Documentos de Académico
Documentos de Profesional
Documentos de Cultura
ORBITINDIA ENGINGEERING
CONSULTANCY SERVICES
DATE 23/10/2018
DOC.
CLIENT PARSOL CHEMICAL PVT LDT NO. 001
DESIGN BASIS REV.
PROJECT BIBSA UNIT-1 NO. 00
Page 2 of 27
C O N T E N T S
1. GENERAL REQUIREMENT
9. GROUNDING 12
17. INSTALLATION 37
Page 3 of 27
1. GENERAL REQUIREMENT
1.1 As a minimum, all instruments and enclosures in field shall be weatherproof as per IEC-60529 to
min IP-65. (This requirement is typical. May be accepted if deviated by Instrument Vendor )
1.2 All electronic/electrical instruments and equipment’s shall be suitable for area classification as per
IEC codes and shall be tested by any recognized authority like CENELEC, ATEX, CMRI, ERTL
etc. and shall be certified by PESO/CCOE Nagpur in India. (Check if Process Material is
Hazardous)
Glossary Units
Area m²
Density kg/m³
Energy, electrical kWh
Energy, mechanical kJ
Energy, thermal kJ [BTU]
Length m (mm for dimensions / inch for piping)
Level mm or m, %
Mass kg or t (ton)
Moment torque Nm
Power kW
Flow, mass kg/h
Flow, volumetric m³/h or m³ (n)/h (*) [SCFD]
Frequency Hz
Pressure (absolute), fluid bar a
Pressure (relative), fluid bar g
Pressure, barometric mbar
Pressure, differential bar or mbar
Sound level dB (A)
Temperature °C (Celsius)
Time h (Hours), min (Minutes), s (Sec)
Velocity m/s
Viscosity, absolute, dynamic cP (centipoise)
Voltage V (Volt)
Volume m³ or m³ (n) (*)
Wobbe Index MJ/Sm³ [Btu/Scf]
1.4 Ranges for instruments shall be selected in general, such that in normal process operation the
indication is between 40% and 60% of span for linear and between 60% and 80% of span for
square root inputs. Ranges for process switches, if used, shall be selected, in general, such that
the set point falls preferably in the middle 30% of full adjustable range i.e. the set point shall fall
between 35% and 65% of adjustable range.
1.5 All process switches shall be provided with hermetically sealed contacts rated for the specified
application. Contacts shall be SPDT type unless otherwise specified. Intrinsic Safe switches shall
have gold plated contacts
1.6 Accuracy of various types of instruments used shall be as per below table:
Page 4 of 27
TYPE OF INSTRUMENT ACCURACY REPEATABILITY
Page 5 of 27
5.7 Electronic transmitters shall generally be two wire type. These shall have transmission/output
signal of 4-20 mA DC + HART and shall be capable of delivering rated current into external load
of at least 600 ohms when powered with 24 V DC nominal voltages.
1.8 All electronic instruments requiring separate power supply, shall generally operate on 230 VAC,
50 Hz. Instruments operating at 24 V DC shall also be acceptable.
1.9 Smart transmitters shall be used in analog mode only unless otherwise specified.
5.10 All electronic transmitters shall be provided with sunshade made of GRP material. ( Not required
as Instruments will be installed inside Building )
5.11 All tubes sizes used shall be preferably of metric sizes. Impulse tube shall be 6 mm OD or 12mm
OD, 316 stainless steel, seamless tubes as a minimum.
5.12 All tube fittings shall be flare-less compression type three piece construction design
5.14 All Electronic Transmitter housing shall be Die cast Aluminum, Epoxy painted.
6.1 All intrinsic safety barriers shall be active type isolating barriers only. Zener barriers shall not be
used.
6.2 Barriers must be selected based on entity concept. Cable parameters shall also be considered
while matching entity parameters.
7.1 Power supply shall be made available at the following voltage levels, unless otherwise specified:
Panel /cabinets lighting, Fan, Utility Socket 230V AC ± 10% (NON-UPS), 1 Phase
For Solenoid valves 24V DC through
7.3 All instruments, Control Systems (PLC and DCS) and analyzer system shall be able to operate at
the following UPS specification:
Voltage level 230 VAC ± 10%
Frequency 50 Hz ± 1%
7.4 For Instruments requiring external 230V AC power, power circuits shall be individually protected
from fault with the help of Miniature Circuit Breakers (MCBs).
