Page 48 of 58 Issue date 10.02.2012 RDSO/SPN/165/2012 Version 3.

Annexure II-D
IPS for upto 6 lines without AFTC RE Area
(SDO/IPS/PI-6L/RE/004)
AVR
230/110 V, 500 VA Track Circuit (UP)
1.5 KVA
230/110 V, 500 VA Track Circuit (DN)
AVR
2 KVA Transformers
FRBC
Inverter 230/110V, 500 VA
n+1 Signals Up
110V, 20A 110 VDC 230/110V, 500 VA
2 KVA
110V, 20A 230/110V, 500 VA Signals Down
2 KVA 230 VAC
230V/ 110V, 20A 230/110V, 500 VA
30.21 A Battery
110V, 20A
AC Mains
110 V, 200AH SM Panel
DC-DC Converters DC-DC Converters
24-32 V, 5 A 12-40 V, 1 A Block Line
24-32 V, 5 A 12-40 V, 1 A UP
Relay
24-32 V, 5 A Internal
24-32 V, 5 A (n + 2) 12-40 V, 1 A Block Line
12-40 V, 1 A DN
24-32 V, 5 A
24-32 V,55AA
24-32 V,
3-6 V, 0.1 A Block Tele UP
24-32 V, 5 A Relay 3-6 V, 0.1 A
24-32 V, 5 A External
3-6 V, 0.1 A Block Tele DN
24-32 V, 5 A 3-6 V, 0.1 A

24-32 V, 5 A Axle Counter 2-12 V, 5 A For Spare Cells


24-32 V, 5 A (Optional)
2-12 V, 5 A

12-28 V, 5 A Panel Indication 24-32 V, 5 A For


12-28 V, 5 A 24-32 V, 5 A Data Logger

12-28 V, 5 A Block Local 24-32 V, 5 A


12-28 V, 5 A 24-32 V, 5 A For EI
HKT 24-32 V, 5 A (Optional)
12-28 V, 1 A & 24-32 V, 5 A
12-28 V, 1 A Magneto
Fuse, 20 A Point Machine
DG Set Capacity
12.5/15 KVA
Note: i) For 60V metal to metal relay circuit, the rating of DC-DC Converter for relay internal and external shall be 60-66V/5A
ii) Depending upon type of block instrument, the DC-DC converter for block line may be taken as 12-40/1A or 40-
100V/1A or 100-150V/1A
iii) SMR shall be in n+1 configuration, DC-DC converter for internal circuits shall be in n+ 2 configurations & for
other circuits in n+1 configuration.