Cable Size
Cooling only
FDM75EXV1 FDM100EXV1 FD125BXY1 FD150BXY1
Model Unit
R75CXY1 RC100BXY1 RC125BXY1 RC150CXY1
Power supply cable size*
a) Indoor Unit mm2 1.0 1.0 1.0 1.0
b) Outdoor Unit mm2 1.5 2.5 4.0 6.0
c) Total mm2 2.5 4.0 4.0 10.0
Number of wire
a) Indoor Unit - - 3 3
b) Outdoor Unit 5 5 5 5
Interconnection cable size* mm2 1.0 1.0 1.0 1.0
Number of wire 4 4 4 4
Recommended fuse*
a) Indoor Unit A 10 12 6 6
b) Outdoor Unit A 25 32 32 50
c) Total A 32 32 40 63
IMPORTANT: * These values are for information only. They should be checked and