KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV

BAY TRAFO#1 30 MVA

1 2 3 4 5
CIRCUIT BREAKER CIRCUIT BREAKER SPARE DIFFERENTIAL/ OVERCURRENT/
SF6 LOW SF6 LOW REF SEF
PRESSURE TRIPPING ALARM PROTECTION TRIP PROTECTION TRIP
6 7 8 9 10
DS/CB HV APPARATUS CB MOTOR SPRING CB HEALTHY TRIP 1&2 TRIPPING
MOTOR SUPPLY LOCAL CONTROL CHARGE OPERATION ALARM FROM 20KV
FAILURE
11 12 13 14 15
DC TRANSFORMER TRANSFORMER RELAY FAILURE SPARE
SUPPLY FAULT 1st FAULT 2nd
FAILURE STAGE STAGE
16 17 18 19 20
SPARE SPARE SPARE SPARE SPARE

ANNUNCIATOR YANG RELAY YANG


NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL BEKERJA
Circuit Breaker SF6 Low Terjadi kebocoran sampai
1 K 434 CB Trip
Pressure Tripping Tekanan Gas SF6 di bawah
Circuit Breaker SF6 Low Terjadi kebocoran sampai Warning Alarm stage 1
2 K 433
Alarm Tekanan Gas SF6 di bawah dan tidak bisa di Reset
3 Spare
Relay Differential Micom P632
4 Differential/REF Protection Trip K 1870 CB Trip
bekerja karena gangguan
K 1500,1871, Relay Over Current.Micom
5 Overcurrent/SEF Protection Trip CB Trip
1872.151 P122 bekerja karena gangguan
K 450 Salah satu MCB Supply 3 phase untuk Motor DS dan Spring
6 DS/CB Motor Supply Failure
K 472 DS atau CB trip pada Local control panel CB tidak bekerja
Control CB / DS trafo berubah pada posisi
7 HV apparatus local control CB / DS bekerja pada posisi lokal
lokal
CB Motor spring charge
8 Motor spring charge CB bekerja
operation
Adanya gangguan pada
9 CB Healthy Trip 1&2 Alarm K 4901-02 Putusnya Tripping Coil
rangkaian Tripping
Adanya kiriman Trip dari
10 Tripping from 20 kV K 4311 CB Trip
Penyulang / Incoming 20 KV
DC Terjadinya salah satu MCB DC CB dan DS Atau Tripping
11 K 271-3
Supply Failure Supply Trip.Pada Control panel. ES1001 Tidak dapat bekerja
12 Transformer fault 1st stage K 481-84 Memerlukan pengecekan ke Trafo Alarm

13 Transformer fault 2nd stage K 482 Terjadinya gangguan pada transformer CB Trip
14 Relay Failure Relay gagal bekerja
15 Spare
16 Spare
17 Spare
18 Spare
19 Spare
20 Spare

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI REGULATOR PANEL
BAY TRAFO#1 30 MVA

1 2 3 4 5
SPARE BUCHOLZ FAN CONTROL FAN AC HV / LV WINDING
ALARM SUPPLY FAILURE SUPPLY FAILURE TEMPERATUR
ALARM
6 7 8 9 10
BUCHOLZ OIL TEMPERATUR HV / LV WINDING PRESSURE RELIEF PRESSURE RELIEF
TRIP INDICATOR TEMPERATUR DEVICE DEVICE FOR
TRIP OLTC
11 12 13 14 15
OLTC PROTECTION COOLING FAULT VOLTAGE SPARE OIL TEMPERATURE
RELAY TRIPPING FAN MOTOR REGULATION ALARM ALARM
FAILURE TAP CHARGE
16 17 18 19 20
SPARE SPARE SPARE SPARE SPARE

RELAY YANG
NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA
BEKERJA

1 Spare
Warning Alarm stage 1
2 Bucholz Alarm K481 Adanya Gas / Udara Pada Trafo
dan tidak bisa di Reset
3 Fan Control Supply Failure K 486 Adanya Salah satu Fan Tidak Bekerja Alarm

4 Fan AC Supply Failure K 485 Suplai tegangan AC untuk Fan tidak ada Alarm
HV / LV WindingTemperatur Terjadinya kenaikan Temperatur
5 K 483 Alarm
Alarm pada Winding
Terdapatnya Udara Yang Sangat
6 Bucholz Trip K 4814 CB Trip
Besar pada main tank
Terjadinya kenaikan temperatur Circuit Breaker ketiga
7 Oil Temperatur Indicator K 4815
pada Oil yang cukup tinggi phasenya akan trip
HV / LV Winding Adanya temperatur pada
8 K 4816 CB Trip
Temperatur Trip winding yang sangat tinggi
Adanya tekanan udara di main tank yang
9 Presurre Relief Device K 4817 CB Trip
sangat Tinggi
Adanya tekanan udara di OLTC yang
10 Presurre Relief Device For OLTC K 4817 CB Trip
sangat Tinggi
OLTC Protection Relay Terjadinya gangguan pada
11 K 4818 CB Trip
Tripping Tap Changer
Cooling Fault Fan Motor Adanya Salah satu MCB
12 K 4805 Alarm
Failure Supply Untuk Fan Trip
Voltage Regulation alarm
13 K 4802 Tap Changer Di Posisi Auto Alarm
Tap Charge
14 Spare
Terjadinya kenaikan temperatur
15 Oil Temperature Alarm Alarm
pada Oil
16 Spare
17 Spare
18 Spare
19 Spare
20 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY LINE 1&2 PANARAN DAN TJ. KASAM

1 2 3 4 5
CIRCUIT BREAKER CIRCUIT BREAKER DISTANCE OVER CURRENT EARTH FAULT
SF6 LOW SF6 LOW PROTECTION PROTECTION PROTECTION
PRESSURE TRIPPING PRESSURE ALARM TRIP TRIP TRIP
6 7 8 9 10
CB POLE HV.APPARATUS CB SPRING CHARGE AUTORECLOSE SPARE
DISCREPANCY LOCAL CONTROL FAILURE SUCCES

11 12 13 14 15
SPARE SPARE DS / CB CB BLOCKING FOR DC SUPPLY
MOTOR SUPPLY MAINTENANCE FAILURE
FAILURE
16 17 18 19 20
CB HEALTHY TRIP 1&2 DEAD LINE TELEPROTECTION MCB VOLTAGE RELAI FAILURE
ALARM DETECTION FAILURE TRANSFORMER
FAILURE OPENED

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Circuit Breaker
1
Pressure Tripping Gas SF6 di bawah Supply Daya putus
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
2
Pressure Alarm Gas SF6 di bawah dan tidak bisa di Reset
3 Distance protection trip Main Protection Bekerja CB Trip

4 Over Current Protection trip Back Up Protection Bekerja CB Trip


Terjadinya Gangguan Phase - Ground
5 Earth Fault protection trip CB Trip
pada Winding
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
6 CB Pole Discrepancy
Circuit Breaker antara R,S,T Phasenya akan trip
7 HV.Apparatus Local Control CB & DS posisi local Indikasi
Alarm dan perlu tindak
8 CB Spring Charge Failure Spring Charge CB tidak bekerja
lanjut
9 Autoreclose succes Autoreclose bekerja dengan baik CB tidak trip

10 Spare

11 Spare

12 Spare
DS/CB motor Supply Salah satu MCB supply tiga phase untuk DS
13 Alarm
failure atau CB Trip pada Local Control Panel
14 CB Bloking for Maintenance Terjadinya Block Untuk Breaker Alarm
Terjadinya salah satu MCB DC Supply Trip CB dan DS atau Tripping
15 DC Supply Failure
pada Control panel tidak dapat bekerja
CB Healthy Trip 1 & 2 Adanya Gangguan pada
16 Putusnya Tripping Coil
Alarm Rangkaian tripping
Dead Line detection
17 Hilang Tegangan Line Alarm
failure
Distance protection tidak dapat memberikan
18 Teleprotection failure Komunikasi antara distance protection gagal
sinyal
Proteksi atau metering tidak
19 MCB Voltage trafo opened Salah satu MCB Trip Pada MK
dapat membaca tegangan
Alarm dan perlu tindak
20 Relay Failure Distance Block
lanjut
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
BUS COUPLER 150 KV

1 2 3 4 5
CIRCUIT BREAKER SPARE 110 V DC DC SUPPLY OVER CURRENT
SF6 LOW BATTERY CHARGER 110 V DC PROTECTION
PRESSURE TRIPPING FAULT FAULT OPERATED
6 7 8 9 10
AC SUPPLY SPARE SPARE HV APPARATUS CIRCUIT BREAKER
380 / 220 VAC LOCAL CONTROL SF6 LOW
PRESSURE ALARM
11 12 13 14 15
CB SPRING ISOLATOR AND CB RELAY FAILURE ON LOAD DC SUPPLY
CHARGE FAILURE MOTOR SUPPLY TRANSFER FAILURE
FAILURE ANOMALY
16 17 18 19 20
HEALTH 48 VDC 48 VDC SPARE SPARE
TRIP 1&2 ALARM DC SUPPLY BATTERY CHARGER
FAULT FAULT

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Circuit Breaker
1
Pressure Tripping Gas SF6 di bawah Supply Daya putus
2 Spare

3 110 V DC battery charger fault MCB 110 DC trip Hilang supply 110 V DC

4 DC supply 110 V DC fault Rectifier tidak bekerja

5 Over Current Protection operated Over current Protection Bekerja CB Trip


Terjadinya salah satu MCB AC Supply Trip CB dan DS atau Tripping
6 AC supply 380/220 VAC
pada Control panel tidak dapat bekerja
7 Spare

8 Spare

9 HV.Apparatus Local Control CB & DS posisi local Indikasi


Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
10
Pressure Alarm Gas SF6 di bawah dan tidak bisa di Reset
Alarm dan perlu tindak
11 CB Spring Charge Failure Spring Charge CB tidak bekerja
lanjut
Isolator dan CB motor Supply Salah satu MCB supply tiga phase untuk DS
12 Alarm
failure atau CB Trip pada Local Control Panel
13 Relay failure Relay gagal bekerja CB tidak trip

14 On load transfer anomaly DS Bus 1 dan Bus 2 "ON"


Terjadinya salah satu MCB DC Supply Trip CB dan DS atau Tripping
15 DC Supply Failure
pada Control panel tidak dapat bekerja
Health Trip 1 & 2 Adanya Gangguan pada
16 Putusnya Tripping Coil
Alarm Rangkaian tripping
Terjadinya salah satu MCB 48 VDC Supply Trip
17 48 VDC supply fault
pada Control panel
18 48 VDC battery charger fault MCB 48 VDC trip Hilang supply 48 V DC

19 Spare
20 Spare

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL
20 KV

1 2 3 4 5 6
INCOMING OUTGOING 1 OUTGOING 2 OUTGOING 3 OUTGOING 4 OUTGOING 5
SPARE AUTO RECLOSE AUTO RECLOSE AUTO RECLOSE AUTO RECLOSE AUTO RECLOSE
LOCK OUT LOCK OUT LOCK OUT LOCK OUT LOCK OUT
7 8 9 10 11 12
SPARE UNDER UNDER UNDER UNDER UNDER
FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY
FAIL FAIL FAIL FAIL FAIL
13 14 15 16 17 18
OVER OVER OVER OVER OVER OVER
CURRENT CURRENT CURRENT CURRENT CURRENT CURRENT
FAIL FAIL FAIL FAIL FAIL FAIL
19 20 21 22 23 24
EARTH EARTH EARTH EARTH EARTH EARTH
FAULT FAIL FAULT FAIL FAULT FAIL FAULT FAIL FAULT FAIL FAULT FAIL

25 26 27 28 29 30
DC SUPPLY DC SUPPLY DC SUPPLY DC SUPPLY DC SUPPLY DC SUPPLY
FAIL FAIL FAIL FAIL FAIL FAIL

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL

1 Incoming spare cadangan untuk incoming trafo


2 Outgoing 1 auto reclose lock out auto reclose bekerja pada outgoing 1 CB trip
3 Outgoing 2 auto reclose lock out auto reclose bekerja pada outgoing 2 CB trip
4 Outgoing 3 auto reclose lock out auto reclose bekerja pada outgoing 3 CB trip
5 Outgoing 4 auto reclose lock out auto reclose bekerja pada outgoing 4 CB trip
6 Outgoing 5 auto reclose lock out auto reclose bekerja pada outgoing 5 CB trip
7 Spare
8 Under frequency fail relay under frekwensi bekerja CB trip
9 Under frequency fail relay under frekwensi bekerja CB trip
10 Under frequency fail relay under frekwensi bekerja CB trip
11 Under frequency fail relay under frekwensi bekerja CB trip
12 Under frequency fail relay under frekwensi bekerja CB trip
13 Over current fail relay over current bekerja CB trip
14 Over current fail relay over current bekerja CB trip
15 Over current fail relay over current bekerja CB trip
16 Over current fail relay over current bekerja CB trip
17 Over current fail relay over current bekerja CB trip
18 Over current fail relay over current bekerja CB trip
19 Earth fault fail relay earth fault bekerja CB trip
20 Earth fault fail relay earth fault bekerja CB trip
21 Earth fault fail relay earth fault bekerja CB trip
22 Earth fault fail relay earth fault bekerja CB trip
23 Earth fault fail relay earth fault bekerja CB trip
24 Earth fault fail relay earth fault bekerja CB trip
CB dan relay atau Tripping tidak dapat
25 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
26 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
27 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
28 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
29 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
30 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY LINE 1&2 SEI BALOI

1 2 3 4 5
DISTANCE SPARE OVER GROUND BUSBAR
PROTECTIVE CURRENT FAULT LOCK OUT
OPERATED
6 7 8 9 10
LOCK OUT CB POLE SPARE SPARE SPARE
RELAY DISCREPANCY
OPERATED
11 12 13 14 15
AUTO AUTO CB SF6/ BAY DRIVING DISTANCE
RECLOSE RECLOSE PRESSURE HYD TROUBLE PROTECTIVE
IN PROGRES LOCK TROUBLE IN OPERATIVE
16 17 18 19 20
TELE CPD HEALTHY CONTROL MCB MK
PROTECTION MCB'S TRIP 1-2 SUPPLY FAILURE
TROUBLES FAILURE FAILURE

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Gangguan ditransmisi (main protec) Distance SHPM 101 ( F.21 ) K.1040 SHPM (F.21) Tekan tombol reset
3 Gangguan arus lebih di Transmisi MCGG 52 (F.50/51 Ph+N) K.1010 MCGG 52 (F.50/51 Ph+N) Tekan tombol reset
4 Gangguan arus ketanah (pohon/tower) MCGG 52 (F.50/51 Ph+N) K.1020 MCGG 52 (F.50/51 Ph+N) Tekan tombol reset
5 MVAJ 24 ( K.401 ) K.2003 & 2007 MVAJ 24 ( K.401 ) Diangkat benderanya
6 Terjadi gangguan lebih besar dari K.1030 & 4302
MVAJ 11 ( K.402 ) MVAJ 11 ( K.402 ) Tekan tombol reset
setting atau sudah 3 kali Reclose MCGG52
7 Salah satu CB trip R-S-T terlalu lama. Timer K.431 & di CB K.61 K.4320 Control panel Tekan tombol reset
11 CB trip dan masuk kembali (Reclose) LFAA 101 ( F.79 ) K.1060 LFAA 101 ( F. 79 ) Tekan tombol reset
12 Relay Auto Reclose perlu di HAR LFAA 101 ( F.79 ) K.1030 Control panel Tekan tombol reset
13 Tekanan Gas SF6 turun di CB K.9 - K.6 - K.5 K.4301-03-04 Control panel Tekan tombol reset
14 MCB di Box Kontrol DS ada yang trip MCB di Box Control DS K.4035 Box Control DS Tekan angka I di MCB
15 Power Supply R. Distance tidak ada Distance SHPM 101 ( F.21 ) K.1050 Distance SHPM 101 ( F.21 ) Tekan tombol reset
16 Gangguan pada Telekomunikasi Telkom K.4315 Control panel Tekan tombol reset
17 MCB MK di serandang ada yang trip MCB di MK K.4311 & 4310 MK di Serandang Naikkan MCB yang trip
18 Triping Coil CB putus / rusak MVAX 31 ( TCS. 1-2-3-4-5-6 ) K.4901 & 4902 Control panel Tekan tombol reset
19 MCB di Kontrol panel ada yang trip MCB trip di Kontrol panel K.271 s/d K.275 Di Kontrol panel Naikan MCB yang trip
20 MCB MK diserandang ada yang trip MCB di MK k.4312 MK di Serandang Naikan MCB yang trip

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL OLTC 150 KV
BAY TRAFO#1

1 3 5 7 9
OIL LEVEL OIL LEVEL BUCHOLZ WINDING OLTC L/R
TRANSFORMER OLTC ALARM TEMP SWITCH
LOW ALARM LOW ALARM ALARM LOCAL " ON "
2 4 6 8 10
BUCHOLZ WINDING PROTECTIVE OVER PRESS CIRCUIT
TRIP TEMP RELAY OLTC VALVE BREAKER
TRIP TRIP TRANSFOR. TRIP 20 KV OPEN

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

Di Trafo minyaknya kurang Cek trafo kalau bahaya Harus dicek team HAR
1 Relay oil Level K.4817
(Baru alarm belum trip) matikan dan laporkan Tambah minyak trafo
Suhu Trafo panas dan relay bucholz Cek trafo kalau bahaya Harus dicek team HAR
2 bekerja mentripkan Trafo Bucholz Relay di Trafo K.1110 matikan dan laporkan Buang gelembung udara
(ada gelembung udara karena panas)
Di OLTC minyaknya kurang Cek OLTC kalau bahaya Harus dicek team HAR
3 Relay oil Level K.4818
(Baru alarm belum trip) matikan dan laporkan Tambah minyak OLTC
Temperatur Trafo terlalu tinggi Harus dicek team HAR
4 Thermometer di Trafo K.1120-25 Panel OLTC kontrol
sehingga Trafo trip Tunggu suhu turun
Suhu Trafo panas relay bucholz Cek trafo kalau bahaya Harus dicek team HAR
5 bekerja alarm berbunyi belum trip Bucholz relay di Trafo K.4813 matikan dan laporkan Buang gelembung udara
(ada gelembung udara karena panas)
Relay pengaman OLTC bekerja Cek trafo kalau bahaya Harus dicek team HAR
6 Relay OLTC K.1130
Karena ada gangguan di OLTC matikan dan laporkan Cek OLTC
Temperatur Trafo Mulai Tinggi Cek trafo kalau bahaya Harus dicek team HAR
7 Thermometer di Trafo K.4814 & 4819
sehingga bunyi alarm dan belum trip matikan dan laporkan Tunggu suhu turun
Tekanan tinggi pada Valve Trafo
8 Relay Pressure K.1145 Panel OLTC kontrol Tekan tombol reset
sehingga Trafo trip
Saklar kontrol di MK OLTC Saklar kontrol di MK OLTC Di MK OLTC Rubah saklar kontrol
9 K.21
dirubah ke posisi lokal Dirubah ke posisi lokal ( Di Trafo ) ke posisi remotte
10 NOT USED NOT USED K.4860 NOT USED NOT USED

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY TRAFO#1

1 2 3 4 5
DIFFERENTIAL OVER CURRENT FIRE RESTRICTED PANEL 20 KV
PROTECTION PRIMARY PROTECTION EARTH FAULT INCOMING 3
NEUTRAL TRIP CB TRIP

6 7 8 9 10
TRAFO FAULT PANEL 20 KV PANEL 20 KV PANEL 20 KV PANEL 20 KV
TRIP INCOMING 1 INCOMING 2 INCOMING 4 INCOMING 5
CB TRIP CB TRIP CB TRIP CB TRIP

11 12 13 14 15
FIRE CB SF6/ HEALTHY BAY DRIVING TAP CHANGER
PROTECTION PRESSURE HYD TRIP 1 - 2 FAILURE TROUBLE
ALARM ALARM LOCK OUT
TROUBLE
16 17 18 19 20
TRAFO FAULT SPARE 20 KV CONTROL MCB MK
ALARM TROUBLES SUPPLY FAILURE FAILURE

