Smart-UPS
230 V
Advanced line interactive power protection
for servers and network equipment
[ SMT1500RMI1U ]
[ SMT1500RMI2U ]
[ SMT3000RMI2U ]
[ SMT1000I ]
Standard Features
High-efficiency Green Mode: Network-grade Power:
Optimum efficiency which saves Provides most stable power
utility and cooling costs. conditions by filtering noise,
automatic voltage regulation (AVR),
Emergency Power Off (EPO):
and surge protection.
Provides for remote UPS shut-
off in the event of a fire or other Communication Ports:
emergency (2,200 VA and above). Serial, USB, and SmartSlot™ for
accessory cards.
Alphanumeric LCD Display:
Intuitive interface provides detailed Advanced Battery Management:
and accurate information with Temperature-compensated
ability to configure locally. charging extends life and
advanced algorithms recommend
Battery Disconnect:
replacement date.
Convenient way to disconnect
battery for transport.
[ SMT1000I ]
2
Smart-UPS Extended Run 750 – 3,000 VA
Convertible extended run models ideal for
critical servers and voice/data switches.
Product Accessories
Additional Features
Slim 2U Rack/Tower and 4U Short Depth
Convertible Forms:
Display rotates easily for use in or out of
[ SMX3000HV ] a rack.
High-frequency Design:
Reduces size of (or eliminates) bulky
transformers making installation even easier.
High-voltage Models:
(2.2 kVA and above)
Configurable output from 200 VA – 240 VA
on high-voltage models.
[ SMX3000RMHV2U ]
3
Smart-UPS Display
Intuitive, easy-to-use LCD interface
Standard Features
LCD Display Screen About:
Clear, consistent, and detailed information in UPS and replacement battery part numbers,
your choice of basic or advanced menus. serial numbers, battery install, and suggested
Power Status: replacement dates
t0QFSBUJOHNPEFBOEFGýDJFODZ Quick Status Indicators
t-PBE7"8BUUT"NQT Online, on battery, fault, and replace battery
t*OQVU0VUQVUWPMUBHFBOEGSFRVFODZ LEDs for quick status identification.
t#BUUFSZDBQBDJUZBOESVOUJNF Escape:
t&OFSHZNFUFSBOENPSF Exits to the previous menu or screen.
Control:
Return:
UPS and outlet group settings Used to enter or confirm settings.
Configuration: Navigation Arrows:
t-BOHVBHF Allow for quick adjustment of settings.
t1PXFSRVBMJUZTFUUJOHT
t"MBSN
EFMBZ
BOEUISFTIPMETFUUJOHT
Test and Diagnostics:
Initiate battery and runtime calibration tests
Logs:
See explanation of last 10 transfers and faults
About:
UPS and replacement battery part numbers,
serial numbers, battery install, and suggested
replacement dates
4
Standard Tower models
5
Standard Rack-mount models
6
Extended Run Rack/Tower Convertible 2U models
Input
Nominal input voltage 230 V 200 – 240 V
Input voltage range for main operations
160 – 286 V (150 – 300 V) 140 – 280V
(Max adjustable range)
Input frequency 50/60 Hz +/- 3 Hz (auto sensing)
Input connection IE C320 C14 IE C320 C20
Surge protection
Surge energy rating 540 J
Full-time multi-pole noise filtering: 0.3% IEEE surge let-through, zero clamping response time,
Filtering
meets UL 1449
Physical
Maximum height – cm (in.) 8.9 (3.5) (2U)
Maximum width – cm (in.) 43.2 (17.0)
Maximum depth – cm (in.) 49.3 (19.0) 66.7 (26.26)
Net weight kg (lb.) (48.5) 22.9 (50.3) 24.8 (54.6) 37.3 (82.1)
Conformance
C-tick, CE, EN62040-1, EN62040-2, EN60950-1,
Regulatory C-tick, CE, EN62040-1, EN62040-2, EN60950-1, GOST, VDE
GOST, VDE, UL 1778
Warranty 3-years electronics, 2-years battery
7
Extended Run Rack/Tower Convertible 4U Short Depth models
©2013 Schneider Electric. All Rights Reserved. Schneider Electric, APC, Smart-UPS, and SmartSlot are trademarks owned by Schneider Electric Industries SAS or its affiliated companies. All other
trademarks are the property of their respective owners.t
Smart-UPS
On-Line 230 V
Unity output power factor single-phase,
double-conversion online UPS
with advanced management features
apc.com
2
A versatile UPS developed
for unstable power
conditions worldwide
Smart-UPS On-Line provides high-density, double-conversion, online power
TM
protection for servers, voice/data networks, medical labs, and light industrial
applications. The Smart-UPS On-Line is capable of supporting loads from
2.2 kVA – 10 kVA in a rack/tower convertible chassis. The 6 kVA, 8 kVA,
and 10 kVA models feature unity output power factor enabling them to support
power-hungry blade servers or heavily loaded equipment racks. When business-
critical systems require runtime in hours, not minutes, Smart-UPS On-Line can be
configured with multiple battery packs to meet aggressive runtime demands.
apc.com 3
Smart-UPS On-Line
Industry-leading power factor maximizing UPS density
Rackmount and Tower SRT 2.2 kVA – 10 kVA
Standard Features
Best-in-class power density
More real power in watts, 0.9
pf on 2.2 kVA – 5 kVA, Unity
on 6 kVA – 10 kVA units.
apc.com 4
apc.com 5
apc.com 6
Smart-UPS On-Line
Proven performance with the world’s largest installed
base of single-phase, double-conversion products
Rackmount and Tower SRT 2.2 kVA – 10 kVA
Additional Features
Embedded network management card
with environmental monitoring
(5 kVA – 10 kVA models)
Remote monitoring and control of the
UPS and the environment via Ethernet
connection while freeing up the SmartSlot TM
Communication ports
Serial, USB, Ethernet, and SmartSlot for
network accessory cards.
Communication protocols
SRT10KXLT shown Modbus serial, USB PowerSummary, HTTP,
SNMP, and Telnet.
Dual input
Enables second input source to be
connected to UPS bypass (230 V, 8 kVA,
and 10 kVA models only).
apc.com 7
Smart-UPS On-Line display
Intuitive, easy-to-use LCD provides clear and accurate
information in multiple languages
Standard Features
LCD display screen
Accurately provides real-time status
updates in your choice of basic or
advanced menus.
Control
• UPS and outlet group settings
• Bypass control
Configuration
• Output voltage, frequency
• Language, brightness, contrast
Backlight screens: • Alarm volume
Amber: Indication of condition that Red: Indication of UPS alarm that • IP address
requires attention requires immediate attention
Test and diagnostics
• Initiate battery and runtime
calibration tests
About
• UPS serial number, battery part number
• Battery install and suggested
replacement dates
apc.com 8
Product Accessories
Management cards SRT009: APC Smart-UPS SRT 5 M extension cable
AP9630: UPS network management card for 72 VDC external battery pack 2.2 kVA UPS
with PowerChute network shutdown
SRT010: APC Smart-UPS SRT 5 M extension cable
AP9631: UPS network management card for 96 VDC external battery pack 3 kVA UPS
with PowerChute network shutdown
Rail kits
and environmental monitoring
SRTRK2: APC Smart-UPS SRT 19 inch rail
AP9335TH: APC by Schneider Electric
TM TM
kit for Smart-UPS SRT 5/6/8/10 kVA UPS Management card
temperature and humidity sensor
SRTRK3: APC 2-post mounting rail kit for
AP9810: APC dry contact I/O accessory Smart-UPS SRT 2.2/3/5/6/8/10 kVA UPS
AP9624: UPS interface expander SRTRK4: APC Smart-UPS SRT 19 in. rail kit
for Smart-UPS SRT 2.2/3 kVA UPS
AP9613: Dry contact I/O SmartSlot card
Backplate kit
Battery packs
SRT001: APC Smart-UPS SRT 5 kVA output HW kit
SRT192BP: APC Smart-UPS SRT 192 V
5 kVA and 6 kVA battery pack SRT012: APC Smart-UPS SRT 2.2/3 kVA
input/output HW kit
SRT192RMBP: APC Smart-UPS SRT 192 V Battery pack
5 kVA and 6 kVA RM battery pack Transformers
SURT002: APC Smart-UPS RT 5,000 VA 230 V
SRT192BP2: APC Smart-UPS SRT 192 V
isolation transformer
8 kVA and 10 kVA battery pack
APTF10K W01: APC W W 10 kVA isolation transformer
SRT192RMBP2: APC Smart-UPS SRT 192 V
8 kVA and 10 kVA RM battery pack Service bypass panels
SBP6KRMI2U: APC service bypass panel 230 V;
SRT72BP: APC Smart-UPS SRT 72 V 2.2 kVA
50 A; MBB; hardwire input; (4) IEC-320 C19 Output
battery pack
SBP10KRMI4U: APC service bypass panel 230
SRT72RMBP: APC Smart-UPS SRT 72 V 2.2 kVA
V; 100 A; MBB; hardwire input; IEC-320 output (8)
RM battery pack
C13 (2) C19
Rail kits
SRT96BP: APC Smart-UPS SRT 96 V 3 kVA
Other
battery pack
SURT013: SURT Equipment Cart
SRT96RMBP: APC Smart-UPS SRT 96 V 3 kVA RM
Replacement Battery Cartridge
battery pack
APCRBC140: RBC for SRT 5 kVA - 10 kVA UPS
SRT002: APC Smart-UPS SRT 5 M Extension Cable
APCRBC141: RBC for SRT 2.2 kVA UPS
for 192 VDC External Battery Packs 5/6 kVA UPS
APCRBC152: RBC for SRT 3 kVA UPS
SRT003: APC Smart-UPS SRT 5 M Extension Cable
for 192 VDC External Battery Packs 8/10 kVA UPS
apc.com 9
Smart-UPS On-Line SRT 2200 VA and SRT 3000 VA
Technical specifications
Output
Power rating 2200 VA/1980 W 3000 VA/2700 W
230 V (208 V, 220 V, 240 V
Nominal output voltage 230 V (220 V, 240 V user selectable)
user selectable)
Output frequency 50/60 Hz ± 3 Hz (auto sense) 50/60 Hz ± 0.1 Hz (user selectable)
Topology Double-conversion online
Online efficiency at full load (typical) 92%
Green mode efficiency at full load (typical) 96% 97%
(8) IEC 320 C13 (4) IEC320 C13
Output connections (switched groups)
(2) IEC 320 C19 (2) IEC320 C19
Input
230 V (208 V, 220 V, 240 V
Nominal input voltage 230 V
user selectable)
Input voltage range full load (half load) 160 – 275 V (100 – 275 V)
Input frequency 40 – 70 Hz auto-selecting
Input connection IEC-60320 C20, Schuko CEE 7/EU1-16P, British BS1363A
Batteries and runtime
Battery type Maintenance-free sealed lead-acid battery with suspended electrolyte, leak proof
Typical backup time at ½ load (min) 11.6 min 11.8 min
Typical backup time at full load (min) 3.9 min 4.0 min
Replacement battery (quantity) APCRBC141 (1) APCRBC152 (1)
External battery pack (tower/rack mount) SRT72BP/SRT72RMBP SRT96BP/SRT96RMBP
Communication and management
Interface ports Serial (RJ45), USB (Type A) and SmartSlot
Control panel High resolution graphical LCD display
Emergency power off (EPO) Yes (NO/NC connections)
Physical
Rack height 85 mm, 2U
Maximum width (RM) 432 mm 432 mm
Maximum depth (RM) 585 mm 636 mm
Net weight 25 Kg 31 kg
Conformance
CE, VDE, RCM, and EAC, IEC/EN CE, VDE, RCM, and EAC, IEC/EN 62040-1, IEC/EN 62040-2,
Regulatory
62040-1, IEC/EN 62040-2 UL-1778, FCC Part 15 Class A, CSA
Warranty Three years electronics/two years battery
apc.com 10
Smart-UPS On-Line SRT 5 kVA – 10 kVA
apc.com 11
Schneider Electric
www.apc.com
October 2015
©2015 Schneider Electric. All Rights Reserved. Schneider Electric, APC, Smart-UPS, PowerChute,
SmartSlot, and Life Is On Schneider Electric are trademarks owned by Schneider Electric Industries SAS or its affiliated This document has been
companies. All other trademarks are the property of their respective owners.• 998-1243569_GMA-US_A printed on recycled paper
Smart-UPS On-Line
1 – 20 kVA
High-density, double-conversion online
power protection with scalable runtime
Rack/Tower Convertible
Ensures integration in various environments
Hot-swappable/User-replaceable Batteries
Ensures continuous operation of the load even
when the batteries are being replaced
Double-conversion Online
Provides tight voltage and frequency regulation
and zero transfer time for reactive loads (machinery,
lab equipment, etc.)
