PRIMER PISO
AMBIENTES LUX AREA LUMENES INTENSIDAD
ESTUDIO 500.00 13.44 6,720.00 70.00
SALA Y COMEDOR 100.00 33.97 3,397.00 70.00
COCINA 300.00 9.52 2,856.00 70.00
DORMITORIO O1 50.00 7.04 352.00 50.00
DORMITORIO 02 50.00 9.23 461.50 50.00
HALL 100.00 3.60 360.00 50.00
PASADISO 100.00 7.43 743.00 50.00
SS.HH1 100.00 1.94 194.00 50.00
SS.HH 100.00 2.69 269.00 40.00
DORMITORIO PRINCIPAL 50.00 12.61 630.50 50.00
SEGUNDO PISO 101.47
DORMITORIO 01 50.00 13.44 672.00 50.00
SS.HH 100.00 3.67 367.00 40.00
COCINA 300.00 9.52 2,856.00 70.00
SALA Y COMEDOR 100.00 33.97 3,397.00 70.00
PATIO LAVANDERIA 300.00 7.14 2,142.00 50.00
SS.HH2 100.00 3.70 370.00 40.00
DORMITORIO 02 200.00 7.04 1,408.00 70.00
DORMITORIO PRINCIPAL 200.00 12.43 2,486.00 50.00
HALL 100.00 4.15 415.00 50.00
HALL 100.00 4.15 415.00 50.00
PASADISO 100.00 2.59 259.00 50.00
TERCER PISO 101.80
DORMITORIO 01 50.00 13.44 672.00 50.00
SS.HH 100.00 3.67 367.00 40.00
COCINA 300.00 9.52 2,856.00 70.00
SALA Y COMEDOR 100.00 33.97 3,397.00 70.00
PATIO LAVANDERIA 300.00 7.14 2,142.00 50.00
SS.HH2 100.00 3.70 370.00 40.00
DORMITORIO 02 200.00 7.04 1,408.00 70.00
DORMITORIO PRINCIPAL 200.00 12.43 2,486.00 50.00
HALL 100.00 4.15 415.00 50.00
HALL 100.00 4.15 415.00 50.00
PASADISO 100.00 2.59 259.00 50.00
CUARTO PISO 101.80
DORMITORIO 01 50.00 13.44 672.00 50.00
SS.HH 100.00 3.67 367.00 40.00
COCINA 300.00 9.52 2,856.00 70.00
SALA Y COMEDOR 100.00 33.97 3,397.00 70.00
PATIO LAVANDERIA 300.00 7.14 2,142.00 50.00
SS.HH2 100.00 3.70 370.00 40.00
DORMITORIO 02 200.00 7.04 1,408.00 70.00
DORMITORIO PRINCIPAL 200.00 12.43 2,486.00 50.00
HALL 100.00 4.15 415.00 50.00
HALL 100.00 4.15 415.00 50.00
PASADISO 100.00 2.59 259.00 50.00
QUINTO PISO
DORMITORIO 01 50.00 13.44 672.00 50.00
SS.HH 100.00 3.67 367.00 40.00
COCINA 300.00 9.52 2,856.00 70.00
SALA Y COMEDOR 100.00 33.97 3,397.00 70.00
PATIO LAVANDERIA 300.00 7.14 2,142.00 50.00
SS.HH2 100.00 3.70 370.00 40.00
DORMITORIO 02 200.00 7.04 1,408.00 70.00
DORMITORIO PRINCIPAL 200.00 12.43 2,486.00 50.00
HALL 100.00 4.15 415.00 50.00
HALL 100.00 4.15 415.00 50.00
PASADISO 100.00 2.59 259.00 50.00
EFICIENCIA TIPO DE FOCO USO
96.00 50.00 1.92
48.53 25.00 1.94
40.80 18.00 2.27
7.04 18.00 0.39
9.23 13.00 0.71
7.20 13.00 0.55
14.86 13.00 1.14
3.88 13.00 0.30
6.73 13.00 0.52
12.61 13.00 0.97
2500 2500
2500
1000 1000
1000 1000
1000 1000
1000 1000
1000 1000
5000
10000 10000 DIAGRAMA UNIFILAR ( ALIMENTADOR G
2250 2250 SUMATORIAS
10000 10000 ƩPI = 267000
2250 2250 ƩMD = 185050
10000 10000
2250 2250 POR CAPACIDAD:
10000 10000 MD
In=
2250 2250 K*V*COSφ
10000 10000
3750 3750 In= 185050
10000 10000 √3*220*0.9
3750 3750
10000 10000 In = 539.59
3750 3750