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Ada gangguan di daerah Trafo MBCH 12 ( F.87 TR ) K.1010 MBCH 12 ( F.87 TR ) Tekan tombol reset
2 Gangguan arus lebih phase-phase MCGG 82 ( F.50/51 ) K.1020 MCGG 82 ( F.50/51 ) Tekan tombol reset
Gangguan arus lebih Neutral MCGG 22 ( F.50/51+ N ) K.1050 MCGG 22 ( F.50/51+ N ) Tekan tombol reset
3 Trafo sudah hampir terbakar Fire Protection K.1155 Box control fire protection Putar kunci OFF
4 Gangguan arus ke tanah MVAC 14 ( F.87 REF.1 & REF 2 ) K.1030 & 1040 MVAC 14 Diangkat benderanya
5 CB Incoming 3 Trip atau di OFF-kan SEPAM 2000 K.401-2 & 4860 SEPAM 2000 Tekan tombol reset
Relay Bucholz,Relay suhu dan K.1110-20-25-30 Di Trafo Relay bucholz dan Tekan tombol reset
6 Gangguan di Trafo CB trip
pressure relief K.1140-45-50 Pressure relief U/suhu tunggu turun
7 CB Incoming 1 Trip atau di OFF-kan SEPAM 2000 K.401-2 & 4860 SEPAM 2000 Tekan tombol reset
8 CB Incoming 2 Trip atau di OFF-kan SEPAM 2000 K.401-2 & 4860 SEPAM 2000 Tekan tombol reset
9 CB Incoming 4 Trip atau di OFF-kan SEPAM 2000 K.401-2 & 4860 SEPAM 2000 Tekan tombol reset
10 CB Incoming 5 Trip atau di OFF-kan SEPAM 2000 K.401-2 & 4860 SEPAM 2000 Tekan tombol reset
11 Suhu di Trafo terlalu tinggi Fire Protection K.4816 Control panel Tekan tombol reset
12 Tekanan Gas SF6 turun Di CB K.9 - K.6 - K.5 K.4301-03-04 Control panel Tekan tombol reset
13 Tripping Coil CB putus / rusak MVAX 31 ( TCS. 1-2-3-4-5-6 ) K.4901 & 4902 Control panel Tekan tombol reset
14 MCB di box Kontrol DS ada yang trip MCB di Box Control DS K.4035 Box Control DS Tekan angka I di MCB
15 MCB Box Tap canger trip di Trafo MCB Q1 dan Q11 Trip K.4812 Box Control Tap canger Naikkan MCB yang trip
16 Gangguan di Trafo Bunyi alarm Relay Bucholz,Relay suhu dan K.4811-13-14-15 Di Trafo Relay buchol dan Tekan tombol reset
( Belum trip-kan CB ) pressure relief K.4817-18-19 Pressure relief U/suhu tunggu turun
18 NOT USED NOT USED k.4870 NOT USED NOT USED
19 MCB di kontrol panel ada yang trip MCB trip di Kontrol panel K.271 s/d K.275 Di kontrol panel Naikan MCB yang trip
20 MCB MK di serandang ada yang trip MCB di MK K.4312 MK di Serandang Naikan MCB yang trip

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BUS COUPLER 150 kV

1 2 3 4 5
OVER GROUND CB SPARE SPARE
CURRENT FAULT TRIP

6 7 8 9 10
SPARE SPARE SPARE SPARE SPARE

11 12 13 14 15
SPARE ON LOAD CB SF6/ CPD BAY DRIVING
TRANSFER PRESSURE HYD MSB'S FAULT
ALARM LOCK OUT FAILURE
TROUBLE
16 17 18 19 20
PANEL 20KV SPARE SPARE CONTROL MCB MK
BUS COUPLER SUPPLY FAILURE
CB TRIP FAILURE

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Gangguan arus lebih MCGG 82 ( F.50/51 ) K.1020 MCGG 82 ( F.50/51 ) Tekan tombol reset
2 Gangguan arus ke tanah MCGG 82 ( F.50/51 Ph + N ) K.1021 MCGG 82 ( F.50/51 Ph + N ) Tekan tombol reset
Gangguan arus lebih Neutral MCGG 22 ( F.50/51+ N ) K.1050 MCGG 22 ( F.50/51+ N ) Tekan tombol reset
3 CB Trip dan Lock Out MCGG 82 ( F.50/51 ) MVAJ 24 (K.401) MVAJ 24 (K.401) Diangkat Benderanya
12 DS Bus 1 dan Bus 2 "ON" OLTX K. MM4XP Kontrol panel Tekan tombol reset
13 Tekanan Gas SF6 turun Di CB K.9-K.6-K.5 K.4301-03-04 Control panel Tekan tombol reset
14 MCB MK di Serandang ada yang trip MCB di MK K.4310 & 4311 Mk di serandang Naikan MCB yang Trip
15 MCB di box Kontrol DS ada yang trip MCB di Box Control DS K.4035 Box Control DS Tekan angka diMCB
16 NOT USED NOT USED NOT USED NOT USED NOT USED
19 MCB di kontrol panel ada yang trip MCB trip di Control panel K.271 s/d K. 275 Di kontrol panel Naikan MCB yang Trip
20 MCB MK di Serandang ada yang trip MCB di MK K.4312 Mk di serandang Naikan MCB yang Trip

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY TRAFO#2 30 MVA

1 2 3 4 5
CB SF6 CB SF6 CB MAIN BACK UP
LOW PRESSURE LOW PRESSURE POLE PROTECTION PROTECTION
TRIPPING ALARM DISCREPANCY OPERATED

6 7 8 9 10
BAY DRIVING HV APPARATUS MOTOR SPRING HEALTHY TRIPPING
FAULT LOCAL CONTROL CHARGE TRIP 1 & 2 FROM 20 KV
OPERATION ALARM

11 12 13 14 15
C1 / T1 / T2 / DC TRANSFORMER SPARE SPARE SPARE
SUPPLY FAULT
FAILURE 2ND STAGE

16 17 18 19 20
SPARE TRANSFORMER SPARE SPARE SPARE
ALARM
IST STAGE

ANNUNCIATOR YANG RELAY YANG


NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL BEKERJA
Circuit Breaker SF6 Low Terjadi kebocoran sampai
1 K 434 CB Trip
Pressure Tripping Tekanan Gas SF6 di bawah
Circuit Breaker SF6 Low Terjadi kebocoran sampai Warning Alarm stage 1
2 K 433
Alarm Tekanan Gas SF6 di bawah dan tidak bisa di Reset
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
3 CB Pole Discrepancy
Circuit Breaker antara R,S,T Phasenya akan trip
Relay Differential Micom P632
4 Main Protection K 1870 CB Trip
bekerja karena gangguan
K 1500,1871, Relay Over Current.Micom
5 Back Up Protection Operated CB Trip
1872.151 P122 bekerja karena gangguan
K 450 Salah satu MCB Supply 3 phase untuk Motor DS dan Spring
6 Bay Driving Fault
K 472 DS atau CB trip pada Local control panel CB tidak bekerja
Control CB / DS trafo berubah pada posisi
7 HV operated local control CB / DS bekerja pada posisi lokal
lokal
Spring charge
8 Motor spring charge CB bekerja
operation
Adanya gangguan pada
9 Healthy Trip 1&2 Alarm K 4901-02 Putusnya Tripping Coil
rangkaian Tripping
Adanya kiriman Trip dari
10 Tripping from 20 kV K 4311 CB Trip
Penyulang / Incoming 20 KV
C1/T1/T2 DC Terjadinya salah satu MCB DC CB dan DS Atau Tripping
11 K 271-3
Supply Failure Supply Trip.Pada Control panel. ES1001 Tidak dapat bekerja
12 Transformer fault 2nd stage K 481-84 Memerlukan pengecekan ke Trafo Alarm
13 Spare
14 Spare
15 Spare
16 Spare
17 Transformer fault 1st stage K 481-84 Memerlukan pengecekan ke Trafo Alarm
18 Spare
19 Spare
20 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI REGULATOR PANEL
BAY TRAFO#2 30 MVA

1 2 3 4 5
MAIN/OLTC OIL BUCHOLZ FAN CONTROL FAN ACHV / LV WINDING
LEVEL LOW ALARM SUPPLY FAILURE SUPPLY FAILURE
TEMPERATUR
ALARM
6 7 8 9 10
BUCHOLZ OIL TEMPERATUR HV / LV WINDING PRESSURE RELIEF PRESSURE RELIEF
TRIP INDICATOR TEMPERATUR DEVICE DEVICE FOR
TRIP OLTC
11 12 13 14 15
OLTC PROTECTION COOLING FAULT VOLTAGE FIRE PROTECTION OIL TEMPERATURE
RELAY TRIPPING FAN MOTOR REGULATION ALARM OUT OF DEVICE ALARM
FAILURE TAP CHARGE
16 17 18 19 20
SPARE SPARE SPARE SPARE SPARE

RELAY YANG
NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA
BEKERJA
Main / OLTC OIL
1 K 484 Terjadi Gangguan Pada OLTC CB Trip
Level Low
Warning Alarm stage 1
2 Bucholz Alarm K481 Adanya Gas / Udara Pada Trafo
dan tidak bisa di Reset
3 Fan Control Supply Failure K 486 Adanya Salah satu Fan Tidak Bekerja Alarm

4 Fan AC Supply Failure K 485 Suplai tegangan AC untuk Fan tidak ada Alarm
HV / LV WindingTemperatur Terjadinya kenaikan Temperatur
5 K 483 Alarm
Alarm pada Winding
Terdapatnya Udara Yang Sangat
6 Bucholz Trip K 4814 CB Trip
Besar pada main tank
Terjadinya kenaikan temperatur Circuit Breaker ketiga
7 Oil Temperatur Indicator K 4815
pada Oil yang cukup tinggi phasenya akan trip
HV / LV Winding Adanya temperatur pada
8 K 4816 CB Trip
Temperatur Trip winding yang sangat tinggi
Adanya tekanan udara di main tank yang
9 Presurre Relief Device K 4817 CB Trip
sangat Tinggi
Adanya tekanan udara di OLTC yang
10 Presurre Relief Device For OLTC K 4817 CB Trip
sangat Tinggi
OLTC Protection Relay Terjadinya gangguan pada
11 K 4818 CB Trip
Tripping Tap Changer
Cooling Fault Fan Motor Adanya Salah satu MCB
12 K 4805 Alarm
Failure Supply Untuk Fan Trip
Voltage Regulation alarm
13 K 4802 Tap Changer Di Posisi Auto Alarm
Tap Charge
Fire Protection Out Of
14 K 4810 Fire Protection Tidak diaktifkan Alarm
Dervice
Terjadinya kenaikan temperatur
15 Oil Temperature Alarm Alarm
pada Oil
16 Spare
17 Spare
18 Spare
19 Spare
20 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY LINE 1&2 SAGULUNG

1 2 3 4 5
CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CB POLE
FAILURE OF GAS CLOSING LOCAL CONTROL OPENING DISCREPANCY
PRESSURE ALARM INHIBITION ALARM POSITION ALARM INHIBITION ALARM ALARM
6 7 8 9 10
MOTOR SUPPLY CVT'S LINE DRIVING FAULT DISTANCE SOFT
HV APPARATUS FAILURE HV APPARATUS MAIN PROTECTION TRIP
FAILURE ALARM ALARM OPERATED
11 12 13 14 15
OC/EF TRIP CIRCUIT PROTECTIVE RELAY AUTORECLOSING BREAKER FAILURE
DIRECTIONAL OC/EF SUPERVISION FAILURE (WATCHDOG) COMMAND PROTECTION OPERATED
BACK UP PROTECTION OPERATED OPERATED ALARM ALARM
16 17 18 19 20
SPARE SPARE SUPPLY 380/220 VAC SPARE SUPPLY 110 VDC
HEATING AND LIGHTING C1/T1/T2 FAILURE
FAILURE ALARM ALARM

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
Circuit Breaker Failure of gas Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
1
Pressure alarm Gas SF6 di bawah dan tidak bisa di Reset
Circuit Breaker Closing CB tertutup dikarenakan
2 Alarm
Inhibition Alarm Adanya Gangguan
Circuit Breaker local control
3 CB posisi local Indikasi
Position Alarm
Circuit Breaker Opening CB terbuka dikarenakan
4 Alarm
Inhibition Alarm Adanya Gangguan
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
5 CB Pole Discrepancy alarm
Circuit Breaker antara R,S,T Phasenya akan trip
Motor Supply HV Apparatus Salah satu MCB supply tiga phase untuk DS
6 Alarm
failure alarm atau CB Trip pada Local Control Panel
7 CVT's line failure CVT rusak Alarm dan tegangan line tidak terbaca
Driving fault HV Apparatus Salah satu MCB Supply 3 phase untuk Motor DS dan Spring
8
alarm DS atau CB trip pada Local control panel CB tidak bekerja
9 Distance main protection operated Main Protection Bekerja CB Trip

10 SOFT trip
OC/EF, directional OC/EF
11 Back Up Protection Bekerja CB Trip
back up protection operated
Terjadi gangguan lebih besar dari
12 Trip circuit supervision operated alarm CB Trip
setting atau sudah 3 kali Reclose
Protective relay failure (watchdog)
13 Distance relay gagal bekerja gangguan meluas
alarm
14 Autoreclosing command CB Trip dan masuk kembali (Reclose) Alarm

15 Breaker failure protection operated CB gagal bekerja Alarm

16 Spare

17 Spare
Supply 380/220 VAC heating dan lighting Terjadinya salah satu MCB AC
18 Heating dan lighting tidak bekerja
failure alarm Supply Trip
19 Spare
Terjadinya salah satu MCB DC CB dan DS Atau Tripping
20 Supply 110 VDC C1/C2/T2 failure alarm
Supply Trip Tidak dapat bekerja
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 20 KV
MERK FLUARC

1 2 3 4 5
AUTO AUTO AUTO AUTO AUTO
RECLOSING RECLOSING RECLOSING RECLOSING RECLOSING

6 7 8 9 10
LOW LOW LOW LOW LOW
OVER CURRENT OVER CURRENT OVER CURRENT OVER CURRENT OVER CURRENT

11 12 13 14 15
HIGH HIGH HIGH HIGH HIGH
OVER CURRENT OVER CURRENT OVER CURRENT OVER CURRENT OVER CURRENT

16 17 18 19 20
LOW LOW LOW LOW LOW
EARTH FAULT EARTH FAULT EARTH FAULT EARTH FAULT EARTH FAULT

21 22 23 24 25
HIGH HIGH HIGH HIGH HIGH
EARTH FAULT EARTH FAULT EARTH FAULT EARTH FAULT EARTH FAULT

26 27 28 29 30
SEPAM / 110 V,DC SEPAM / 110 V,DC SEPAM / 110 V,DC SEPAM / 110 V,DC SEPAM / 110 V,DC
FAILURE FAILURE FAILURE FAILURE FAILURE

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL

1 Autoreclosing CB trip dan masuk kembali pada outgoing 1 Alarm


2 Autoreclosing CB trip dan masuk kembali pada outgoing 2 Alarm
3 Autoreclosing CB trip dan masuk kembali pada outgoing 3 Alarm
4 Autoreclosing CB trip dan masuk kembali pada outgoing 4 Alarm
5 Autoreclosing CB trip dan masuk kembali pada outgoing 5 Alarm
6 Low overcurrent Relay outgoing 1 bekerja akibat gangguan arus lebih yang kecil CB trip
7 Low overcurrent Relay outgoing 2 bekerja akibat gangguan arus lebih yang kecil CB trip
8 Low overcurrent Relay outgoing 3 bekerja akibat gangguan arus lebih yang kecil CB trip
9 Low overcurrent Relay outgoing 4 bekerja akibat gangguan arus lebih yang kecil CB trip
10 Low overcurrent Relay outgoing 5 bekerja akibat gangguan arus lebih yang kecil CB trip
11 High overcurrent Relay outgoing 1 bekerja akibat gangguan arus lebih yang besar CB trip
12 High overcurrent Relay outgoing 2 bekerja akibat gangguan arus lebih yang besar CB trip
13 High overcurrent Relay outgoing 3 bekerja akibat gangguan arus lebih yang besar CB trip
14 High overcurrent Relay outgoing 4 bekerja akibat gangguan arus lebih yang besar CB trip
15 High overcurrent Relay outgoing 5 bekerja akibat gangguan arus lebih yang besar CB trip
16 Low earthfault Relay outgoing 1 bekerja akibat gangguan ke tanah yang kecil CB trip
17 Low earthfault Relay outgoing 2 bekerja akibat gangguan ke tanah yang kecil CB trip
18 Low earthfault Relay outgoing 3 bekerja akibat gangguan ke tanah yang kecil CB trip
19 Low earthfault Relay outgoing 4 bekerja akibat gangguan ke tanah yang kecil CB trip
20 Low earthfault Relay outgoing 5 bekerja akibat gangguan ke tanah yang kecil CB trip
21 High earthfault Relay outgoing 1 bekerja akibat gangguan ke tanah yang besar CB trip
22 High earthfault Relay outgoing 2 bekerja akibat gangguan ke tanah yang besar CB trip
23 High earthfault Relay outgoing 3 bekerja akibat gangguan ke tanah yang besar CB trip
24 High earthfault Relay outgoing 4 bekerja akibat gangguan ke tanah yang besar CB trip
25 High earthfault Relay outgoing 5 bekerja akibat gangguan ke tanah yang besar CB trip
26 Sepam / 110 VDC failure MCB 110 VDC Supply Trip pada outgoing 1 Relay tidak bekerja
27 Sepam / 110 VDC failure MCB 110 VDC Supply Trip pada outgoing 2 Relay tidak bekerja
28 Sepam / 110 VDC failure MCB 110 VDC Supply Trip pada outgoing 3 Relay tidak bekerja
29 Sepam / 110 VDC failure MCB 110 VDC Supply Trip pada outgoing 4 Relay tidak bekerja
30 Sepam / 110 VDC failure MCB 110 VDC Supply Trip pada outgoing 5 Relay tidak bekerja
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 20 KV
MERK AREVA

1 2 3 4 5 6
INCOMING OUT GOING 1 OUT GOING 2 OUT GOING 3 OUT GOING 4 OUT GOING 5
SPARE AUTO RECLOSE AUTO RECLOSE AUTO RECLOSE AUTO RECLOSE AUTO RECLOSE
LOCK OUT LOCK OUT LOCK OUT LOCK OUT LOCK OUT

7 8 9 10 11 12
SPARE UNDER FREQUENCY UNDER FREQUENCY UNDER FREQUENCY UNDER FREQUENCY UNDER FREQUENCY
FAIL FAIL FAIL FAIL FAIL

13 14 15 16 17 18
OVERCURRENT OVERCURRENT OVERCURRENT OVERCURRENT OVERCURRENT OVERCURRENT
FAIL FAIL FAIL FAIL FAIL FAIL

19 20 21 22 23 24
EARTH FAULTH EARTH FAULTH EARTH FAULTH EARTH FAULTH EARTH FAULTH EARTH FAULTH
FAIL FAIL FAIL FAIL FAIL FAIL

25 26 27 28 29 30
DC SUPPLY DC SUPPLY DC SUPPLY DC SUPPLY DC SUPPLY DC SUPPLY
FAIL FAIL FAIL FAIL FAIL FAIL

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL

1 Incoming spare cadangan untuk incoming trafo


2 Outgoing 1 auto reclose lock out auto reclose bekerja pada outgoing 1 CB trip
3 Outgoing 2 auto reclose lock out auto reclose bekerja pada outgoing 2 CB trip
4 Outgoing 3 auto reclose lock out auto reclose bekerja pada outgoing 3 CB trip
5 Outgoing 4 auto reclose lock out auto reclose bekerja pada outgoing 4 CB trip
6 Outgoing 5 auto reclose lock out auto reclose bekerja pada outgoing 5 CB trip
7 Spare
8 Under frequency fail relay under frekwensi bekerja CB trip
9 Under frequency fail relay under frekwensi bekerja CB trip
10 Under frequency fail relay under frekwensi bekerja CB trip
11 Under frequency fail relay under frekwensi bekerja CB trip
12 Under frequency fail relay under frekwensi bekerja CB trip
13 Over current fail relay over current bekerja CB trip
14 Over current fail relay over current bekerja CB trip
15 Over current fail relay over current bekerja CB trip
16 Over current fail relay over current bekerja CB trip
17 Over current fail relay over current bekerja CB trip
18 Over current fail relay over current bekerja CB trip
19 Earth fault fail relay earth fault bekerja CB trip
20 Earth fault fail relay earth fault bekerja CB trip
21 Earth fault fail relay earth fault bekerja CB trip
22 Earth fault fail relay earth fault bekerja CB trip
23 Earth fault fail relay earth fault bekerja CB trip
24 Earth fault fail relay earth fault bekerja CB trip
CB dan relay atau Tripping tidak dapat
25 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
26 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
27 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
28 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
29 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
30 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY LINE 1&2 SEI BALOI

1 2 3 4 5
DISTANCE SPARE OVER GROUND BUSBAR
PROTECTIVE CURRENT FAULT PROTECTIVE
OPERATED LOCK OUT

6 7 8 9 10
LOCK OUT CB POLE SPARE SPARE SPARE
RELAY DISCREPANCY
OPERATED

11 12 13 14 15
AUTO AUTO RECLOSE CB BAY DRIVING DISTANCE
RECLOSE MAINTENANCE TROUBLES FAULT PROTECTIVE
IN PROGRES LOCK OUT LOCK OUT ( CB ) IN OPERATIVE