Serial Connectivity
Enables quick and easy configuration of
the UPS
Scalable Runtime
Allows additional run time to be quickly
added as needed
Built-in Automatic
and Manual Bypass
Ensures seamless power to the load even in
the event of catastrophic UPS failure
Field-replaceable Power
Distribution Panels
Enables quick in-field modification of output
receptacles to fit changing needs
Product Accessories
Management Cards Rail Kits
AP9610: Relay I/O SmartSlot™ Card SURTRK: APC Smart-UPS RT 482 mm Rail Kit 1 kVA
(Not compatible with SURTD UPS models) and 2 kVA
AP9622: Modbus®/Jbus Interface Card SURTRK2: APC Smart-UPS RT 482 mm Rail Kit
(Not compatible with SURTD UPS models) for Smart-UPS RT 3/5/6/8/10 kVA
AP9630: UPS Network Management Card SURTRK4: APC Smart-UPS RT 482 mm Rail Kit
AP9631: UPS Network Management Card with for Smart-UPS RT 15/20 kVA
Environmental Monitoring
Battery Packs
AP9810: APC™ Dry Contact I/O Accessory
SURT48XLBP: APC Smart-UPS RT 48 V
(Not compatible with SURTD UPS models)
Battery Pack
AP9620: Legacy Communications SmartSlot Card
SURT48RMXLBP: APC Smart-UPS RT 48 V
(Compatible with SURTD UPS models only)
RM Battery Pack
Transformers SURT192XLBP: APC Smart-UPS RT 192 V
APTF10KW01: APC WW 10 kVA Isolation Battery Pack
Transformer SURT192RMXLBP: APC Smart-UPS RT 192 V
APTF20KW01: APC WW 20 kVA Isolation RM Battery Pack
Transformer SURT192RMXLBP2: APC Smart-UPS RT 192 V
SURT001: APC Smart-UPS RT 3000 VA 230 V RM Battery Pack 2 Rows
Isolation Transformer
Service Bypass Panels
SURT002: APC Smart-UPS RT 5000 VA 230 V
SBP3000: APC Service Bypass Panel 100 – 240 V;
Isolation Transformer
30 A; BBM; Hardwire Input/Output
Backplate Kits SBP6KRMI2U: APC Service Bypass Panel 230 V;
SURT007: APC Smart-UPS RT 3/5/6 kVA Input/ 50 A; MBB; Hardwire Input; (4) IEC 320 C19 Output
Output Hardwire Kit SBP10KRMI4U: APC Service Bypass Panel 230 V;
SYPD10: Symmetra™ RM 230 V Backplate Kit with 100 A; MBB; Hardwire Input; IEC 320 Output (8)
(2) IEC 320 C19 and (1) IEC 60309 C13 (2) C19
SBP20KP: APC Service Bypass Panel
Other 200/208/230/240 V 125 A HW Input/Output
SURT013: SURT Equipment Cart SBP20KRMI4U: APC Service Bypass Panel 230 V
125 A HW Input IEC 320 Output (8) C19
Technical Specifications
UPS VA 1000 2000 3000 5000 6000 8000 10000 15000 20000
Output
Topology Double-conversion Online
Configurable for
Nominal Output Voltage Configurable for 220 : 230 or 240 nominal output voltage 220 : 230 : 240 : 400 V
nominal output voltage
Efficiency at Full Load Up to 92%
Output Frequency
50/60 Hz +/- 3 Hz user adjustable
(sync to mains)
Output Power Capacity 700 W 1400 W 2100 W 3500 W 4200 W 6400 W 8000 W 12 kW 16 kW
(1) Hardwire 3-wire
(1) Hardwire 3-wire
(H + N + G); (1) Hardwire
Output Connections (6) IEC 320 C13 (8) IEC 320 C13; (2) IEC 320 C19 (H + N + G); (4) IEC 320
5-wire (3PH + N + G);
C13; (4) IEC 320 C19
(8) IEC 320 C19
Input
Nominal Input Voltage 230 V 230 V or 400 V
Input Frequency 45 – 65 Hz (auto sensing)
British BS1363A; IEC 320 C20; Hardwire 3-wire Hardwire 3-wire (1PH + N + G);
Input Connections
Schuko CEE 7/EU1-16P (1PH + N + G) Hardwire 5-wire (3PH + N + G)
Bypass Automatic and Manual (Built-in)
Battery
Battery Type Maintenance-free sealed lead-acid battery with suspended electrolyte: leak proof
Replacement Battery RBC57 RBC44
Runtime See Chart Below
Communications and Management
DB-9 RS-232,
Interface Port(s) RJ-45 10/100 Base-T, RJ-45 Serial, SmartSlot
SmartSlot, USB
Pre-installed
— — — AP9631
SmartSlot Card
Emergency Power Off
Yes
(EPO)
Control panel LEDs LCD Display
Physical
Rack Height 2U 3U 6U 12 U
Maximum Height 432 mm 533 mm
Maximum Width 85 mm 130 mm 263 mm 432 mm
Maximum Depth 483 mm 660 mm 736 mm 773 mm
Net Weight 25.00 kg 54.55 kg 110.91 kg 247.70 kg
©2012 Schneider Electric. All Rights Reserved. Schneider Electric, APC, Smart-UPS, PowerChute, SmartSlot, and Symmetra are trademarks owned by Schneider Electric Industries SAS or its affiliated companies.
EMAIL ESUPPORT APCCOM s &AIRGROUNDS 2OAD 7EST +INGSTON 2) 53! s
Galaxy 300
3: 3-phase: 10/15/20/30/40/60/80 kVA
3:1-phase: 10/15/20/30 kVA
buildings, and technical facilities. The online double-conversion topology supplies true isolation between
input and output with zero transfer time. Available with integrated batteries or external batteries with
robust charger, the UPS includes an internal mechanical bypass and simplified parallel capability for
higher levels of availability. Remote and local monitoring/management capability is achieved through a
built-in communication card with a simple Web/SNMP interface and a user-friendly display available in
18 languages. Both 3:3- and 3:1-phase configurations are available for convenient power distribution.
Serviceability is greatly enhanced by front access for ease of maintenance in confined spaces. The
Galaxy 300 has been ruggedized with conformance-coated boards and dust filter to better withstand
harsh environments. All of these features, along with the included start-up and on-site warranty, make the
Galaxy 300 the easiest UPS in its class to install, manage, and maintain.
schneider-electric.com/en/product-range/61895-mge-galaxy-300
Features and benefits
Galaxy 300
Economy
Availability
Power factor corrected input — Prevents the need
Dual mains input — Allows standard installation of
for oversizing cables, circuit breakers, and generator.
one or two independent power sources.
Temperature-compensated battery charging —
Automatic internal bypass — Built-in 100 percent
Sensors monitor battery temperature and adjust
rated bypass static switch prevents interruption
charger voltage to prevent premature aging and
by allowing load transfer to utility power during
extend battery lifetime.
heavy overloads.
Reduced footprint — Compact wide or narrow
Parallel 1+1 for redundancy — Connected
tower makes best use of available space.
equipment can be powered with two UPS units in
parallel to increase system redundancy.
Simplified Installation
Ruggedized design — With conformance-coated
Easy to install — Wheeled unit rolls into place, and
boards and included dust filter to better withstand
all wiring connections are easily identifiable for
harsh environments.
time-saving installation.
Integrated battery backup — Provides higher level
Start-up wizard — Step-by-step guidance and
of availability with up to 30 minutes of runtime.
intuitive menu screens for easy set-up and
A robust charger — Provides all-in-one solution for system navigation.
the most common runtime requirements.
Manageability
Serviceability
Built-in management card for SNMP — Remote
Manual maintenance bypass — Easily accessible and local monitoring and management capabilities
maintenance bypass allows complete isolation of with simple Web/SNMP interface.
each part of the system, facilitating maintenance
operations without power interruption. User-friendly graphical interface — Easy-to-read
LCD provides mimic diagrams, audible alarms, and
Front-access servicing — Push-open door multilanguage display, simplifying operation.
and slide-out boards simplify installation and
maintenance while minimizing space requirements.
schneider-electric.com/en/product-range/61895-mge-galaxy-300 2
Galaxy 300
QM1 QOP
~ =
Economy = ~
=
Optimized features — The Galaxy 300 is designed to =
QB
provide optimal performance. The most in-demand features
have been carefully selected to propose the right solution -+
QM2
for predictable and reliable power protection, offering the
benefits of a true double-conversion online architecture. Q3BP
=
Simplified maintenance — A full maintenance bypass =
with front access permits complete isolation of each part QB
Q3BP
Availability
Galaxy 300 with transformer option
Wide input voltage range — For harsh
electrical environments.
Options
External battery cabinet — For additional runtime.
Supplied with breakers and temperature sensors.
Communication cards
s¬ Network Management Card supplied with the product
(AP9630) for Web/SNMP functions, and modbus TCP
with RJ45 interface
s¬ Optional card (AP9635) for additional features such
as modbus/Jbus over RS485, Teleservice, and
environmental sensors: Temperature (AP9335T),
Temperature and Humidity (AP9335TH),
Dry contact I/O (AP9810)
schneider-electric.com/en/product-range/61895-mge-galaxy-300 3
Technical specifications
Rated power (kVA/kW) 10/8 15/12 20/16 30/24 40/32 60/54* 80/72*
Frequency (Hz) 45 – 65 Hz
Input voltage tolerance utility operation 340 V to 477 V at full load (-15% to +20% at 400 V)
Output
Overload capacity utility operation 125% for 2 minutes, 150% for 10 seconds 125% for 10 minutes, 150% for 1 minute
Regulatory
Safety IEC/EN62040-1-1
Approvals CE TUV
Environmental
Operating temperature 0 °C to 35 °C 0 °C to 40 °C
Schneider Electric
www.schneider-electric.com
October 2015
Document Number 998-3863_GMA-US_C
t1BSBMMFMDBQBCJMJUZ
t/FUXPSLNBOBHFBCJMJUZ
t*1GPSJOEVTUSJBMFOWJSPONFOUT
t"WBJMBCMFJOBOEWFSTJPOT
Features and benefits
t#BUUFSJFT t6QUPGPVSFYUFSOBMSVOUJNFGSBNFTXJUICBUUFSJFT
t.PEVMBSQPXFSNPEVMF t1BSBMMFMNBJOUFOBODFCZQBTTQBOFMoXBMMNPVOU
t(FOFSBUPSDPNQBUJCMF t4JOHMFVOJUNBJOUFOBODFCZQBTToXBMMNPVOU
t1BSBMMFMDBQBCJMJUZVQUPGPVSVOJUTGPSDBQBDJUZ t&NQUZGSBNFGPSUIJSEQBSUZUSBOTGPSNFST
BOESFEVOEBODZPOUIFWFSTJPOVQUPUXP t&NQUZCBUUFSZGSBNFGPSCBUUFSJFTonPPSNPVOU
VOJUTGPSSFEVOEBODZPOUIFWFSTJPO t#BZJOHLJUTGPSXJEFBOEOBSSPXGPSNGBDUPSTUP
93GSBNFT
Serviceability
t.BOVBMNBJOUFOBODFCZQBTT Typical applications
t6TFSSFQMBDFBCMFBJSmMUFST t$PNNFSDJBMCVJMEJOHTTIPQnPPST
IPUFMT
t#BUUFSZSFQMBDFNFOUXJUIPVUUPPMT BOEDPOWFOUJPODFOUFST
t'SPOUBDDFTTTFSWJDJOH t5SBOTQPSUBUJPOBOEJOGSBTUSVDUVSFT
t1IBSNBDFVUJDBMBOEDIFNJDBMQMBOUT
Economy t4FNJDPOEVDUPSQMBOUT
t*OQVUQPXFSGBDUPSDPSSFDUJPO
t'PPEBOECFWFSBHFQMBOUT
t5FNQFSBUVSFDPNQFOTBUFECBUUFSZDIBSHJOH
t0UIFSJOEVTUSJBMGBDJMJUJFTBOEQSPDFTTQMBOUT
t&GmDJFODZVQUPQFSDFOU
Support and service
Simplified installation t4UBSUVQTFSWJDFTJODMVEFE
t8JSJOHDPOOFDUJPOT
t8PSMEXJEFTVQQPSUBOEBGUFSTBMFTTFSWJDFT
t#VTCBSDPOOFDUJPOT
t8IFFMT
Manageability
t#VJMUJO8FC4/.1NBOBHFNFOU
BOEFOWJSPONFOUBMNPOJUPSJOH
t-$%EJTQMBZ
t"VEJCMFBMBSNT
](BMBYZ