90250 Por lo tanto : 03 cables de 240
8000 8000
POR CAIDA DE TENSION:
8000 8000
ΔV = K*IN*ɗ*L
8000 8000 S
8000 8000
6000 6000
400 400
6000 6000
400 400
6000 6000
400 400
6000 6000
400 400
6000 6000
400 400
32000
3000 3000
6000 6000
6000 6000
3000 3000
3000 3000
4000 4000
4000 4000
4000 4000
4000 4000
4000 4000
41000
1000 1000
1000 1000
1000 1000
1000 1000
1000 1000
400 400
600 600
500 500
600 600
600 600
600 600
600 600
600 600
350 350
350 350
350 350
350 350
350 350
1000 1000
1000 1000
250 250
800 800
14300
185050
NIFILAR ( ALIMENTADOR GENERAL)
CUADRO DE DATOS CUADRO DE DATOS
CUADRO DE DATOS PARA MONOFASICO
PARA TRIFASICO K 1
K= √3 = 1.732 V= 220
V= 220 COS φ = 0.8
COS φ = 0.9 ɗ= 0.0175
ɗ= 0.0175 L=
L= 2.76
mm2(THW)
2500 2500
1000 1000
10000 10000
2250 2250
8000 8000
6000 6000
400 400
3000 3000
4000 4000
1000 1000
400 400
600 600
600 600
500 500
800 800
350 350
33400
De MAX. DEMANDA(w)
2500 2500
1000 1000
10000 10000
2250 2250
10000 10000
3750 3750
8000 8000
6000 6000
400 400
3000 3000
4000 4000
1000 1000
600 600
350 350
44850
De MAX. DEMANDA(w)
2500 2500
1000 1000
8000 8000
6000 6000
400 400
3000 3000
4000 4000
1000 1000
600 600
350 350
26850
De MAX. DEMANDA(w)
2500 2500
1000 1000
10000 10000
2250 2250
10000 10000
3750 3750
8000 8000
6000 6000
400 400
3000 3000
4000 4000
1000 1000
600 600
1000 1000
350 350
45850
De MAX. DEMANDA(w)
2500 2500
1000 1000
10000 10000
2250 2250
10000 10000
3750 3750
8000 8000
6000 6000
400 400
3000 3000
4000 4000
1000 1000
250 250
600 600
350 350
45100
potencia instalada = 0
MAXIMA DEMANDA = 33400
POR CAPACIDAD
IN= 97.39
SEGÚN TABLA 3-
1. CIRCUITOS DE ALUMBRADO
CI = M.D = 2500
CALCULO DE AMPERAJE
IN= 14.20
CI = M.D = 100
36
39
50
EL MAYOR
IN= 0.00
TIPO DE CABLE 2
CAIDA DE TENSIÓN
AV= 0
25 mm
11.05
< 5.5V
A
4 SALIDAS DE 25W IN = 0.56818182
2 SALIDAS DE 18W IN = 0.20454545
3 SALIDAS DE 13W IN = 0.22159091
1SALIDA DE 50W IN = 0.28409091
1.5 mm
| CALCULO DE CONDUCTO
SUMATORIAS CUADRO DE DATOS CUADRO DE DATOS SUMATORIAS
ƩPI = 52950 CUADRO DE DATOS PARA MONOFASICO ƩPI =
ƩMD = 33400 PARA TRIFASICO K 1 ƩMD =
K= √3 = 1.732 V= 220
POR CAPACIDAD: V= 220 COS φ = 0.8 POR CAPACIDAD:
MD COS φ = 0.9 ɗ= 0.0175
In= In=
K*V*COSφ ɗ= 0.0175 L=
L= 2.76
In= 33400 In=
√3*220*0.9
In = 97.39 In =
CIRCUITO DE ALUMBRADO:SEGÚN CNE 25 WATTS/100 m², 16, 17, 18 SALIDAS POR 100 m²
MD = WATTS CIRCUITO DE ALUMBRADO:
POR CAPACIDAD K= 1
In= 2500 14.20 Amp. V= 220 POR CAPACIDAD
1*220*0.8 COS φ = 0.8 In=
L= 13.45
CI = MD = SALIDAS * w = WATTS ɗ= 0.0175
K= 2 CI = MD = SALIDAS *
CI = M.D = 4 SALIDAS DE 25W 4 25 100 WATTS
2 SALIDAS DE 18W 2 18 36 WATTS
3 SALIDAS DE 13W 3 13 39 WATTS
1SALIDA DE 50W 1 50 50 WATTS
EL (IN) MAYOR = 14.20 Amp.
