THHN COPPER (30A AMPACITY)
+ 5.5 sq.mm GREEN GROUND WIRE
• PROTECTION: 30-AMPERE TRIP/ 3-POLE 220V CIRCUIT
BREAKER
3.4.5 WATER HEATER LOADS - 5
• EXAMPLE: FOR A 10,000 WATT 230V HEATER 3-PHASE
• FOR THE LOAD CURRENT, I = POWER / VOLTAGE /1.732
• I = 10,000W / 23OV / 1.732 = 25.10 AMPERES

• FOR THE CIRCUIT HOMERUN


• = 25.10 AMPERES X 125% = 31.37 AMPERES

• USE A MINIMUM OF 40-AMPERE CIRCUIT


• WIRES: THREE – 5.5sq.mm THHN COPPER (40A AMPACITY)
+ 8.0 sq.mm GREEN GROUND WIRE
• PROTECTION: 40-AMPERE TRIP/ 3-POLE 220V CIRCUIT
BREAKER
3.5.1 PUMP LOADS – DOMESTIC
WATER SUPPLY, SUMP PUMP - 1
• EXAMPLE: FOR A 1 HP 230V PUMP 1-PHASE AC MOTOR
• FOR THE LOAD CURRENT, I = POWER / VOLTAGE
• I = 1HP X 746 WATTS / 23OV /0.8PF / 0.9 EFF’Y = 4.5 AMPERES FULL
LOAD

• FOR THE CIRCUIT HOMERUN


• = 4.5 AMPERES + 25% X 4.5 = 5.62 AMPERES

• USE A MINIMUM OF 20-AMPERE CIRCUIT


• WIRES: 2 – 2.0sq.mm THHN COPPER (25A AMPACITY)
+ 2.0 sq.mm GREEN GROUND WIRE
• PROTECTION: 15-AMPERE TRIP/ 2-POLE 240V CIRCUIT BREAKER
PLUS MAGNETIC STARTER W/ THERMAL OVERLOAD RELAY SET @
4.5 AMPERES
3.5.2 PUMP LOADS – DOMESTIC
WATER SUPPLY, SUMP PUMP - 2
• EXAMPLE: FOR A 7.5 HP 230V PUMP 3-PHASE AC MOTOR
• FOR THE LOAD CURRENT, I = HP / VOLTAGE/ PF/ EFF’Y/ 1.732
• I = 7.5HP X 746 WATTS / 23OV /0.8PF / 0.9 EFF’Y/1.732 =
19.50AMPERES FULL LOAD
• FOR THE CIRCUIT HOMERUN
• = 19.50 AMPERES + 25% X 19.50 = 24.37 AMPERES

• USE A MINIMUM OF 30-AMPERE CIRCUIT


• WIRES: THREE – 3.5sq.mm THHN COPPER (30A AMPACITY)
+ 2.0 sq.mm GREEN GROUND WIRE
• PROTECTION: 40-AMPERE TRIP/ 3-POLE 240V CIRCUIT BREAKER
PLUS MAGNETIC STARTER W/ THERMAL OVERLOAD RELAY SET @
19.5 AMPERES
3.5.3 PUMP LOADS – DOMESTIC
WATER SUPPLY, SUMP PUMP - 3
• EXAMPLE: FOR A 10 HP 230V PUMP 3-PHASE AC MOTOR
• FOR THE LOAD CURRENT, I = HP / VOLTAGE/ PF/ EFF’Y/ 1.732
• I = 10HP X 746 WATTS / 23OV /0.8PF / 0.9 EFF’Y/1.732 =
26.0AMPERES FULL LOAD