16 17 18 19 20
TELE CPD HEALTHY MCB DC MCB AC
PROTECTION MCB'S TRIP 1-2 FAILURE FAILURE
TROUBLES TRIP

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Gangguan di transmisi (main protec) Distance SHPM 101 ( F. 21 ) K.211 SHPM ( F.21 ) Tekan tombol reset
3 Gangguan arus lebih di Transmisi SPAJ 140 C (F.50/51 Ph+N) K.551 SPAJ 140 C (F.50/51 Ph+N) Tekan tombol reset
4 Gangguan arus ke tanah (pohon/tower) SPAJ 140 C (F.50/51 Ph+N) K.552 SPAJ 140 C (F.50/51 Ph+N) Tekan tombol reset
5 NOT USED MVAJ 24 ( 94 ) K.941 MVAJ 24 ( 94 ) Diangkat benderanya
6 MVAJ 11 ( 86) K.86 MVAJ 11 ( 86) Diangkat benderanya
11 CB Trip dan masuk kembali (Reclose) LFAA 101 (79) K.791 LFAA 101 (79) Tekan tombol reset
12 Relay auto Reclose perlu di HAR LFAA 101 (79) K.79 LFAA 101 (79) Tekan tombol reset
13 K.30Y1 Control panel Tekan tombol reset
14 CB tidak bisa masuk K.30Y2 Control panel Tekan tombol reset
15 Power supply R. Distance tidak ada Distance SHPM 101 ( F. 21 ) K.212 Distance SHPM 101 ( F. 21 ) Tekan tombol reset
16 Gangguan pada telekomunikasi Telkom K.30Y7 Control panel Tekan tombol reset
17 MCB MK di serandang ada yang trip MCB di MK K.30Y3 MK di Serandang Naikan MCB yang trip
18 Tripping Coil CB Putus / Rusak MVAX 31 ( TCS. 1-2-3-4-5-6 ) K.4423-26/30Y8 Control panel Tekan tombol reset
19 MCB DC di kontrol panel dan MCB DC trip di control panel dan K.30Y4 Di kontrol panel dan Naikan MCB yang trip
MK serandang ada yang trip MK Di serandang MK di Serandang
20 MCB AC di kontrol,relay panel dan MCB AC di CP,RP & MK K.30Y5 MCB AC di CP,RP & MK Naikan MCB yang trip
MK serandang ada yang trip

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL OLTC 150 / 20 KV
BAY TRAFO#1 30 MVA

1 2 3
WTI TERMOMETER PROTECTION
TRIP TRIP RELAY OLTC
TRIP

4 5 6
PRESSURE BUCHOLZ SPARE
RELIEF RELAY
TRIP TRIP

7 8 9
WTI TERMOMETER OIL LEVEL
ALARM ALARM ALARM

10 11 12
TAP BUCHOLZ CONTROL
TROUBLES RELAY SUPPLY
ALARM FAULT

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

Di Trafo ada gangguan dan trafo trip Cek Trafo Kalau Bahaya Harus di Cek Team HAR
1 Relay suhu winding Trafo K.12
karena suhu body trafo tinggi matikan dan Laporkan Tunggu suhu Turun
Di Trafo ada gangguan dan trafo trip Cek Trafo Kalau Bahaya Harus di Cek Team HAR
2 Thermometer di Trafo K.15
karena suhu body trafo tinggi matikan dan Laporkan Tunggu suhu Turun
Di Trafo ada gangguan dan trip Cek Trafo Kalau Bahaya
3 Di OLTC Trafo K.13 Harus di Cek Team HAR
Karena OLTC terganggu matikan dan Laporkan
Di trafo ada gangguan dan trip Cek Trafo Kalau Bahaya Harus diCek Team HAR
4 Pressure relief Relay di Trafo K.14
Karena tekanan minyak yang tinggi matikan dan Laporkan Tekan tombol reset
Di Trafo ada Gangguan dan trip Cek Trafo Kalau Bahaya Harus diCek Team HAR
5 Bucholz Relay di Trafo K.11
karena di trafo ada gelembung udara matikan dan Laporkan Buang gelembung Udara
Ditrafo ada gangguan baru alarm Cek Trafo Kalau Bahaya Harus diCek Team HAR
7 Relay suhu winding Trafo K.30Y5
karena suhu body trafo tinggi matikan dan Laporkan Tunggu suhu turun
Di Trafo ada gangguan baru alarm Cek Trafo Kalau Bahaya Harus diCek Team HAR
8 Thermometer di Trafo K.30Y6
Karena tekanan suhu tinggi matikan dan Laporkan Tunggu suhu turun
Di Trafo ada gangguan baru alarm Minyak di Consenvator Trafo Harus diCek Team HAR
9 Relay Oil Level K.30Y3
Karena minyak trafo yang kurang Kurang Tambah minyak Trafo
Di Trafo ada gangguan baru alarm
10 Di OLTC Trafo K.1001 Panel OLTC Harus diCek Team HAR
karena di tap trafo ada masalah
Di Trafo ada gangguan baru alarm Cek Trafo Kalau Bahaya
11 karena di Trafo mulai ada gelembung Busholz Relay Di Trafo K.30Y4 Matikan dan laporkan Harus diCek Team HAR
gelembung udara
12 MCB di panel OLTC trip Panel OLTC Trafo K.272 & K.273 Panel OLTC Trafo Naikkan MCB yang trip

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 / 20 KV
BAY TRAFO#1 30 MVA

1 2 3 4 5
DIFFERENTIAL PRIMARY TRAFO FAULT RESTRICTED PANEL 20KV
SEC.GROUND TRIP EARTH FAULT INCOMING
OVER CURRENT (REF) CB TRIP

6 7 8 9 10
SPARE SPARE SPARE SPARE SPARE

11 12 13 14 15
CB HEALTHY 20KV CUBICLE BAY DRIVING TRAFO FAULT
TROUBLES TRIP 1-2 TROUBLES FAILURE ALARM
LOCK OUT

16 17 18 19 20
MCB DC MCB AC SPARE SPARE SPARE
FAILURE FAILURE

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Ada gangguan di Daerah Trafo SPAD 330 C ( F.87 ) K.57 SPAD 330 C ( F.87 ) Tekan tombol reset
Gangguan arus lebih Phase-phase SPAJ 140 C & SPAJ 110 C SPAJ 140 C & SPAJ 110 C
2 K.30X2 Tekan tombol reset
Gangguan arus lebih Neutral ( F.50/51 ) ( F.50/51 )
DiTrafo ada gangguan dan trip Bucholz,winding tem,Protective
gelembung udara, temperatur lilitan relay,over pressrue & termometer Trip
3 K.11,12,13,14 & 15 Harus diCek tim HAR Harus di Cek tim HAR
tinggi,OLTC tidak normal,tekanan tinggi
dan suhu tinggi
SPAE 010 MA ( 64 H ) SPAE 010 MA ( 64 H )
4 Gangguan arus keTanah K.30X3 Tekan tombol reset
SPAE 010 MA ( 64 L ) SPAE 010 MA ( 64 L )
5 CB Incoming Trafo trip MCGG 22 R,T, ( 50 + 51 N ) K.30X1 MCGG 22 R,T, N Tekan tombol reset
11 CB ada masalah dan lock out K.30Y1 Kontrol panel Tekan tombol reset
12 Tripping Coil CB Putus / Rusak MVAX 31 ( TCS. 1-2-3-4-5-6 ) K.4424 Control panel Tekan tombol reset
13 Kubikel 20kV ada masalah K.30Y10 Panel 20KV Tekan tombol reset
14 K.30Y11
DiTrafo ada gangguan tapi masih alarm Buchoze,winding tem,Protective Cek Trafo dan kalau bahaya
gelembung udara, temperatur lilitan relay,over pressrue & termometer Trip matikan Trafo dan Laporkan
15 K.11,12,13,14 & 15 Harus di Cek tim Har
tinggi,OLTC tidak normal,tekanan tinggi
dan suhu tinggi
MCB DC di Kontrol panel dan MK MCB DC trip di kontrol panel dan Di kontrol panel dan MK
16 K.30Y7 Naikkan MCB yang trip
ada yang trip MK serandang di serandang
MCB AC di kontrol panel,relay panel, MCB AC di Control - Relay panel, Di CP,RP kontrol OLTC Naikkan MCB yang trip
17 K.30Y8
Kontrol OLTC dan MK ada yang Trip. kontrol panel OLTC & MK MK serandang

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BUS COUPLER 150 kV

1 2 3 4 5
Over GROUND CB SPARE SPARE
Current FAULT TRIP

6 7 8 9 10
SPARE SPARE SPARE SPARE SPARE

11 12 13 14 15
O / C INTERNAL SPARE CB TROUBLES CPD MCB'S BAY DRIVING
FAULT LOCK OUT TRIP FAULT

16 17 18 19 20
SPARE SPARE SPARE MCB DC MCB AC
FAILURE FAILURE

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Gangguan arus Lebih SPAJ 140 C ( F 50/51 N ) K.50 SPAJ 140 C ( F 50/51 N ) Tekan tombol reset
Gangguan arus keTanah
2 SPAJ 140 C ( F 50/51 N ) K.50N SPAJ 140 C ( F 50/51 N ) Tekan tombol reset
Gangguan arus lebih Neutral
3 CB trip & Lock Out MCGG 82 ( F.50/51 ) MVAJ 24(K.94) MVAJ 24(K.94) Di angkat benderanya
11 Ada gangguan di Coupler SPAJ 140 C ( F 50/51 N ) SPAJ 140 C ( F 50/51 N ) Tekan tmbol reset
13 CB ada masalah dan lock out K.30y3 Kontrol panel
14 MCB MK di serandang ada yang trip MCB di MK K.21&22 MK di Serandang Naikan MCB yang trip
15 MCB di Box Control CB ada Yang trip MCB di Box Control CB K.30y7 Box Control CB Tekan angka di MCB
MCB DC di kontrol panel dan MK MCB DC di kontrol panel Di Kontrol panel dan MK
19 K.271 s/d 275 Naikan MCB yang trip
ada Yang trip MK serandang trip di Serandang
MCB AC di kontrol panel dan MK MCB AC di kontrol panel Di Kontrol panel dan MK
20 K.4312 Naikan MCB yang trip
ada Yang trip MK serandang trip di Serandang

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY LINE 1&2 NONGSA

1 2 3 4 5
CIRCUIT BREAKER CIRCUIT BREAKER DISTANCE OVER CURRENT F67N
SF6 LOW SF6 LOW PROTECTION PROTECTION OPERATE
PRESSURE TRIPPING PRESSURE ALARM
6 7 8 9 10
POLE HV.APPARATUS SPRING CHARGE SPARE AUTORECLOSE
DISCREPANCY LOCAL CONTROL FAILURE SUCCES

11 12 13 14 15
SPARE SPARE ISOLATOR & CB BLOCKING FOR C1 / T1 / T2 /
MOTOR SUPPLY MAINTENANCE DC SUPPLIES
FAILURE FAILURE
16 17 18 19 20
HEALTHY TRIP 1 & 2 DEAD LINE CARRIER MCB VOLTAGE DISTANCE & DIRECTIONAL
ALARM DETECTION FAILURE TRANSFORMER PROTECTION RELAY
FAILURE OPENED IN OPERATIVE ALARM

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Circuit Breaker
1
Pressure Tripping Gas SF6 di bawah Supply Daya putus
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
2
Pressure Alarm Gas SF6 di bawah dan tidak bisa di Reset
3 Distance protection Main Protection Bekerja CB Trip

4 Over Current Protection Back Up Protection Bekerja CB Trip


Terjadinya Gangguan Phase - Ground
5 F67N operate CB Trip
pada Winding
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
6 Pole Discrepancy
Circuit Breaker antara R,S,T Phasenya akan trip
7 HV.Apparatus Local Control CB & DS posisi local Indikasi
Alarm dan perlu tindak
8 Spring Charge Failure Spring Charge CB tidak bekerja
lanjut
9 Spare

10 Autoreclose succes Autoreclose bekerja dengan baik CB tidak trip

11 Spare

12 Spare
Isolator & CB motor Supply Salah satu MCB supply tiga phase untuk
13 Alarm
failure DS atau CB Trip pada Local Control Panel
14 Bloking for Maintenance Terjadinya Block Untuk Breaker Alarm
Terjadinya salah satu MCB DC Supply CB dan DS atau Tripping
15 C1/T1/T2 DC Supplies Failure
trip pada Control panel tidak dapat bekerja
Healthy Trip 1 & 2 Adanya Gangguan pada
16 Putusnya Tripping Coil
Alarm Rangkaian tripping
Dead Line detection
17 Hilang Tegangan Line Alarm
failure
Komunikasi antara distance protection Distance protection tidak dapat memberikan
18 Carrier failure
gagal sinyal
Proteksi atau metering tidak
19 MCB Voltage tranformer opened Salah satu MCB Trip Pada MK
dapat membaca tegangan
Distance & directional protection relay in Alarm dan perlu tindak
20 Distance Block
operative alarm lanjut
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY LINE 1&2 TJ. KASAM

1 2 3 4 5
CIRCUIT BREAKER CIRCUIT BREAKER DISTANCE OVER CURRENT F67N
SF6 LOW SF6 LOW PROTECTION PROTECTION OPERATE
PRESSURE TRIPPING PRESSURE ALARM
6 7 8 9 10
POLE HV.APPARATUS SPRING CHARGE AUTORECLOSE SPARE
DISCREPANCY LOCAL CONTROL FAILURE SUCCES

11 12 13 14 15
SPARE SPARE ISOLATOR & CB BLOCKING FOR C1 / T1 / T2 /
MOTOR SUPPLY MAINTENANCE DC SUPPLIES
FAILURE FAILURE
16 17 18 19 20
HEALTHY TRIP 1 & 2 DEAD LINE CARRIER MCB VOLTAGE DISTANCE & DIRECTIONAL
ALARM DETECTION FAILURE TRANSFORMER PROTECTION RELAY
FAILURE OPENED IN OPERATIVE ALARM

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Circuit Breaker
1
Pressure Tripping Gas SF6 di bawah Supply Daya putus
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
2
Pressure Alarm Gas SF6 di bawah dan tidak bisa di Reset
3 Distance protection Main Protection Bekerja CB Trip

4 Over Current Protection Back Up Protection Bekerja CB Trip


Terjadinya Gangguan Phase - Ground
5 F67N operate CB Trip
pada Winding
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
6 Pole Discrepancy
Circuit Breaker antara R,S,T Phasenya akan trip
7 HV.Apparatus Local Control CB & DS posisi local Indikasi
Alarm dan perlu tindak
8 Spring Charge Failure Spring Charge CB tidak bekerja
lanjut
9 Autoreclose succes Autoreclose bekerja dengan baik CB tidak trip

10 Spare

11 Spare

12 Spare
Isolator & CB motor Supply Salah satu MCB supply tiga phase untuk
13 Alarm
failure DS atau CB Trip pada Local Control Panel
14 Bloking for Maintenance Terjadinya Block Untuk Breaker Alarm
Terjadinya salah satu MCB DC Supply CB dan DS atau Tripping
15 C1/T1/T2 DC Supplies Failure
trip pada Control panel tidak dapat bekerja
Healthy Trip 1 & 2 Adanya Gangguan pada
16 Putusnya Tripping Coil
Alarm Rangkaian tripping
Dead Line detection
17 Hilang Tegangan Line Alarm
failure
Komunikasi antara distance protection Distance protection tidak dapat memberikan
18 Carrier failure
gagal sinyal
Proteksi atau metering tidak
19 MCB Voltage tranformer opened Salah satu MCB Trip Pada MK
dapat membaca tegangan
Distance & directional protection relay in Alarm dan perlu tindak
20 Distance Block
operative alarm lanjut
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY TRAFO#2 30 MVA

1 2 3 4 5
CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER MAIN PROTECTION BACK UP
SF6 LOW SF6 LOW POLE PROTECTION
PRESSURE TRIPPING ALARM DISCREPANCY OPERATED
6 7 8 9 10
BAY DRIVING HV APPARATUS MOTOR SPRING HEALTHY TRIP 1&2 TRIPPING
FAULT LOCAL CONTROL CHARGE OPERATION ALARM FROM 20KV

11 12 13 14 15
C1/T1/T2 DC TRANSFORMER SPARE SPARE SPARE
SUPPLY FAULT 2nd
FAILURE STAGE
16 17 18 19 20
SPARE TRANSFORMER SPARE SPARE SPARE
FAULT 1st
STAGE

ANNUNCIATOR YANG RELAY YANG


NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL BEKERJA
Circuit Breaker SF6 Low Terjadi kebocoran sampai
1 K 434 CB Trip
Pressure Tripping Tekanan Gas SF6 di bawah
Circuit Breaker SF6 Low Terjadi kebocoran sampai Warning Alarm stage 1
2 K 433
Alarm Tekanan Gas SF6 di bawah dan tidak bisa di Reset
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
3 CB pole discrepancy
Circuit Breaker antara R,S,T Phasenya akan trip
Relay Differential Micom P632
4 Main Protection K 1870 CB Trip
bekerja karena gangguan
K 1500,1871, Relay Over Current.Micom
5 Backup Protection Operated CB Trip
1872.151 P122 bekerja karena gangguan
K 450 Salah satu MCB Supply 3 phase untuk Motor DS dan Spring
6 Bay driving fault
K 472 DS atau CB trip pada Local control panel CB tidak bekerja
Control CB / DS trafo berubah pada posisi
7 HV apparatus local control CB / DS bekerja pada posisi lokal
lokal
Motor spring charge
8 Motor spring charge CB bekerja
operation
Adanya gangguan pada
9 Healthy Trip 1&2 Alarm K 4901-02 Putusnya Tripping Coil
rangkaian Tripping
Adanya kiriman Trip dari
10 Tripping from 20 kV K 4311 CB Trip
Penyulang / Incoming 20 KV
C1/T1/T2 DC Terjadinya salah satu MCB DC CB dan DS Atau Tripping
11 K 271-3
Supply Failure Supply Trip.Pada Control panel. ES1001 Tidak dapat bekerja
12 Transformer fault 2nd stage K 482 Terjadinya gangguan pada transformer CB Trip
13 Spare
14 Spare
15 Spare
16 Spare
17 Transformer fault 1st stage K 481-84 Memerlukan pengecekan ke Trafo Alarm
18 Spare
19 Spare
20 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI REGULATOR PANEL
BAY TRAFO#2 30 MVA

1 2 3 4 5
MAIN/OLTC OIL BUCHOLZ FAN CONTROL FAN AC HV / LV WINDING
LEVEL LOW ALARM SUPPLY FAILURE SUPPLY FAILURE TEMPERATUR
ALARM
6 7 8 9 10
BUCHOLZ OIL TEMPERATUR HV / LV WINDING PRESSURE RELIEF PRESSURE RELIEF
TRIP INDICATOR TEMPERATUR DEVICE DEVICE FOR
TRIP OLTC
11 12 13 14 15
OLTC PROTECTION COOLING FAULT VOLTAGE FIRE FIRE
RELAY TRIPPING FAN MOTOR REGULATION ALARM PROTECTION PROTECTION
FAILURE TAP CHARGE OUT OF DEVICE OUT OPERATE
16 17 18 19 20
SPARE SPARE SPARE SPARE SPARE

RELAY YANG
NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA
BEKERJA
Main / OLTC OIL
1 K 484 Terjadi Gangguan Pada OLTC CB Trip
Level Low
Warning Alarm stage 1
2 Bucholz Alarm K481 Adanya Gas / Udara Pada Trafo
dan tidak bisa di Reset
3 Fan Control Supply Failure K 486 Adanya Salah satu Fan Tidak Bekerja Alarm

4 Fan AC Supply Failure K 485 Suplai tegangan AC untuk Fan tidak ada Alarm
HV / LV Winding Temperatur Terjadinya kenaikan Temperatur
5 K 483 Alarm
Alarm pada Winding
Terdapatnya Udara Yang Sangat
6 Bucholz Trip K 4814 CB Trip
Besar pada main tank
Terjadinya kenaikan temperatur Circuit Breaker ketiga
7 Oil Temperatur Indicator K 4815
pada Oil yang cukup tinggi phasenya akan trip
HV / LV Winding Adanya temperatur pada
8 K 4816 CB Trip
Temperatur Trip winding yang sangat tinggi
Adanya tekanan udara di main tank yang
9 Presurre Relief Device K 4817 CB Trip
sangat Tinggi
Adanya tekanan udara di OLTC yang
10 Presurre Relief Device For OLTC K 4817 CB Trip
sangat Tinggi
OLTC Protection Relay Terjadinya gangguan pada
11 K 4818 CB Trip
Tripping Tap Changer
Cooling Fault Fan Motor Adanya Salah satu MCB
12 K 4805 Alarm
Failure Supply Untuk Fan Trip
Voltage Regulation alarm
13 K 4802 Tap Changer Di Posisi Auto Alarm
Tap Charge
Fire Protection Out Of
14 K 4810 Fire Protection Tidak diaktifkan Alarm
Dervice
Fire Protection Out
15 Fire Protection Tidak bekerja Alarm
operate
16 Spare
17 Spare
18 Spare
19 Spare
20 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY LINE 1&2 SEI BALOI

