1008 kW, Tier 2, Chilled Water, 18115 ft
Facility Power
The facility power system provides power to all of the critical and non-critical
components within the datacenter. It consists of a single power path with N+1
UPSs, backed up by N+1 generators, to achieve a Tier 2 redundant
architecture.
The facility power system has a QED-2 switchboard with a 3200 amp main bus
that feeds both the IT space and facility cooling UPSs. One 1.4 MW Symmetra
MW UPS serves as the IT space UPS. A 60 kVA Galaxy 5000 UPS supplies
protected power to N+1 pumps. The main bus also feeds an I-Line facility
cooling distribution panel, providing power to N+1 chillers in the mechanical
DESIGN OPTIONS space. The power distribution architecture from the electrical space to the IT
This reference design can be modified as space utilizes a combination of LV power panels and the iBusway power
follows without a significant effect on the distribution system. The design can also support additional peripheral devices
like lighting, access control systems, and environmental monitoring and control
design’s performance attributes:
devices.
Add StruxureWare Power Monitoring Power meters integrate with (optional) StruxureWare Power Monitoring Expert
Expert to monitor power quality and allow for predictive maintenance & diagnostics of
the system.
Provision for load bank
Change UPS batteries Every component in this design is built and tested to the applicable ANSI,
(classic or modular batteries, NEMA, UL or IEEE standards.
short/ long backup times) Design details and schematics are available in the Engineering Package (see
Add/change standby generator options page 7).
(location, tank size, fuel type)
3 CHW
IT space UPS redundancy N+1
480V 4x 300kVA 225A, 480V, 65kA
Pumps
208/120V PMM IT space UPS runtime @ rated load 5 minutes
© 2014 Schneider Electric. All rights reserved.
Facility Cooling
The facility cooling design is comprised of a chilled water cooling system in the
IT space, integrated with a single chilled water loop with N+1 pumps in the
mechanical space and an N+1 packaged chiller outdoors. Altogether, they form
a Tier 2 redundant architecture.
The facility cooling contains three 700 kW air-cooled water chillers with axial
fans and a free-cooling system. Economization is achieved with dry coolers
integrated within the chiller to save energy during favorable outdoor conditions.
A thermal storage system is offered as an option to provide 5 minutes of
continuous cooling after a power outage or chiller restart.
DESIGN OPTIONS The piping architecture feeds room-based Uniflair chilled water CRAHs in the IT
space. It also feeds room-based Uniflair CRAHs in the electrical space. More
This reference design can be modified as information on the cooling configuration is provided in the IT space section of
follows without a significant effect on the this document.
design’s performance attributes: This design is instrumented to work with (optional) StruxureWare Cooling
Monitoring Expert.
Add StruxureWare Cooling
Design details such as dimensions, equipment placement, temperature set
Monitoring Expert
points, pipe sizing, flow rates, and pressure drops are available in the
Engineering Package (See page 7).
Packaged Chiller
700kW
System
bypass
Chemical dosing
pot
Packaged Chiller
700kW Chilled
Water
Supply
Buffer Tank
(optional)
IT Space
A single power distribution path from the electrical space powers the Tier 2 IT
space, consisting of 180 kW of critical cooling load and 1008 kW of critical IT
load, fed by busway in an N configuration.
336 NetShelter racks of an average 3 kW per rack density are arranged in a
highly scalable and adaptable “pod” fashion. Smaller starting loads can be
supported by making adjustments such as reducing the number of IT pods or
decreasing the capacity of the UPS. Likewise, larger loads can be reached by
using a “step and repeat” approach with this design as the baseline. This
flexibility drives efficiency and defers capital expenditure until needed.
Each pod is powered by two 225A iBusway power distribution lines. Each rack is
DESIGN OPTIONS configured with a metered rack-mount PDU to enable remote monitoring of the
This reference design can be modified as units for efficiency and capacity management.
follows without a significant effect on the Uniflair chilled water room-based CRAHs, in an N+1 configuration, control the
design’s performance attributes: removal of heat by monitoring the temperature in the room and the pressure in
the contained hot aisle.
Add environmental and security
The security of the room is maintained at multiple points. At the rack level,
management
Change rack options (tall, wide, access is controlled by a door lock and sensor. At the room level, security
deep) cameras are utilized for monitoring.
Change power distribution options Design details and schematics are available in the Engineering Package (see
(Rack PDU type: basic, switched) page 7).
Add StruxureWare Data Center
Expert
C C C
IT SPACE ATTRIBUTES
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
IT load 1008 kW
Input voltage 480 V
Supply voltage to IT 208 V
C
B
B
B
B
2
PMM PMM PMM PMM
IT floor space 11100 ft © 2014 Schneider Electric. All rights reserved.
B
B
B R R R R R R R R R R R R R R R R R R R R R
B R R R R R R R R R R R R R R R R R R R R R
B R R R R R R R R R R R R R R
B
B
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
R R R R R R R R R R R R R R R R R R R R R
C C
Design Attributes
OVERVIEW Value Unit
Target availability Tier 2 Tier
Annualized PUE at 100% load 1.65 / 1.46 / 1.54
Data center IT capacity 1008 kW
2
IT & facility floor space 18115 ft
Average density 3 kW/rack
FACILITY POWER Value Unit
Total amps (main bus) 3200 A
Input voltage (main bus) 480 V
Switchboard kAIC 65 kA
Power path Single
Generator redundancy N+1
IT space UPS capacity 1200 kW
IT space UPS redundancy N+1
IT space UPS runtime @ rated load 5 minutes
IT space UPS output voltage 480 V
Facility cooling UPS capacity 54/60 kW/kVA
Facility cooling UPS redundancy N
Facility cooling UPS runtime @ rated load 5 minutes
FACILITY COOLING Value Unit
Total cooling capacity 1400 kW
Input voltage 480 V
Heat rejection medium Chilled Water
Mechanical redundancy N+1
Outdoor heat exchange Air-Cooled, Packaged Chiller
Coolant supply temperature 59 F
Coolant return temperature 69 F
Storage tank size (optional) 5000 gallons
Ride-through time 5 minutes
Economizer type Water-Side
IT SPACE Value Unit
IT load 1008 kW
Input voltage 480 V
Supply voltage to IT 208 V © 2014 Schneider Electric. All rights reserved.
Control level: Experts, on site or remotely, can control process performance and
ensure business continuity in real time, while tracking energy consumption in a highly
critical and secure environment.
Operations level: Functional managers can optimize operations, energy, and assets
through smart analytical tools, often spanning multiple sites.
Enterprise level: C-level executives can drive their sustainability strategy efficiently,
choosing the best scenario that meets their business objective to conserve
enterprise-wide resources.
StruxureWare for Data Centers allows for flexibility when requirements and
implementation strategies change over time. StruxureWare software applications
and suites simplify integration time, improve reliability, enhance visibility to energy
information, and streamline operational efficiency.
>
© 2014 Schneider Electric. All rights reserved.
Demo:
Visit www.apc.com/software to learn more about StruxureWare for Data Centers!
Engineering Package
Bill of materials
One-line schematics
> Click here to register to receive the Engineering Package for this design, or email
ReferenceDesigns@Schneider-Electric.com.