• FOR THE CIRCUIT HOMERUN


• = 26.0 AMPERES + 25% X 26.0 = 32.5 AMPERES

• USE A MINIMUM OF 40-AMPERE CIRCUIT


• WIRES: THREE – 3.5sq.mm THHN COPPER (40A AMPACITY)
+ 2.0 sq.mm GREEN GROUND WIRE
• PROTECTION: 50-AMPERE TRIP/ 3-POLE 240V CIRCUIT BREAKER
PLUS MAGNETIC STARTER W/ THERMAL OVERLOAD RELAY SET @
26.0 AMPERES
3.5.4 PUMP LOADS – DOMESTIC
WATER SUPPLY, SUMP PUMP - 4
• EXAMPLE: FOR A 20 HP 400V PUMP 3-PHASE AC MOTOR
• FOR THE LOAD CURRENT, I = HP / VOLTAGE/ PF/ EFF’Y/ 1.732
• I = 20HP X 746 WATTS / 400V /0.8PF / 0.9 EFF’Y/1.732 =
29.9AMPERES FULL LOAD

• FOR THE CIRCUIT HOMERUN


• = 29.9 AMPERES + 25% X 29.9 = 37.4 AMPERES

• USE A MINIMUM OF 40-AMPERE CIRCUIT WIRE


• WIRES: THREE – 5.5sq.mm THHN COPPER (40A AMPACITY)
+ 3.5 sq.mm GREEN GROUND WIRE
• PROTECTION: 50-AMPERE TRIP/ 3-POLE / 400V CIRCUIT
BREAKER PLUS MAGNETIC STARTER W/ THERMAL OVERLOAD
RELAY SET @ 30.0 AMPERES
3.6 FIRE PUMP & JOCKEY PUMP
3.6.1 FIRE PUMP CIRCUIT SIZING
• ASSUME: 3HP MIN. PER FLOOR LEVEL
• EXAMPLE:
• FOR A 22 STOREY BUILDING,
• HP RATING OF FIRE PUMP
• = 22 FLOOR X 3HP/FLOOR = 66HP
• USE 75HP FIRE PUMP, @ 230V RATING,
• I = 75HP X 746W / 1.732/ 230V /0.8PF / 0.9 EFF’Y
• I = 195 AMPERES FULL LOAD
• Iw = 195 X 125% = 243.7 AMPS
• USE: THREE – 125mm2 THHN + 50mm2 GROUND in 65mm
dia. RSC or IMC (AMPACITY = 265 AMPS)
• PROTECTION: 600AT/600AF/3P 240V CIRCUIT BREAKER
3.6.2 FIRE PUMP CIRCUIT SIZING
• EXAMPLE:
• FOR A 22 STOREY BUILDING,
• HP RATING OF FIRE PUMP
• = 22 FLOOR X 3HP/FLOOR = 66HP
• USE 75HP FIRE PUMP, @ 400V RATING,
• I = 75HP X 746W / 1.732/ 400V /0.8PF / 0.9 EFF’Y
• I = 112 AMPERES FULL LOAD
• Iw = 112 X 125% = 140 AMPS
• USE: THREE – 50mm2 THHN + 22mm2 GROUND in
50mm dia. RSC or IMC (AMPACITY = 150 AMPS)
• PROTECTION: 400AT/400AF/3P 400V CIRCUIT BREAKER
3.7 STAIRWELL PRESSURIZATION LOAD
• IN THE EXAMPLE, THE SELECTED HP RATING IS 15HP..
• THE FULL LOAD CURRENT FOR A 230V 3-PH SYSTEM IS,
• I = 15HP X 746 / 1.732/ 230V / 0.8PF/ 0.9 EFF’Y
• 39AMPERES
• Iw = 39 X 125% = 48.7 AMPS
• USE: THREE – 8.0mm2 THHN + 5.5mm2 GROUND in
25mm dia. RSC or IMC (AMPACITY = 55 AMPS)
• PROTECTION: 60AT/100AF/3P 240V CIRCUIT BREAKER
3.8 ELEVATOR LOADS
• EXAMPLE, FOR A 25HP 3-PHASE 400 VOLTS 60HZ
VARIABLE FREQUENCY DRIVE (VFD) MOTOR, THE
FULL LOAD CURRENT IS,
• I = 25HP X 746 / 1.732/ 400V / 0.8PF/ 0.9 EFF’Y
• 37.4 AMPERES
• Iw = 37.4 X 125% = 46.7 AMPS
• USE: THREE – 8.0mm2 THHN + 5.5mm2 GROUND
in 25mm dia. RSC or IMC (AMPACITY = 55 AMPS)
• PROTECTION: 60AT/100AF/3P 400V CIRCUIT
BREAKER
3.9.1 LOAD SCHEDULES & DESIGN
COMPUTATIONS-1
3.9.2 LOAD SCHEDULES & DESIGN
COMPUTATIONS-2
3.9.4 SIZING THE TRANSFORMER
• The total connected load is
• kVA = 1.732 x V x I / 1000
• = 1.732 x 220 volts x 365.72 amperes / 1000
• = 139.35 kVA total conn. load