Features that make the difference
3FEVDFTJOTUBMMBUJPODPTUT 80
0 20 40 60 80 100
Low line voltage Nominal line voltage High line voltage Battery operation
Load (%)
Rugged industrial environments Optional auxillaries
tSturdy enclosure tExternal runtime frame with batteries
NNIFBWZHBUFTUFFMGSPOUDPWFSBOEGSBNFEFTJHO "EETBEEJUJPOBMSVOUJNFDPOmHVSBUJPOXJUI
PSXJUIPVUCSFBLFS
tEasily replaceable air filters
1SFWFOUEVTUBOEEFCSJTGSPNBGGFDUJOH614 tSingle- or parallel-unit bypass panel,
QFSGPSNBODF BSSFTUBODFWBMVFPGQFSDFOUBTQFS wall mounted
™
"4)3"&
1SPWJEFTTQBDFTBWJOHTBOEUVSOLFZTPMVUJPO
GPSQBSBMMFMDPOmHVSBUJPOT
tIP51
3VHHFEJ[FEFODMPTVSFXJUIESJQTIJFMEBOEEVTU tCommunication cards
QSPUFDUJPOUIBUQSFWFOUTMJRVJETBOEEJSUQBSUJDMFT /FUXPSLNBOBHFNFOUDBSETVQQMJFEXJUI
GSPNFOUFSJOHUIF614 UIFQSPEVDUPQUJPOBMDBSETBWBJMBCMFGPS
BEEJUJPOBMGFBUVSFT
tFloor anchoring
1SFWFOUTUIF614GSPNUJMUJOH
tWheels
"MMPXTUIF614UPCFFBTJMZSPMMFEJOUPQMBDF
](BMBYZ
Technical specifications: 3:1 and 3:3
Rated power (kVA/kW) 10/8 (3:3 only) 15/12 20/16 30/24 40/32
Normal AC supply input
Input voltage (V) 380/400/415 V (three-phase + neutral)
Frequency (Hz) Synchronized to mains
Input power factor > 0.98 at load > 50%
THDI < 5% at full load
Input voltage tolerance utility operation 304 V to 477 V at full load, 200 V to 477 V at half load (for 400 V)
Dual mains input Yes
Input voltage tolerance bypass +10% standard +4, 6, 8, 10% (programmable)
Backfeed protection Built-in backfeed contactor
Output
3:1 (220/230/240 V)
Nominal output voltage (V)
3:3 (380/400/415 V) three-phase + neutral
Efficiency at full load (AC-AC at nominal mains) 94.5% 95.8% 95.5% 95.8% 96.0%
Efficiency at 50% load (AC-AC at nominal mains) 94.7% 95.3% 95.7% 95.5% 95.5%
DC-AC nominal battery voltage 94.1% 95.1% 94.9% 95.2% 95.0%
Load power factor 0.5 leading to 0.5 lagging
Output frequency Mains synchronized in normal operation 50 Hz + 0.05% free-running
Overload capacity utility operation 125% for 10 minutes, 150% for 60 seconds
Overload battery utility operation 150% for 60 seconds
V THD < 2% from 0 to 100% linear load, < 3.5% full non-linear load
Output voltage tolerance +/-1% static, +/-5% at 100% load step
Communication and management
Communication interface Network management card with environmental monitor
Control panel Power view multifunction LCD, status, and control console
Emergency power off (EPO) Yes
Dimensions and weights
Dimensions (H x W x D) narrow tower 1,490 x 352 x 838 mm N/A
Dimensions (H x W x D) wide tower 1,490 x 523 x 838 mm
Weight (kg) — narrow tower 214 (3:3 only) 402 N/A
Weight (kg) — wide tower 443 (3:3 only) 472 656 662
Protection
Surge IEC61000-4-5
Thermal, short circuit Yes
Regulatory
Safety IEC/ EN62040 1-1
EMC/EMI/RFI EN50091-2, IEC 62040-2
Approvals ANSI, IEEE
Environmental
Operating temperature 0 to 40 °C
Storage temperature -15 to 45 °C
Relative humidity 0 to 95% non-condensing
Operating elevation 0 to 1,000 m
Storage elevation 0 to 15,000 m
< 43.3 dBA at < 70% load, < 46.2 dBA at < 70% load,
Maximum audible noise at 1 m from unit
< 51.3dBA at 100% load < 55.0dBA at 100% load
Protection class IP51
(QWUDGD GH &$
9
N9$
9
7LSR GH FRQH[LyQ 3+ 1 3(
)UHFXHQFLD GH
HQWUDGD +]
'LVWRUVLyQ D SOHQD FDUJD
DUPyQLFD WRWDO GH
FRUULHQWH 7+',
&RUULHQWH GH
HQWUDGD QRPLQDO
$
&RUULHQWH GH
HQWUDGD Pi[LPD
$
/tPLWH GH
FRUULHQWH GH
HQWUDGD $
9
N9$
9
7LSR GH FRQH[LyQ 3+ 1 3(
)UHFXHQFLD GH
HQWUDGD +]
'LVWRUVLyQ D SOHQD FDUJD
DUPyQLFD WRWDO GH
FRUULHQWH 7+',
&RUULHQWH GH
HQWUDGD QRPLQDO
$
&RUULHQWH GH
HQWUDGD Pi[LPD
$
&$ GH GHULYDFLyQ
1RWD (O 6$, SXHGH IXQFLRQDU FRQ XQD IUHFXHQFLD GH HQWUDGD GH GHULYDFLyQ GH +] R
+] (O YDORU GH IUHFXHQFLD VH SXHGH FRQ¿JXUDU PHGLDQWH OD SDQWDOOD GHO 6$, 6HWXS
&RQ¿JXUDFLyQ ! 6HWWLQJV 3DUiPHWURV ! 6\VWHP 6LVWHPD ! )UHTXHQF\ )UHFXHQFLD
9
N9$
9
7LSR GH FRQH[LyQ 3+ 1 3(
)UHFXHQFLD GH HQWUDGD R
+]
&RUULHQWH GH HQWUDGD
QRPLQDO $
9
N9$
9
7LSR GH FRQH[LyQ 3+ 1 3(
)UHFXHQFLD GH HQWUDGD +] R
&RUULHQWH GH HQWUDGD
QRPLQDO $
6DOLGD GH &$
9
N9$
9
7LSR GH FRQH[LyQ 3+ 1 3(
&DSDFLGDG GH VDOLGD SDUD PLQXWR IXQFLRQDPLHQWR QRUPDO
SDUD PLQXWRV IXQFLRQDPLHQWR QRUPDO
SDUD PLQXWR IXQFLRQDPLHQWR FRQ EDWHUtDV
FRQWLQXR IXQFLRQDPLHQWR FRQWLQXR
SDUD PV IXQFLRQDPLHQWR GH GHULYDFLyQ
7ROHUDQFLD GH WHQVLyQ 9 D FDUJD FRPSOHWD
9
N9$
9
7LSR GH FRQH[LyQ 3+ 1 *
&DSDFLGDG GH VDOLGD SDUD PLQXWR IXQFLRQDPLHQWR QRUPDO
SDUD PLQXWRV IXQFLRQDPLHQWR QRUPDO
SDUD PLQXWR IXQFLRQDPLHQWR FRQ EDWHUtD
SDUD PLQXWRV IXQFLRQDPLHQWR FRQ EDWHUtD
FRQWLQXD IXQFLRQDPLHQWR GH GHULYDFLyQ
SDUD PV IXQFLRQDPLHQWR GH GHULYDFLyQ
7ROHUDQFLD GH WHQVLyQ 9 D FDUJD FRPSOHWD
&RUULHQWH GH VDOLGD
QRPLQDO $
)UHFXHQFLD GH VDOLGD +] SDUD +] QRPLQDO
VLQFURQL]DFLyQ FRQ
UHG HOpFWULFD
9HORFLGDG GH FDPELR
GH YROWDMH +]V
'LVWRUVLyQ DUPyQLFD OLQHDO
WRWDO GH YROWDMH QR OLQHDO
7+'8
)DFWRU GH SRWHQFLD GH
VDOLGD
5HVSXHVWD GH FDUJD
GLQiPLFD
5HJXODFLyQ GH
WHQVLyQ GH VDOLGD
Input Voltage : 400V AC 3Ph 50Hz Output Voltage :230V AC 1Ph 50Hz Battery - Nominal Voltage : +/-192V DC
G35T15K3I2B2S
15kVA/ G35T15K3I2B4S 15kVA/
18.5 20.3 65 65 41.2 25 80
12kW G35T15K3I3B4S 12kW
G35T15K3I4B4S
G35T20K3I2B2S
20kVA/ G35T20K3I2B4S 20kVA/
24.8 27.3 86.6 86.6 55 32 100
16kW G35T20K3I3B4S 16kW
G35T20K3I4B4S
30kVA/ G35T30K3I3B4S 30kVA/
36.7 40.3 129.9 129.9 82.5 50 160
24kW G35T30K3I4B4S 24kW
40kVA/ 40kVA/
G35T40K3I4B4S 49.6 54.6 173.2 173.2 110.1 63 200
32kW 32kW
&
6LVWHPD HQ SDUDOHOR FRQ XQLGDGHV 6$, ± N9$
9
t*OUFSWBMPTEFQPUFODJBBNQMJBCMFT
t#ZQBTTJOUFSOPQBSBNBOUFOJNJFOUP
t.POJUPSJ[BDJØOTFODJMMB
t$BQBDJEBEEFGVODJPOBNJFOUPFOQBSBMFMP
t"DDFTPGSPOUBMQBSBNBOUFOJNJFOUP
t"MUBEJTQPOJCJMJEBE
t#BKPOJWFMEFSVJEP
Características y ventajas
].(&(BMBYZ
MGE Galaxy 5500
Eficiente:)BTUBVOFONPEPPOMJOFEFEPCMF
DPOWFSTJØO
Diseño flexible:1FSNJUFVOBBNQMJBHBNBEF
DPOmHVSBDJPOFTQBSBDVBMRVJFSFOUPSOP
].(&(BMBYZ
Características del MGE Galaxy 5500
6
1 Tecnología basada en IGBT para
3
proteger la calidad del suministro
1
4VNJOJTUSBVOBBMJNFOUBDJØOMJNQJBZFTUBCMFB
DBSHBTWVMOFSBCMFT
HBSBOUJ[BOEPMBQSPUFDDJØO
EFMPTFMFNFOUPTWJUBMFTZVOSFOEJNJFOUP
ØQUJNP
BEFNÈTEFQSPMPOHBSTVWJEBÞUJM
2 Entrada doble
4
1FSNJUFMBDPOFYJØOBEPTTVNJOJTUSPTEF
FOUSBEBJOEFQFOEJFOUFTQBSBBVNFOUBSMB
EJTQPOJCJMJEBE
3 Funcionamiento en paralelo
$POFDUFIBTUBTFJTVOJEBEFTFOQBSBMFMPQBSB
BVNFOUBSMBDBQBDJEBEZMBSFEVOEBODJBEF
5
BDVFSEPDPOTVTSFRVJTJUPTEFBMJNFOUBDJØO
4 Componentes redundantes
"VNFOUBOFMSFTQBMEP
JODSFNFOUBOMBmBCJMJEBE 2
ZHBSBOUJ[BOVOGVODJPOBNJFOUPDPOUJOVP
].(&(BMBYZ
Opciones del MGE Galaxy 5500
Opciones
t "SNBSJPTEFCZQBTTNBOVBMQBSBTJTUFNBTFO
QBSBMFMP
t "SNBSJPTDPOQSPUFDDJØO*1
t $PGSFTEFCZQBTTEFNBOUFOJNJFOUPFYUFSOP
t "SNBSJPDPOFOUSBEBTVQFSJPSEFDBCMFT
Tarjeta de gestión de red 2 SAI Schneider Bypass externo para Galaxy
t 0USBTPQDJPOFTEFDPNVOJDBDJPOFT con monitorización ambiental, acceso 5500 para montaje en pared
fuera de banda y Modbus
t 4PGUXBSFQBSBHFTUJØOBWBO[BEBEFMBBMJNFOUBDJØO
t 5SBOTGPSNBEPSDPNQBDUP
t 0QDJØOEFQSPUFDDJØOCBDLGFFE
t 1SPUFDDJØOBEJDJPOBMDPOmMUSP*&$PQDJPOBM
t 0QDJØOEFTJODSPOJ[BDJØO QBSBTJODSPOJ[BSMB
VOJEBE4"*DPOVOBGVFOUFFYUFSOB
].(&(BMBYZ
Software StruxureWare
-BTVOJEBEFT4"*ZMPTTJTUFNBTEFBMJNFOUBDJØOTFHVSBEF"1$™CZ4DIOFJEFS
&MFDUSJD™TPOVODPNQPOFOUFGVOEBNFOUBMEFDVBMRVJFSBSRVJUFDUVSBEJTF×BEB
QBSBBQMJDBDJPOFTFTQFDJBMNFOUFJNQPSUBOUFT
DPNPDFOUSPTEFEBUPT
FOUPSOPT
JOEVTUSJBMFT
JOGSBFTUSVDUVSBTZFEJmDJPT
-BHFTUJØOJOUFMJHFOUFEFMBFOFSHÓBDPOFTUPTTJTUFNBTFTQPTJCMFHSBDJBTBMB
BSRVJUFDUVSBEFTJTUFNB4DIOFJEFS&MFDUSJD&DP4USVYVSF™DPOIBSEXBSFZTPGUXBSF
JOUFHSBEPT-BTBQMJDBDJPOFTZTVJUFTEFTPGUXBSF4USVYVSF8BSF™TPOVOFMFNFOUP
DMBWFEFMBBSRVJUFDUVSB&DP4USVYVSF&MTPGUXBSF4USVYVSF8BSFBZVEBBNBYJNJ[BS
MBmBCJMJEBEEFMTJTUFNBZBPQUJNJ[BSMBFmDJFODJBPQFSBUJWB
&MTPGUXBSF4USVYVSF8BSFGPS%BUB$FOUFSTSFDPQJMBZHFTUJPOBJOGPSNBDJØOFO
UJFNQPSFBMTPCSFBDUJWPT
VTPEFSFDVSTPTZFTUBEPPQFSBUJWPEVSBOUFUPEPFM
H
DJDMPEFWJEBEFMDFOUSPEFEBUPT&TUFTPGUXBSFEFHFTUJØOEFMBJOGSBFTUSVDUVSB
EFDFOUSPTEFEBUPT %$*.
JOUFHSBDPNQMFUBNFOUFFM.(&(BMBYZ(SBDJBT
BMBQMFOBWJTJCJMJEBEEFMTJTUFNB
MPTTVQFSWJTPSFTQVFEFONPOJUPSJ[BSZFNQMFBS
FTUBJOGPSNBDJØOQBSBPQUJNJ[BSFMSFOEJNJFOUPEFMDFOUSPZDVNQMJSMPTPCKFUJWPT
OGPSNÈUJDPT
FNQSFTBSJBMFTZEFTFSWJDJP
JOGPSNÈUJDPT
FNQSFTBSJBMFTZEFTFSWJDJP
].(&(BMBYZ
Una completa cartera de servicios
Planes Advantage
1BRVFUFTEFTFSWJDJPTnFYJCMFTRVFPGSFDFOVO
NBOUFOJNJFOUPTJONPMFTUJBTQBSBNFKPSBSFMUJFNQP
EFBDUJWJEBEDPOVODPTUFFTUBCMFDJEP-PTQBRVFUFT
"EWBOUBHF1MVT
1SJNF
6MUSBZ.BYDVCSFOTFSWJDJPT
EFTPQPSUFUÏDOJDP
NBOUFOJNJFOUPQSFWFOUJWP
SFTQVFTUBSÈQJEBin situZNPOJUPSJ[BDJØOSFNPUB
DPO
BNQMJBDJØOPQDJPOBMEFMPTUJFNQPTEFSFTQVFTUB
].(&(BMBYZ
Especificaciones técnicas
Potencia nominal (kVA/kW) 20/18 30/27 40/36 60/54 80/72 100/90 120/108
Entrada de alimentación de CA normal
1
Tensión de entrada (V) 250 V a 470 V, trifásica
Entradas de CA normal y de bypass independientes, comunes opcionalmente
Frecuencia (Hz) 45 – 66 Hz
Factor de potencia de entrada > 0,99
THDI < 3% a plena carga
Entrada de CA de bypass
Intervalo de tensión de entrada (380 V, 400 V, 415 V) +/-10%
Frecuencia 50 Hz/60 Hz +/-10%
Salida
Tensión de salida entre fases (V) 380 V/400 V/415 V, trifásica + neutro
Factor de potencia de la carga 0,9
Frecuencia de salida 50 o 60 Hz +/-0,1%
Capacidad de funcionamiento con sobrecarga 125% durante 10 minutos; 150% durante 60 segundos
Regulación de la tensión de salida +/- 1%
Distorsión armónica total (THD) < 2% entre fases y de fase a neutro para cargas no lineales
Tolerancia de la tensión de salida +1% estática, +/-2% con salto de carga del 100%
Eficiencia total
Eficiencia a plena carga (CA/CA) con carga del 100% hasta el 94%
2
Modo ECO hasta el 97%
Comunicación y gestión
Panel de control LCD multifunción, estado y consola de control
Dimensiones y pesos
SAI sin batería (Al x An x P) 1900 x 712 x 850 mm
SAI con batería interna (Al x An x P) 1900 x 1112 x 850 mm
Peso en kg (SAI sin batería) 400 kg 520 kg
Dimensiones SAI con transformador 1900 x 1190 x 850 mm 1900 x 1265 x 850 mm
Peso SAI con transformador 705 kg 1045 kg
Armario para baterías, estrecho (Al x An x P) 1900 x 712 x 850 mm, peso: 135 kg
Armario para baterías, ancho (Al x An x P) 1900 x 1012 x 850 mm, peso: 150 kg
Armario auxiliar, estrecho (Al x An x P) 1900 x 712 x 850 mm, peso: 135 kg mín.