8. CONTROL SYSTEMS
8.1 Control and monitoring function of field instruments shall be done by DCS / PLC system from
Main Control Room.
Page 6 of 27
8.4 Redundancy philosophy for DCS/PLC shall be as follows:
[x] Controllers:
[x] CPU Redundant
[x] Process input/output card back-up [x] Redundant I/Os for closed loops & I/O
related to
[x] Non-Redundant I/Os for rest
(i) Type
[x] PLC Based [ ] Through DCS / PLC
(iii) Interface
[x] Serial Link with PCS [x] Hardwired Interface with DCS/PLC
(As Required)
9. GROUNDING
9.1 All control room mounted panels (including panel mounted bulk supply earth) shall be connected
to the ‘Body Ground’ bus which is isolated from 'AC mains earth'. The total resistance of system
ground shall be less than 5Ω unless otherwise recommended by system manufacturer.
9.2 All circuit grounds, shields, drain wires and safety barriers (if used) shall be secured to 'Safety
Ground' which is isolated from 'AC mains earth’. This bus shall typically be 25 mm wide and 6
mm thick, made of copper. The resistance of ‘Safety Ground’ shall be less than 1Ω.
9.3 All field mounted panels, shelters, instruments, JB’s, carrying voltage more than 24 V shall be
connected to 'AC mains earth'.
9.4 Shield wires of all instruments will be connected to Control room end only. The Instrument side
shield shall be properly cut and insulated ensuring that it does not touch to instrument casing or
cable gland.
9.5 Colour coding for grounding copper cable shall be Green / Yellow.
9.6 Instrumentation grounding system at Control building shall be connected at two points to the
electrical earthing system.
10.1 The instrument connections installed on vessels, tanks, standpipes and piping shall be per
ANNEXURE-I.
10.2 Pneumatic instrument connections of ¼” NPT (F) shall be used for signal and air supply. ½” NPT
(F) connection may be used where ¼” NPT (F) is not sufficient.
Page 7 of 27
11. CABLING PHILOSOPHY
11.1 Instrumentation Cables shall be laid in trays for above ground installation. Tray Material shall be
galvanized. .
11.2 MCT Block – For cable entry in Control Room. ( Check if Required )
11.3 Cables
11.3.1 All cables shall be flame retardant low smoke (FRLS) as per IEC 60332 Part III, Cat. A. All Fire
resistant cables shall be as per IEC 331 Cat. A.
Page 8 of 27
11.3.2 Instrument signal cables shall be polyvinyl chloride (PVC) insulated and PVC sheathed cables of
rated voltage 300/500 V with primary insulation of 85°C PVC as per IS-5831 Type –C.
11.3.3 For signal and control cables, inner jacket Colour shall be black. Outer jacket Colour shall be light
blue for intrinsically safe application and black for others.
11.3.4 All multi pair cables shall have 6 pair / 12 pairs while multitriad cable shall have 6 triads / 8 triads.
11.3.5 All power supply cables shall be as per IS-1554 Part I. Minimum conductor size shall be 2.5 mm 2.
All these cables shall be PVC insulated and armoured (Check if armoring is required ?) and
FRLS.
11.4.1 Separate junction boxes and cables shall be considered for following:
11.4.2 Junction Boxes used for terminating intrinsically safe signals, shall be Ex ’e’ certified suitable for
Zone-1, Gr. IIA, T4. JBs shall be made of SS316 material (Material to be decided ). Plate
thickness shall be min 2 mm.
In general, multi-pair cable entry for 6 Pair / 6 Triad JB shall be 1” ET with check nut & for 12-
Pair / 8 Triad JB, it shall be 1 ½” ET with check nut.
11.4.3 Junction Boxes used for terminating non-intrinsically safe signals, shall be Ex ’d’ certified suitable
for Zone-1, Gr. IIA, T4. JBs shall be made of SS316 material. In general, multi-pair cable entry for
6 pair / 6 triad jb shall be 1” NPT (F) & for 12-pair / 8 triad jb, it shall be 1 ½” NPT (F).
11.4.4 The junction boxes shall be weatherproof to IP-65. (Deviation from Vendor shall be acceptable)
11.4.5 Each JB shall be provided with 2 multi-cable entries with one entry plugged with weather-proof /
Ex-proof plugs as required.