• The Demand Load is


• Demand kVA = Total kVA Conn. Load x Demand Factor
• Assume a 40% Demand Factor
• Demand kVA = 139.35 kVA x 0.40 = 55.74 kVA
• Average kVA per phase = 55.74 / 3 = 18.58 kVA
• Use: Three 25 kVA 1-phase distribution transformers in bank
For 3-Ph 4-W + G System
• When using the 400v/230v 3-phase 4-wire +
ground system, the phase current is the same
as the line current, henceforth the formula
becomes:
• Iph = Iline
• KVA = Itotal x V/1000
• KVA = 210 x 400/1000
• = 84 KVA
3.9.3 TYP.POWER RISER DIAGRAM
3.9.4 SIZING THE STANDBY POWER
• The total connected load is
• = 139.35 kVA total conn. load
• The calculated Demand Load is
• kVA = 55.74 kVA
• Assuming a 100% emergency power back up
• Genset kW = 55.74 x 0.80 pf = 44.6 kW demand
• Assuming a maximum loading of 70%
• The kW capacity of the generator = 44.6 / 0.70 = 63.7 kW
• Use: 75 kW 230 volts 3-phase 60 Hertz 1800 RPM diesel engine
generator set complete with accessories, i.e. starting battery,
fuel day tank, exhaust silencer, metering, manual or automatic
transfer switch, etc.

3.9.5 SIZING THE SOLAR POWER
• Assume an available roof area of 30 mtrs by 20 mtrs, and about 205
of the area to be allotted for anchoring the panels and for
maintenance access,
• The number of 250 watts solar panels is,
• = 20 x 30 x 80% / 1.6m x 1.0m
• = 300 panels
• The Total kW capacity of the Solar Power Supply system is,
• = 300 panels x 250 watts / 1000
• = 75 kW maximum possible
• Use: 6 each 12kW grid tie inverters (to be connected 4 x 6kW
inverters per phase) 240 volts DC input, 220 volts AC 1-phase, pure
sine wave output.
• Note: Option to arrange a net metering agreement with the Utility
company. Any extra energy generated during day time will be
3.9.6 Typ. Grid Tie Solar Power System
3.10 TYP. FIRE DETECTION & ALARM SYSTEM
(FDAS) LAYOUT
3.10.1 TYP. FIRE DETECTION & ALARM
SYSTEM (FDAS) RISER DIAGRAM-1
3.10.2 TYP. FIRE DETECTION & ALARM
SYSTEM (FDAS) RISER DIAGRAM-2
3.11 TYP. GROUDING SYSTEM FOR
LOW/MID/HIGH-RISE BUILDINGS
3.11.1 TYP. GROUNDING CONNECTION
DETAILS
3.11.2 TYP. GROUNDING CONNECTION
DETAILS
3.11.3 LIGHTNING PROTECTION
SYSTEM (EARLY STREAMER TYPE)
3.11.4 TYP. LIGHTNING PROTECTION
SYSTEM FOR TALL BUILDING

HV Insulated Cable
3.12 TYP.AUXILIARY- TELEPHONE,
CABLE TV & CCTV LAYOUT
3.12.1 TYP. AUXILIARY- TELEPHONE &
CABLE TV RISER DIAGRAMS-1
3.12.2 TYP. AUXILIARY- TELEPHONE & CABLE TV
RISER DIAGRAMS-2
 THANK YOU & GOD BLESS!
M A B U H A Y !

También podría gustarte