1 2 3 4 5
DISTANCE SPARE OVER GROUND BUS PROT
PROTECTIVE CURRENT FAULT LOCK OUT
OPERATED

6 7 8 9 10
LOCK OUT CB POLE SPARE SPARE SPARE
RELAY DISCREPANCY
OPERATED

11 12 13 14 15
AUTO AUTO RECLOSE CB BAY DRIVING DISTANCE
RECLOSE MAINTENANCE TROUBLES FAULT PROTECTIVE
IN PROGRESS LOCK OUT LOCK OUT IN OPERATIVE

16 17 18 19 20
TELE CPD HEALTHY MCB DC MCB AC
PROTECTION MCB'S TRIP 1 - 2 FAILURE FAILURE
TROUBLES TRIP

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Gangguan di transmisi (main protec) Distance SHPM 101 ( 21 ) K.211 SHPM ( 21 ) Tekan tombol Reset
3 Gangguan arus lebih di Transmisi SPAJ 140 C (F.50/51 Ph+N) k.551 SPAJ 140 C (F.50/51 Ph+N) Tekan tombol Reset
4 Gangguan arus keTanah (pohon/tower) SPAJ 140 C (F.50/51 Ph+N) K.552 SPAJ 140 C (F.50/51 Ph+N) Tekan tombol Reset
5 NOT USED 94.1 (TCS.1) dan (TCS.2) K.30X1 MVAJ 24 ( 94 ) Diangkat benderanya
6 86.1 dan 86.2 (Lock Out Relay) K.86 MVAJ 11 ( 86 ) Diangkat benderanya
7 Timer K.471 & K.472 CONTROL PANEL
11 CB trip dan masuk kembali (reclose) LFAA 101 ( 79 ) K.30Y7 LFAA 101 ( 79 ) Tekan tombol Reset
12 Relay auto reclose perlu di Har LFAA 101 ( 79 ) K.791 & K.792 LFAA 101 ( 79 ) Tekan tombol Reset
13 K.30Y1 Control panel Tekan tombol Reset
14 CB tidak bisa masuk K.30Y2 CONTROL PANEL Tekan tombol Reset
15 Power suply R. Distance tidak ada Distance SHPM 101 ( 21 ) K.212 Distance SHPM 101 ( 21 ) Tekan tombol Reset
16 Gangguan pada Telekomunikasi Telkom K.30Y8 Control panel Tekan tombol Reset
MCB PT MK di serandang
17 MCB PT di MK K.30Y3 MK di Serandang Naikkan MCB yg Trip
ada yang trip
18 Tripping Coil CB putus/Rusak MVAX 31 ( TCS.1-2-3-4-5-6 ) K.4423-26-29-212 Control Panel Tekan tombol reset
19 MCB DC di Kontrol panel MCB DC trip di Control Panel K.30Y6 Di kontrol panel Naikan MCB yg trip
MCB AC di kontrol panel,relay panel,
20 MCB AC di CP,RP, & MK K.30Y5 MCB AC di CP,RP, & MK Naikkan MCB yg trip
dan MK .3 serandang ada yang trip

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL OLTC 150 KV
BAY TRAFO 60 MVA

1 2 3
WTI TERMOMETER PROTECTION
TRIP TRIP RELAY OLTC
TRIP

4 5 6
PRESSURE BUCHOLZ SPARE
RELIEF RELAY
TRIP TRIP

7 8 9
WTI TERMOMETER OIL LEVEL
ALARM ALARM ALARM

10 11 12
TAP BUCHOLZ CONTROL
TROUBLES RELAY SUPPLY
ALARM FAULT

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

Di Trafo ada gangguan dan trafo trip Cek Trafo Kalau Bahaya Harus di Cek Team HAR
1 Relay suhu winding Trafo K.12
karena suhu body trafo tinggi matikan dan Laporkan Tunggu suhu Turun
Di Trafo ada gangguan dan trafo trip Cek Trafo Kalau Bahaya Harus di Cek Team HAR
2 Thermometer di Trafo K.15
karena suhu body trafo tinggi matikan dan Laporkan Tunggu suhu Turun
Di Trafo ada gangguan dan trip Cek Trafo Kalau Bahaya
3 Di OLTC Trafo K.13 Harus di Cek Team HAR
Karena OLTC terganggu matikan dan Laporkan
Di trafo ada gangguan dan trip Cek Trafo Kalau Bahaya Harus diCek Team HAR
4 Pressure relief Relay di Trafo K.14
Karena tekanan minyak yang tinggi matikan dan Laporkan Tekan tombol reset
Di Trafo ada Gangguan da trip Cek Trafo Kalau Bahaya Harus diCek Team HAR
5 Bucholz Relay di Trafo K.11
karena di trafo ada gelembung udara matikan dan Laporkan Buang gelembung Udara
Di trafo ada gangguan baru alarm Cek Trafo Kalau Bahaya Harus diCek Team HAR
7 Relay suhu winding Trafo K.30Y5
karena suhu body trafo tinggi matikan dan Laporkan Tunggu suhu turun
Di Trafo ada gangguan baru alarm Cek Trafo Kalau Bahaya Harus diCek Team HAR
8 Thermometer di Trafo K.30Y6
Karena tekanan suhu tinggi matikan dan Laporkan Tunggu suhu turun
Di Trafo ada gangguan baru alarm Minyak di Consenvator Trafo Harus diCek Team HAR
9 Relay Oil Level K.30Y3
Karena minyak trafo yang kurang Kurang Tambah minyak Trafo
Di Trafo ada gangguan baru alarm
10 Di OLTC Trafo K.1001 Panel OLTC Harus diCek Team HAR
karena di tap trafo ada masalah
Di Trafo ada gangguan baru alarm Cek Trafo Kalau Bahaya
11 karena di Trafo mulai ada gelembung Bucholz Relay Di Trafo K.30Y4 Matikan dan laporkan Harus diCek Team HAR
gelembung udara
12 MCB di panel OLTC trip Panel OLTC Trafo K.272 & K.273 Panel OLTC Trafo Naikkan MCB yang trip

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY TRAFO 60 MVA

1 2 3 4 5
DIFFERENTIAL PRIMARY TRAFO FAULT RESTRICTED PANEL 20KV
SEC.GROUND TRIP EARTH FAULT INCOMING
OVER CURRENT CB TRIP

6 7 8 9 10
SPARE SPARE SPARE SPARE SPARE

11 12 13 14 15
CB HEALTHY 20KV CUBICLE BAY DRIVING TRAFO FAULT
TROUBLES TRIP 1-2 TROUBLES FAILURE ALARM
LOCK OUT

16 17 18 19 20
MCB DC MCB AC FIRE PROTECTION SPARE SPARE
FAILURE FAILURE OUT OF SERVICE

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Ada gangguan di Daerah Trafo SPAD 330 C ( F.87 ) K.87 SPAD 330 C ( F.87 ) Tekan tombol reset
Gangguan arus lebih Phase-phase SPAJ 140 C & SPAJ 110 C Tekan tombol reset
2 K.30X2 SPAJ 140 C
Gangguan arus lebih Neutral ( F.50/51 ) Tekan tombol reset
Relay bucholz,Relay suhu dan Di Trafo Relay bucholz dan Tekan tombol reset
3 Gangguan di Trafo CB yang Trip K.11,-17
pressure relief pressure relief U/suhu Tunggu turun
4 Gangguan arus keTanah SPAE 10 ( 64 H )+( 64 L ) K.30X3 SPAE 10 ( 64 H )+( 64 L ) Tekan tombol reset
5 CB Incoming Trafo 60 MVA trip MCGG 22 R,T,N K.30X1 MCGG 22 R,T, N Tekan tombol reset
11 K.30X1
12 Tripping Coil CB Putus / Rusak MVAX 31 ( TCS. 1-2-3-4-5-6 ) K.4424 MVAX 31 ( TCS. 1-2-3-4-5-6 ) Angkat keatas dan
13 Dan panel kontrol Tekan tombol reset
14 K.30Y10
15 K.30Y3,-Y6
k.30Y9,30Y2
K.1001,271-273
16 MCB DC di Kontrol panel MK1 Trip K.30Y7
17 MCB AC di kontrol panel,relay panel, K.30Y8
MK 1 trip
18 Box fire alarm K.30Y12

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 / 20 KV
BAY LINE 1&2 TJ.SENGKUANG, BATU BESAR, DAN SEI HARAPAN

1 2 3 4 5
DISTANCE SPARE OVER GROUND BUS PROT
PROTECTIVE CURRENT FAULT LOCK OUT
OPERATED

6 7 8 9 10
LOCK OUT CB POLE SPARE SPARE SPARE
RELAY DISREPANCY
OPERATED

11 12 13 14 15
AUTO AUTO RECLOSE CB BAY DRIVING DISTANCE
RECLOSE MAINTENANCE TROUBLES FAULT PROTECTIVE
IN PROGRES LOCK OUT LOCK OUT IN OPERATIVE

16 17 18 19 20
TELE CPD HEALTHY MCB DC MCB AC
PROTECTION MCB'S TRIP 1 - 2 FAILURE FAILURE
TROUBLES TRIP

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Gangguan di transmisi (main protec) Distance SHPM 101 ( 21 ) K.1040 SHPM ( 21 ) Tekan tombol Reset
3 Gangguan arus lebih di Transmisi MCGG 52 (F.50/51 Ph+N) k.1010 MCGG 52 (F.50/51 Ph+N) Tekan tombol Reset
4 Gangguan arus keTanah (pohon/tower) MCGG 52 (F.50/51 Ph+N) K.1020 MCGG 52 (F.50/51 Ph+N) Tekan tombol Reset
5 NOT USED MVAJ 24 ( K.401 ) K.2003&2007 MVAJ 24 ( K.401 ) Diangkat benderanya
6 Terjadi Gangguan Lebih besar dari MVAJ 11 ( K.402 ) K.1030&4302 MVAJ 11 ( K.402 )
setting atau sudah tiga kali reclose MCGG 52
7 Salah satu CB trip R-S-T Terlalu lama Timer K.431 & di CB K.61 K.4302 Control panel Tekan tombol Reset
11 CB Trip dan masuk kembali LFAA 101 ( 79 ) K.1060 LFAA 101 ( 79 ) Tekan tombol Reset
12 Relay Auto reclose perlu di Har LFAA 101 ( 79 ) K.1030 Control panel Tekan tombol Reset
13 Tekanan Gas SF6 turun di CB K.9-K.6-K.5 K.4301-03-04 Control panel Tekan tombol Reset
14 MCB di Box Kontrol DS ada yang trip MCB di Box Kontrol DS K.4035 Box Control DS Tekan angka I di MCB
15 Power suplay R Distance tidak ada Distance SHPM 101 ( F.21 ) K.1050 Distance SHPM 101 ( F.21 ) Tekan tombol Reset
16 Gangguan pada Telakomunikasi Telkom K.4315 Control panel Tekan tombol Reset
17 MCB MK di Serandang ada yang trip MCB di MK K.4311&4310 MK di Serandang Naikkan MCB yg trip
18 Tripping Coil CB putus / Rusak MVAX 31 ( TCS.1-2-3-4-5-6 ) K.4901&4902 Control Panel Tekan tombol reset
19 MCB DC di Kontrol panel ada yang trip MCB trip di Control Panel K.271 s/d 275 Di kontrol panel Naikkan MCB yg trip
20 MCB MK di Serandang ada yang trip MCB di MK K.4312 MK di Serandang Naikkan MCB yg trip

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL OLTC 150 KV
BAY TRAFO#1 60 MVA

1 4 7 10 13 16
OIL LEVEL OIL LEVEL BUCHOLZ WINDING TRANSF FIRE PROTEC
TRANSFORMER OLTC ALARM TEMP COOLING OUT OF
LOW ALARM LOW ALARM ALARM FAULT ALARM SERV ALARM
2 5 8 11 14 17
BUCHOLZ WINDING PROTECTIVE OVER PRESS OVER PRESS FIRE PROTEC
TRIP TEMP RELAY OLTC VALVE VALVE OPRATED
TRIP TRIP OLTC TRIP TRANSFOR. TRIP TRIP
3 6 9 12 15 18
OLTC VOLTAGE OLTC L/R TRANSF TRANSF CIRCUIT SPARE
REGULATOR SWITCH COOLING COOLING BREAKER
ALARM LOCAL "ON" ON "OUT" 20 KV OPEN

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

Di Trafo minyaknya kurang Cek trafo kalau bahaya Harus dicek team HAR
1 Relay oil Level K.4817
(Baru alarm belum trip) matikan dan laporkan Tambah minyak trafo
Suhu Trafo panas relay bucholz Cek trafo kalau bahaya Harus dicek team HAR
2 bekerja menTripkan Trafo Bucholz Relay di Trafo K.1110 matikan dan laporkan Buang gelembung udara
(ada gelembung udara karena panas)
3 Regulator voltage Gangguan Regulator volt (MK.30) P.OLTC K.5 Panel OLTC kontrol Harus dicek team HAR
Di OLTC minyaknya kurang Cek OLTC kalau bahaya Harus dicek team HAR
4 Relay oil Level K.4818
(Baru alarm belum trip) matikan dan laporkan Tambah minyak OLTC
Temperatur Trafo terlalu tinggi Harus dicek team HAR
5 Thermometer di Trafo K.1120-25 Panel OLTC kontrol
sehingga Trafo trip Tunggu suhu turun
Saklar kontrol di MK OLTC Saklar Kontrol di MK OLTC di MK OLTC Rubah saklar kontrol
6 K.21
di Rubah ke posisi lokal Di Rubah ke posis lokal ( Di Trafo ) ke posisi remote
Suhu Trafo panas relay bucholz Cek trafo kalau bahaya Harus dicek team HAR
7 bekerja alarm berbunyi belum trip Bucholz relay di Trafo K.4813 matikan dan laporkan Buang gelembung udara
(ada gelembung udara karena panas)
Relay pengaman OLTC bekerja Cek trafo kalau bahaya Harus dicek team HAR
8 Relay OLTC K.1130
Karena ada gangguan di OLTC matikan dan laporkan Cek OLTC
Kipas-kipas pendingin bekerja Cek trafo kalau bahaya Harus dicek team HAR
9 Relay Thermometer K.1
karena suhu Trafo mulai panas tinggi matikan dan laporkan Tunggu suhu turun
Temperatur Trafo Mulai Tinggi Cek trafo kalau bahaya Harus dicek team HAR
10 Thermometer di Trafo K.4814 & 4819
sehingga bunyi alarm dan belum trip matikan dan laporkan Tunggu suhu turun
Tekanan tinggi pada Valve OLTC Cek trafo kalau bahaya Harus dicek team HAR
11 Relay Pressure K.1140
sehingga Trafo trip matikan dan laporkan Tekan tombol reset
Kipas-kipas pendingin Mati
12 Relay Thermometer K.2 Panel OLTC kontrol Tekan tombol reset
Karena suhu Trafo Turun
MCB Q1 sampai Q11 ada yang trip Panel di MK OLTC Naikan MCB yang Trip
13 MCB Q1-Q11 di MK OLTC Trip K.4811
di MK OLTC di Trafo ( di Trafo )
14 Tekanan tinggi pada Valve Trafo Relay Pressure K.1145 Panel OLTC kontrol Tekan Tombol Reset
15 NOT USED NOT USED K.4860 NOT USED NOT USED
Di Box Fire Protection saklar Kunci kontrol posisi "Out Off Harus di cek Team Har
16 K.4816 Box Fire Protection
Kontrolnya posisi "out of service" Service" Kunci kontrol di ON kan
Fire Protection di Operasikan Di Operasikan di Box fire
17 Manual ( jangan di Operasikan dulu Protection secara manual K.1155 Di Box Fire Protection Harus di cek Team Har
Sebelum dapat izin dari atasan )
18 Spare Spare Spare Spare Spare

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY TRAFO#1 60 MVA

1 2 3 4 5
DIFFERENTIAL OVER CURRENT FIRE RESTRICTED PANEL 20 KV
PROTECTION PRIMARY PROTECTION EARTH FAULT INCOMING 3
NEUTRAL TRIP CB TRIP

6 7 8 9 10
TRAFO FAULT PANEL 20 KV PANEL 20 KV PANEL 20 KV PANEL 20 KV
TRIP INCOMING 1 INCOMING 2 INCOMING 4 INCOMING 5
CB TRIP CB TRIP CB TRIP CB TRIP

11 12 13 14 15
FIRE CB SF6/ HEALTHY BAY DRIVING TAP CHANGER
PROTECTION PRESSURE HYD TRIP 1 - 2 FAILURE TROUBLE
ALARM ALARM LOCK OUT
TROUBLE
16 17 18 19 20
TRAFO SPARE 20 KV CONTROL MCB MK
FAULT TROUBLES SUPPLY FAILURE
ALARM FAILURE

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Ada gangguan di daerah Trafo MBCH 12 ( F.87 TR ) K.1010 MBCH 12 ( F.87 TR ) Tekan tombol reset
Gangguan arus lebih phase-phase MCGG 82 ( F.50/51 ) K.1020 MCGG 82 ( F.50/51 ) Tekan tombol reset
2
Gangguan arus lebih Neutral MCGG 22 ( F.50/51+ N ) K.1050 MCGG 22 ( F.50/51+ N ) Tekan tombol reset
3 Trafo sudah hampir terbakar Fire Protection K.1155 Box control fire protection Putar kunci OFF
4 Gangguan arus ke tanah MVAC 14 ( F.87 REF.1 & REF 2 ) K.1030 & 1040 MVAC 14 Diangkat benderanya
5 CB Incoming 3 Trip atau di OFF-kan SEPAM 2000 K.401-2 & 4860 SEPAM 2000 Tekan tombol reset
Relay Bucholz,Relay suhu dan K.1110-20-25-30 Di Trafo Relay buchol dan Tekan tombol reset
6 Gangguan di Trafo CB trip
pressure relief K.1140-45-50 Pressure relief U/suhu tunggu turun
7 CB Incoming 1 Trip atau di OFF-kan SEPAM 2000 K.401-2 & 4860 SEPAM 2000 Tekan tombol reset
8 CB Incoming 2 Trip atau di OFF-kan SEPAM 2000 K.401-2 & 4860 SEPAM 2000 Tekan tombol reset
9 CB Incoming 4 Trip atau di OFF-kan SEPAM 2000 K.401-2 & 4860 SEPAM 2000 Tekan tombol reset
10 CB Incoming 5 Trip atau di OFF-kan SEPAM 2000 K.401-2 & 4860 SEPAM 2000 Tekan tombol reset
11 Suhu di Trafo terlalu tinggi Fire Protection K.4816 Control panel Tekan tombol reset
12 Tekanan Gas SF6 turun Di CB K.9 - K.6 - K.5 K.4301-03-04 Control panel Tekan tombol reset
13 Triping Coil CB putus / rusak MVAX 31 ( TCS. 1-2-3-4-5-6 ) K.4901 & 4902 Control panel Tekan tombol reset
14 MCB di box Kontrol DS ada yang trip MCB di Box Control DS K.4035 Box Control DS Tekan angka I diMCB
15 MCB Box Tap canger trip di Trafo MCB Q1 dan Q11 Trip K.4812 Box Control Tap canger Naikan MCB yang trip
16 Gangguan di Trafo Bunyi alarm Relay Bucholz,Relay suhu dan K.4811-13-14-15 Di Trafo Relay buchol dan Tekan tombol reset
( Belum trip-kan CB ) pressure relief K.4817-18-19 Pressure relief U/suhu tunggu turun
18 NOT USED NOT USED k.4870 NOT USED NOT USED
19 MCB di kontrol panel ada yang trip MCB trip di Kontrol panel K.271 s/d K.275 Di kontrol panel Naikan MCB yang trip
20 MCB MK di serandang ada yang trip MCB di MK K.4312 MK di Serandang Naikan MCB yang trip

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BUS COUPLER 150 KV

1 2 3 4 5
OVER GROUND CB SPARE SAPRE
CURRENT FAULT TRIP

6 7 8 9 10
SPARE SPARE SPARE SPARE SPARE

11 12 13 14 15
SPARE ON LOAD CB SF6/ CPD BAY DRIVING
TRANSFER PRESSURE HYD MCB'S FAULT
ALARM LOCK OUT FAILURE
TROUBLE
16 17 18 19 20
PANEL 20KV SPARE SPARE CONTROL MCB MK
BUS COUPLER SUPPLY FAILURE
CB TRIP FAILURE