11.4.6 All spare cable entries shall be provided with suitable weatherproof / Exproof plugs as required.
11.4.7 Cable entries shall be from bottom, for all cables (multi-pair & single pair).
11.4.8 All cable glands shall be of SS304 for on-shore application & SS316 (Material to be decided ).
11.4.9 All cable glands shall be weatherproof to IP65 for on-shore area & IP-66 for off-shore area. For
flameproof application cable glands shall be provided with CMRI certification / CCOE approval
along with weatherproof certification.
Engineering Spares for all control systems & construction materials shall be provided as per
guidelines provided in respective specifications.
Page 9 of 27
12.2 Mandatory Spares:
Mandatory spares for each instrument & system shall be as per mandatory spare parts philosophy
A list of Recommended Spares for two years operation for all the applicable items shall be
provided by vendor.
13. INSTRUMENT AIR DISTRIBUTION
13.1 Instrument air distribution shall generally be through instrument air manifold fabricated from 1”
pipe with isolation and drain valves. Where the instruments are located sparsely, the branch way
may be applied. 10% spare connections shall be provided in each manifold.
13.2 Each instrument using air shall be equipped with its individual isolating valve.
13.3 Air distribution manifold, isolating valves, tubing fittings shall be of min. SS316.
15.1 All pressure / differential pressure instruments shall be provided with 2-way / 5-way manifolds as
per the installation standards, and shall have accessibility. All primary piping / tubing (impulse
lines) shall have a slope of 1 in 10 on the horizontal run.
15.4 Mounting of instruments / JB on the stanchion or instrument support shall generally be at the
height of 1.3 mars form the grade level / finished floor level.
15.5 Extension in the impulse piping/tubing of suitable length may have to be provided for those
instruments installations where process fluid temperature is higher / lower (Cryogenic services)
than the maximum withstanding temperature of the instrument/diaphragm.
15.6 All direct mounted instruments like thermowells for RTD / temperature gauge, pressure gauges;
pressure switches etc. shall be installed in such a way that they have good readability and
accessibility.
15.7 All the cables entering in Field Instrument / Central Control Rooms shall be through MCT.
15.8 All tubes/branch cables shall be properly laid on cable trays which shall be supported at 1.5 m
intervals.
15.10 The capillary of all capillary type instruments shall be supported properly and shall be protected
against mechanical damage.
D/P type flow meters employing square edged concentric orifice plates shall normally be used
where the piping sizes are 2 inches and larger.
(ii) Materials
[x] 316 SS
[ ] 304 SS
Tag number, diameter (mm) of orifice, nominal pipe size (in), flange rating, materials and
UPSTREAM (or “UP”) shall be engraved on the upstream face of the tab handle.
The minimum upstream and downstream straight lengths required for installation of
orifice shall be as specified in the P&IDs. Where it is not available in P&IDs, the values
without parentheses ("zero additional uncertainty" values) given in ISO 5167 part 2 for
Orifice plates shall be followed to the extent possible.
16.1.2 Variable Area Flowmeters (Rotameters)
Page 11 of 27
(i) [x] Rangability of more than 4:1 is required
(ii) [x] Local indication/control is required
(iii) [x] Nature of fluid, such as viscous and crystallizing
(3) Body
(i) Type
[x] Metal tube type
[ ] Glass tube type (only non-critical flows, e.g. purge, seal, flushing etc.)
(5) Protections
(1) Differential pressure instruments shall be the standard level transmitters for process
control applications.
(2) Other types of level instruments such as electrical capacitance, ultrasonic or radar type
may be used for special applications.
(3) All external level instruments, individual connected or flanged connected, shall be
equipped with isolation valves (each level measurement must be equipped with its own
process valve), drain and vent connection if required.
Page 12 of 27
16.2.3 Other type level instruments
Other type level instruments such as ball float type level switches with external float chamber,
float or displacement type tank gauges, capacitance type, Radar, Ultrasonic type etc. shall be
considered individually to the service conditions.
(1) Type
(i) [ ] Transparent
(ii) [x] Magnetic
(2) Installation
(3) Specifications
(c) [x] Large chamber type for liquids that vaporize or condense rapidly
at ambient temperature.
(v) Material of Body chamber / flange: [x] As per Piping Spec or equivalent
(vi) Overlapping Range [x] 50 mm visible length for staggered level gauges
(2) Connections
(6) Protections
(ii) Over range protector (gauge saver) shall be provided where a pressure gauge
shall not withstand to a protuberant pressure due to unavoidable operation.