Armario auxiliar, ancho (Al x An x P) 1900 x 1012 x 850 mm, peso: 150 kg mín.
Armario auxiliar de 475 mm con transformador de
1900 x 475 x 850 mm, peso: 118 kg mín., 305 kg máx.
aislamiento hasta 60 kVA (Al x An x P)
Armario auxiliar de 550 mm con transformador de
1900 x 550 x 850 mm, peso: 118 kg mín., 527 kg máx.
aislamiento, 80-120 kVA (Al x An x P)
Bypass de sistema en paralelo
1000 x 800 x 303 mm mín., 1900 x 1010 x 850 mm máx., peso: 71 kg mín., 280 kg máx.
(montado en pared o en armario) (Al x An x P)
Normativas
Seguridad IEC 62040-1, EN 62040-1
EMC/EMI/RFI IEC 62040-2, EN 62040-2
Certificaciones CE, TÜV
Datos ambientales
Temperatura de funcionamiento 0 a 40 °C 3
Temperatura de almacenamiento -20 a 45 °C
Humedad relativa 0-95% sin condensación
Altura de funcionamiento 0–1000 m
Altura de almacenamiento 0–12 000 m
Ruido máximo audible a 1 metro de la unidad 55,5 dBA 61,4 dBA 60,2 dBA
1
Con un nivel de carga del 70% 2 Sólo disponible en productos unitarios
3
Existe riesgo de envejecimiento prematuro de la batería por encima de 25 ºC
ª4DIOFJEFS&MFDUSJD"MM3JHIUT3FTFSWFE"MMUSBEFNBSLTBSFPXOFECZ4DIOFJEFS&MFDUSJD*OEVTUSJFT4"4PSJUTBGGJMJBUFEDPNQBOJFTt@&4
)DFLOLW\ 3ODQQLQJ
$& ,QSXW
$& LQSXW N9$ N9$ N9$ N9$ N9$ N9$ N9$
5DWHG FXUUHQW
1RUPDO $& LQSXW $
5DWHG FXUUHQW
$& %\SDVV LQSXW $
0D[LPXP &RQWLQXRXV
LQSXW FXUUHQW DW 8 9
$
,QSXW FXUUHQW DW 8 9
RYHUORDG ,Q OLPLWHG WR
PLQ $
,QSXW FXUUHQW DW 8 9
RYHUORDG ,Q OLPLWHG WR
PLQ $
7+', DW IXOO ORDG
DW ± ORDG
0D[LPXP 6KRUW &LUFXLW
:LWKVWDQG N$
,QSXWRXWSXW IXVH UDWLQJV
$
5DWHG FXUUHQWV ZLWK EDWWHU\ ÀRDW FKDUJLQJ 8 QRUPDO $& LQSXW 8 $& E\SDVV LQSXW 8 ORDG 9 3
ORDG 31 ORDG FRV SKL
$& 2XWSXW
N9$ N9$ N9$ N9$ N9$ N9$ N9$
2YHUORDG IRU PLQXWHV
&DSDFLW\ IRU PLQXWH
IRU VHFRQG
9ROWDJH ±
7ROHUDQFH
9
1RPLQDO
2XWSXW
&XUUHQW
2XWSXW
FXUUHQW
OLPLWDWLRQ
$
2XWSXW +] RU +]
)UHTXHQF\
7+'8 SKDVH WR SKDVH SKDVH WR QHXWUDO IRU OLQHDU ORDGV
SKDVH WR SKDVH SKDVH WR QHXWUDO IRU QRQOLQHDU ORDGV
&UHVW IDFWRU
1RWH 7KH FLUFXLW EUHDNHUV UHFRPPHQGHG DERYH DUH IRU D N$ EUHDNLQJ FDSDFLW\ 7KH
FLUFXLW EUHDNHUV UHFRPPHQGHG DERYH IROORZ WKH UHTXLUHPHQWV IRU GLVFULPLQDWLRQ ZLWK WKH
836 IXVHV
:$51,1* 6WLFN D ODEHO ZLWK WKH IROORZLQJ WH[W RQ HDFK XSVWUHDP FLUFXLW EUHDNHU
³,VRODWH 8QLQWHUUXSWLEOH 3RZHU 6XSSO\ 836 EHIRUH ZRUNLQJ RQ WKLV FLUFXLW´
(DUWKOHDNDJH FXUUHQW
836 HDUWKOHDNDJH FXUUHQW LV $
)XVHV
7LPHFXUUHQW FXUYHV IRU 836 LQSXW DQG RXWSXW IXVHV
&RQQHFWLRQV DUH PDGH WR SUHGULOOHG WHUPLQDOV +ROH GLDPHWHU PP PP IRU N9$
3(FDEOHV 3URWHFWLYH (DUWK FDEOHV FRQQHFW WR WKH HDUWKLQJ WHUPLQDO +ROH GLDPHWHU PP PP IRU
N9$
1RWH 7KH ¿QDO ZHLJKW RI WKH HQFORVXUH ZLWK EDWWHULHV GHSHQG RQ FKRVHQ UXQWLPH QXPEHU RI
EDWWHU\ EORFNV DQG EDWWHU\ EUDQG DQG W\SH 7KH ZHLJKWV JLYHQ KHUH DUH RQO\ DSSUR[LPDWH
ZHLJKWV PHDVXUHG ZLWK DQ $3& EDWWHU\ VROXWLRQ DQG PXVW RQO\ EH XVHG DV DQ LQGLFDWLRQ
RI DQ DSSUR[LPDWH ¿QDO ZHLJKW
%DWWHU\ EDFNXS WLPH LV DGYHUVHO\ DIIHFWHG E\ KLJK DQG ORZ WHPSHUDWXUHV ,W LV VLJQL¿FDQWO\ UHGXFHG
DW WHPSHUDWXUHV XQGHU &
$ERYH & EDWWHU\ VHUYLFH OLIH LV UHGXFHG E\ IRU HYHU\ & WHPSHUDWXUH LQFUHDVH $ERYH &
EDWWHU\ PDQXIDFWXUHUV QR ORQJHU JXDUDQWHH RSHUDWLRQ GXH WR WKH ULVN RI WKHUPDO UXQDZD\
/RVVHV FDOFXODWHG ZLWK PD[ FXUUHQW ĺ 9 DQG 5/ ORDG FRVI # ORDG
UPS Bypass
UPS Mains Input 1 UPS Output UPS - Recom m ended Over current Protection Device Ratings
Input 1
Battery Discharge
UPS Mechanical Data
Current(A)
UPS Required
UPS Upstream protection
UPS UPS Dow nstrem Heat air flow
SKU Number for UPS
Rating System protection in Loss
Nominal Maximum Nominal Nominal Nominal Maximum Typical Floor (m 3/h)
output reference w ith (kW)23
Current(A) Current(A) Current(A) Current(A) Discharge Discharge CB on separate Normal CB on separate Bypass CB on common Bypass Upstream Dimensions Weight Loading
Power
and Normal AC input protection
Current Current AC input (A) AC input (A) HxW xD (Kg)14 data in
(A)
(A) (A) (mm) 14 Kg/m2
80kVA/ G55TUPSM80HS25 80kVA/ C60N C 25A/
115 116 116 116 226 270 NSX 160F 3P-TM160D NSX 160F 4P-TM160D NSX 160F 4P-TM160D 1900x712x850 520 859.22 4.86 2556
72kW G55TUPSM80HINS26 72kW C60N B 50A
Notes.
1. Rated currents with battery float charging.
2. At <150% for 10seconds.
3. Input and bypass cables must be run in separate conduits from output cables. Not more than three conductors in raceway assumed; ambient temperature of 30°C (86°F) assumed.
4. If initial load is less than UPS' rated output, it is recommended that AC input, battery, and AC output wiring and over current protection be sized to UPS’ full load rating to accommodate possible future expansion.
5. Only copper cables are considered.
6. DC cables should be sized for a total maximum of less than 1% of CB rating.
7. OCPD = Over current Protection Device. Recommended represents 125% of nominal full load current (continuous).
8. Minimum-sized grounding conductors are recommended. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity.
9. Wiring requirements:
- AC Input/Output: 3Ø, 3 or 4 wire + ground, depending on UPS configuration.
See Installation Manual and submittal drawings for specific instructions.
- DC Input: 2 wire (positive and negative) + ground
10. All wiring to be in accordance with all applicable national and/or local electrical codes.
11. Minimum access clearance per UPS drawings.
12. The cable sizes are based on an environment with ambient max temperature of 35 degrees C.
13. Control wiring and power wiring must be run in separate conduit.
14. Weights and dimensions shown do not include battery cabinet(s) or other options
15. Backup emergency generator must be properly sized for UPS application and equipped with an isochronous governor for frequency regulation,and a UPS-compatible voltage regulator for voltage stability.
16. If site configuration requires an external maintenance bypass, phase parity between UPS input and UPS bypass must be ensured. Consult applications engineer.
17. The terminals have minimum size requirements for cables.
18. Each PFC or Boost pack contains a 63A fuse per phase. 10-20kVA Ups has one pack and 30-40kVA UPS have two packs.
19. Average weight references installed weight with batteries.
20. Temperature rating of conductors: 90°C (194°F). 75°C (167°F) cable terminal conductors assumed.
21. Input : THDI < 3% at full load, <5% at 25-75%.
22.Output : THDU 1% Phase to Phase, 1.5% Phase to Neutral for Linear Loads.
2% Phase to Phase, 3.5% Phase to Neutral for Non Linear Loads.
23.Heat losses refers to maximum loading and fully charged batteries
24.Ratings of the cables and overcurrent devices supplied for information only. User to consult with their engineering services before adopting
25. Applicable for IEC countries except Asia Pacific countries and Japan.
26. Applicable for Asia Pacific countries and Japan.
EFFICIENCY DETAILS
SYSTEM 25%LOAD 50%LOAD 75%LOAD 100%LOAD
80kVA 400V 90.23 93.14 93.58 93.42
Sheet No. Component /Detail Description
1 Draw ing Guide MGE Galaxy 5500 80kVA 400V 2 Mod(N+1) 15 min w ith EB Draw ing guide
2-4 Solution MGE Galaxy 5500 80kVA 400V 2 Mod(N+1) 15 min w ith EB
5-6 UPS MGE Galaxy 5500 80kVA 400V
7 Battery MGE Galaxy 5500 Battery Cabinet 1012mm
8 External Bypass MGE Galaxy 5500 External Bypass (TNS) 150kVA 400V
9-11 System One Line Diagram MGE Galaxy 5500 80kVA 400V 2 Mod(N+1) 15 min w ith EB, System One Line Diagram
12 System Wiring Diagram MGE Galaxy 5500 80kVA 400V 2 Mod(N+1) 15 min w ith EB, System Wiring Diagram
Floor Loading Data in Kg/m²
UPS 859
Battery Cabinet (1012mm) 1428
UPS Bypass
UPS Mains Input 1 UPS Output UPS - Recom m ended Over current Protection Device Ratings
Input 1
Battery Discharge
UPS Mechanical Data
Current(A)
UPS Required
UPS Upstream protection
UPS UPS Dow nstrem Heat air flow
SKU Number for UPS
Rating System protection in Loss
Nominal Maximum Nominal Nominal Nominal Maximum Typical Floor (m 3/h)
output reference w ith (kW)23
Current(A) Current(A) Current(A) Current(A) Discharge Discharge CB on separate Normal CB on separate Bypass CB on common Bypass Upstream Dimensions Weight Loading
Power
and Normal AC input protection
Current Current AC input (A) AC input (A) HxWxD (Kg)14 data in
(A)
(A) (A) (mm) 14 Kg/m2
80kVA/ G55TUPSM80HS25 80kVA/ C60N C 25A/
115 116 116 116 226 270 NSX 160F 3P-TM160D NSX 160F 4P-TM160D NSX 160F 4P-TM160D 1900x712x850 520 859.22 4.86 2556
72kW G55TUPSM80HINS26 72kW C60N B 50A
Notes.
1. Rated currents with battery float charging.
2. At <150% for 10seconds.
3. Input and bypass cables must be run in separate conduits from output cables. Not more than three conductors in raceway assumed; ambient temperature of 30°C (86°F) assumed.
4. If initial load is less than UPS' rated output, it is recommended that AC input, battery, and AC output wiring and over current protection be sized to UPS’ full load rating to accommodate possible future expansion.
5. Only copper cables are considered.
6. DC cables should be sized for a total maximum of less than 1% of CB rating.
7. OCPD = Over current Protection Device. Recommended represents 125% of nominal full load current (continuous).
8. Minimum-sized grounding conductors are recommended. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity.
9. Wiring requirements:
- AC Input/Output: 3Ø, 3 or 4 wire + ground, depending on UPS configuration.
See Installation Manual and submittal drawings for specific instructions.
- DC Input: 2 wire (positive and negative) + ground
10. All wiring to be in accordance with all applicable national and/or local electrical codes.
11. Minimum access clearance per UPS drawings.
12. The cable sizes are based on an environment with ambient max temperature of 35 degrees C.
13. Control wiring and power wiring must be run in separate conduit.
14. Weights and dimensions shown do not include battery cabinet(s) or other options
15. Backup emergency generator must be properly sized for UPS application and equipped with an isochronous governor for frequency regulation,and a UPS-compatible voltage regulator for voltage stability.
16. If site configuration requires an external maintenance bypass, phase parity between UPS input and UPS bypass must be ensured. Consult applications engineer.