IN = 0.56818182
IN = 0.20454545
IN = 0.22159091
IN = 0.28409091
POR CAPACIDAD
MD =
In=
ΔV =
CALCULO DE CONDUCTOR O DIAGRAMA UNIFILAR TD- (SEGUNDO NIVEL) CALCULO DE CONDUCTOR O DIAGRA
UMATORIAS CUADRO DE DATOS CUADRO DE DATOS SUMATORIAS
64450 CUADRO DE DATOS PARA MONOFASICO ƩPI = 36450
44850 PARA TRIFASICO K 1 ƩMD = 26850
K= √3 = 1.732 V= 220
OR CAPACIDAD: V= 220 COS φ = 0.8 POR CAPACIDAD:
MD COS φ = 0.9 ɗ= 0.0175 MD
In=
K*V*COSφ ɗ= 0.0175 L= K*V*COSφ
L= 2.76
44850 In= 26850
√3*220*0.9 √3*220*0.9
130.78 In = 78.29
RCUITO DE ALUMBRADO:SEGÚN CNE 25 WATTS/100 m², 16, 17, 18 SALIDAS POR 100 m² CIRCUITO DE ALUMBRADO:
MD = WATTS
OR CAPACIDAD K= 1 POR CAPACIDAD
2500 14.20 Amp. V= 220 In= 2500
1*220*0.8 COS φ = 0.8 1*220*0.8
L= 14.65
CI = MD = SALIDAS * w = WATTS ɗ= 0.0175 CI = MD = SALIDAS * w =
K= 2
CI = M.D = 5 SALIDAS DE 25W 5 25 125 WATTS CI = M.D =
1 SALIDAS DE 18W 1 18 18 WATTS
4 SALIDAS DE 13W 4 13 52 WATTS
1 SALIDA DE 12W 1 12 12 WATTS
EL (IN) MAYOR = 14.20 Amp. EL (IN) MAYOR =
IN = 0.71022727
IN = 0.10227273
IN = 0.29545455
IN = 0.06818182
CALCULO DE CONDUCTOR O DIAGRAMA UNIFILAR TD-1 (SEGUNDO NIVEL) CALCULO DE CONDUCTOR O DIAGRA
UITO DE TOMACORRIENTES: SEGÚN CNE 144 W Ó 0.81 Amp., 16, 17, 18 SALIDAS POR 100 m² CIRCUITO DE TOMACORRIENTES:
MD = 14.58
K= 2
V= 220
OR CAPACIDAD COS φ = 0.8 POR CAPACIDAD
L= 53.08
In = 18 SALIDAS * 0.81 Amp. = 14.58 Amperios ɗ= 0.0175 In = 18 SALIDAS * 0.81 Amp. =
Por lo tanto : 02 cables de 2.5 mm² (THW)+ 01 cable de 2.5 mm² (THW) Por lo tanto :
cable 10 mm2
OR CAIDA DE TENSION POR CAIDA DE TENSION
Por lo tanto :
Por lo tanto : 03 cables de 2.5 mm2(THW)
POR CAIDA DE TENSION
OR CAIDA DE TENSION
ΔV = K*I*ɗ*L
K*I*ɗ*L ΔV = 1.66 < 3.3 V S
S
3.4 CALENTADOR DE AGUA PARA BAÑO
.3 COCINA ELECTRICA
MD = 6400
√3 = 1.732
V= 220
COS φ = 1
L= 9.59 POR CAPACIDAD
OR CAPACIDAD ɗ= 0.0175 MD =
6400 WATTS
In= MD
MD = 6400 = 16.80 Amp. K*V*COSφ
K*V*COSφ √3*220*1
Por lo tanto :