(iii) Pulsation dampener shall be provided for pulsating services (discharge piping of
reciprocating pumps and compressors).
(iv) Diaphragm protection shall be used where necessary to protect gauges from
corrosive fluid, crystallizing fluid, fluid including solids and high viscous fluid. The
connection size and the material shall be as follows:
(a) Connection : [x] Flanged : [x] 2in. [ ] 3in.
[ ] Screwed : [ ] 1/2 in.
(b) Materials :
Diaphragm : [x] 316 SS or better
Flange : [ ] As per Piping Spec or equivalent
Capillary : [ ] Refer to par. 2.4.3 (2) (I)
Page 14 of 27
Small pressure gauges equipped for pneumatic instruments e.g. valve positioners, air
filter regulators etc. shall normally be specified by the manufacturer who supplies the
parent-instrument.
In general, the gauges shall be provided for each process heater to measure draft at the
burners, and in the stack, if required by the process. The type of gauges shall be as
follows:
[ ] Vertical case and flush mounting type
[ ] Horizontal case and flush mounting type
[ ] Dial gauge type
[ ] Flush mounting type
[ ] Wall mounting type
(1) In general, pressure switches shall be avoided. Alarms / trips set limits shall be derived
from analog transmitters in control room.
(2) When pressure switch is used, materials and connections shall be the same specification
as pressure gauge.
(3) Types:
[x] Non-indicating type
[ ] Indicating type
[x] Adjustable set point : [x] 1 setter [ ] 2 setters (High and Low etc.)
: [ ] Fixed differential pressure
: [x] Adjustable differential pressure
(1) Pressure and DP transmitters shall be intrinsically safe and SMART type with HART
protocol, however used in analog (4-20 mA DC) output mode.
16.4.1 Thermowells
Temperature elements like thermocouples, RTD, bi-metallic sensor and liquid/gas filled sensor
shall be equipped with thermowell, except where they are not feasible to install in the service
such as skin temp. measurement, bearings of rotating machine, etc. The specifications shall be
as follows:
(1) Constructions:
[x] standard (Refer Annexure-II for standard Dwg)
[x] Drilled bar stock
(2) Connections:
[x] Flanged
Refer ANNEXURE-I for other details
Page 15 of 27
16.4.2 Resistance Temperature Detectors (RTD)
RTD (Pt 100 Ω at 0 °C) shall be considered as standard method of temperature measurement.
The elements shall be MgO insulated and metal sheathed type and shall be of three-wire system,
Duplex type. The applicable operating temperature range will be (-) 200 to 500 °C. Dual element
type probes are preferred. Both elements shall be isolated from each other & thermowell. Both
elements shall be wired upto terminals in element head. Only single element shall be wired to
transmitter
Note 4: For skin temperature monitoring, RTD type elements are considered. Other
measuring technologies are not considered.
16.4.3 Thermocouples
(1) Standard
[x] IEC 60584
[ ] ANSI MC 96.1
[ ] DIN 43710
[ ] BS 4937
(2) Thermocouples:
Thermocouples shall be used for temperature above 500 °C. Type ‘K’ thermocouple shall
be used. Thermocouples shall normally be of Magnesium Oxide (MgO) insulated and
metal sheathed type and the hot junction shall be ungrounded to the sheath. Dual
element type probes are preferred. Both elements shall be isolated from each other &
thermowell. Both elements shall be wired upto terminals in element head. Only single
element shall be wired to transmitter
(1) Type:
[x] Bimetal type
[x] Liquid/Gas filled type with temperature compensator (Note 5 & 6).
[x] Fixed angle type (for filled thermal system)
[x] Every angle type (for bimetallic)
Note 5. Filled thermal system temperature instruments shall be used where bi-metal
type is not feasible.
6. Mercury filled instrument shall not be used.
(2) Indicator:
[x] 100mm dial
Page 16 of 27
[ ] 150mm dial
[ ] Adjustable pointer
(3) Thermobulb:
[ ] Nickel plated brass bulb
[x] Stainless steel bulb
[x] Sliding union connection
[x] 1/2in. [ ] R [x] NPT (M)
Note 7: Manufacturer’s formula may be used in order to determine the suitable size after
purchase order.
Valve sizing and capacity shall normally be determined in consideration of the following
points.
Note 8: Maximum allowable sound level dBA measured at 1m from pipe surface and 1m
downstream of the valve outlet.