KONTAKTOR/
NO ARTI INDIKASI RELAY YANG BEKERJA AUX RELAY LOKASI RESET CARA RESET
YANG KERJA

1 Gangguan arus lebih MCGG 82 ( F.50/51 ) K.1020 MCGG 82 ( F.50/51 ) Tekan tombol reset
2 Gangguan arus ke tanah MCGG 82 ( F.50/51 Ph + N ) K.1021 MCGG 82 ( F.50/51 Ph + N ) Tekan tombol reset
Gangguan arus lebih Neutral MCGG 22 ( F.50/51+ N ) K.1050 MCGG 22 ( F.50/51+ N ) Tekan tombol reset
3 CB Trip dan Lock Out MCGG 82 ( F.50/51 ) MVAJ 24 (K.401) MVAJ 24 (K.401) Diangkat Benderanya
12 DS Bus 1 dan Bus 2 "ON" OLTX K. MM4XP Kontrol panel Tekan tombol reset
13 Tekanan Gas SF6 turun Di CB K.9-K.6-K.5 K.4301-03-04 Control panel Tekan tombol reset
14 MCB MK di Serandang ada yang trip MCB di MK K.4310 & 4311 Mk di serandang Naikan MCB yang Trip
15 MCB di box Kontrol DS ada yang trip MCB di Box Control DS K.4035 Box Control DS Tekan angka 1 di MCB
16 NOT USED NOT USED NOT USED NOT USED NOT USED
19 MCB di kontrol panel ada yang trip MCB trip di Control panel K.271 s/d K. 275 Di kontrol panel Naikan MCB yang Trip
20 MCB MK di Serandang ada yang trip MCB di MK K.4312 Mk di serandang Naikan MCB yang Trip

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY TRAFO#2 30 MVA

1 2 3 4 5 6
RELAY DIFFERENTIAL TCS COIL 1 TCS COIL 2 CB CB SUPPLY
IMPERATIVE PROTECTION OPERATED OPERATED OPENING PROTECTION
(87 T) TRIP INHIBITION FAIL

7 8 9 10 11 12
150KV SIDE REF 20KV SIDE REF RELAY TRNSFORMER CB CB SUPPLY
PROTECTION PROTECTION IN TEST ELECTRO UNCHARGED PROT
( 64 L ) TRIP ( 64 L ) TRIP POSITION MECHANICAL SPRING FAIL
TRIP
13 14 15 16 17 18
150KV SIDE 20 KV SIDE DC MCB AC MCB MARSHALING SPARE
PHASE & EARTH EARTH O/C FAIL FAIL MCB TRIP
O/C PROTECTION PROTECTION
(50/51 N) TRIP (51 N) TRIP
19 20 21 22 23 24
LOCK OUT 1 LOCK OUT 2 GENERAL CB LOW SPARE SPARE
RELAY RELAY TRANSFORMER PRESSURE
OPERATED OPERATED INTERNAL ALARM
ALARM

NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA

1 Relay imperative

2 Differential protection (87T) trip Main protection bekerja CB Trip

3 TCS coil 1 operated Tripping coil 1 bekerja CB Trip

4 TCS coil 2 operated Tripping coil 2 bekerja CB Trip


CB terbuka dikarenakan
5 CB opening inhibition Alarm
Adanya Gangguan
Adanya Salah satu MCB
6 CB supply protection fail Alarm
Supply Untuk CB trip
Proteksi REF di sisi 150 kV
7 150 kV side REF protection (64L) trip CB Trip
bekerja
Proteksi REF di sisi 20 kV
8 20 kV side REF protection (64L) trip CB Trip
bekerja
9 Relay in test position Proteksi relay dalam posisi pengetesan Alarm

10 Transformer electro mechanical trip

11 CB uncharged spring Spring charge CB tidak bekerja CB tidak bekerja


Adanya Salah satu MCB
12 CB supply protection fail Alarm
Supply Untuk CB trip
150 kV side phase & earth O/C Back up protection di sisi 150 kV
13 CB Trip
protection (50/51N) trip bekerja karena gangguan phase-earth O/C
20 kV side earth O/C Back up protection di sisi 20 kV
14 CB Trip
protection (51N) trip bekerja karena gangguan earth O/C
15 DC MCB fail MCB untuk Supply VDC trip Supply VDC untuk peralatan tidak ada

16 AC MCB fail MCB untuk Supply VAC trip Supply VAC untuk peralatan tidak ada

17 Marshaling MCB trip MCB di marshaling kios ada yang trip Alarm
18 Spare
19 Lock out 1 relay operated Relay lock out 1 bekerja Alarm

20 Lock out 2 relay operated Relay lock out 2 bekerja Alarm

21 General transformer internal alarm Gangguan pada internal trafo Alarm


Terjadi kebocoran sampai Warning Alarm stage 1
22 CB low pressure alarm
Tekanan Gas SF6 di bawah dan tidak bisa di Reset
23 Spare
24 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI REGULATOR PANEL 150 KV
BAY TRAFO#2 30 MVA

1 2 3 4 5 6
OIL LEVEL INDICATOR OIL LEVEL WINDING TEMP GENERAL WINDING TEMP WINDING TEMP
MAIN TANK INDICATOR INDICATOR TRANSFORMER INDICATOR INDICATOR
LOW LEVEL MAIN TANK ALARM INTERNAL LV SIDE HV SIDE
ALARM HIGH LEVEL ALARM ALARM TRIP TRIP
7 8 9 10 11 12
OIL LEVEL INDICATOR OIL LEVEL VOLTAGE BUCHOLZ POWER AC POWER
OLTC INDICATOR REGULATOR RELAY SUPPLY SUPPLY
LOW LEVEL OLTC DEVICE FAIL MAIN TANK UNDER TRIP
ALARM HIGH LEVEL ALARM TRIP VOLTAGE
13 14 15 16 17 18
BUCHOLZ PRESSURE PRESSURE PRESSURE DC POWER COOLING
RELAY RELIEF DEVICE RELIEF DEVICE RELIEF DEVICE SUPPLY FAN
MAIN TANK OLTC OLTC MAIN TANK TRIP FAILURE
ALARM ALARM TRIP TRIP
19 20 21 22 23 24
PRESSURE OIL TEMP PROTECTIVE OIL TEMP AC MCB DC MCB
RELIEF DEVICE INDICATOR RELAY INDICATOR TRIP TRIP
MAIN TANK MAIN TANK OLTC TRIP MAIN TANK
ALARM ALARM TRIP

NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA


Oil level indicator main tank Terjadi Gangguan Pada main tank trafo
1 CB Trip
low level alarm karena level minyak main tank trafo turun
Oil level indicator main tank Terjadi Gangguan Pada main tank trafo
2 CB Trip
high level alarm karena level minyak main tank trafo naik
Winding Temperatur indikator Terjadinya kenaikan Temperatur
3 Alarm
Alarm pada Winding
4 General transformer internal alarm Gangguan pada internal trafo Alarm
Winding Temperatur indikator LV side Adanya temperatur pada
5 CB Trip
Trip winding sisi LV yang sangat tinggi
Winding Temperatur indikator HV side Adanya temperatur pada
6 CB Trip
Trip winding sisi HV yang sangat tinggi
Oil level indicator OLTC Terjadi Gangguan Pada OLTC trafo
7 CB Trip
low level alarm karena level minyak OLTC turun
Oil level indicator OLTC Terjadi Gangguan Pada OLTC trafo
8 CB Trip
high level alarm karena level minyak OLTC naik
9 Voltage Regulator device fail Tap Changer Di Posisi Auto Alarm
Bucholz relay bekerja karena terdapatnya
10 Bucholz relay main tank trip CB Trip
udara yang sangat besar pada main tank
11 Power supply under voltage Tegangan di power supply turun Alarm
MCB VAC untuk power
12 AC power supply trip Supply VAC untuk peralatan tidak ada
supply trip
Warning Alarm stage 1
13 Bucholz relay main tank alarm Adanya Gas / Udara Pada Trafo
dan tidak bisa di Reset
Warning Alarm stage 1
14 Pressure relief device OLTC alarm Adanya tekanan udara di OLTC
dan tidak bisa di Reset
Adanya tekanan udara di OLTC yang
15 Pressure relief device OLTC trip CB Trip
sangat Tinggi
Adanya tekanan udara di main tank yang
16 Pressure relief device main tank trip CB Trip
sangat Tinggi
MCB VDC untuk power
17 DC power supply trip Supply VDC untuk peralatan tidak ada
supply trip
Adanya Salah satu MCB
18 Cooling fan failure Alarm
Supply Untuk Fan Trip
Warning Alarm stage 1
19 Pressure relief device main tank alarm Adanya tekanan udara di main tank
dan tidak bisa di Reset
Oil temperatur indicator main tank Terjadinya kenaikan temperatur minyak Warning Alarm stage 1
20
Alarm pada main tank trafo dan tidak bisa di Reset
Relay OLTC bekerja karena ada
21 Protective relay OLTC trip CB Trip
gangguan di OLTC trafo
Oil temperatur indicator main tank Terjadinya kenaikan temperatur minyak
22 CB Trip
trip pada main tank trafo yang tinggi
Salah satu MCB suplai VAC
23 AC MCB trip Alarm
trip
Salah satu MCB suplai VDC
24 DC MCB trip Alarm
trip
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY TRAFO#3 30 MVA

1 2 3 4 5 6
RELAY DIFFERENTIAL TCS COIL 1 TCS COIL 2 CB CB SUPPLY
IMPERATIVE PROTECTION OPERATED OPERATED OPENING PROTECTION
(87 T) TRIP INHIBITION FAIL

7 8 9 10 11 12
150KV SIDE REF 20KV SIDE REF RELAY TRNSFORMER CB CB SUPPLY
PROTECTION PROTECTION IN TEST ELECTRO UNCHARGED PROT
( 64 L ) TRIP ( 64 L ) TRIP POSITION MECHANICAL SPRING FAIL
TRIP
13 14 15 16 17 18
150KV SIDE 20 KV SIDE DC MCB AC MCB MARSHALING SPARE
PHASE & EARTH EARTH O/C FAIL FAIL MCB TRIP
O/C PROTECTION PROTECTION
(50/51 N) TRIP (51 N) TRIP
19 20 21 22 23 24
LOCK OUT 1 LOCK OUT 2 GENERAL CB LOW SPARE SPARE
RELAY RELAY TRANSFORMER PRESSURE
OPERATED OPERATED INTERNAL ALARM
ALARM

NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA

1 Relay imperative

2 Differential protection (87T) trip Main protection bekerja CB Trip

3 TCS coil 1 operated Tripping coil 1 bekerja CB Trip

4 TCS coil 2 operated Tripping coil 2 bekerja CB Trip


CB terbuka dikarenakan
5 CB opening inhibition Alarm
Adanya Gangguan
Adanya Salah satu MCB
6 CB supply protection fail Alarm
Supply Untuk CB trip
Proteksi REF di sisi 150 kV
7 150 kV side REF protection (64L) trip CB Trip
bekerja
Proteksi REF di sisi 20 kV
8 20 kV side REF protection (64L) trip CB Trip
bekerja
9 Relay in test position Proteksi relay dalam posisi pengetesan Alarm

10 Transformer electro mechanical trip

11 CB uncharged spring Spring charge CB tidak bekerja CB tidak bekerja


Adanya Salah satu MCB
12 CB supply protection fail Alarm
Supply Untuk CB trip
150 kV side phase & earth O/C Back up protection di sisi 150 kV
13 CB Trip
protection (50/51N) trip bekerja karena gangguan phase-earth O/C
20 kV side earth O/C Back up protection di sisi 20 kV
14 CB Trip
protection (51N) trip bekerja karena gangguan earth O/C
15 DC MCB fail MCB untuk Supply VDC trip Supply VDC untuk peralatan tidak ada

16 AC MCB fail MCB untuk Supply VAC trip Supply VAC untuk peralatan tidak ada

17 Marshaling MCB trip MCB di marshaling kios ada yang trip Alarm
18 Spare
19 Lock out 1 relay operated Relay lock out 1 bekerja Alarm

20 Lock out 2 relay operated Relay lock out 2 bekerja Alarm

21 General transformer internal alarm Gangguan pada internal trafo Alarm


Terjadi kebocoran sampai Warning Alarm stage 1
22 CB low pressure alarm
Tekanan Gas SF6 di bawah dan tidak bisa di Reset
23 Spare
24 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI REGULATOR PANEL 150 KV
BAY TRAFO#3 30 MVA

1 2 3 4 5 6
OIL LEVEL INDICATOR OIL LEVEL WINDING TEMP GENERAL WINDING TEMP WINDING TEMP
MAIN TANK INDICATOR INDICATOR TRANSFORMER INDICATOR INDICATOR
LOW LEVEL MAIN TANK ALARM INTERNAL LV SIDE HV SIDE
ALARM HIGH LEVEL ALARM ALARM TRIP TRIP
7 8 9 10 11 12
OIL LEVEL INDICATOR OIL LEVEL VOLTAGE BUCHOLZ POWER AC POWER
OLTC INDICATOR REGULATOR RELAY SUPPLY SUPPLY
LOW LEVEL OLTC DEVICE FAIL MAIN TANK UNDER TRIP
ALARM HIGH LEVEL ALARM TRIP VOLTAGE
13 14 15 16 17 18
BUCHOLZ PRESSURE PRESSURE PRESSURE DC POWER COOLING
RELAY RELIEF DEVICE RELIEF DEVICE RELIEF DEVICE SUPPLY FAN
MAIN TANK OLTC OLTC MAIN TANK TRIP FAILURE
ALARM ALARM TRIP TRIP
19 20 21 22 23 24
PRESSURE OIL TEMP PROTECTIVE OIL TEMP AC MCB DC MCB
RELIEF DEVICE INDICATOR RELAY INDICATOR TRIP TRIP
MAIN TANK MAIN TANK OLTC TRIP MAIN TANK
ALARM ALARM TRIP

NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA


Oil level indicator main tank Terjadi Gangguan Pada main tank trafo
1 CB Trip
low level alarm karena level minyak main tank trafo turun
Oil level indicator main tank Terjadi Gangguan Pada main tank trafo
2 CB Trip
high level alarm karena level minyak main tank trafo naik
Winding Temperatur indikator Terjadinya kenaikan Temperatur
3 Alarm
Alarm pada Winding
4 General transformer internal alarm Gangguan pada internal trafo Alarm
Winding Temperatur indikator LV side Adanya temperatur pada
5 CB Trip
Trip winding sisi LV yang sangat tinggi
Winding Temperatur indikator HV side Adanya temperatur pada
6 CB Trip
Trip winding sisi HV yang sangat tinggi
Oil level indicator OLTC Terjadi Gangguan Pada OLTC trafo
7 CB Trip
low level alarm karena level minyak OLTC turun
Oil level indicator OLTC Terjadi Gangguan Pada OLTC trafo
8 CB Trip
high level alarm karena level minyak OLTC naik
9 Voltage Regulator device fail Tap Changer Di Posisi Auto Alarm
Bucholz relay bekerja karena terdapatnya
10 Bucholz relay main tank trip CB Trip
udara yang sangat besar pada main tank
11 Power supply under voltage Tegangan di power supply turun Alarm
MCB VAC untuk power
12 AC power supply trip Supply VAC untuk peralatan tidak ada
supply trip
Warning Alarm stage 1
13 Bucholz relay main tank alarm Adanya Gas / Udara Pada Trafo
dan tidak bisa di Reset
Warning Alarm stage 1
14 Pressure relief device OLTC alarm Adanya tekanan udara di OLTC
dan tidak bisa di Reset
Adanya tekanan udara di OLTC yang
15 Pressure relief device OLTC trip CB Trip
sangat Tinggi
Adanya tekanan udara di main tank yang
16 Pressure relief device main tank trip CB Trip
sangat Tinggi
MCB VDC untuk power
17 DC power supply trip Supply VDC untuk peralatan tidak ada
supply trip
Adanya Salah satu MCB
18 Cooling fan failure Alarm
Supply Untuk Fan Trip
Warning Alarm stage 1
19 Pressure relief device main tank alarm Adanya tekanan udara di main tank
dan tidak bisa di Reset
Oil temperatur indicator main tank Terjadinya kenaikan temperatur minyak Warning Alarm stage 1
20
Alarm pada main tank trafo dan tidak bisa di Reset
Relay OLTC bekerja karena ada
21 Protective relay OLTC trip CB Trip
gangguan di OLTC trafo
Oil temperatur indicator main tank Terjadinya kenaikan temperatur minyak
22 CB Trip
trip pada main tank trafo yang tinggi
Salah satu MCB suplai VAC
23 AC MCB trip Alarm
trip
Salah satu MCB suplai VDC
24 DC MCB trip Alarm
trip
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
20 KV SWITCH GEAR MCSET-4

1 7 13 19 25
FEEDER 1 FEEDER 1 FEEDER 1 FEEDER 1 FEEDER 1
OVER CURRENT EARTH FAULTH AUTO UNDER UNDER
CIRCUIT CIRCUIT RECLOSER VOLTAGE FREQUENCY

2 8 14 20 26
FEEDER 2 FEEDER 2 FEEDER 2 FEEDER 2 FEEDER 2
OVER CURRENT EARTH FAULTH AUTO UNDER UNDER
CIRCUIT CIRCUIT RECLOSER VOLTAGE FREQUENCY

3 9 15 21 27
FEEDER 3 FEEDER 3 FEEDER 3 FEEDER 3 FEEDER 3
OVER CURRENT EARTH FAULTH AUTO UNDER UNDER
CIRCUIT CIRCUIT RECLOSER VOLTAGE FREQUENCY

4 10 16 22 28
FEEDER 4 FEEDER 4 FEEDER 4 FEEDER 4 FEEDER 4
OVER CURRENT EARTH FAULTH AUTO UNDER UNDER
CIRCUIT CIRCUIT RECLOSER VOLTAGE FREQUENCY

5 11 17 23 29
FEEDER 5 FEEDER 5 FEEDER 5 FEEDER 5 FEEDER 5
OVER CURRENT EARTH FAULTH AUTO UNDER UNDER
CIRCUIT CIRCUIT RECLOSER VOLTAGE FREQUENCY

6 12 18 24 30
FEEDER 6 FEEDER 6 FEEDER 6 FEEDER 6 FEEDER 6
OVER CURRENT EARTH FAULTH AUTO UNDER UNDER
CIRCUIT CIRCUIT RECLOSER VOLTAGE FREQUENCY

NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA

1 s/d 6 Feeder 1 … 6 overcurrent circuit Terjadi gangguan arus lebih pada feeder CB 20 kV Trip

7 s/d 12 Feeder 1 … 6 earthfault circuit Terjadi gangguan ke tanah pada feeder CB 20 kV Trip

13 s/d 18 Feeder 1 … 6 autorecloser CB 20 kV trip dan masuk kembali Alarm

19 s/d 24 Feeder 1 … 6 undervoltage Tegangan 20 kV turun dibawah settingan CB 20 kV Trip

25 s/d 30 Feeder 1 … 6 under frekwensi Frekwensi turun dibawah settingan CB 20 kV Trip


Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
20 KV SWITCH GEAR SCHNEIDER ELECTRIC

1 2 3 4 5
UFR 1 UFR 2 AUTO AUTO AUTO
RECLOSING 3 RECLOSING 4 RECLOSING 5
6 7 8 9 10
LOW LOW LOW LOW LOW
OVER CURRENT OVER CURRENT OVER CURRENT OVER CURRENT OVER CURRENT
11 12 13 14 15
HIGH HIGH HIGH HIGH HIGH
OVER CURRENT OVER CURRENT OVER CURRENT OVER CURRENT OVER CURRENT
16 17 18 19 20
LOW LOW LOW LOW LOW
EARTH FAULT EARTH FAULT EARTH FAULT EARTH FAULT EARTH FAULT
21 22 23 24 25
HIGH HIGH HIGH HIGH HIGH
EARTH FAULT EARTH FAULT EARTH FAULT EARTH FAULT EARTH FAULT
26 27 28 29 30
SPAM / 110 V DC SPAM / 110 V DC SPAM / 110 V DC SPAM / 110 V DC SPAM / 110 V DC
FAILURE FAILURE FAILURE FAILURE FAILURE

NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA

1 s/d 2 Feeder 1 … 2 UFR Frekwensi turun dibawah settingan CB 20 kV Trip

3 s/d 5 Feeder 3 … 5 auto reclosing CB 20 kV trip dan masuk kembali Alarm

6 s/d 10 Feeder 6 … 10 low over current Gangguan arus lebih pada settingan min. CB 20 kV Trip

11 s/d 15 Feeder 11 … 15 high over current Gangguan arus lebih pada settingan max. CB 20 kV Trip

16 s/d 20 Feeder 16 … 20 low earth fault Gangguan ke tanah pada settingan min. CB 20 kV Trip

21 s/d 25 Feeder 21 … 25 high earth fault Gangguan ke tanah pada settingan max. CB 20 kV Trip
Suplai VDC hilang dan SPAM tidak
25 s/d 30 SPAM/110 VDC failure MCB 110 VDC trip
bekerja
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
20 KV SWITCH GEAR SCHNEIDER ELECTRIC