Por lo tanto : 03 cables de 2.5 mm2(THW)
POR CAIDA DE TENSION
OR CAIDA DE TENSION
ΔV = K*I*ɗ*L
K*I*ɗ*L ΔV = 1.95 < 3.3 V S
S
3.5 RESTO DE ARTEFACTOS
3.4 DUCHA ELECTRICA
MD = 3000
√3 = 1.732
V= 220
COS φ = 1
L= 12.23 POR CAPACIDAD
OR CAPACIDAD ɗ= 0.0175 MD =
3000 WATTS
In= MD
MD = 3000 = 7.87 Amp. K*V*COSφ
K*V*COSφ √3*220*1
Por lo tanto :
Por lo tanto : 03 cables de 1 mm2(THW)
POR CAIDA DE TENSION
OR CAIDA DE TENSION
ΔV = K*I*ɗ*L
K*I*ɗ*L ΔV = 2.92 < 3.3 V S
S S
OR CAIDA DE TENSION
OR CAIDA DE TENSION
In = 133.69
SEGÚN CNE 25 WATTS/100 m², 16, 17, 18 SALIDAS POR 100 m² CIRCUITO DE ALUMBRADO:SEGÚN CNE 25 WATTS/100 m², 16, 17, 18 SALIDAS
MD = WATTS
K= 1 POR CAPACIDAD
14.20 Amp. V= 220 In= 2500 14.20
COS φ = 0.8 1*220*0.8
L= 14.65
CI = MD = SALIDAS * w = WATTS ɗ= 0.0175 CI = MD = SALIDAS * w = WATTS
K= 2
5 SALIDAS DE 25W 5 25 125 WATTS CI = M.D = 4 SALIDAS DE 25W
1 SALIDAS DE 18W 1 18 18 WATTS 2 SALIDAS DE 18W
4 SALIDAS DE 13W 4 13 52 WATTS 3 SALIDAS DE 13W
1 SALIDA DE 12W 1 12 12 WATTS 1SALIDA DE 50W
L (IN) MAYOR = 14.20 Amp. EL (IN) MAYOR = 14.20
IN = 0.71022727 IN = 0.56818182
IN = 0.10227273 IN = 0.20454545
IN = 0.29545455 IN = 0.22159091
IN = 0.06818182 IN = 0.28409091
ULO DE CONDUCTOR O DIAGRAMA UNIFILAR TD-1 (TERCER NIVEL) CALCULO DE CONDUCTOR O DIAGRAMA UNIFILAR TD-1 (CUARTO N
SEGÚN CNE 144 W Ó 0.81 Amp., 16, 17, 18 SALIDAS POR 100 m² CIRCUITO DE TOMACORRIENTES:
SEGÚN CNE 144 W Ó 0.81 Amp., 16, 17, 18 SALIDA
MD = 14.58
K= 2
V= 220
COS φ = 0.8 POR CAPACIDAD
L= 53.08
8 SALIDAS * 0.81 Amp. = 14.58 Amperios ɗ= 0.0175 In = 18 SALIDAS * 0.81 Amp. = 14.58
02 cables de 2.5 mm² (THW)+ 01 cable de 2.5 mm² (THW) Por lo tanto : 02 cables de 2.5 mm² (THW)+ 01 cable de 2.5 mm
cable 10 mm2 cable 10
POR CAIDA DE TENSION
03 cables de 1 mm2(THW)
Por lo tanto : 03 cables de 4
POR CAPACIDAD
MD = 4000
In= MD = 4000
K*V*COSφ √3*220*1
ΔV = K*I*ɗ*L ΔV =
S
POR CAPACIDAD
MD = 2950
In= MD = 2950
