Está en la página 1de 31

EQUIPMENT: iFLOW

PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02

3. EQUIPMENT DESCRIPTIONS
SECTION EQUIPMENT DESCRIPTION PART No.
3.1 80 litre container assembly - 300 bar (with contacted pressure gauge) 73130006H
80 litre container assembly - 300 bar (with standard pressure gauge) 73130007H
140 litre container assembly - 300 bar (with contacted pressure gauge) 74106020H
140 litre container assembly - 300 bar (with standard pressure gauge) 74106021H
80 litre container assembly - 200 bar (with contacted pressure gauge) 73131025H
80 litre container assembly - 200 bar (with standard pressure gauge) 73131026H
140 litre container assembly - 200 bar (with contacted pressure gauge) 74106018H
140 litre container assembly - 200 bar (with standard pressure gauge) 74106019H
Container label (INERGEN) 35116318
Pilot container label 35116391
80 litre container assembly - 300 bar (Australian work cover approved with c/press g) 73130032
80 litre container assembly - 300 bar PESO (INDIA) approved 73130029
140 litre container assembly - 300 bar PESO (INDIA) approved 74106044
3.2.1 300 bar iFLOW container valve (without limit switch) 21114042
300 bar iFLOW container valve (with limit switch) 21114043
3.2.2 200 bar iFLOW container valve (without limit switch) 21114040
200 bar iFLOW container valve (with limit switch) 21114041
3.3.1 3/8 in. 180° discharge nozzle 30400007
1/2 in. 180° discharge nozzle 30400008
3/4 in. 180° discharge nozzle 30400009
1 in. 180° discharge nozzle 30400010
1-1/4 in. 180° discharge nozzle 30400011
1-1/2 in. 180° discharge nozzle 30400012
2 in. 180° discharge nozzle 30400013
3.3.2 3/8 in. 360° discharge nozzle 30400000
1/2 in. 360° discharge nozzle 30400001
3/4 in. 360° discharge nozzle 30400002
1 in. 360° discharge nozzle 30400003
1-1/4 in. 360° discharge nozzle 30400004
1-1/2 in. 360° discharge nozzle 30400005
2 in. 360° discharge nozzle 30400006
Nozzle orifice plate 3/8 in. 30440032
Nozzle orifice plate 1/2 in. 30440042
Nozzle orifice plate 3/4 in. 30440052
Nozzle orifice plate 1 in. 30440062
Nozzle orifice plate 1-1/4 in. 30440072
Nozzle orifice plate 1-1/2 in. 30440082
Nozzle orifice plate 2 in. 30440092
Nozzle/pipe sealing plate 3/8 in. 30410320
Nozzle/pipe sealing plate 1/2 in. 30410420
Nozzle/pipe sealing plate 3/4 in. 30410520
Nozzle/pipe sealing plate 1 in. 30410620
Nozzle/pipe sealing plate 1-1/4 in. 30410720
Nozzle/pipe sealing plate 1-1/2 in. 30410820
Nozzle/pipe sealing plate 2 in. 30410920
3.4 Pneumatic actuator 30116APB
3.5 Manual actuator 30180APB
3.6 Pneumatic -manual actuator 3018NAPB
3.7 Discharge pressure switch 30330010
3.8 Pressure gauge assembly - standard (300 bar) 42116056
Pressure gauge assembly- contacted (300 bar) 42116057
Pressure gauge assembly- standard (200 bar) 42116054
Pressure gauge assembly- contacted (200 bar) 42116055

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 17 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02

SECTION EQUIPMENT DESCRIPTION PART No.


