Application Information

Cable Size

Cooling only
FDM75EXV1 FDM100EXV1 FD125BXY1 FD150BXY1
Model Unit
R75CXY1 RC100BXY1 RC125BXY1 RC150CXY1
Power supply cable size*
a) Indoor Unit mm2 1.0 1.0 1.0 1.0
b) Outdoor Unit mm2 1.5 2.5 4.0 6.0
c) Total mm2 2.5 4.0 4.0 10.0
Number of wire
a) Indoor Unit - - 3 3
b) Outdoor Unit 5 5 5 5
Interconnection cable size* mm2 1.0 1.0 1.0 1.0
Number of wire 4 4 4 4
Recommended fuse*
a) Indoor Unit A 10 12 6 6
b) Outdoor Unit A 25 32 32 50
c) Total A 32 32 40 63

2FD200BXY1 2FG250BXY1 2FG300BXY1 3FG300BXY1


Model Unit
RC100BXY1 x 2 RC125BXY1 x 2 RC150CXY1 x 2 RC100BXY1 x 3
Power supply cable size*
a) Indoor Unit mm2 1.0 1.0 1.0 1.0
b) Outdoor Unit mm2 2.5 4.0 6.0 2.5
c) Total mm2 10.0 16.0 25.0 25.0
Number of wire
a) Indoor Unit 5 5 5 5
b) Outdoor Unit 5 5 5 5
Interconnection cable size* mm2 1.0 1.0 1.0 1.0
Number of wire 1x2 1x2 1x2 1x3
Recommended fuse*
a) Indoor Unit A 10 16 16 16
b) Outdoor Unit A 32 32 50 32
c) Total A 63 80 125 100

3FG350BXY1 4FG400BXY1 3FG450BXY1


Model Unit
RC100BXY1 RC125BXY1 x 2 RC100BXY1 x 4 RC150CXY1 x 3
Power supply cable size*
a) Indoor Unit mm2 1.5 1.5 1.0 2.5
b) Outdoor Unit mm2 4.0 4.0 2.5 6.0
c) Total mm2 2.5 2.5 35.0 50.0
Number of wire
a) Indoor Unit 5 5 5 5
b) Outdoor Unit 5 5 5 5
Interconnection cable size* mm2 1.0 1.0 1.0 1.0
Number of wire 1x3 1x3 1x4 1x3
Recommended fuse*
a) Indoor Unit A 20 20 20 25
b) Outdoor Unit A 32 32 32 50
c) Total A 100 100 125 175

IMPORTANT: * These values are for information only. They should be checked and
selected to comply with local and/or national codes and regulations.
They are also subject to the type of installation and size of conductors.