K*V*COSφ √3*220*1
ΔV = K*I*ɗ*L ΔV =
S
RAMA UNIFILAR TD- (CUARTO NIVEL NIVEL) CALCULO DE CONDUCTOR O DIAGRAMA UNIFILAR TD- (QUINTO NIVEL NIVEL)
UADRO DE DATOS CUADRO DE DATOS SUMATORIAS CUADRO DE DATOS
UADRO DE DATOS PARA MONOFASICO ƩPI = 64700 CUADRO DE DATOS
ARA TRIFASICO K 1 ƩMD = 45100 PARA TRIFASICO
1.732 V= 220 K= √3 = 1.732
220 COS φ = 0.8 POR CAPACIDAD: V= 220
0.9 ɗ= 0.0175 MD COS φ = 0.9
In=
0.0175 L= K*V*COSφ ɗ= 0.0175
2.76 L= 2.76
In= 45100
√3*220*0.9
In = 131.51
5 WATTS/100 m², 16, 17, 18 SALIDAS POR 100 m² CIRCUITO DE ALUMBRADO:SEGÚN CNE 25 WATTS/100 m², 16, 17, 18 SALIDAS POR 100 m²
MD = WATTS MD =
K= 1 POR CAPACIDAD K=
Amp. V= 220 In= 2500 14.20 Amp. V=
COS φ = 0.8 1*220*0.8 COS φ =
L= 14.65 L=
ɗ= 0.0175 CI = MD = SALIDAS * w = WATTS ɗ=
K= 2 K=
4 25 100 WATTS CI = M.D = 6 SALIDAS DE 25W 4 25
2 18 36 WATTS 3 SALIDAS DE 18W 2 18
3 13 39 WATTS 5 SALIDAS DE 13W 3 13
1 50 50 WATTS 1SALIDA DE 50W 1 50
Amp. EL (IN) MAYOR = 14.20 Amp.
IN = 0.56818182
IN = 0.20454545
IN = 0.22159091
IN = 0.28409091
AGRAMA UNIFILAR TD-1 (CUARTO NIVEL) CALCULO DE CONDUCTOR O DIAGRAMA UNIFILAR TD-1 (SEGUNDO NIVEL)
44 W Ó 0.81 Amp., 16, 17, 18 SALIDAS POR 100 m² CIRCUITO DE TOMACORRIENTES: SEGÚN CNE 144 W Ó 0.81 Amp., 16, 17, 18 SALIDAS POR 100 m²
MD = 14.58 MD =
K= 2 K=
V= 220 V=
COS φ = 0.8 POR CAPACIDAD COS φ =
L= 53.08 L=
Amperios ɗ= 0.0175 In = 18 SALIDAS * 0.81 Amp. = 14.58 Amperios ɗ=
.5 mm² (THW)+ 01 cable de 2.5 mm² (THW) Por lo tanto : 02 cables de 2.5 mm² (THW)+ 01 cable de 2.5 mm² (THW)
mm2 cable 10 mm2
POR CAIDA DE TENSION
5.5 V
3.3 V
EGUNDO NIVEL)
18 SALIDAS POR 100 m²
14.58
2
220
0.8
53.08
0.0175
3.3 V
EGUNDO NIVEL)
12250
1.732
220
1
6.58
0.0175
Amp.
3.3 V
13750
1.732
220
1
4.09
0.0175
Amp.
3.3 V
8000
1.732
220
1
6.54
0.0175
Amp.
3.3 V
6400
1.732
220
1
9.59
0.0175
Amp.
3.3 V
3000
1.732
220
1
12.23
0.0175
Amp.
3.3 V
4000
1.732
220
1
10.35
0.0175
Amp.
3.3 V
2200
1.732
220
1
23
0.0175
Amp.
3.3 V