17. The terminals have minimum size requirements for cables.
18. Each PFC or Boost pack contains a 63A fuse per phase. 10-20kVA Ups has one pack and 30-40kVA UPS have two packs.
19. Average weight references installed weight with batteries.
20. Temperature rating of conductors: 90°C (194°F). 75°C (167°F) cable terminal conductors assumed.
21. Input : THDI < 3% at full load, <5% at 25-75%.
22.Output : THDU 1% Phase to Phase, 1.5% Phase to Neutral for Linear Loads.
2% Phase to Phase, 3.5% Phase to Neutral for Non Linear Loads.
23.Heat losses refers to maximum loading and fully charged batteries
24.Ratings of the cables and overcurrent devices supplied for information only. User to consult with their engineering services before adopting
25. Applicable for IEC countries except Asia Pacific countries and Japan.
26. Applicable for Asia Pacific countries and Japan.
EFFICIENCY DETAILS
SYSTEM 25%LOAD 50%LOAD 75%LOAD 100%LOAD
80kVA 400V 90.23 93.14 93.58 93.42
Sheet No. Component /Detail Description
1 Draw ing Guide MGE Galaxy 5500 120kVA 400V Unitary 10min draw ing guide
2-4 Solution MGE Galaxy 5500 120kVA 400V Unitary 10min
5-6 UPS MGE Galaxy 5500 120kVA 400V
7 Battery MGE Galaxy 5500 Battery Cabinet 1012mm
8 -10 System One Line Diagram MGE Galaxy 5500 120kVA 400V Unitary 10min System One Line Diagram
11 System Wiring Diagram MGE Galaxy 5500 120kVA 400V Unitary 10min System Wiring Diagram
WEIGHT AND RUNTIME TABLE
UPS Power Rating 120 KVA
Runtime in Minutes(M) 10
UPS Cabinet Weight in kg 520
Battery Cabinet Weight in kg 1350
UPS Bypass
UPS Mains Input1 UPS Output UPS - Recom m ended Over current Protection Device Ratings
Input1
Battery Discharge
UPS Mechanical Data
Current(A)
UPS
UPS Upstream protection UPS Required
UPS Heat
SKU Number Dow nstrem air flow for
Rating System Loss
Nominal Maximum Nominal Nominal protection in UPS (m 3/h)
output Typical Floor (kW)23
Current(A) Current(A) Current(A) Current(A) Nominal Maximum reference w ith
Power CB on separate Normal CB on separate Bypass CB on common Bypass Dimensions Loading
Discharge Discharge Upstream Weight
AC input (A) AC input (A) and Normal AC input (A) HxWxD data in
Current (A) Current (A) protection (Kg) 14
(mm) 14 Kg/m2
C60N C 32A/
120kVA/ G55TUPSU120HS25 120kVA/
171 173 174 174 347 405 NSX 250F 3P- TM250D NSX 250F 4P- TM250D NSX 250F 4P- TM250D C120N B 63A/ 1900x712x850 520 859.22 8.41 2556
108kW 26
108kW
G55TUPSU120HINS NSX100 TMG
Notes.
1. Rated currents with battery float charging.
2. At <150% for 10seconds.
3. Input and bypass cables must be run in separate conduits from output cables. Not more than three conductors in raceway assumed; ambient temperature of 30°C (86°F) assumed.
4. If initial load is less than UPS' rated output, it is recommended that AC input, battery, and AC output wiring and over current protection be sized to UPS’ full load rating to accommodate possible future expansion.
5. Only copper cables are considered.
6. DC cables should be sized for a total maximum of less than 1% of CB rating.
7. OCPD = Over current Protection Device. Recommended represents 125% of nominal full load current (continuous).
8. Minimum-sized grounding conductors are recommended. Parity-sized ground conductors are recommended. Neutral conductors to be sized for full capacity.
9. Wiring requirements:
- AC Input/Output: 3Ø, 3 or 4 wire + ground, depending on UPS configuration.
See Installation Manual and submittal drawings for specific instructions.
- DC Input: 2 wire (positive and negative) + ground
10. All wiring to be in accordance with all applicable national and/or local electrical codes.
11. Minimum access clearance per UPS drawings.
12. The cable sizes are based on an environment with ambient max temperature of 35 degrees C.
13. Control wiring and power wiring must be run in separate conduit.
14. Weights and dimensions shown do not include battery cabinet(s) or other options
15. Backup emergency generator must be properly sized for UPS application and equipped with an isochronous governor for frequency regulation,and a UPS-compatible voltage regulator for voltage stability.
16. If site configuration requires an external maintenance bypass, phase parity between UPS input and UPS bypass must be ensured. Consult applications engineer.
17. The terminals have minimum size requirements for cables.
18. Each PFC or Boost pack contains a 63A fuse per phase. 10-20kVA Ups has one pack and 30-40kVA UPS have two packs.
19. Average weight references installed weight with batteries.
20. Temperature rating of conductors: 90°C (194°F). 75°C (167°F) cable terminal conductors assumed.
21. Input : THDI < 3% at full load, <5% at 25-75%.
22.Output : THDU 1% Phase to Phase, 1.5% Phase to Neutral for Linear Loads.
2% Phase to Phase, 3.5% Phase to Neutral for Non Linear Loads.
23.Heat losses refers to maximum loading and fully charged batteries
24.Ratings of the cables and overcurrent devices supplied for information only. User to consult with their engineering services before adopting
25. Applicable for IEC countries except Asia Pacific countries and Japan.
26. Applicable for Asia Pacific countries and Japan.
27. ECO mode is available with Unitary configuration.
EFFICIENCY DETAILS
SYSTEM 25%LOAD 50%LOAD 75%LOAD 100%LOAD
120kVA 400V 90.51 93.60 93.78 93.16
Galaxy VM
160/200 kVA - Con capacidad de operación en paralelo para soportar 800 kVA.
Protección de energía trifásica
Galaxy VM
Integración Fácil de instalar
• Suite de software y aplicaciones • Sistema diseñado para un cableado más
sencillo en espacios de instalación confinados
StruxureWare™ de Schneider Electric
• Opciones para distintas configuraciones de • Gabinete único con entrada superior e inferior
conexión a tierra de cables
• Adaptable para soportar instalaciones • Ruedas integradas para mejor movilidad de UPS
completas y gabinetes modulares de baterías
• Certificación antisísmica
• Sistemas de monitoreo – BMS, modbus, etc.
Se integra
Ahorro en costos de energía para proteger
su mundo
• Modo de doble conversión de eficiencia alta
• Modo ECO
Hace sus Reduce sus
• Modo ECOnversion decisiones costos de energía
sencillas a través de alta
Opciones flexibles de almacenamiento eficiencia
de energía.
• Disponibilidad de baterías tradicionales (plomo- Incrementa
la flexibilidad de
ácido regulado por válvula) y modulares
su almacenamiento
• Tiempos de respaldo cortos y extendidos de energía
• Modos de carga seleccionables
2 | Galaxy VM
Características de Galaxy VM
Se integra para proteger su mundo
Prueba de energía
inteligente
Habilidad de probar la unidad UPS con
carga completa sin la necesidad de rentar
un banco de carga y antes de poner la
carga del cliente en operación
Integración a la infraestructura de su
instalación
• Ocupa un menor espacio físico
• Instalación contra la pared
Bypass CA
• Opera a 40°C continuamente sin perder potencia
Normal CA Normal CA Normal CA Normal CA Normal CA
• Capacidad sísmica integrada, con aprobación
para IBC® nivel 2
• Niveles de ruido audible bajos
• Filtros de polvo intercambiables para ambientes
exigentes
• Relés de entrada y salida configurables
• Entrada de cables superior e inferior
• Capacidad de operación en paralelo de
Carga múltiples unidades para aumentar capacidad o
redundancia.
Conexión paralela distribuída para energía y redundancia • Arranque en frío: capacidad de iniciar la unidad
UPS con batería sin energía de la red principal
• Capacidad de sincronización externa
3 | Galaxy VM
Características de Galaxy VM
Reduce sus costos de energía a través de alta eficiencia
Modo ECO
• Eficiencia de hasta 99,5%.
• Cumple con la clasificación 1 del
estandar IEC® 62040- 3 para salida
de UPS.
Modo ECOnversion
Habilita el control de la corriente de entrada con ECOnversion de Galaxy VM cumple con la Clase 1 de IEC
prácticamente la misma calidad de las UPS en línea 62040-3: transferencia sin interrupciones durante una falla de
energía.
Conmutador de bypass
100%
80%
Carga 60%
Valor nominal (% de voltaje)
Entrada CA 40%
–60%
Bateria
–80%
–100%
0,1 1 10 100 1.000
4 | Galaxy VM
Características de Galaxy VM
Incrementa la flexibilidad de su almacenamiento de energía
Se integra
para proteger
su mundo
Reduce
Hace sus sus costos
decisiones de energía a
sencillas través de alta
eficiencia
Incrementa
la flexibilidad de
su almacenamiento
de energía
Elementos opcionales
Galaxy VM
• Tarjetas de administración Caja de automático de baterías empotrada al muro
5 | Galaxy VM
Características de Galaxy VM
Hace sus decisiones más sencillas
Se integra
para proteger
su mundo
Reduce
Hace sus sus costos
decisiones de energía a
través de alta
sencillas eficiencia
Incrementa
la flexibilidad de
su almacenamiento
de energía
Pantalla LCD
6 | Galaxy VM
Suite de software Struxureware para
Data Centers
En el ambiente de centro de datos, nuestra unidad Galaxy VM se
administra completamente a través del software Struxureware para
Data Centers, una suite integral de aplicaciones de administración
de infraestructura de centro de datos. Ésta permite que los negocios
prosperen a través de la administración de sus centro de datos a
través de dominios múltiples, lo que entrega una inteligencia
concreta para un balance ideal de alta disponibilidad y eficiencia
máxima a lo largo de todo el ciclo de vida del centro de datos. Las
suites y aplicaciones del software Struxureware son elementos
claves de la arquitectura integrada de sistemas de hardware y
software EcoStruxure™ de Schneider Electric, un sistema diseñado
para la administración inteligente de la energía.
Planes Advantage
Los paquetes de servicio flexible ofrecen un sistema de manutención
uniforme a modo de mejorar el tiempo en funcionamiento con un costo
predecible. Los paquetes Advantage Plus, Prime, Ultra y Max son paquetes
de servicio completo que incluyen soporte técnico, manutención preventiva,
respuesta en terreno rápida y monitoreo remoto. Se encuentran
disponibles mejoras en los tiempos de respuesta.
Manutención preventiva
Servicios de mantenimiento preventivo realizados en campo mantienen
sus sistemas críticos funcionando con la máxima eficiencia.
7 | Galaxy VM
Especificaciones técnicas
1 Voltaje de entrada: (320 V a V nominal + 20%) para carga completa. (V nominal + 20% hasta 600V) para 1 minuto de carga completa. (250V = 320 V) dependiendo de la carga.
2 Para temperaturas de operación de 40°C a 50°C, reduzca la potencia de la carga en 2,5% por cada 1°C.
©2013 Schneider Electric. Todos los derechos reservados. Schneider Electric, ECOnversion, Galaxy, StruxureWare, APC y EcoStruxure son marcas registradas de Schneider Electric Industries SAS o sus empresas afiliadas.