1 9 17 25
OVER CURRENT OVER CURRENT SPARE SPARE
INCOMING 1 OUT GOING 1
2 10 18 26
OVER CURRENT SPARE SPARE SPARE
INCOMING 2
3 11 19 27
EARTH FAULT EARTH FAULT SPARE SPARE
INCOMING 1 OUT GOING
4 12 20 28
EARTH FAULT SPARE SPARE SPARE
INCOMING 2
5 13 21 29
UNDER VOLTAGE UNDER VOLTAGE SPARE SPARE
INCOMING 1 OUT GOING
6 14 22 30
UNDER VOLTAGE SPARE SPARE SPARE
INCOMING 2
7 15 23
UNDER FREQUENCY UNDER FREQUENCY SPARE
INCOMING 1 OUT GOING
8 16 24
UNDER FREQUENCY SPARE SPARE
INCOMING 2

NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA

1 s/d 2 Overcurrent incoming 1 & 2 Gangguan arus lebih pada incoming 1&2 CB 20 kV Trip

3 s/d 4 Earthfault incoming 1 & 2 Gangguan ke tanah pada settingan min. CB 20 kV Trip

5 s/d 6 Under voltage incoming 1 & 2 Tegangan turun dibawah settingan CB 20 kV Trip

7 s/d 8 Under frekwensi incoming 1 & 2 Frekwensi turun dibawah settingan CB 20 kV Trip

9 Overcurrent outgoing 1 Gangguan arus lebih pada outgoing CB 20 kV Trip

10 Spare

11 Earthfault outgoing Gangguan ke tanah pada outgoing CB 20 kV Trip

12 Spare

13 Under voltage outgoing Tegangan turun dibawah settingan CB 20 kV Trip

14 Spare

15 Under frekwensi outgoing Frekwensi turun dibawah settingan CB 20 kV Trip

16 s/d 30 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
20 KV SWITCH GEAR SCHNEIDER ELECTRIC

1 5 9 13 17 21
OVER EARTH OVER EARTH SPARE SPARE
CURRENT FAULTH CURRENT FAULTH
OUT GOING 1 OUT GOING 1 COUPLER COUPLER

2 6 10 14 18 22
OVER EARTH OVER EARTH SPARE SPARE
CURRENT FAULTH CURRENT FAULTH
OUT GOING 2 OUT GOING 2 INCOMING B INCOMING B

3 7 11 15 19
OVER EARTH OVER EARTH SPARE
CURRENT FAULTH CURRENT FAULTH
OUT GOING 3 OUT GOING 3 OUT GOING 4 OUT GOING 4

4 8 12 16 20
OVER EARTH OVER EARTH SPARE
CURRENT FAULTH CURRENT FAULTH
INCOMING A INCOMING A OUT GOING 5 OUT GOING 5

NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA

1 s/d 3 Overcurrent pada outgoing 1 s/d 3 Gangguan arus lebih pada outgoing CB 20 kV Trip

4 Overcurrent pada incoming A Gangguan arus lebih pada incoming CB 20 kV Trip

5 s/d 7 Earthfault outgoing 1 s/d 3 Gangguan ke tanah pada outgoing CB 20 kV Trip

8 Earthfault incoming A Gangguan ke tanah pada incoming A CB 20 kV Trip

9 Overcurrent coupler Gangguan arus lebih pada coupler 20 kV CB coupler 20 kV Trip

10 Earthfault incoming B Gangguan ke tanah pada incoming B CB 20 kV Trip

11 s/d 12 Overcurrent outgoing 4 s/d 5 Gangguan arus lebih pada outgoing CB 20 kV Trip

13 Earthfault coupler Gangguan ke tanah pada coupler 20 kV CB coupler 20 kV Trip

14 Earthfault incoming B Gangguan ke tanah pada incoming B CB 20 kV Trip

15 s/d 16 Earthfault outgoing 4 s/d 5 Gangguan ke tanah pada coupler 20 kV CB coupler 20 kV Trip

17 s/d 22 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY TRAFO#1 30 MVA

1 2 3 4 5
CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER MAIN PROTECTION BACK UP
SF6 LOW SF6 LOW POLE PROTECTION
PRESSURE TRIPPING ALARM DISCREPANCY OPERATED
6 7 8 9 10
BAY DRIVING HV APPARATUS MOTOR SPRING HEALTHY TRIP 1&2 TRIPPING
FAULT LOCAL CONTROL CHARGE OPERATION ALARM FROM 20KV

11 12 13 14 15
C1/T1/T2 DC TRANSFORMER SPARE SPARE SPARE
SUPPLY FAULT 2nd
FAILURE STAGE
16 17 18 19 20
SPARE TRANSFORMER SPARE SPARE SPARE
FAULT 1st
SATGE

ANNUNCIATOR YANG RELAY YANG


NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL BEKERJA
Circuit Breaker SF6 Low Terjadi kebocoran sampai
1 K 434 CB Trip
Pressure Tripping Tekanan Gas SF6 di bawah
Circuit Breaker SF6 Low Terjadi kebocoran sampai Warning Alarm stage 1
2 K 433
Alarm Tekanan Gas SF6 di bawah dan tidak bisa di Reset
Circuit Breaker Pole Terjadinya ketakserempakan Posisi Dari Circuit Breaker Ke Tiga
3 K 4511
Discrepancy pada cicuit breaker antara R,S,T Phasenya akan trip
Relay Differential Micom P632
4 Main Protection K 1870 CB Trip
bekerja karena gangguan
K 1500,1871, Relay Over Current.Micom
5 Back Up Protection Operated CB Trip
1872.151 P122 bekerja karena gangguan
K 450 Salah satu MCB Supply 3 phase untuk Motor DS dan Spring
6 Bay Driving Fault
K 472 DS atau CB trip pada Local control panel CB tidak bekerja
Control CB / DS trafo berubah pada posisi
7 HV apparatus local control CB / DS bekerja pada posisi lokal
lokal

8 Motor spring charge operation Motor spring charge CB bekerja


Adanya gangguan pada
9 Healthy Trip 1&2 Alarm K 4901-02 Putusnya Tripping Coil
rangkaian Tripping
Adanya kiriman Trip dari
10 Tripping from 20 kV K 4311 CB Trip
Penyulang / Incoming 20 KV
C1 / T1 / T2 DC Terjadinya salah satu MCB DC CB dan DS Atau Tripping
11 K 271-3
Supply Failure Supply Trip.Pada Control panel. ES1001 Tidak dapat bekerja
12 Transformer fault 2nd stage K 482 Terjadinya gangguan pada transformer CB Trip
13 Spare
14 Spare
15 Spare
16 Spare
17 Transformer fault 1st stage K 481-84 Memerlukan pengecekan ke Trafo Alarm
18 Spare
19 Spare
20 Spare

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI REGULATOR PANEL
BAY TRAFO#1 30 MVA

1 2 3 4 5
MAIN/OLTC OIL BUCHOLZ FAN CONTROL FAN AC HV / LV WINDING
LEVEL LOW ALARM SUPPLY FAILURE SUPPLY FAILURE TEMPERATUR
ALARM
6 7 8 9 10
BUCHOLZ OIL TEMPERATUR HV / LV WINDING PRESSURE RELIEF PRESSURE RELIEF
TRIP INDICATOR TEMPERATUR DEVICE DEVICE FOR
TRIP OLTC
11 12 13 14 15
OLTC PROTECTION COOLING FAULT VOLTAGE FIRE FIRE
RELAY TRIPPING FAN MOTOR REGULATION ALARM PROTECTION PROTECTION
FAILURE TAP CHARGE OUT OF DEVICE OUT OPERATE
16 17 18 19 20
SPARE SPARE SPARE SPARE SPARE

RELAY YANG
NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA
BEKERJA
Main / OLTC OIL
1 K 484 Terjadi Gangguan Pada OLTC CB Trip
Level Low
Warning Alarm stage 1
2 Bucholz Alarm K481 Adanya Gas / Udara Pada Trafo
dan tidak bisa di Reset
3 Fan Control Supply Failure K 486 Adanya Salah satu Fan Tidak Bekerja Alarm

4 Fan AC Supply Failure K 485 Suplai tegangan AC untuk Fan tidak ada Alarm
HV / LV WindingTemperatur Terjadinya kenaikan Temperatur
5 K 483 Alarm
Alarm pada Winding
Terdapatnya Udara Yang Sangat
6 Bucholz Trip K 4814 CB Trip
Besar pada main tank
Terjadinya kenaikan temperatur Circuit Breaker ketiga
7 Oil Temperatur Indicator K 4815
pada Oil yang cukup tinggi phasenya akan trip
HV / LV Winding Adanya temperatur pada
8 K 4816 CB Trip
Temperatur Trip winding yang sangat tinggi
Adanya tekanan udara di main tank yang
9 Presurre Relief Device K 4817 CB Trip
sangat Tinggi
Adanya tekanan udara di OLTC yang
10 Presurre Relief Device For OLTC K 4817 CB Trip
sangat Tinggi
OLTC Protection Relay Terjadinya gangguan pada
11 K 4818 CB Trip
Tripping Tap Changer
Cooling Fault Fan Motor Adanya Salah satu MCB
12 K 4805 Alarm
Failure Supply Untuk Fan Trip
Voltage Regulation alarm
13 K 4802 Tap Changer Di Posisi Auto Alarm
Tap Charge
Fire Protection Out Of
14 K 4810 Fire Protection Tidak diaktifkan Alarm
Device
15 Fire Protection Out Operate Fire Protection Tidak diaktifkan Alarm
16 Spare
17 Spare
18 Spare
19 Spare
20 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL 150 KV
BAY LINE 1&2 BATU BESAR

1 2 3 4 5
CIRCUIT BREAKER CIRCUIT BREAKER DISTANCE OVER CURRENT F67N
SF6 LOW SF6 LOW PROTECTION PROTECTION OPERATE
PRESSURE TRIPPING PRESSURE ALARM
6 7 8 9 10
POLE HV.APPARATUS SPRING CHARGE SPARE SPARE
DISCREPANCY LOCAL CONTROL FAILURE

11 12 13 14 15
SPARE SPARE ISOLATOR & CB BLOCKING FOR C1 / T1 / T2 /
MOTOR SUPPLY MAINTENANCE DC SUPPLIES
FAILURE FAILURE
16 17 18 19 20
HEALTHY TRIP 1 & 2 DEAD LINE CARRIER MCB VOLTAGE DISTANCE & DIRECTIONAL
ALARM DETECTION FAILURE TRANSFORMER PROTECTION RELAY
FAILURE OPENED IN OPERATIVE ALARM

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Circuit Breaker
1
Pressure Tripping Gas SF6 di bawah Supply Daya putus
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
2
Pressure Alarm Gas SF6 di bawah dan tidak bisa di Reset
3 Distance protection Maip Protection Bekerja CB Trip

4 Over Current Protection Back Up Protection Bekerja CB Trip


Terjadinya Gangguan Phase - Ground
5 F67 Operate CB Trip
pada Winding
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
6 Pole Discrepancy
Circuit Breaker antara R,S,T Phasenya akan trip
7 HV.Apparatus Local Control CB & DS posisi local Indikasi
Alarm dan perlu tindak
8 Spring Charge Failure Spring Charge CB tidak bekerja
lanjut
9 Spare

10 Spare

11 Spare

12 Spare
Isolator dan CB Supply Salah satu MCB supply tiga phase untuk DS
13 Alarm
failure atau CB Trip pada Local Control Panel
14 Bloking for Maintenance Terjadinya Block Untuk Breaker Alarm
Terjadinya salah satu MCB DC Supply Trip CB dan DS atau Tripping
15 C1 / T1 / T2 / DC Supply Failure
pada Control panel tidak dapat bekerja
Healthy Trip 1 & 2 Adanya Gangguan pada
16 Putusnya Tripping Coil
Alarm Rangkaian tripping
Dead Line detection
17 Hilang Tegangan Line Alarm
failure
18 Carrier failure Gangguan bawaan
Proteksi atau metering tidak
19 MCB Voltage trafo opened Salah satu MCB Trip Pada MK
dapat membaca tegangan
Distance & directional protection Alarm dan perlu tindak
20 Distance Block
relay in operative Alarm lanjut
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
BUS COUPLER 150 KV

1 2 3 4 5
CIRCUIT BREAKER POLE 110 V DC RECTIFIER OVER CURRENT
SF6 LOW DISCREPANCY FAULT FAULT PROTECTION
PRESSURE TRIPPING OPERATED
6 7 8 9 10
AC SUPPLY HV APPARATUS SPARE SPARE CIRCUIT BREAKER
FAILURE LOCAL CONTROL SF6 LOW
PRESSURE TRIPPING
11 12 13 14 15
CB SPRING ISOLATOR AND CB SPARE ON LOAD C1/ T1/T2/DC
CHARGE FAILURE MOTOR SUPPLY TRANSFER PROTECTION
FAILURE ANOMALY OUT OPERATE
16 17 18 19 20
HEALTH SPARE SPARE SPARE SPARE
TRIP 1&2 ALARM

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Circuit Breaker
1
Pressure Tripping Gas SF6 di bawah Supply Daya putus
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
2 Pole Discrepancy
Circuit Breaker antara R,S,T Phasenya akan trip
3 110 V DC fault MCB 110 DC trip Hilang supply 110 V DC

4 Rectifier fault Rectifier tidak bekerja

5 Over Current Protection operated Over current Protection Bekerja CB Trip


Terjadinya salah satu MCB AC Supply Trip CB dan DS atau Tripping
6 AC supply failure
pada Control panel tidak dapat bekerja
7 HV.Apparatus Local Control CB & DS posisi local Indikasi

8 Spare

9 Spare
Circuit Breaker SF6 Low Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
10
Pressure Alarm Gas SF6 di bawah dan tidak bisa di Reset
Alarm dan perlu tindak
11 CB Spring Charge Failure Spring Charge CB tidak bekerja
lanjut
Isolator dan CB Supply Salah satu MCB supply tiga phase untuk DS
12 Alarm
failure atau CB Trip pada Local Control Panel
13 Spare

14 On load transfer anomaly DS Bus 1 dan Bus 2 "ON"


C1 / T1 / T2 / DC protection out Terjadinya salah satu MCB DC Supply Trip CB dan DS atau Tripping
15
operate pada Control panel tidak dapat bekerja
Health Trip 1 & 2 Adanya Gangguan pada
16 Putusnya Tripping Coil
Alarm Rangkaian tripping
17 Spare

18 Spare

19 Spare
20 Spare

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR DI CONTROL PANEL
20 KV
1 2 3 4 5 6
INCOMING OUTGOING 1 OUTGOING 2 OUTGOING 3 OUTGOING 4 OUTGOING 5
SPARE AUTO RECLOSE AUTO RECLOSE AUTO RECLOSE AUTO RECLOSE AUTO RECLOSE
LOCK OUT LOCK OUT LOCK OUT LOCK OUT LOCK OUT
7 8 9 10 11 12
SPARE UNDER UNDER UNDER UNDER UNDER
FREQUENCY FREQUENCY FREQUENCY FREQUENCY FREQUENCY
FAIL FAIL FAIL FAIL FAIL
13 14 15 16 17 18
OVER OVER OVER OVER OVER OVER
CURRENT CURRENT CURRENT CURRENT CURRENT CURRENT
FAIL FAIL FAIL FAIL FAIL FAIL
19 20 21 22 23 24
EARTH EARTH EARTH EARTH EARTH EARTH
FAULT FAIL FAULT FAIL FAULT FAIL FAULT FAIL FAULT FAIL FAULT FAIL

25 26 27 28 29 30
DC SUPPLY DC SUPPLY DC SUPPLY DC SUPPLY DC SUPPLY DC SUPPLY
FAIL FAIL FAIL FAIL FAIL FAIL

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL

1 Incoming spare cadangan untuk incoming trafo


2 Outgoing 1 auto reclose lock out auto reclose bekerja pada outgoing 1 CB trip
3 Outgoing 2 auto reclose lock out auto reclose bekerja pada outgoing 2 CB trip
4 Outgoing 3 auto reclose lock out auto reclose bekerja pada outgoing 3 CB trip
5 Outgoing 4 auto reclose lock out auto reclose bekerja pada outgoing 4 CB trip
6 Outgoing 5 auto reclose lock out auto reclose bekerja pada outgoing 5 CB trip
7 Spare
8 Under frequency fail relay under frekwensi bekerja CB trip
9 Under frequency fail relay under frekwensi bekerja CB trip
10 Under frequency fail relay under frekwensi bekerja CB trip
11 Under frequency fail relay under frekwensi bekerja CB trip
12 Under frequency fail relay under frekwensi bekerja CB trip
13 Over current fail relay over current bekerja CB trip
14 Over current fail relay over current bekerja CB trip
15 Over current fail relay over current bekerja CB trip
16 Over current fail relay over current bekerja CB trip
17 Over current fail relay over current bekerja CB trip
18 Over current fail relay over current bekerja CB trip
19 Earth fault fail relay earth fault bekerja CB trip
20 Earth fault fail relay earth fault bekerja CB trip
21 Earth fault fail relay earth fault bekerja CB trip
22 Earth fault fail relay earth fault bekerja CB trip
23 Earth fault fail relay earth fault bekerja CB trip
24 Earth fault fail relay earth fault bekerja CB trip
CB dan relay atau Tripping tidak dapat
25 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
26 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
27 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
28 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
29 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
CB dan relay atau Tripping tidak dapat
30 DC Supply fail Terjadinya salah satu MCB DC Supply Trip
bekerja
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR PANEL CONTROL 150 KV
TRAFO#1 30 MVA

1 2 3 4 5
CB LOW GAS TRANSFORMER CB TRIP CB MOTOR CB LOW GAS
PRESSURE FAULT CIRCUIT OVER RUN PRESSURE
LOCK OUT TRIP FAILURE WARNING

6 7 8 9 10
TRANSFORMER SPARE CB MOTOR SPARE DC
FAULT SUPPLY SUPPLY
ALARM FAILURE FAILURE

11 12 13 14 15
SPARE DISCONNECTOR TRANSFORMER AC SUPPLY DC CHARGER
MOTOR DIFFERENTIAL TRIP 110 V TRIP
SUPPLY PROTECTION ALARM ALARM
FAILURE OPERATED
16 17 18 20 21
TRANSFORMER INTERTRIP DC 48 V DC 110 TRIP DC CHARGER
BACK UP FROM 20 KV TRIP ALARM 48 V TRIP
PROTECTION ALARM ALARM
OPERATED

NO ARTI INDIKASI AKIBATNYA / RELAY YANG BEKERJA LOKASI RESET CARA RESET

1 Tekanan Gas SF6 turun CB tidak dapat bekerja di panel control


Relay Bucholz,Relay suhu dan Cek OLTC kalau bahaya Tekan tombol reset
2 Gangguan di Trafo CB trip
pressure relief matikan dan laporkan U/suhu tunggu turun
Kesalahan rangkaian menyebabkan CB trip
3
CB trip
4
Terjadi kebocoran sampai di panel control Warning Alarm stage 1
5
Tekanan Gas SF6 di bawah
Gangguan di Trafo Bunyi alarm Relay Bucholz,Relay suhu dan Di Trafo Relay bucholz dan Tekan tombol reset
6
( Belum trip-kan CB ) pressure relief Pressure relief U/suhu tunggu turun
7 Spare
Suplai tegangan untuk penggerak CB tidak dapat bekerja
8
motor CB tidak ada
9 Spare
Terjadinya salah satu MCB DC CB dan DS Atau Tripping
10
Supply Trip.Pada Control panel. ES1001 Tidak dapat bekerja
11 Spare
Suplai tegangan untuk penggerak
12 DS tidak dapat bekerja
motor DS tidak ada
13 Ada gangguan di Daerah Trafo Relay differensial trafo
14 MCB di kontrol panel ada yang trip MCB trip di Kontrol panel Di kontrol panel Naikan MCB yang trip
15 MCB di DC charger 110 V trip DC charger tidak bekerja
Backup Relay Over Current.
16 CB Trip
bekerja karena gangguan
Adanya kiriman Trip dari penyulang /
17 CB Trip
Incoming 20 KV
18 MCB di DC 48 V trip DC charger tidak bekerja
19 Spare
20 MCB di DC 110 V trip DC charger tidak bekerja
21 MCB di DC charger 48 V trip DC charger tidak bekerja

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR REGULATOR PANEL
TRAFO#1 30 MVA

1 5 9 13 17 21
OIL LEVEL WINDING TEMP OIL OIL PRESS TRANSFORMER SPARE
TRANSFORMER ALARM TEMPERATUR VALVE COOLING
LOW ALARM TRIP TRANSFORMER "OUT"
TRIP
2 6 10 14 18 22
OIL LEVEL TRANSFORMER WINDING TAP CHARGE SPARE SPARE
OLTC COOLING TEMP IN
LOW ALARM FAULT ALARM TRIP PROGRAM