(1) Characteristic
(2) Materials
[ ] 304 SS
[x] 316 SS
[ ] Stellited seat face for erosive service 440B/C.S.S is used instead of Stellite but
not for corrosive fluid.
The following leakage class conformed to ANSI/FCI 70-2 shall normally be applied to
each type of valve.
Class Application
[ ]I : Manufacturer’s recommendation
[ ] II : Double ported valves or cage guided valves
[ ] III : Valves as determined by
Page 18 of 27
[x] IV : Single ported valves (Control valves)
[x] V : Metal Seated valves (On-Off valves)
[x] VI : Soft seated valves (On-Off valves)
Note 9: Allowable leakage class shall be as per process specific requirements.
16.7.8 Bonnets
(1) Valve actuators shall be pneumatic only. Motorized / Electrically operated actuators shall
not be used. Valve actuators shall normally be of spring diaphragm or piston type. All
actuators shall be adequate to fully stroke the valve under the maximum differential
pressure specified by the process requirements.
(2) The following air pressure shall normally be used to determine the actuator spring and/or
the size of actuator.
16.7.10 Handwheel
Page 19 of 27
[x] Emergency Shutdown Valves / On-Off Valves
[x] Control valves (As per P&ID)
Application [x] Used as the pilot valve to trip a shutdown valve On/Off valve
[ ] On-Off control valve in utility services (e.g. pilot gas, etc.)
(3) [ ] Other
[ ] Indian Boiler Regulations
16.8.2 Type
The valves shall normally be of direct spring loaded type and provided with full nozzle type. For
special service conditions, following types may be considered:
Page 20 of 27
[x] Packed lever
16.8.4 Materials
(1) Body:
(3) Spring
Input Output
[x] Closed circuit (Open at trip) Energized (De-energized at trip)
Page 21 of 27
[ ] Electro-mechanical relay
[x] PLC
[x] PCS
(3) Functions
(1) General
(ii) Construction:
[ ] Free-standing open type
[x] Free-standing closed type
(2) Dimensions
All of the internal wiring shall be completed at shop before shipment. The wiring manner
shall be as follows:
(ii) Terminals:
[x] Screwless compression ring type
[ ] Tubular screw terminal with pressure plate
(i) Markers for wires, tubes, terminals, connectors, switches, circuit breakers, panel
number etc. shall be permanently affixed on them.
Page 22 of 27
Local control panels will be similar to the specifications as described in par 16.10.1 except for the
following specifications:
(2) Type:
(1) Type:
[x] Conventional
[ ] Mini-DCS
[ ] Existing control room
16.11.6 Marshalling Boards with Terminal Block for external signal cable
[x] Yes
[ ] No
Page 23 of 27
(1) Operation room:
[ ] Pit [x] Free access floor
[ ] Overhead
(2) Terminals for external cable (except for multi-pin connector of system cable)
[x] Screwless compression ring type
[ ] Tubular screw terminal with pressure plate
17. INSTALLATION
Process tappings for instrument connected to piping, vessels, and equipment shall be as
specified in ANNEXURE-I, unless other special connections are required.
Page 24 of 27
[ ] Provided by other than instrument manufacturer
[ ] Fabricated at site
(2) Air set (air filter and regulator with output gauge) for locally mounted instruments
[x] Equipped with each instrument
(a) Materials:
[ ] Electrolytic zinc-coated steel plated and/or frames
[x] Hot dip galvanized steel plates and/or frames for on-shore
Page 25 of 27
(b) Protection cover: [x] Yes [ ] No
(ii) Trench/Trough
(a) Trench:
[ ] Concrete trench : [ ] with cover
[ ] Buried cable
(b) Trough:
[ ] Concrete trough : [ ] with cover
Com. Power
Signal cables cables cables
150
mm
[x] Tray:
[ ] with cover [x] without cover
Page 26 of 27
Signal Cables Electrolytic copper [x] PVC [x] FRLS
[x]- 4 to 20 mA [x] 1.5 conductor of 7 strands [x] PVC sheathed
[x]- Digital Input with each strand of [x] Al backed Mylar
[x]- RTD For Single pair / 0.43 mm dia. for 1.0 tape shield along with
Triad, Multitriad mm2 and 0.53 mm drain wire (individual
dia. for 1.5 mm2, and overall shield)
twisted pair [x] Armoured
[x] 1.0
[x] 1.5
For Multipair
Page 27 of 27