Todas las marcas registradas son propiedad de sus respectivos propietarios. •email: esupport@apc.com •132 Fairgrounds Road, West Kingston, RI 02892 EE.UU. • www.schneider-electric.com 998-1203811_GMA-US
± N9$ 9 )DFLOLW\ 3ODQQLQJ
)DFLOLW\ 3ODQQLQJ
,QSXW 6SHFLILFDWLRQV
N9$ N9$
,QSXW 9 9 9 9 9 9
YROWDJH 9
&RQQHFWLRQV ±ZLUH / / / 3(
9ROWDJH UDQJH ±
9
)UHTXHQF\
UDQJH +]
1RPLQDO LQSXW
FXUUHQW $
0D[LPXP
LQSXW FXUUHQW
$
,QSXW FXUUHQW
OLPLWDWLRQ $
7RWDO DW ORDG
KDUPRQLF DW ORDG
GLVWRUWLRQ DW ORDG
7+',
0D[LPXP 5DWHG FRQGLWLRQDO VKRUW±FLUFXLW FXUUHQW ,FF N$
LQSXW VKRUW 5DWHG SHDN ZLWKVWDQG FXUUHQW ,SN ,FF [
FLUFXLW 'HYLFH 5HIHU WR 5HTXLUHG 8SVWUHDP %UHDNHUV SDJH
ZLWKVWDQG
N$ ,FF
3URWHFWLRQ %XLOWLQ EDFNIHHG FRQWDFWRU
5DPSLQ $GDSWLYH 6HF
7KH V\VWHP FDQ RSHUDWH DW 9 IRU PLQXWH
±$
)DFLOLW\ 3ODQQLQJ ± N9$ 9
2XWSXW 6SHFLILFDWLRQV
N9$ N9$
1RPLQDO 9 9 9 9 9 9
RXWSXW
YROWDJH 9
&RQQHFWLRQV ±ZLUH / / / 1 3(
±ZLUH / / / 3(
2YHUORDG IRU PLQXWH QRUPDO RSHUDWLRQ DW &
FDSDFLW\ IRU PLQXWHV QRUPDO RSHUDWLRQ DW &
IRU VHFRQG EDWWHU\ RSHUDWLRQ DW &
IRU PLQXWH EDWWHU\ RSHUDWLRQ DW &
IRU PV E\SDVV RSHUDWLRQ DW &
2XWSXW 6\PPHWULF ORDG ±
YROWDJH VWDWLF
WROHUDQFH DIWHU PV
DIWHU PV
2XWSXW SRZHU
IDFWRU
1RPLQDO
RXWSXW FXUUHQW
$
7RWDO DW OLQHDU ORDG
KDUPRQLF DW QRQ±OLQHDU ORDG
GLVWRUWLRQ
7+'8
2XWSXW V\QF WR E\SDVV
IUHTXHQF\ +] IUHHUXQQLQJ
+]
6OHZ UDWH 3URJUDPPDEOH
+]VHF
2XWSXW 'RXEOHFRQYHUVLRQ 9),66
SHUIRUPDQFH
FODVVLILFDWLRQ
DFFRUGLQJ WR
,(&
(1
/RDG &UHVW 8QOLPLWHG
)DFWRU
/RDG 3RZHU OHDGLQJ WR ODJJLQJ ZLWKRXW GHUDWLQJ
)DFWRU
±$
± N9$ 9 )DFLOLW\ 3ODQQLQJ
%DWWHU\ 6SHFLILFDWLRQV
N9$ N9$
&RQQHFWLRQV '& '& 3(
&KDUJLQJ SRZHU LQ RI RXWSXW FKDUJH ORDG
SRZHU FKDUJH ORDG
1RPLQDO EDWWHU\ YROWDJH 9'&
1RPLQDO IORDW YROWDJH 9'&
(QG RI GLVFKDUJH YROWDJH IXOO ORDG
9'&
(QG RI GLVFKDUJH YROWDJH QR ORDG
9'&
%DWWHU\ FXUUHQW DW IXOO ORDG DQG
QRPLQDO EDWWHU\ YROWDJH $
%DWWHU\ FXUUHQW DW IXOO ORDG DQG
PLQLPXP EDWWHU\ YROWDJH $
7HPSHUDWXUH FRPSHQVDWLRQ P9 SHU & IRU 7 ! &
P9 SHU & IRU 7 &
5LSSOH FXUUHQW & PLQXWHV EDFNXS WLPH
%DWWHU\ WHVW 0DQXDODXWRPDWLF VHOHFWDEOH
'HHS GLVFKDUJH SURWHFWLRQ <HV
5HFKDUJH DFFRUGLQJ WR EDWWHU\ <HV
WHPSHUDWXUH
&ROG VWDUW <HV
±$
)DFLOLW\ 3ODQQLQJ ± N9$ 9
'$1*(5
+$=$5' 2) (/(&75,& 6+2&. (;3/26,21 25 $5& )/$6+
7KH VSHFLILHG XSVWUHDP EUHDNHUV EHORZ DUH UHTXLUHG WR REWDLQ WKH FRQGLWLRQDO
VKRUW±FLUFXLW FXUUHQW UDWLQJ ,FF DW N$ V\PPHWULFDO UPV
±$
± N9$ 9 )DFLOLW\ 3ODQQLQJ
N9$
8QLWV LQ
SDUDOOHO
0%% 6,% 0%% 6,% 0%% 6,%
%UHDNHU 16+ 0LF 16+ 0LF 16+ 0LF
5DWLQJ $
,U $
,VG
7U
7RUTXH 6SHFLILFDWLRQV
%ROW VL]H 7RUTXH
0 1P OEIW
0 1P OEIW
0 1P OEIW
0 1P OEIW
0 1P OEIW
0 1P OEIW
±$
)DFLOLW\ 3ODQQLQJ ± N9$ 9
3K\VLFDO
:HLJKWV DQG 'LPHQVLRQV
836
±$
± N9$ 9 )DFLOLW\ 3ODQQLQJ
±$
)DFLOLW\ 3ODQQLQJ ± N9$ 9
.LWV
±$
± N9$ 9 )DFLOLW\ 3ODQQLQJ
&OHDUDQFH
127( &OHDUDQFH GLPHQVLRQV DUH SXEOLVKHG IRU DLUIORZ DQG VHUYLFH DFFHVV RQO\
&RQVXOW ZLWK WKH ORFDO VDIHW\ FRGHV DQG VWDQGDUGV IRU DGGLWLRQDO UHTXLUHPHQWV LQ
\RXU ORFDO DUHD
127( 7KH 836 V\VWHP FDQ EH SODFHG XS DJDLQVW WKH ZDOO DQG WKHUH LV QR
UHTXLUHPHQW IRU UHDU RU VLGH DFFHVV
(QYLURQPHQW
2SHUDWLQJ 6WRUDJH
7HPSHUDWXUH & WR & & WR & IRU V\VWHPV ZLWK
EDWWHULHV
& WR & IRU V\VWHPV ZLWKRXW
EDWWHULHV
±$
)DFLOLW\ 3ODQQLQJ ± N9$ 9
+HDW 'LVVLSDWLRQ
±$
Galaxy VM Modular Battery Cabinet Runtimes in Minutes
Typical battery runtimes in minutes for systems with modular battery cabinets
NOTE: Battery runtimes are intended as an estimate at 0.9 power factor.
(2) GVMMODBCWS
x30 30 22.5
(1) GVMMODBCNS
(3) GVMMODBCWS
x42 46 34.5
(1) GVMMODBCNS
(4) GVMMODBCWS
x54 62.5 47.5
(1) GVMMODBCNS
(5) GVMMODBCWS
x66 79.5 60.5
(1) GVMMODBCNS
(6) GVMMODBCWS
x78 97.5 74
(1) GVMMODBCNS
(7) GVMMODBCWS
x90 115 88
(1) GVMMODBCNS
Example:
160 kVA and 30 minutes runtime then the SKUs to be ordered are:
GVMMODBCWS = 2
+
GVMMODBCNS = 1
+
GVMMBTU = 30
Galaxy VM Classical Battery Cabinet Runtimes in Minutes
NOTE: Battery runtimes are intended as an estimate at 0.9 power factor.
Europe Applicable for Galaxy VM 200 kVA UPS: GVMSB200KHS and GVMPB200KHS
SKU Number
Middle East to Order:
GVMCBCWEA GVMCBC2NEC GVMCBC2WEC GVMCBC2WED GVMCBC3WEC GVMCBC3WED
Africa Contains
1
x
2
x
2
x
2
x
3
x
3
x
40 40 40 40 40 40
% load kW of load XP12V2500 XP12V1800 XP12V2500 XP12V3000 XP12V2500 XP12V3000
At ambient temperature @ 25 °C
All runtimes are given in minutes at 0.9 PF of load
Example:
Requirement is to obtain 20.4 minutes backup time for
connecting a 200 kVA UPS (assume 80% load),the SKUs
to be ordered for the backup time are:
GVMCBC2WED = 1
Classical Battery Cabinet Runtime in Minutes
NOTE: Battery runtimes are intended as an estimate at 0.9 power factor.
Europe Applicable for Galaxy VM 160 kVA UPS: GVMSB160KHS and GVMPB160KHS
SKU Number
Middle East to Order:
GVMCBCWEA GVMCBC2NEC GVMCBC2WEC GVMCBC2WED GVMCBC3WEC GVMCBC3WED
Africa Contains
1
x
2
x
2
x
2
x
3
x
3
x
40 40 40 40 40 40
XP12V2500
% load kW of load XP12V2500 XP12V1800 XP12V2500 XP12V3000 XP12V3000
At ambient temperature @ 25 °C
All runtimes are given in minutes at 0.9 PF of load
MGE Galaxy 7000
160/200/250/300/400/500 kVA
Power efficiency for business continuity
Performance
f three-phase power
protection with high adaptability to meet
the unique requirements of medium to
large data centers, industry, buildings,
and mission-critical environments
t'MFYJCMFBOEWFSZBEBQUBCMF
t"EWBODFEFMFDUSJDBMGFBUVSFT
t1BSBMMFMDBQBCMFVQUPVOJUT
t)JHIFGGJDJFODZ
t0VUQVUTZODISPOJ[BUJPOUPFYUFSOBMTPVSDF
t)JHIBWBJMBCJMJUZBSDIJUFDUVSFTDPNQPOFOU
t&GGJDJFODZCPPTUFSNPEFPOQBSBMMFMJOTUBMMBUJPOT
t&$0.PEFPOCPUITJOHMFVOJUTBOE
QBSBMMFMJOTUBMMBUJPOT
t4NBSU1PXFS5FTU 41P5
GFBUVSF
Features and Benefits
MGE Galaxy 7000 includes features and options that continue to solve customer needs, including flexibility
to grow/expand power requirements with N+1 parallel/redundant modules with several choices including:
Isolated redundant, Integrated Parallel, and Centralized Static Switch making the MGE Galaxy 7000 a leader
with high availability architectures for mission critical environments. Easy to install and maintain is the basis of
the core design for this new UPS with only front electrical connections and fully serviceable components. MGE
Galaxy 7000 includes additional UPS solutions such as: bus synchronization boxes, IP32 enclosures, back-feed
protection, frequency conversion capabilities, and flexible and extended battery solutions including VRLA,
NiCad, external matching maintenance bypass cabinets, and paralleling gear. User friendly graphical display
with multiple language options, and an SNMP with network-based power management card that all ship
standard. MGE Galaxy 7000 available services include start-up, preventive maintenance, fast response time,
and comprehensive service packages designed for hassle-free system maintenance.
t &GýDJFODZ#PPTUFS.PEFPO t )FBMUIDBSF
QBSBMMFMJOTUBMMBUJPOT t 1FUSPDIFNJDBM
t 6UJMJUZ
].(&(BMBYZ
An innovative solution to make life simple
The MGE Galaxy 7000 is easy to choose. The MGE Galaxy 7000 is easy to operate.
It can operate at different frequencies and Any screen may be selected as the
voltages i.e., 50/60 Hz and 380 – 440 V. It standard display. For example, if output
also displays all information in 19 languages. measurements are a critical parameter,
Compatible with all load types select the output measurement screen
t 0VUQVUQPXFSGBDUPSVQUP
JOMJOFXJUIUIF as the default display.
MBUFTUHFOFSBUJPOPG*5BQQMJDBUJPOT Locally
t /PEFSBUJOHGPSMFBEJOHQPXFSGBDUPST t 5IF.(&(BMBYZJOUVJUJWFVTFSJOUFSGBDF
t )JHITIPSUDJSDVJUBOEPWFSMPBEDBQBDJUJFTGPS QSPWJEFTDMFBS
SFMFWBOUJOGPSNBUJPOGPSFBTZ
NPUPSMPBET PQFSBUJPO8JUIJUT
UJNFTUBNQFEFWFOUT
TUBUJTUJDBMBOBMZTJT
BOEFOFSHZþPXQJDUPHSBNT
Compatible with all battery types
TZTUFNNBOBHFNFOUDPVMEOPUCFTJNQMFS
t -FBEBDJECBUUFSJFT WFOUFE
TFBMFE
t /J$BE Remotely
t 5IF.(&(BMBYZQSPWJEFTWBMVBCMF
Compatible with all backup time
JOGPSNBUJPOUPTVQFSWJTJPOTZTUFNTPO
t 5IFIJHIQPXFSDIBSHFSSBQJEMZDIBSHFTCBUUFSJFT
o 5IF614BOEJUTFOWJSPONFOU
GPSCBDLVQUJNFTVQUPGPVSIPVST
o $POUSPMMFETIVUEPXOPGPQFSBUJOHTZTUFNT
Harmonic free rectifier t "OVNCFSPGEJGGFSFOUDPNNVOJDBUJPOQSPUPDPMT
t /PBEEJUJPOBMIBSNPOJDýMUFSJOHJTSFRVJSFE BSFBWBJMBCMFGPSSFNPUFPQFSBUJPO
o &UIFSOFU.CQTXJUI)5514FODSZQUJPO
Easy integration into electrical networks GPSCSPXTFSBOE/.4TVQFSWJTJPO
o +#VT.PECVTGPS#.4TZTUFNT
Schneider Electric,™ a leader in harmonic
o .PEFNGPSUFMFTFSWJDF
management, has built a true IGBT rectifier into
o 4JNQMFQSPHSBNNBCMFDVSSFOUMPPQDPOUBDUT
the MGE Galaxy 7000. Upstream THDI is less than
5% and the input power factor is greater than 0.99.
Seismic compliant
t -FTTSFBDUJWFQPXFS
t 'FXFSIBSNPOJDTJOKFDUFEVQTUSFBN The MGE Galaxy 7000 has been tested for seismic
t 4BWJOHTJOOFUXPSLDPNQPOFOUSBUJOHTTVDIBT compliancy using a specific anchoring system
DJSDVJUCSFBLFST
DBCMFT
FUD engineered by APC by Schneider Electric. This
t 'VMMZDPNQBUJCMFXJUIHFOFSBUPSTFUToBL7" allows in option to be compliant to the following
614POMZSFRVJSFTBL7"HFOFSBUPSTFU worldwide recognized standards:
t 'FBUVSFTBTPGUTUBSUDBQBCJMJUZ t &&&)JHI-FWFM
t (3$03&;POF
The MGE Galaxy 7000 is easy to install. t "$-FWFM
Phase sequence detection prevents start-up
if the phase order is incorrect.
t 4NBMMGPPUQSJOU
t /POFFEGPSSFBSPSTJEFBDDFTTBMMDPOOFDUJPOT
BSFNBEFUISPVHIUIFGSPOU
t *OUFHSBUJPOPGBMMTXJUDIFTSFRVJSJOHDPOOFDUJPO
t 3FBEZGPSBMMTZTUFNFBSUIJOHBSSBOHFNFOUT
].(&(BMBYZ
Efficient product: power availability
t /
PEFSBUJOH
FWFOGPSMPBETXJUIBMFBEJOH
QPXFSGBDUPS
t #FOFýUT
Loads
o )JHIGBVMUDMFBSJOHDBQBDJUZGPSCFUUFS
EJTDSJNJOBUJPOJOUIFFMFDUSJDBMOFUXPSL
o $PNQBUJCJMJUZXJUIBMMUZQFTPGMPBET
JODMVEJOH AC Normal AC Normal AC Bypass
DPNQVUFSMPBETBOEMPBETXJUIIJHIDSFTUGBDUPST Live standby
redundancy
Clean, stable output waveform
5IFEJHJUBMMZDPOUSPMMFE*(#5TBOEIJHIUFDIOPMPHZ
PVUQVUýMUFSQSPWJEFBWFSZDMFBO
TUBCMFPVUQVU
WPMUBHFXBWFGPSNXJUIMFTTUIBOUPUBMIBSNPOJD
EJTUPSUJPO 5)%6
FWFOGPS
t 4UFQQFEMPBETXJUDIJOH
t 6OCBMBODFEMPBET
t #FOFýUT
o 0QUJNVNTVQQMZGPSMPBET Priority load Priority load
o *ODSFBTFEMJGFFYQFDUBODZGPSUIF
QSPUFDUFEFRVJQNFOU
AC Bypass
Easy to upgrade Distributed parallel
AC Normal AC Normal AC Normal AC Normal connection for
Power and redundancy upgrades
t 1PXFSSFRVJSFNFOUTDBODIBOHFPWFSUJNF increased power
t .(&(BMBYZPVUQVUDBOCFNVMUJQMJFECZB and redundancy.