3 7 11 15 19 23
BUCHOLZ OLTC PROTECTION OLTC L/R SPARE SPARE
ALARM VOLTAGE RELAY SWITCH LOCAL
REGULATOR OLTC TRIP "ON"
ALARM
4 8 12 16 20 24
OIL BUCHOLZ OIL PRESS TRANSFORMER SPARE SPARE
TRANSFORMER TRIP VALVE COOLING
OLTC TRIP "ON"

NO ARTI INDIKASI RELAY YANG BEKERJA LOKASI RESET CARA RESET

Di Trafo minyaknya kurang Cek trafo kalau bahaya Harus dicek team HAR
1 Relay oil Level
(Baru alarm belum trip) matikan dan laporkan Tambah minyak trafo
Di OLTC minyaknya kurang Cek OLTC kalau bahaya Harus dicek team HAR
2 Relay oil Level
(Baru alarm belum trip) matikan dan laporkan Tambah minyak OLTC
Suhu Trafo panas relay bucholz Cek trafo kalau bahaya Harus dicek team HAR
3 bekerja alarm berbunyi belum trip Bucholz relay di Trafo matikan dan laporkan Buang gelembung udara
(ada gelembung udara karena panas)
Temperatur Trafo Mulai Tinggi Cek trafo kalau bahaya Harus dicek team HAR
5 Thermometer di Trafo
sehingga bunyi alarm dan belum trip matikan dan laporkan Tunggu suhu turun
6 MCB ada yang trip di MK OLTC Trafo MCB Q1-Q11 di MK OLTC Trip Panel di MK OLTC Naikan MCB yang Trip
7 Regulator voltage Gangguan Regulator volt di Panel OLTC Panel OLTC kontrol Harus dicek team HAR
Suhu Trafo panas relay bucholz Cek trafo kalau bahaya Harus dicek team HAR
8 bekerja mentripkan Trafo Bucholz Relay di Trafo matikan dan laporkan Buang gelembung udara
(ada gelembung udara karena panas)
Temperatur minyak trafo tinggi yang Cek trafo kalau bahaya Harus dicek team HAR
9
menyebabkan trafo trip matikan dan laporkan Tunggu suhu turun
Temperatur Trafo terlalu tinggi Harus dicek team HAR
10 Thermometer di Trafo Panel OLTC kontrol
sehingga Trafo trip Tunggu suhu turun
Relay pengaman OLTC bekerja Cek trafo kalau bahaya Harus dicek team HAR
11 Relay OLTC
Karena ada gangguan di OLTC matikan dan laporkan Cek OLTC
Tekanan tinggi pada Valve OLTC Cek trafo kalau bahaya Harus dicek team HAR
12 Relay Pressure
sehingga Trafo trip matikan dan laporkan Tekan tombol reset
13 Tekanan tinggi pada Valve Trafo Relay Pressure Panel OLTC kontrol Tekan Tombol Reset
14 Tap changer trafo sedang bekerja -
Saklar kontrol di MK OLTC Saklar Kontrol di MK OLTC di MK OLTC Rubah saklar kontrol
15
di rubah ke posisi lokal Di rubah ke posisi lokal ( Di Trafo ) ke posisi remote
Kipas-kipas pendingin bekerja Cek trafo kalau bahaya Harus dicek team HAR
16 Relay Thermometer
karena suhu Trafo mulai panas tinggi matikan dan laporkan Tunggu suhu turun
Kipas-kipas pendingin Mati
17 Relay Thermometer Panel OLTC kontrol Tekan tombol reset
Karena suhu Trafo Turun
19 Spare
20 Spare
21 Spare
22 Spare
23 Spare
24 Spare

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR PANEL CONTROL 150 KV
TRAFO#2 30 MVA

1 2 3 4 5
CB SF6 LOW CB SF6 LOW CB POLE MAIN BACK UP
PRESSURE PRESSURE DISCREPANCY PROTECTION PROTECTION
TRIPPING ALARM OPERATED

6 7 8 9 10
BAY HV APPARATUS MOTOR HEALTHY TRIPPING
DRIVING LOCAL SPRING TRIP 1 & 2 FROM 20 KV
FAULT CONTROL CHARGE ALARM
OPERATION
11 12 13 14 15
C1/T1/T2/DC TRANSFORMER SPARE SPARE SPARE
SUPPLY FAULT AND
FAILURE STAGE

16 17 18 20 21
SPARE TRANSFORMER SPARE SPARE SPARE
ALARM
IST STAGE

NO ARTI INDIKASI AKIBATNYA / RELAY YANG BEKERJA LOKASI RESET CARA RESET

1 Tekanan Gas SF6 turun CB tidak dapat bekerja di panel control


Terjadi kebocoran sampai
2 di panel control Warning Alarm stage 1
Tekanan Gas SF6 di bawah
Terjadinya ketakserempakan Posisi Circuit Breaker Ke Tiga phasenya akan
3
daripada cicuit breaker antara R,S,T trip
4 Ada gangguan di Daerah Trafo CB trip Relay differensial, tripping coil trafo Tekan reset pada relay
Backup Relay Over Current.
5 CB Trip Relay overcurrent trafo Tekan reset pada relay
bekerja karena gangguan
Salah satu MCB Supply 3 phase untuk Motor DS dan Spring Di local control panel CB atau DC Naikkan MCB supply 3
6 DS atau CB trip pada Local control CB tidak bekerja phasa yang trip
panel
Control CB trafo berubah pada posisi CB bekerja pada posisi lokal
7
lokal
8 Motor spring charge CB bekerja
Adanya gangguan pada rangkaian
9 Putusnya Tripping Coil
Tripping
Adanya kiriman Trip dari penyulang / Di penyulang / incoming 20 kV
10 CB Trip
Incoming 20 KV
Terjadinya salah satu MCB DC supply CB dan DS Atau Tripping tidak dapat di control panel Naikkan MCB yang trip
11
Trip.Pada Control panel. bekerja
12 Memerlukan pengecekan ke Trafo Alarm
13 Spare
14 Spare
15 Spare
16 Spare
17 Terjadinya gangguan pada transformer CB Trip
19 Spare
20 Spare
21 Spare

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR REGULATOR PANEL
TRAFO#2 30 MVA

1 5 9 13 17
OLTC HV/LV PRESSURE VOLTAGE SPARE
OIL LEVEL WINDING RELIEF REGULATOR
LOW TEMPERATURE DEVICE ALARM
ALARM TAP CHANGER
2 6 10 14 18
BUCHOLZ BUCHOLZ PRESSURE FIRE SPARE
ALARM TRIP RELIEF PROTECTION
DEVICE OUT
FOR OLTC DEVICE
3 7 11 15 19
FAN CONTROL OIL TEMP OLTC OIL SPARE
SUPPLY INDICATOR PROTECTION TEMPERATURE
FAILURE RELAY ALARM
TRIPPING
4 8 12 16 20
FAN AC HV/LV COOLING SPARE SPARE
SUPPLY WINDING FAULT FAN
FAILURE TEMPERATUR MOTOR
TRIP FAILURE

RELAY YANG
NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA
BEKERJA
OLTC oil
1 K 484 Terjadi Gangguan Pada OLTC CB Trip
Level Low
Warning Alarm stage 1
2 Bucholz Alarm K481 Adanya Gas / Udara Pada Trafo
dan tidak bisa di Reset
3 Fan Control supply Failure K 486 Adanya Salah satu Fan Tidak Bekerja Alarm

4 Fan AC Supply Failure K 485 Suplai tegangan AC untuk Fan tidak ada Alarm
Terjadinya kenaikan Temperatur
5 HV / LV winding Temperatur alarm K 483 Alarm
pada Winding
Terdapatnya Udara Yang Sangat
6 Bucholz Trip K 4814 CB Trip
Besar pada main tank
Terjadinya kenaikan temperatur Circuit Breaker ketiga
7 Oil Temperatur Indicator K 4815
pada Oil yang cukup tinggi phasenya akan trip
HV / LV Winding Adanya temperatur pada
8 K 4816 CB Trip
Temperatur trip winding yang sangat tinggi
Adanya tekanan udara yang
9 Pressure Relief Device K 4817 CB Trip
sangat Tinggi
Adanya tekanan udara di OLTC yang
10 Presurre Relief Device For OLTC K 4817 CB Trip
sangat Tinggi
OLTC Protection Relay Terjadinya gangguan pada
11 K 4818 CB Trip
Tripping Tap Changer
Cooling Fault Fan Motor Adanya Salah satu MCB
12 K 4805 Alarm
Failure Supply Untuk Fan Trip
Voltage Regulator alarm
13 K 4802 Tap Changer Di Posisi Auto Alarm
Tap Changer
Fire Protection Out
14 K 4810 Fire Protection Tidak diaktifkan Alarm
Dervice
Terjadinya kenaikan temperatur
15 Oil Temperature Alarm K 4815 Alarm
pada Oil yang cukup tinggi
16 s/d 20 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
BUS COUPLER 150 KV

1 2 3 4 5
CB SF6 POLE SPARE SPARE OVER
LOW DISCREPANCY CURRENT
PRESSURE PROTECTION
TRIPPING OPERATED
6 7 8 9 10
SPARE SPARE CB SPARE CB SF6
TRIPPING LOW
PRESSURE
ALARM
11 12 13 14 15
CB ISOLATOR AND 20 KV BJL C1/T1/T2/DC
SPRING CB MOTOR GENERAL SUPPLIES
CHARGE SUPPLY ALARM FAILURE
FAILURE FAILURE
16 17 18 19 20
HEALTHY SPARE SPARE SPARE SPARE
TRIP 1 & 2
ALARM

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
CB SF6 Low Terjadinya Kebocoran sampai tekanan Circuit Breaker
1
Pressure Tripping Gas SF6 di bawah Supply Daya putus
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
2 Pole Discrepancy
Circuit Breaker antara R,S,T Phasenya akan trip
3 Spare

4 Spare

5 Over Current Protection operated Over current Protection Bekerja CB Trip

6 Spare

7 Spare

8 CB tripping CB bekerja akibat gangguan CB Trip

9 Spare
CB SF6 Low Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
10
Pressure Alarm Gas SF6 di bawah dan tidak bisa di Reset
Alarm dan perlu tindak
11 CB Spring Charge Failure Spring Charge CB tidak bekerja
lanjut
Isolator dan CB Supply Salah satu MCB supply tiga phase untuk
12 Alarm
failure DS atau CB Trip pada Local Control Panel
13 20 kV general alarm

14 BJL
C1 / T1 / T2 / DC Terjadinya salah satu MCB DC CB dan DS atau Tripping
15
supplies failure supply trip pada Control panel tidak dapat bekerja
Healthy Trip 1 & 2 Adanya Gangguan pada
16 Putusnya Tripping Coil
Alarm Rangkaian tripping
17 s/d 20 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
LINE 1 HARAPAN & PANARAN

1 2 3 4 5
CB SF6 CB SF6 DISTANCE OVER F67N
LOW LOW PROTECTION CURRENT OPERATED
PRESSURE PRESSURE PROTECTION
ALARM TRIPPING
6 7 8 9 10
POLE HV SPRING AUTO BJL
DISCREPANCY APPARATUS CHARGE RECLOSING
LOCAL FAILURE PROGRESS
CONTROL
11 12 13 14 15
SPARE SPARE ISOLATOR BLOCKING C1/T1/T2/DC
AND CB MOTOR FOR SUPPLIES
SUPPLY MAINTENANCE
FAILURE
16 17 18 19 20
HEALTHY DEAD LINE CARRIER MCB DISTANCE &
TRIP 1&2 FAILURE FAILURE VOLTAGE DIRECTIONAL
ALARM TRANSFORMER PROTECTION RELAY
OPERATED IN OPERATIVE ALARM

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
CB SF6 Low Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
1
Pressure Alarm Gas SF6 di bawah dan tidak bisa di Reset
CB SF6 Low Terjadinya Kebocoran sampai tekanan Circuit Breaker
2
pressure Tripping Gas SF6 di bawah Supply Daya putus
3 Distance protection Main Protection Bekerja CB Trip

4 Over Current protection Back Up Protection Bekerja CB Trip


Terjadinya Gangguan Phase - Ground
5 F67N Operated CB Trip
pada Winding
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
6 Pole Discrepancy
Circuit Breaker antara R,S,T Phasenya akan trip
7 HV.Apparatus local control CB & DS posisi local Indikasi
Alarm dan perlu tindak
8 Spring Charge Failure Spring Charge CB tidak bekerja
lanjut
9 Autoreclosing progress CB trip dan masuk kembali Alarm

10 BJL

11 Spare

12 Spare
Isolator dan CB motor supply Salah satu MCB supply tiga phase untuk
13 Alarm
failure DS atau CB Trip pada Local Control Panel
14 Blocking for maintenance Terjadinya Block Untuk Breaker Alarm
Terjadinya salah satu MCB DC Supply CB dan DS atau Tripping
15 C / T1 / T2 / DC Supplies
trip pada Control panel tidak dapat bekerja
Healthy Trip 1 & 2 Adanya Gangguan pada
16 Putusnya Tripping Coil
Alarm Rangkaian tripping
Dead Line
17 Hilang Tegangan Line Alarm
failure
18 Carrier failure
Proteksi atau metering tidak
19 MCB VT operated Salah satu MCB bekerja / Trip Pada MK
dapat membaca tegangan
Distance & directional protection relay Alarm dan perlu tindak
20 Distance Block
in operative alarm lanjut
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
LINE 2 HARAPAN & PANARAN

1 2 3 4 5
CB FAILURE CB CB LOCAL CB CB POLE
OF GAS CLOSING CONTROL OPENING DISCREPANCY
PRESSURE INHIBITION POSITION INHIBITION ALARM
ALARM ALARM ALARM TRIP
6 7 8 9 10
MOTOR SUPPLY CVT'S DRIVING DISTANCE SOTF/STUB
HV APPARATUS INCOMING FAULT LINE TRIP
FAILURE FAILURE HV APPARATUS PROTECTION LOCK OUT
ALARM ALARM OPERATED
11 12 13 14 15
CO/CF TRIP CIRCUIT PROTECTIVE AUTO BJL
DISCREPANCY SUPERVISION RELAY FAILURE RECLOSING FAILURE PROTECTIVE
BJL OPERATED ALARM BJL OPERATED
ALARM LOCK OUT
16 17 18 19 20
SPARE SPARE SUPPLY 400/230 SPARE SUPPLY 110 VDC
VAC HEATING AND C/T1/T2/R1/R2
LIGHTING FAILURE FAILURE
ALARM ALARM

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
CB failure of gas Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
1
Pressure Alarm Gas SF6 di bawah dan tidak bisa di Reset
2 CB closing inhibition alarm CB menutup kembali akibat gangguan Alarm

3 CB local control position alarm Control CB pada posisi lokal Alarm

4 CB opening inhibition trip CB terbuka akibat gangguan CB Trip


Terjadinya ketakserempakan posisi dari
5 CB Pole Discrepancy Alarm Alarm
Circuit Breaker antara R,S,T
Motor supply HV apparatus failure Salah satu MCB supply tiga phase untuk Alarm dan perlu tindak
6
Alarm motor DS atau CB Trip lanjut
Alarm dan perlu tindak
7 CVT'S incoming failure CVT tidak membaca tegangan line
lanjut
Alarm dan perlu tindak
8 Driving fault HV apparatus alarm MCB di Box Kontrol DS ada yang trip
lanjut
Main protection/ distance relay bekerja
9 Distance line protection operated CB Trip
akibat adanya gangguan
10 SOTF/STUB trip lockout Gangguan SOTF/STUB CB Trip

11 CO/CF discrepancy BJL Alarm

12 Trip circuit supervision operated alarm TCS bekerja akibat gangguan Alarm

13 Protective relay failure alarm Distance relay gagal bekerja Alarm

14 Autoreclosing BJL CB trip dan masuk kembali Alarm

15 BJL failure protective operated lockout Distance relay gagal bekerja Alarm

16 Spare

17 Spare
Supply 400/230 VAC heating and Terjadinya salah satu MCB AC Supply
18 Heating & lighting tidak menyala
lighting failure alarm trip pada Control panel
19 Spare
Supply 110 VDC C / T1 / T2 / R1 / R2 Terjadinya salah satu MCB DC Supply CB dan DS atau Tripping
20
failure alarm trip pada Control panel tidak dapat bekerja
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR PANEL CONTROL 150 KV
TRAFO#1 30 MVA

1 2 3 4 5
CB SF6 LOW CB SF6 LOW CB POLE MAIN BACK UP
PRESSURE PRESSURE DISCREPANCY PROTECTION PROTECTION
TRIPPING ALARM OPERATED

6 7 8 9 10
BAY HV APARATUS MOTOR HEALTHY TRIPPING
DRIVING LOCAL SPRING TRIP 1 & 2 FROM 20 KV
FAULT CONTROL CHARGE ALARM
OPERATION
11 12 13 14 15
C1/T1/T2/DC TRANSFORMER SPARE SPARE SPARE
SUPPLY FAULT 2'ND
FAILURE STAGE

16 17 18 20 21
SPARE TRANSFORMER SPARE SPARE SPARE
ALARM
1'ST STAGE

NO ARTI INDIKASI AKIBATNYA / RELAY YANG BEKERJA LOKASI RESET CARA RESET

1 Tekanan Gas SF6 turun CB tidak dapat bekerja di panel control


Terjadi kebocoran sampai Tekan reset pada control
2 Warning Alarm stage 1 di panel control
Tekanan Gas SF6 di bawah panel trafo#1 30 MVA
Terjadinya ketakserempakan Posisi Circuit Breaker Ke Tiga phasenya akan
3
daripada cicuit breaker antara R,S,T trip
4 Ada gangguan di Daerah Trafo CB trip Relay differensial, tripping coil trafo Tekan reset pada relay
Backup Relay Over Current.
5 CB Trip Relay overcurrent trafo Tekan reset pada relay
bekerja karena gangguan
Salah satu MCB Supply 3 phase untuk Motor DS dan Spring Di local control panel CB atau DC Naikkan MCB supply 3
6 DS atau CB trip pada Local control CB tidak bekerja phasa yang trip
panel
Control CB trafo berubah pada posisi CB bekerja pada posisi lokal
7
lokal
8 Motor spring charge CB bekerja
Adanya gangguan pada rangkaian
9 Putusnya Tripping Coil
Tripping
Adanya kiriman Trip dari penyulang / Di penyulang / incoming 20 kV
10 CB Trip
Incoming 20 KV
Terjadinya salah satu MCB DC supply CB dan DS Atau Tripping tidak dapat di control panel Naikkan MCB yang trip
11
Trip pada Control panel bekerja
12 Terjadinya gangguan pada transformer CB Trip
13 s/d 16 Spare
17 Memerlukan pengecekan ke Trafo Alarm
18 s/d 21 Spare

Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.


