EVECD01 system is suitable for ladder type with

asynchronous motor as driving system.

The fault codes of EVECD01 system can be divided into two categories: all possible fault types
of drivers, as shown in Table 8-1, the display range of fault codes is E001-E040; all possible
faults in elevator logic, as shown in Table 8-2, the display range of fault codes is E041-E112.
The fault code table is as follows:

Protection code Protection name Protection setpoint

E001 Too much acceleration


Low grid voltage
Accelerated Operating Driver power is low
Overcurrent

Driver to Ground Short Circuit

E002 Too much deceleration


Load inertia torque is high

Overcurrent in
Driver power is low
decelerating operation

Driver to Ground Short Circuit

E003 Overcurrent in
Constant Speed
(1) Sudden change or abnormality
of load
Operation
(2) Low grid voltage
(3) Driver power is low

(4) Closed-loop vector high-speed


operation, sudden code disc
disconnection or failure
(5) Driver to Ground Short Circuit

E004 (1) Abnormal input voltage


(2) When the instantaneous stop
occurs, restart the motor which is
still rotating

E005 Deceleration
overvoltage
(1) Too much deceleration
(2) Load inertia

(3) Abnormal input voltage


E006 Constant speed (1) Abnormal change of input
operation overvoltage voltage

(2) Load inertia

E007 Control power supply


overvoltage
(1) Abnormal input voltage
(2) Error setting of driver type
E008 Input side phase gap Input R, S, T with missing phase

E009 Output phase missing U, V, W phase-out output (or load


three-phase serious asymmetry)

E010 Power Module Fault (1) Driver instantaneous


overcurrent
(2) Three-phase output with the
same or grounding short circuit

(3) Blockage or fan damage

(4) Excessive ambient temperature

(5) Control board wiring or plug-in


loosening
(6) Damage of auxiliary power
supply and undervoltage of
driving voltage

(7) Power Module Bridge Arm


Through
(8) Control board abnormality

E011 Power Module


Radiator Overheating
(1) Excessive ambient temperature

(2) Duct obstruction


(3) Fan damage
(4) Abnormal power module
E012
for ladder type with
driving system.

o two categories: all possible fault types


fault codes is E001-E040; all possible
play range of fault codes is E041-E112.

Protection Action Processing

Reducing acceleration
Check the input power supply
Selection of Drivers with High Power
Level

Check whether the driver is short-


circuited to the ground
Reduce deceleration
Added appropriate brake assemblies for
energy consumption

Selection of Drivers with High Power


Level

Check whether the driver is short-


circuited to the ground
(1) Load checking or load reduction
mutations

(2) Check the input power supply


(3) Selection of Drivers with High Power
Level

(4) Check the code disc and its wiring

(5) Check whether the driver is short-


circuited to the ground

(1) Check the input power supply


(2) Avoid shutdown and restart

(1) Reducing deceleration


(2) Increase energy consumption brake
assembly

(3) Check the input power supply


(1) Installation of input reactor
(2) Added appropriate energy
consumption brake components

(1) Check the input power supply


(2) Reset the model or seek service
(1) Check the input power supply

(2) Inspection of installation wiring


Check output wiring

(1) See Convection Countermeasure

(2) Rewiring

(3) Drainage duct or replacement fan

(4) Reducing ambient temperature

(5) Check and reconnect

(6) Seeking services

(7) Seeking services

(8) Seeking services


(1) Reducing ambient temperature

(2) Cleaning air duc


(3) Fan replacement
(4) Seeking services