GBDUPSPGFJHIU3FEVOEBODZDBOBMTPCFBEEFEPS
VQHSBEFEBTOFFEFEFH
/
/PS/
Flexible architecture
High availability results not only from UPS
reliability, but also from innovative and resilient
architectures providing: Load
t 4PVSDFSFEVOEBODZ
t 1PXFSEJTUSJCVUJPOSFEVOEBODZ
AC Normal AC Bypass
Distribution
AC Bypass AC Normal
redundancy with
Synchronization the Static Transfer
module Switch (Upsilon STS)
Upsilon STS
Upsilon STS
Load 1
Upsilon STS
Load 2
Load 3
].(&(BMBYZ
Efficient product: energy savings
Up to 94.5% efficiency
means significant savings
Up
5IFJOOPWBUJWFUFDIOPMPHZCVJMUJOUPUIF 107.5%
mo to 1
.(&(BMBYZ
JODMVEJOHEJHJUBMFMFDUSPOJDTGPS re 07.
po 5%
Environment adaptation
Ambient temperature adaptability 100%
%JHJUBMFMFDUSPOJDTPGGFSBEEJUJPOBMGFBUVSFT5IF
BWBJMBCMFPVUQVUQPXFSJTBVUPNBUJDBMMZBEBQUFE
20 30 35
UPUIFUFNQFSBUVSFFH
BL7"614EFMJWFST TOC
L7"BU¡$BNCJFOUUFNQFSBUVSF
Overall efficiency
With EBM
of 2+1 500kVA UPS’s Without EBM
100,00%
Efficiency Booster Mode (EBM)
available on parallel installation 95,000%
Overall efficiency %
5IFJOOPWBUJWFBOEIJHIMZBOUJDJQBUFE&GýDJFODZ
90,000%
#PPTUFS.PEFGVODUJPOIFMQTUPNBJOUBJOIJHIFTU
HMPCBMFGýDJFODZJOBQBSBMMFMTZTUFN
XJUIPVUBOZ 85,000%
DPNQSPNJTFPOUIFHMPCBMBWBJMBCJMJUZPGUIFTZTUFN
t #FOFýUT 80,000%
o *NQSPWFTZTUFNFGýDJFODZCZBOBWFSBHFPG 75,000%
o 3FEVDFFMFDUSJDJUZDPOTVNQUJPOBOEDPPMJOHPG
UIF614SPPN 70,000%
o .BOBHFZPVSFOFSHZ
65,000%
0% 10% 20% 30% 40% 50% 60% 70% 80%
Overall load level %
AC Bypass
Smart Power Test (SPoT) feature
5IJTBEWBODFEGFBUVSFDSFBUFTTJHOJýDBOUTBWJOHT AC Normal AC Normal AC Normal AC Normal
EVSJOHPWFSBMMTZTUFNJOTUBMMBUJPO#ZSFNPWJOH
UIFOFFEGPSBMPBECBOL
BEEJUJPOBMCSFBLFSTBOE
TXJUDIHFBSTBSFOPUOFDFTTBSZ
t #FOFýUT
o *OTUBMMBUJPODBOCFUFTUFEBUBOZMPBEMFWFM
BOEBUBOZQPXFSGBDUPS
o 41P5DBOCFVTFEPOCPUITJOHMFBOE
QBSBMMFMTZTUFNT
Load
].(&(BMBYZ
Reducing environmental impact for sustainable development
3FEVDJOHUIFOVNCFSPGQBSUTJNQSPWFTSFMJBCJMJUZBOE t )JHIFGýDJFODZ614TPMVUJPOTUPSFEVDFIFBUMPTTFT
SFEVDFTJNQBDUPOUIFFOWJSPONFOU5IF.(&(BMBYZ o 6QUPFGýDJFODZJOPOMJOFNPEF
EFTJHOUFBNVTFEBEWBODFEEJHJUBMFMFDUSPOJDT o *NQSPWFTHMPCBMFGýDJFODZPGBQBSBMMFMTZTUFNBU
UPBDIJFWFTBWJOHT MPXMPBEMFWFMWJB&GýDJFODZ#PPTUFS.PEF
t 'FXFSFMFDUSPOJDCPBSET o 6QUPFGýDJFODZJO&$0.PEF
t 4PGUXBSFVQEBUFTWJBEPXOMPBEJOHJOTUFBEPG
DIBOHJOHCPBSET
Raw materials
5IBOLTUPJUTDPNQBDUTJ[FBOEMPXXFJHIU
UIF
.(&(BMBYZSFRVJSFTGFXFSSBXNBUFSJBMTBOE
UIFUZQFTVTFEBSFNPSFFOWJSPONFOUBMMZGSJFOEMZ
t 1PXFSFGýDJFOUDPNQPOFOUT
o 4QFDJýDDIPLFDPJMT
o 4NBMMFSPVUQVUýMUFST
t /FXEFTJHOGPSBUSBOTGPSNFSMFTT614
o .PSFTJMJDPO
MFTTDPQQFS
o .PSFQPXFSGVM*(#5T
The weight of the MGE Galaxy 7000 has been halved
compared to the previous generation.
].(&(BMBYZ
StruxureWare for Data Centers Software Suite
"1$™CZ4DIOFJEFS&MFDUSJD™614VOJUTBOETFDVSFQPXFSTZTUFNTBSFB
DPSFDPNQPOFOUPGBOZBSDIJUFDUVSFEFTJHOFEGPSIJHIMZDSJUJDBMBQQMJDBUJPOT
TVDIBTEBUBDFOUFST
JOEVTUSZFOWJSPONFOUT
JOGSBTUSVDUVSF
BOECVJMEJOHT
*OUFMMJHFOUFOFSHZNBOBHFNFOUPGUIFTFTZTUFNTJTFOBCMFECZ
4DIOFJEFS&MFDUSJD&DP4USVYVSF™JOUFHSBUFEIBSEXBSFBOETPGUXBSFTZTUFN
BSDIJUFDUVSF4USVYVSF8BSF™TPGUXBSFBQQMJDBUJPOTBOETVJUFTBSFBLFZ
FMFNFOUPGUIF&DP4USVYVSFBSDIJUFDUVSF4USVYVSF8BSFTPGUXBSFIFMQT
NBYJNJ[FTZTUFNSFMJBCJMJUZBOEPQUJNJ[FPQFSBUJPOBMFGýDJFODZ
4USVYVSF8BSFGPS%BUB$FOUFSTTPGUXBSFDPMMFDUTBOENBOBHFTSFBMUJNF
JOGPSNBUJPOBCPVUBTTFUT
SFTPVSDFVTF
BOEPQFSBUJPOTUBUVTUISPVHIPVUUIF
EBUBDFOUFSMJGFDZDMF5IJTEBUBDFOUFSJOGSBTUSVDUVSFNBOBHFNFOU %$*.
TPGUXBSFGVMMZJOUFHSBUFTUIF.(&(BMBYZ6148JUIGVMMTZTUFNWJTJCJMJUZ
NBOBHFSTDBONPOJUPSBOEBQQMZUIJTJOGPSNBUJPOJOPSEFSUPPQUJNJ[FEBUB
DFOUFSQFSGPSNBODFUPNFFU*5
CVTJOFTT
BOETFSWJDFPSJFOUFEHPBMT
].(&(BMBYZ
Technical Specifications
Bypass AC input
Input voltage range (380 V, 400 V, 415 V, 440 V(6) ) +/- 10%
Frequency 50 Hz / 60 HZ +/- 10%
Output
Power factor up to 11
Phase-to-phase voltage setting 380/400/415 V/440 v, three-phase + neutral
Voltage regulation +/- 1%
Frequency 50 or 60 Hz +/- 0.1%
Permissible overloads 150% for 30 s, 125% for 10 minutes
Voltage distortion (THDU) < 2% Ph/Ph and Ph/N for non-linear loads
Battery
Number of battery chains managed Up to 2 circuit breakers
Type Sealed lead-acid, vented, Ni-Cd
Overall efficiency
Double conversion Up to 94.5%
ECO Mode Up to 99%1
Environmental conditions
Operating temperature Up to 40°C 3
Humidity Up to 95% (non-condensing)
Operating altitude Up to 1,000 m, without derating
Color RAL 9023
IP degree of protection IP20 Standard, IP32 Optional
Parallel configurations
Integrated parallel units Up to 8 units
Parallel modules with remote centralized static Up to 8 units
bypass switch4
Standards
Construction and safety IEC/EN 62040-1, IEC/EN 60950
Performance and topology IEC 62040-3 / VFI SS 111
Design and manufacture ISO 14001, ISO 9001, IEC 60146
EMC immunity IEC 61000-4
EMC emissions IEC 62040-2 C3
Approvals LCIE - CE Mark
Seismic compliancy(5) IEEE 693 High - Level 2 AC156 - Zone 1 & 2 GR63CORE
6
*OQVUWPMUBHFXJOEPX
ª4DIOFJEFS&MFDUSJD"MM3JHIUT3FTFSWFE4DIOFJEFS&MFDUSJD
"1$
BOE.(&(BMBYZBSFUSBEFNBSLTPXOFECZ4DIOFJEFS&MFDUSJD*OEVTUSJFT4"4PSJUTBGGJMJBUFEDPNQBOJFT"MMPUIFSUSBEFNBSLTBSFUIFQSPQFSUZPGUIFJS
SFTQFDUJWFPXOFSTFNBJMFTVQQPSU!BQDDPNt'BJSHSPVOET3PBE
8FTU,JOHTUPO
3*64"t@(."64
3ODQL¿FDFLyQ GH LQVWDODFLyQ
1RWD 3DUD WHQVLRQHV LQWHUIiVLFDV GH 9 \ XQD FDUJD FRQ XQ IDFWRU GH SRWHQFLD GH
(VSHFL¿FDFLRQHV GH EDWHUtD
7LSR %DWHUtD GH SORPR iFLGR %DWHUtD GH SORPR iFLGR 1L&DG
VHOODGD FRQ YHQWLODFLyQ
1~PHUR PtQPi[ GH
FHOGDV
7HQVLyQ ÀRWDQWH SRU FHOGD 9 9 9
7HQVLyQ ÀRWDQWH PtQPi[ 9 9 9 9 9 9
7HQVLyQ GH LJXDODFLyQ SRU 1R DSOLFDEOH 9 9
FHOGD
7HQVLyQ DPSOL¿FDGRUD SRU 1R DSOLFDEOH 9 9
FHOGD
7HQVLyQ PtQ SRU FHOGD 9 9 9 9 9
&RUULHQWH GH UHFDUJD [ & [ & &
Efficiency Details
System 25% load load 50% 75% load 100% load
250 kVA 400 V 89.7 93.2 93.8 93.8
*DOD[\9;
+LJKO\(IILFLHQW )OH[LEOH2SHUDWLQJ0RGHV
/RZ2ZQHUVKLS&RVWV 6FDODEOH
,QWHUQDO5HGXQGDQF\ 0RGXODU'HVLJQ
+LJKO\HIILFLHQWVFDODEOHSKDVHSRZHU
SURWHFWLRQZLWKIOH[LEOHRSHUDWLQJPRGHVIRU
ODUJHIDFLOLWLHVGDWDFHQWHUVDQGEXVLQHVV
FULWLFDODSSOLFDWLRQV
*DOD[\9;2YHUYLHZ
N:1
Symmetra PX
Scalable from 16 kW to 500 kW. Parallel-capable up to 2,000 kW.
High performance, right-sized, modular, scalable, three-phase
power protection with ultra-high availability and efficiency for
any size data center or high density power zone
The APC Symmetra™ PX UPSs are world-class, redundant, scalable, high-efficiency power protection
systems designed to cost effectively provide high levels of availability. Seamlessly integrating into today’s
state-of-the-art data center designs, the Symmetra PX UPSs are true modular systems. The Symmetra
PX UPS is built from swappable modules - power, battery, intelligence, and bypass - all engineered into a
design that is easily and efficiently serviceable. This architecture can scale power and runtime as demand
grows or as higher levels of availability are required.
The Symmetra PX family serves as the core power train that drives APC InfraStruxure™ systems for small,
medium, and large data centers. Highly manageable, each Symmetra PX offer features self-diagnostic
capabilities and standardized modules which mitigate the risk of human error, resulting in increased
overall data center reliability. Optional N+1 module-level redundancy further enhances power protection
and peace of mind without increasing the footprint of your power protection solution.
The Symmetra PX family delivers high availability, extreme agility, and low TCO in an aesthetic form factor.
With industry-leading power density, the Symmetra PX has the ability to fit seamlessly onto the data
center floor or into the back room. Other features include automated predictive diagnostics and advanced
battery management which lead to a highly predictable, efficient, and simplified UPS architecture.