KETERANGAN ANNUNCIATOR REGULATOR PANEL
TRAFO#1 30 MVA

1 2 3 4 5
MAIN/OLTC OIL BUCHHOLZ FAN CONTROL FAN AC HV / LV WINDING
LEVEL LOW ALARM SUPPLY FAILURE SUPPLY FAILURE TEMPERATUR
ALARM
6 7 8 9 10
BUCHHOLZ OIL TEMPERATUR HV / LV WINDING PRESSURE RELIEF PRESSURE RELIEF
TRIP INDICATOR TEMPERATUR DEVICE DEVICE FOR
TRIP OLTC
11 12 13 14 15
OLTC PROTECTION COOLING FAULT VOLTAGE FIRE FIRE
RELAY TRIPPING FAN MOTOR REGULATION ALARM PROTECTION PROTECTION
FAILURE TAP CHARGE OUT OF DEVICE OUT OPERATE
16 17 18 19 20
SPARE SPARE SPARE SPARE SPARE

RELAY YANG
NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA
BEKERJA
Main / OLTC OIL
1 K 484 Terjadi Gangguan Pada OLTC CB Trip
Level Low
Warning Alarm stage 1
2 Bucholz Alarm K481 Adanya Gas / Udara Pada Trafo
dan tidak bisa di Reset
3 Fan Control Supply Failure K 486 Adanya Salah satu Fan Tidak Bekerja Alarm

4 Fan AC Supply Failure K 485 Suplai tegangan AC untuk Fan tidak ada Alarm
HV / LV WindingTemperatur Terjadinya kenaikan Temperatur
5 K 483 Alarm
Alarm pada Winding
Terdapatnya Udara Yang Sangat
6 Bucholz Trip K 4814 CB Trip
Besar pada main tank
Terjadinya kenaikan temperatur Circuit Breaker ketiga
7 Oil Temperatur Indicator K 4815
pada Oil yang cukup tinggi phasenya akan trip
HV / LV Winding Adanya temperatur pada
8 K 4816 CB Trip
Temperatur Trip winding yang sangat tinggi
Adanya tekanan udara di main tank yang
9 Presurre Relief Device K 4817 CB Trip
sangat Tinggi
Adanya tekanan udara di OLTC yang
10 Presurre Relief Device For OLTC K 4817 CB Trip
sangat Tinggi
OLTC Protection Relay Terjadinya gangguan pada
11 K 4818 CB Trip
Tripping Tap Changer
Cooling Fault Fan Motor Adanya Salah satu MCB
12 K 4805 Alarm
Failure Supply Untuk Fan Trip
Voltage Regulation alarm
13 K 4802 Tap Changer Di Posisi Auto Alarm
Tap Charge
Fire Protection Out Of
14 K 4810 Fire Protection Tidak diaktifkan Alarm
Device
15 Fire Protection Out Operate Fire Protection Tidak diaktifkan Alarm
16 Spare
17 Spare
18 Spare
19 Spare
20 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR PANEL CONTROL 150 KV
TRAFO TM2500

1 6 11 16 21 26
CIRCUIT BREAKER BAY DRIVING C1 / T1 / T2 DC BUCHOLZ RUNNING IDEC AZUMI
SF6 LOW PRESSURE FAULT SUPPLIES RELAY
TRIPPING FALURE ALARM

2 7 12 17 22
CIRCUIT BREAKER HV APARATUS BUCHHOLZ OIL TEMPERATUR INCOMMING
SF6 LOW PRESSURE LOCAL CONTROL RELAY INDICATOR
ALARM TRIP ALARM

3 8 13 18 23
MAIN SPRING CHARGE OIL TEMPERATUR HV / LV WINDING CB OPEN
PROTECTION FAILURE INDICATOR TEMPERATUR POSITION
OPERATE TRIP ALARM 11,5 KV

4 9 14 19 24
BACK UP HEALTHY TRIP 1&2 HV / LV WINDING PRESSURE RELIEF CB CLOSE
PROTECTION ALARM TEMPERATUR DEVICE ALARM POSITION
OPERATE TRIP 11,5 KV

5 10 15 20 25
FAN CONTROL REF 1 PRESSURE RELIEF COOLING ON SPARE
SUPPLY OPERATE DEVICE TRIP
FAILURE

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
Circuit Breaker SF6 Low Terjadi kebocoran sampai
1 CB Trip
Pressure Tripping Tekanan Gas SF6 di bawah
Circuit Breaker SF6 Low Terjadi kebocoran sampai Warning Alarm stage 1
2
Alarm Tekanan Gas SF6 di bawah dan tidak bisa di Reset
Relay Differential Micom P632
3 Main protection operate CB Trip
bekerja karena gangguan
Relay Over Current.Micom
4 Back Up Protection Operate CB Trip
P122 bekerja karena gangguan
5 Fan Control supply Failure Suplai tegangan AC untuk Fan tidak ada Alarm
Salah satu MCB Supply 3 phase untuk Motor DS dan Spring
6 Bay Driving Fault
DS atau CB trip pada Local control panel CB tidak bekerja
Control CB / DS trafo berubah pada posisi
7 HV apparatus local control CB / DS bekerja pada posisi lokal
lokal

8 Spring charge failure Motor spring charge CB gagal bekerja Alarm dan CB tidak bisa masuk
Adanya gangguan pada
9 Healthy Trip 1&2 Alarm Putusnya Tripping Coil
rangkaian Tripping
10 REF 1 operate Relay REF 1 bekerja CB Trip
C1 / T1 / T2 DC Terjadinya salah satu MCB DC CB dan DS Atau Tripping
11
Supply Failure Supply Trip.Pada Control panel. ES1001 Tidak dapat bekerja
Terdapatnya Udara Yang Sangat
12 Bucholz relay trip CB Trip
Besar pada main tank
Terjadinya kenaikan temperatur Circuit Breaker ketiga
13 Oil Temperatur Indicator trip
pada Oil yang cukup tinggi phasenya akan trip
HV / LV Winding Adanya temperatur pada
14 CB Trip
Temperatur trip winding yang sangat tinggi
Adanya tekanan udara yang
15 Pressure Relief Device trip CB Trip
sangat Tinggi
Terdapatnya Udara pada main tank yang
16 Bucholz relay alarm Alarm
mengganggu trafo
Terjadinya kenaikan temperatur
17 Oil Temperatur Indicator alarm Alarm
pada Oil trafo
HV / LV Winding Adanya temperatur pada
18 Alarm
Temperatur alarm winding yang tinggi
Adanya tekanan udara yang
19 Pressure Relief Device alarm Alarm
Tinggi
20 Cooling on Pendingin trafo bekerja indikasi
21 Running Trafo dalam keadaan on indikasi
22 Incomming CB incoming 20 kV on indikasi
23 CB open position 11.5 kV CB 11.5 kV trafo posisi off indikasi
24 CB close position 11.5 kV CB 11.5 kV trafo posisi on indikasi
25 Spare
26 IDEC azumi
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR REGULATOR PANEL 150 KV
TRAFO TM2500

1 2 3 4 5
MAIN / OLTC OIL BUCHHOLZ FAN CONTROL FAN AC HV/LV WINDING
LEVEL LOW ALARM SUPPLY SUPPLY TEMPERATUR
FAILURE FAILURE ALARM

6 7 8 9 10
BUCHHOLZ OIL HV/LV WINDING PRESSURE PRESSURE
TRIP TEMPERATUR TEMPERATUR RELIEF RELIEF
INDICATOR TRIP DEVICE DEVICE
FOR OLTC
11 12 13 14 15
OLTC COOLING VOLTAGE FIRE OIL TEMPERATUR
PROTECTION FAULT FAN REGULATOR PROTECTION ALARM
RELAY TRIPPING MOTOR FAILURE ALARM TAP CHARGE OUT OF DEVICE

16 17 18 19 20
SPARE SPARE SPARE SPARE SPARE

RELAY YANG
NO ANNUNCIATOR YANG TIMBUL MAKSUD ANNUNCIATOR AKIBATNYA
BEKERJA
OLTC oil
1 K 484 Terjadi Gangguan Pada OLTC CB Trip
Level Low
Warning Alarm stage 1
2 Bucholz Alarm K481 Adanya Gas / Udara Pada Trafo
dan tidak bisa di Reset
3 Fan Control supply Failure K 486 Adanya Salah satu Fan Tidak Bekerja Alarm

4 Fan AC Supply Failure K 485 Suplai tegangan AC untuk Fan tidak ada Alarm
Terjadinya kenaikan Temperatur
5 HV / LV winding Temperatur alarm K 483 Alarm
pada Winding
Terdapatnya Udara Yang Sangat
6 Bucholz Trip K 4814 CB Trip
Besar pada main tank
Terjadinya kenaikan temperatur Circuit Breaker ketiga
7 Oil Temperatur Indicator K 4815
pada Oil yang cukup tinggi phasenya akan trip
HV / LV Winding Adanya temperatur pada
8 K 4816 CB Trip
Temperatur trip winding yang sangat tinggi
Adanya tekanan udara yang
9 Pressure Relief Device K 4817 CB Trip
sangat Tinggi
Adanya tekanan udara di OLTC yang
10 Presurre Relief Device For OLTC K 4817 CB Trip
sangat Tinggi
OLTC Protection Relay Terjadinya gangguan pada
11 K 4818 CB Trip
Tripping Tap Changer
Cooling Fault Fan Motor Adanya Salah satu MCB
12 K 4805 Alarm
Failure Supply Untuk Fan Trip
Voltage Regulator alarm
13 K 4802 Tap Changer Di Posisi Auto Alarm
Tap Changer
Fire Protection Out of
14 K 4810 Fire Protection Tidak diaktifkan Alarm
Dervice
Terjadinya kenaikan temperatur
15 Oil Temperature Alarm K 4815 Alarm
pada Oil yang cukup tinggi
16 s/d 20 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR REGULATOR PANEL 150 KV
TRAFO PLTG UNIT 1&2

1 5 9 13
DIFFERENTIAL NEUTRAL OVER LOCK OUT TRANSFORMER
PROTECTION CURRENT RELAY BUCHHOLZ
TRIP SR 745 PROTECTION OPERATED TRIP
TRIP SR 760
2 6 10 14
GROUND FAULT OVER CURRENT DC SUPPLY TRANSFORMER
PROTECTION PROTECTION PROTECTION OIL TEMPERATURE
TRIP SR 745 FAILURE SR 760 CUBICLE TRIP
FAILURE
3 7 11 15
DIFFERENTIAL TRIPPING COIL 1 AC SUPPLY TRANSFORMER
PROTECTION FAILURE PROTECTION WINDING
FAILURE SR 760 CUBICLE TEMPERATURE
SR 745 FAILURE TRIP
4 8 12 16
PHASE OVER CURRENT TRIPPING COIL 2 TRANSFORMER TRANSFORMER
PROTECTION FAILURE OIL LEVEL PRESSURE
TRIP SR 760 SR 760 MINIMUM TRIP RELIEF TRIP

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
Main protection/relay SR 745 bekerja
1 Differential protection trip SR 745 CB Trip
karena adanya gangguan internal trafo
Relay SR 745 bekerja akibat gangguan
2 Ground fault protection trip SR 745 CB Trip
arus lebih ke tanah
Main protection/relay SR 745 gagal
3 Differential protection failure SR 745 Alarm
bekerja mengisolir gangguan
Back up protection over current / relay
4 Phase over current protection trip SR 760 CB Trip
SR 760 bekerja
Back up protection neutral over current
5 Neutral overcurrent protection trip SR 760 CB Trip
/ relay SR 760 bekerja
Back up protection/relay SR 760 gagal
6 Overcurrent protection failure SR 760 Alarm
bekerja mengisolir gangguan
7 Tripping coil 1 failure SR 760 Tripping coil 1 gagal mentripkan CB Alarm

8 Tripping coil 2 failure SR 760 Tripping coil 2 gagal mentripkan CB Alarm

9 Lock out relay operated Lock out relay bekerja Alarm


MCB VDC untuk suplai proteksi pada
10 DC supply protection cubicle failure Alarm
kubikel trip
MCB VAC untuk suplai proteksi pada
11 AC supply protection cubicle failure Alarm
kubikel trip
12 Transformer oil level minimum trip Minyak trafo di main tank berkurang CB Trip
Terdapatnya Udara pada main tank yang
13 Transformer buchholz trip CB Trip
sangat Tinggi
Terjadinya kenaikan temperatur
14 Transformer oil temperatur trip CB Trip
pada Oil yang tinggi
Adanya temperatur pada
15 Transformer winding temperatur trip CB Trip
winding trafo yang sangat tinggi
Adanya tekanan udara yang
16 Transformer pressure relief trip CB Trip
sangat Tinggi
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR REGULATOR PANEL 150 KV
TRAFO PLTG UNIT 3&4

1 5 9 13
DC SUPPLY MECHANISM CB OVER CURRENT NEGATIVE SEQUENCE
CONTROL CUBICLE CLOSING PROTECTION PROTECTION TRIP
FAILURE LOCK OUT TRIP SR-745 SR-760

2 6 10 14
AC SUPPLY DC MOTOR NEUTRAL OVER SPARE
CONTROL CUBICLE POWER SUPPLY CURRENT
FAILURE FAILURE PROTECTION TRIP
SR-745
3 7 11 15
LOSS OF SF6 AC SUPPLY TRANSFORMER SPARE
MARSHALLING OVERLOAD
FAILURES SR-745

4 8 12 16
GENERAL LOCK OUT CVT'S NEGATIVE SEQUENCE SPARE
SF6 MCB PROTECTION TRIP
TRIP SR-745

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
MCB VDC untuk suplai control pada
1 DC supply control cubicle failure Alarm
kubikel trip
MCB VAC untuk suplai control pada
2 AC supply control cubicle failure Alarm
kubikel trip
Terjadi kebocoran sampai tekanan gas
3 Loss of SF6 Alarm
SF6 di bawah
4 General lock out SF6 Tekanan Gas SF6 turun CB Trip

5 Mechanism CB closing lock out Closing lock out CB bekerja Alarm


MCB VDC untuk suplai motor DS/CB
6 DC motor power supply failure Alarm
trip
MCB VAC untuk suplai MK ada yang
7 AC supply marshalling failures Alarm
trip
8 CVT's MCB trip MCB pada CVT's ada yang trip Alarm
Back up protection over current / relay
9 Over current protection trip SR 745 CB Trip
SR 745 bekerja
Back up protection neutral over current
10 Neutral over current protection trip SR 745 CB Trip
/ relay SR 745 bekerja
Relay SR 745 bekerja akibat kelebihan
11 Transformer overload SR 745 CB Trip
beban trafo
Relay SR 745 bekerja akibat gangguan
12 Negative sequence protection trip SR 745 CB Trip
arus lebih urutan negatif
Relay SR 760 bekerja akibat gangguan
13 Negative sequence protection trip SR 760 CB Trip
arus lebih urutan negatif
14 s/d 16 Spare
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
BUS COUPLER 150 KV

1 7 13 19
CIRCUIT BREAKER SPARE CIRCUIT BREAKER CIRCUIT BREAKER
LOW GAS TRIP CIRCUIT MOTOR
PRESSURE LOCKOUT FAILURE OVERRUN

2 8 14 20
CIRCUIT BREAKER SPARE CT BUS WIRE CIRCUIT BREAKER
LOW GAS SUPERVISION ALARM MOTOR SUPPLY
PRESSURE WARNING FAILURE

3 9 15 21
SPARE DC SUPPLY SPARE DISCONNECTOR
FAILURE MOTOR SUPPLY
FAILURE

4 10 16
BUSBAR ZONE 1 BUSBAR ZONE 2 SPARE
PROTECTION PROTECTION
OPERATED OPERATED

5 11 17
OVERCURRENT ON LOAD SPARE
PROTECTION TRANSFER
OPERATED ABNORMALITY

6 12 18
SPARE SPARE SPARE

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
Circuit breaker Low gas Terjadinya Kebocoran sampai tekanan Circuit Breaker
1
Pressure lock out Gas SF6 di bawah Supply Daya putus
Circuit breaker Low gas Terjadinya Kebocoran pada Warning Alarm stage 1
2
Pressure warning Gas SF6 dan tidak bisa di Reset
3 Spare
Relay proteksi busbar untuk zone 1
4 Busbar zone 1 protection operated CB Trip
bekerja
5 Over Current Protection operated Over current Protection Bekerja CB Trip

6 Spare

7 Spare

8 Spare

9 DC supply failure MCB untuk supply VDC ada yang trip Alarm
Relay proteksi busbar untuk zone 2
10 Busbar zone 2 protection operated CB Trip
bekerja
11 On load transfer abnormality DS Bus 1 dan Bus 2 "ON" Alarm

12 Spare

13 Circuit breaker trip circuit failure Rangkaian tripping gagal mentripkan CB Alarm

14 CT bus wire supervision alarm Alarm

15 s/d 18 Spare

19 Circuit breaker motor overrun Motor CB bekerja tidak normal Alarm


Salah satu MCB supply tiga phase untuk
20 Circuit breaker motor supply failure Alarm
CB Trip pada Local Control Panel
Salah satu MCB supply tiga phase untuk
21 Disconnector motor supply failure Alarm
DS Trip pada Local Control Panel
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
LINE 1 & 2 MUKA KUNING

1 2 3 4 5
CB SF6 CB SF6 DISTANCE OVERCURRENT F67N
LOW PRESSURE LOW PRESSURE PROTECTION PROTECTION OPERATED
TRIPPING ALARM

6 7 8 9 10
POLE HV APPARATUS SPRING A/R SUCCESS SPARE
DISCREPANCY LOCAL CONTROL CHARGE
FAILURE

11 12 13 14 15
SPARE SPARE ISOLATOR BLOCKING C1 / T1 / T2 / DC
& CB MOTOR FOR SUPPLIES
SUPPLY FAILURE MAINTENANCE

16 17 18 19 20
HEALTHY DEADLINE CARRIER MCB VOLTAGE DISTANCE &
TRIP 1 & 2 DETECTION FAILURE TRANSFORMER DIRECTIONAL
ALARM FAILURE OPENED PROTECTION RELAY
IN OPERATIVE ALARM

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
CB SF6 Low Terjadinya Kebocoran sampai tekanan
1 CB Trip
pressure Tripping Gas SF6 di bawah
CB SF6 Low Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
2
pressure alarm Gas SF6 di bawah dan tidak bisa di Reset
3 Distance protection Main Protection Bekerja CB Trip

4 Over Current protection Back Up Protection Bekerja CB Trip


Terjadinya Gangguan Phase - Ground
5 F67N Operate CB Trip
pada Winding
Terjadinya ketakserempakan posisi dari Circuit Breaker ketiga
6 Pole Discrepancy
Circuit Breaker antara R,S,T Phasenya akan trip
7 HV.Apparatus local control CB & DS posisi local Indikasi
Alarm dan perlu tindak
8 Spring Charge Failure Spring Charge CB tidak bekerja
lanjut
9 Autoreclosing progress CB trip dan masuk kembali Alarm

10 Spare

11 Spare

12 Spare
Isolator dan CB motor supply Salah satu MCB supply tiga phase untuk
13 Alarm
failure DS atau CB Trip pada Local Control Panel
14 Blocking for maintenance Terjadinya Block Untuk Breaker Alarm
Terjadinya salah satu MCB DC Supply CB dan DS atau Tripping
15 C / T1 / T2 / DC Supplies
trip pada Control panel tidak dapat bekerja
Healthy Trip 1 & 2 Adanya Gangguan pada
16 Putusnya Tripping Coil
Alarm Rangkaian tripping
Dead Line detection
17 Hilang Tegangan Line Alarm
failure
18 Carrier failure
Proteksi atau metering tidak
19 MCB VT opened Salah satu MCB bekerja / Trip Pada MK
dapat membaca tegangan
Distance & directional protection relay Alarm dan perlu tindak
20 Distance Block
in operative alarm lanjut
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.
KETERANGAN ANNUNCIATOR DI CONTROL PANEL
LINE 1 & 2 SAGULUNG

1 2 3 4 5
CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER
FAILURE OF GAS CLOSING INHIBITION LOCAL CONTROL OPENING INHIBITION POLES DISCREPANCY
PRESSURE ALARM ALARM POSITION ALARM TRIP ALARM

6 7 8 9 10
MOTOR SUPPLY CVT'S LINE DRIVING FAULT DISTANCE SOFT / STUB
HV APPARATUS FAILURE HV APARATUS ALARM MAIN PROTECTION TRIP
FAILURE ALARM OPERATED

11 12 13 14 15
OC/EF TRIP CIRCUIT PROTECTIVE RELAY AUTORECLOSING BREAKER FAILURE
DIRECTIONAL OC / EF SUPERVISION FAILURE ( WATCHDOG ) COMMAND PROTECTION
BACK-UP PROTECTION OPERATED ALARM OPERATED
OPERATED ALARM
16 17 18 19 20
SPARE SPARE SUPPLY 400/230 VAC SPARE SUPPLY 110 VDC
HEATING AND LIGHTING C/T1/T2/R1/R2
FAILURE ALARM FAILURE ALARM

ANNUNCIATOR YANG
NO MAKSUD ANNUNCIATOR AKIBATNYA
TIMBUL
CB failure of gas Terjadinya Kebocoran sampai tekanan Warning Alarm stage 1
1
Pressure Alarm Gas SF6 di bawah dan tidak bisa di Reset
2 CB closing inhibition alarm CB menutup kembali akibat gangguan Alarm

3 CB local control position alarm Control CB pada posisi lokal Alarm

4 CB opening inhibition trip CB terbuka akibat gangguan CB Trip


Terjadinya ketakserempakan posisi dari
5 CB Pole Discrepancy Alarm Alarm
Circuit Breaker antara R,S,T
Motor supply HV apparatus failure Salah satu MCB supply tiga phase untuk Alarm dan perlu tindak
6
Alarm motor DS atau CB Trip lanjut
Alarm dan perlu tindak
7 CVT'S line failure CVT tidak membaca tegangan line
lanjut
Alarm dan perlu tindak
8 Driving fault HV apparatus alarm MCB di Box Kontrol DS ada yang trip
lanjut
Main protection/ distance relay bekerja
9 Distance main protection operated CB Trip
akibat adanya gangguan
10 SOTF/STUB trip Gangguan SOTF/STUB CB Trip
OC/EF, directional OC/EF back up
11 Back up protection bekerja CB Trip
protection operated
12 Trip circuit supervision operated alarm TCS bekerja akibat gangguan Alarm

13 Protective relay failure alarm Distance relay gagal bekerja Alarm

14 Autoreclosing command CB trip dan masuk kembali Alarm

15 Breaker failure protection operated Distance relay gagal bekerja Alarm

16 Spare

17 Spare
Supply 400/230 VAC heating and Terjadinya salah satu MCB AC Supply
18 Heating & lighting tidak menyala
lighting failure alarm trip pada Control panel
19 Spare
Supply 110 VDC C / T1 / T2 / R1 / R2 Terjadinya salah satu MCB DC Supply CB dan DS atau Tripping
20
failure alarm trip pada Control panel tidak dapat bekerja
Catatan : Sebelum reset alarm gangguan, catat dulu gangguannya.