Symmetra PX features
Availability Total Cost of Ownership
4XBQQBCMFQPXFS
CBUUFSZ
BOEJOUFMMJHFODF 6OJUZQPXFSGBDUPSDPSSFDUFE L8L7"
NPEVMFT
5Ã7WFSJýFEFGýDJFODZSBUJOHT
"VUPNBUJDJOUFSOBMCZQBTT
*OUFMMJHFOUCBUUFSZNBOBHFNFOU
4FMGEJBHOPTJOH
ýFMESFQMBDFBCMFNPEVMFT
0OFZFBSXBSSBOUZBOETUBSUVQTFSWJDFJODMVEFE
3FEVOEBOUJOUFMMJHFODFNPEVMF
Manageability
4XBQQBCMFTUBUJDCZQBTTTXJUDI /FUXPSLNBOBHFNFOUJODMVEFE
$POýHVSBCMFGPS/PS/NPEVMFMFWFM 3FNPUFBDDFTTUPTZTUFNEBUBPWFS)551
SFEVOEBODZ )5514
5FMOFU
44)
BOE4/.1 W
5PPMMFTTNPEVMFSFQMBDFNFOU 4FDPOEBSZ/FUXPSL.BOBHFNFOU
.PEVMFTGFBUVSFMFTTUIBONJOVUFBWFSBHF $BSETVQQPSUFE
NFBOUJNFUPSFQBJS .553
$POýHVSBCMFBMBSNOPUJýDBUJPOT
Scalability 4USVYVSF8BSF™%BUB$FOUFS&YQFSUDPNQBUJCMF
&YUFOEFECBUUFSZSVOUJNFBWBJMBCMF
4NBSU4MPU™ESZDPOUBDUFOWJSPONFOUBMPSCVJMEJOH
4DBMBCMFQPXFSNPEVMFT NBOBHFNFOUTZTUFNDBSET
4XBQQBCMFCBUUFSZNPEVMFT
"FTUIFUJD/FU4IFMUFS™GPSNGBDUPS
2 | Symmetra PX
Symmetra PX 48 kW
2
Features
t"EBQUBCMFUPL8QPXFSDBQBDJUZ
XJUIUIF
PQUJPOPG/SFEVOEBODZVQUPL8PS/
SFEVOEBODZVQUPL8
t&NCFEEFENPEVMBSQPXFSEJTUSJCVUJPO
t%VBMNBJOTJOQVU UPQPSCPUUPNGFFE
t1PXFS7JFX™EJTQMBZJOUFSGBDF"OFBTZUPSFBE-$%
TDSFFOBMMPXTZPVUPWJFX614
CBUUFSZ
BOEQPXFS
EJTUSJCVUJPOTUBUVTBOEDPOýHVSFTFUUJOHT
2 Power modules
L8QPXFSNPEVMFTTVQQMZQFSDFOU
FGýDJFODZEPXOUPQFSDFOUMPBEJOH
SFEVDJOH
QPXFSBOEDPPMJOHDPTUT
3 Battery modules
4XBQQBCMFCBUUFSZNPEVMFTGFBUVSFBEWBODFE
CBUUFSZNPOJUPSJOHBOEUFNQFSBUVSF
Scalable to 48 kW
DPNQFOTBUFECBUUFSZDIBSHJOHUIBUFYUFOET
CBUUFSZMJGF
.BOBHFNFOU$BSE t0OTJUFXBSSBOUZFYUFOTJPO
t'$$"
t&YUFOEFESVOUJNFCBUUFSZ t"EWBOUBHFQMBOT
t&/*&$
GSBNFT"EEVQUPGPVSMJOFVQ
BOENBUDICBUUFSZGSBNFTUP
FYUFOESVOUJNF
]4ZNNFUSB19
Symmetra PX 96/160 kW
Features
t"EBQUBCMFUPL8PSL8QPXFSDBQBDJUZ
XJUIUIFPQUJPOPG/SFEVOEBODZVQUPPS
L8
PS/SFEVOEBODZVQUPL8PSL8
1
t0QUJPOBMUISFFJOPOFNPEVMBSQPXFSEJTUSJCVUJPO
FODMPTVSFXJUINBJOUFOBODFCZQBTTBOENPEVMBS
CBUUFSJFT
t%VBMNBJOTJOQVU UPQPSCPUUPNGFFE
t1PXFS7JFXEJTQMBZJOUFSGBDF"OFBTZUPSFBE-$%
TDSFFOBMMPXTZPVUPWJFX614
CBUUFSZ
BOEQPXFS
EJTUSJCVUJPOTUBUVTBOEDPOýHVSFTFUUJOHT
1 Power modules 3
L8QPXFSNPEVMFTTVQQMZQFSDFOU
FGýDJFODZEPXOUPQFSDFOUMPBEJOH
SFEVDJOH
QPXFSBOEDPPMJOHDPTUT 2 Scalable
2 Battery modules to 160 kW
#BUUFSZNPEVMFTGFBUVSFBEWBODFECBUUFSZ
NPOJUPSJOHBOEUFNQFSBUVSFDPNQFOTBUFE
CBUUFSZDIBSHJOHUIBUFYUFOECBUUFSZMJGF
Wall-mounted FYUFOTJPO
maintenance bypass DPOýHVSBUJPOTJOB
t'$$"
DPNQBDUGPPUQSJOUGPSUIF t"EWBOUBHFQMBOT
panel
FMFDUSJDBMSPPN"WBJMBCMF t&/*&$
300mm maintenance JOTFMFDUSFHJPOT
bypass panel DPOUBDUZPVS4DIOFJEFS
]4ZNNFUSB19
Symmetra PX 250/500 kW
Features
t4VQQPSUTVQUPGPVS614TJOQBSBMMFMXJUI
DVTUPNTXJUDIHFBS
Approvals
t1BSBMMFMBCMFGPSDBQBDJUZ .8
PSTZTUFNMFWFM tCE t6-
SFEVOEBODZ .8/
t6-
t&/*&$
t1BUFOUFEVMUSBIJHIFGýDJFODZ BU DMBTT"
t$4"$/P
MPBE
BUMPBE
t'$$QBSU
t/PS/NPEVMFMFWFMBOETZTUFNMFWFM t6-6-D-JTUFE
t&/*&$
SFEVOEBODZ
t&/*&$
t4XBQQBCMF
NPEVMBSCBUUFSJFTXJUI
JOUFHSBUFENPOJUPSJOH
t&OFSHZNPOJUPSJOHEJTQMBZTL8IPVUQVUPG Support and Service
FBDI614 Included: Optional:
t%VBMNBJOTJOQVU
UPQPSCPUUPNGFFE t0OFZFBSXBSSBOUZ t"TTFNCMZ
]4ZNNFUSB19
Symmetra PX 250/500 options
1BSBMMFM$BCMFT 5IJSEQBSUZ4XJUDIHFBS,JU
]4ZNNFUSB19
Modular Power Distribution Features
t4ZNNFUSB19L8GFBUVSFTBOPQUJPOBM
1PXFS%JTUSJCVUJPO6OJUXJUI.BJOUFOBODF#ZQBTT
1BOFMBOE#BUUFSJFTXJUIOPGPPUQSJOUQFOBMUZ
2
t4ZNNFUSB19JTDPNQBUJCMFXJUIUIF
"1$L8.PEVMBS3FNPUF1PXFS1BOFM
Modular RPP
3
5IFTPVSDFPGBNQFSBHFGPSUIFEJTUSJCVUJPO
IPVTJOH
UIFQPXFSCBDLQMBOF
UIFNBJODJSDVJUNPOJUPSJOH
CVT
BOEUIFTVQQPSUTUSVDUVSFGPSUIF1%.T&BDI
.PEVMBS311TIBSFTUIFTBNFCBTJDEFTJHO
XIJDI
FOBCMFTTJNQMFJOTUBMMBUJPOGPSBOZ1PXFS%JTUSJCVUJPO
.PEVMFTJOUPBOZ.PEVMBS311PGDPNNPOWPMUBHF
]4ZNNFUSB19
StruxureWare Data Center Expert
*OUIFEBUBDFOUFSFOWJSPONFOU
PVS4ZNNFUSB19614TBSFGVMMZNBOBHFEUISPVHI
4USVYVSF8BSFGPS%BUB$FOUFST
BOJOUFHSBUFETVJUFPGEBUBDFOUFSJOGSBTUSVDUVSF
NBOBHFNFOU %$*.
BQQMJDBUJPOT*UFOBCMFTCVTJOFTTFTUPQSPTQFSCZNBOBHJOH
UIFJSEBUBDFOUFSTBDSPTTNVMUJQMFEPNBJOT
QSPWJEJOHBDUJPOBCMFJOUFMMJHFODFGPS
BOJEFBMCBMBODFPGIJHIBWBJMBCJMJUZBOEQFBLFGýDJFODZUISPVHIPVUUIFFOUJSFEBUB
DFOUFSMJGFDZDMF4USVYVSF8BSFJTBLFZFMFNFOUPG4DIOFJEFS&MFDUSJD&DP4USVYVSF
BOJOUFHSBUFEIBSEXBSFBOETPGUXBSFTZTUFNBSDIJUFDUVSFGPSJOUFMMJHFOUFOFSHZ
NBOBHFNFOU
'MFYJCMFTFSWJDFQBDLBHFTPGGFSIBTTMFGSFFTZTUFNNBJOUFOBODFUPJNQSPWF
VQUJNFBUBQSFEJDUBCMFDPTU5IFTFQBDLBHFTQSPWJEFZPVSTZTUFNXJUIUIFDBSF
JUOFFETUPPQFSBUFNPTUFGýDJFOUMZXIJMFNJOJNJ[JOHEPXOUJNF5IF"EWBOUBHF
1MVT
1SJNF
6MUSB
BOE.BYBSFGVMMTFSWJDFQBDLBHFTUIBUJODMVEFUFDIOJDBM
TVQQPSU
QSFWFOUJWFNBJOUFOBODF
BOERVJDLPOTJUFSFTQPOTF3FTQPOTFUJNF
VQHSBEFTBSFBWBJMBCMF
3.4JTBOFDPOPNJDBMBOEFBTZUPVTF8FCCBTFETFSWJDFUIBUMFUTZPVRVJDLMZ
SFTQPOEUPFOWJSPONFOUBMPSTZTUFNDIBOHFT5SBJOFEUFDIOJDJBOTQSPWJEF
TFDVSFIPVSNPOJUPSJOHPGZPVSQIZTJDBMJOGSBTUSVDUVSFUPEJBHOPTFBOESFTPMWF
QSPCMFNTCFGPSFUIFZCFDPNFDSJUJDBM
Preventive Maintenance
1SFWFOUJWFNBJOUFOBODFPOTJUFFYBNJOBUJPOTPGZPVSDSJUJDBMTZTUFNTBSF
EFTJHOFEUPQSFWFOUQSPCMFNTCFGPSFUIFZPDDVSBOELFFQZPVSTZTUFNSVOOJOH
BUNBYJNVNFGýDJFODZ
*OUIFFWFOUPGBTZTUFNJTTVF
BO'4&XJMMBSSJWFPOTJUFCZUIFOFYUCVTJOFTT
EBZUPJTPMBUF
EJBHOPTF
BOEDPSSFDUUIFQSPCMFNJOBTMJUUMFUJNFBTQPTTJCMF
NJOJNJ[JOHEPXOUJNF6QHSBEFTUPFWFOGBTUFSSFTQPOTFUJNFTBSFBWBJMBCMF
]4ZNNFUSB19
Technical specifications
Symmetra PX 48 kW
Input
Grid system 3P + N + G
Voltage range 340 - 477 V @ full load
Frequency 50 Hz
Frequency range 40 - 70 Hz with 10 Hz/s slew rate
Power factor (PF) > 0.99 @ load > 25 %, > 0.95 @ load > 15%, > 0.90 @ load > 10%
I thd (full load) < 5%
Nominal input current 77 A @ 380 V, 73 A @ 400 V, 70 A @ 415 V
Maximum input current 84.4 A @ 380 V, 80.2 A @ 400 V, 77.3 A @ 415 V
Input current limit 98.3 A @ 380 V/400 V/415 V
Maximum input short-circuit level 30 kA
Ouput
Power rating 48 kW
Grid system 3P + N + G
Voltage (nominal) 380/400/415 V L-L
Nominal output current 73 A @ 380 V, 69 A @ 400 V, 67 A @ 415 V
Maximum output current (in bypass @ 110% overload) 91 A @ 380 V, 87 A @ 400 V, 83 A @ 415 V
Frequency 50/60 Hz bypass synchronized, 50/60 Hz +/-0.1% free running
Synchronized slew rate Programmable to 0.25, 0.5, 1, 2, 4, 6Hz/s
Overload (normal and battery operation) 150% for 60 seconds, 125% for 10 min, 100% continuous
V thd < 2% from 0 to 100% linear load, < 6% full non-linear load according to IEC/EN 62040-3
Load PF From 0.5 leading to 0.5 lagging without any derating
Bypass
V nominal 380 V/400 V/415 V
Voltage (range) +/-10% from selected voltage
Frequency (nominal) 50/60 Hz
Frequency (range) +/-0.1 Hz, +/-3 Hz, +/-10 Hz (user–selectable)
Nominal input current 73 A @ 380 V, 69 A @ 400 V, 67 A @ 415 V
Maximum overload input current (125% continuous) 84.4 A @ 380 V, 80.2 A @ 400 V, 77.3 A @ 415 V
Efficiency
AC–AC at nominal mains t 95% at 35% - 100% load; t 90% @ 15% - 34% load
DC–AC at nominal battery voltage t 94% at 25% - 100% load; t 90% @ 15% - 24% load
Mechanical
Dimensions (HxWxD) 1,991 x 600 x 1,070 mm
Weight 796 kg
Environmental
Storage temperature, UPS, and batteries -15 to 40 °C with batteries, approximately 6 - 8 months @ 25 °C battery self discharge,
1 - 2 months @ 45 °C
Operating temperature* 0 to 40 °C (32 to 104 °F)
Full load loss at nominal mains (BTU) 7,719
Regulatory compliance
CE, EN/IEC 62040-1-1, EN/IEC/UL 60950-1, EN 50091-2/IEC 62040-2 (class A), FCC15A, EN/IEC 62040-3
]4ZNNFUSB19
Technical specifications
]4ZNNFUSB19
Technical specifications
]4ZNNFUSB19
Technical specifications continued
Maximum (UPS with MBwD and Maximum (UPS with MBwD and
6 min battery runtime): 6 min battery runtime):
1,991 x 3,100 x 1,070 mm 1,991 x 5,200 x 1,070 mm
Weight Minimum (standalone UPS, no batteries): Minimum (standalone UPS, no batteries):
1,057 kg 1,722 kg
Maximum (UPS with MBwD Maximum (UPS with MBwD
and 6 min battery runtime): 4,509 kg and 6 min battery runtime): 8,336 kg
Environmental
Storage temperature, UPS only -30 to 70 °C (-22 to 158 °F)
Storage temperature, UPS, and batteries -15 to 40 °C (5 to 104 °F) Battery self discharge: approximately 6 - 8 months @ 25 °C;
1 - 2 months @ 45 °C
Operating temperature* 0 to 40 °C (32 to 104 °F)
Full load loss at nominal mains (BTU) 30,946 BTU/hr 61,893 BTU/hr
Regulatory compliance
UL Listed, ULc Listed, CE, EN/IEC 62040-2 (class A), FCC part 15, EN/IEC 62040-3, EN/IEC 62040-1-1, UL 1778, UL 60950-1, CSA C22.2 No. 107.3-05