3.9 3 litre pilot container - standard 70100075H
13 litre pilot container - standard 70100082H
50 litre pilot container - standard 70121011H
3 litre pilot container - (Australian work cover approved) 70100084
13 litre pilot container - (PESO (India) approved ) 70100083
50 litre pilot container - (PESO (India) approved ) 70121012
3.10 Gas metron 30110604
3.11 iFLOW check valve 21114011
Blind cap ¾ in. 30390160
Dowty seal ¾ in. 95108010
3.12 iFLOW discharge hose - 350 mm long ¾ in. (80 litre) 91116026
iFLOW discharge hose - 450 mm long ¾ in. (140 litre) 91116045
iFLOW discharge hose - 590 mm long ¾ in. (80 litre) 91116030
iFLOW discharge hose - 690 mm long ¾ in. (140 litre) 91116046
3.13 iFLOW discharge hose ‘Y’ connector 35116261
iFLOW discharge hose connector 35116260
3.14 Wall mount bracket (3 containers) 36116200
Wall mount bracket (2 containers) 36116274
Support screw 36116291
Set of bolts 36116292
iFLOW bracket 36116293
Single row manifold bracket 30680006
Manifold support single/double row 30640006
3.15 iFLOW 140 litre container bracket single row bracket (2 containers) 30602100
iFLOW 140 litre container bracket single row bracket (3 containers) 30603100
iFLOW modular bracket 30621010
Bolt Assembly 36116292
iFLOW 140 litre container bracket double row bracket (4 containers) 3060410D
iFLOW 140 litre container bracket double row bracket (6 containers) 3060610D
Manifold Support Single 3064006
U bolt (1 in.) 3060060
U bolt (2 in.) 3060090
U bolt (3 in.) 30600110
U bolt (4 in.) 30600120
3.16 iFLOW actuation hose - 580 mm long ¼ in. 30506014
iFLOW actuation hose - 700 mm long ¼ in. 30522001
3.17 1/4 in. bleed valve 20007020
3.18.1 Pilot valve adaptor 35116381
3.18.2 Pilot line non return valve 20006020
3.19 Decompression screw 30027301
3.20 Selector valve 20mm (¾ in.) w/solenoid w/o manual 21100050
Selector valve 25mm (1 in.) w/solenoid w/o manual 21100060
Selector valve 30mm (1¼ in.) w/solenoid w/o manual 21100070
Selector valve 38mm (1½ in.) w/solenoid w/o manual 21100080
Selector valve 50mm (2 in.) w/solenoid w/o manual 21100090
Selector valve 65mm (2½ in.) w/solenoid w/o manual 62116006
Selector valve 75mm (3 in.) w/solenoid w/o manual 62116004
Selector valve 100mm (4 in.) w/solenoid w/o manual 62116005
Outlet Union (3/4 in) 30888001
Outlet Union (1 in) 30888002
Outlet Union (1 1/4 in) 30888003
Outlet Union (1 1/2 in) 30888004
Outlet Union (2 in) 30888005
Outlet Union (2 1/2 in) 30888006
Outlet Union (3 in) 30888007
Outlet Union (4 in) 30888008
PAGE 18 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02

SECTION EQUIPMENT DESCRIPTION PART No.


3.20 Pneumatic Cylinder Fitting 30880007
3.20.1 Solenoid with Manual Release 30130250
Solenoid only with blind cap 30130251
Selector valve solenoid mounting bracket (3 solenoids) 30650013
Selector valve solenoid mounting bracket (4 solenoids) 30650014
Selector valve solenoid mounting bracket (2 solenoids) 30650022
3.20.2 Lock off assembly 302.200.072
3.20.3 Selector valve manifold - standard (2 selector valves) TBA
Selector valve manifold - standard (3 selector valves) TBA
Selector valve manifold - standard (4 selector valves) TBA
Selector valve manifold - standard (5 selector valves) TBA
Selector valve manifold - standard (6 selector valves) TBA
Selector valve manifold - galvanised (2 selector valves) TBA
Selector valve manifold - galvanised (3 selector valves) TBA
Selector valve manifold - galvanised (4 selector valves) TBA
Selector valve manifold - galvanised (5 selector valves) TBA
Selector valve manifold - galvanised (6 selector valves) TBA
Welded nipple for selector valve TBA
3.21 1 in. diameter iFLOW manifold - standard and galv (80 litre container) TBA
2 in. diameter iFLOW manifold - standard and galv(80 litre container) TBA
3 in. diameter iFLOW manifold - standard and galv (80 litre container) TBA
4 in. diameter iFLOW manifold - standard and galv (80 litre container) TBA
1 in. diameter iFLOW manifold - standard and galv (140 litre container) TBA
2 in. diameter iFLOW manifold - standard and galv (140 litre container) TBA
3 in. diameter iFLOW manifold - standard and galv (140 litre container) TBA
4 in. diameter iFLOW manifold - standard and galv (140 litre container) TBA
3.22 Pressure relief valve 62104002
3.23 Half hard 6mm copper pipe - 3 metres 308.002.002
Copper pipe (6 x 4mm) 30804060
Copper pipe coupling (1/4 in. x 6 mm) 30880007
Equal tee (6 mm) 30880015
Hose connector (1/4 in. to hose - female/female) 30880008
Bonded seal (1/4 in. dowty) 31199813
3.24 Goose neck wrench 35017401 to 35017404
3.25 Manual release caution plate 63013030
3.26 Door caution plate - lock-off 63013031
3.27 Door caution plate - no lock-off 63013032

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 19 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.1 iFLOW INERGEN CONTAINER AND VALVE ASSEMBLIES

iFLOW systems are configured around a range of eight temperature information are fitted to all containers.
container and valve assemblies. Containers are coloured red to BS4800 : 04 E53 with a green
Each basic assembly consists of: top dome to RAL 7031.
1) Container c/w transport cap Containers must not be subject to direct sunlight or adverse
2) Valve assembly weather conditions and must not be positioned where
3) Container labels water can accumulate around the base.
Each container size can be supplied with either a standard * Container for Australian Work Cover Approved Market
pressure gauge or a contacted pressure gauge fitted. Only.
** PESO (INDIA) Approved Market.
Each assembly is provided with a specific charge of INERGEN
to a maximum pressure of 200 bar or 300 bar (+0 / -5 bar) at
15°C.
Filling details for each type and size of container are shown
in Tables 8.
GB DANGER
HIGH PRESSURE CONTAINER, CAPABLE OF VIOLENT
DISCHARGE. EXTREMELY HAZARDOUS. MAY CAUSE
SEVERE INJURY. DO NOT REMOVE PRESSURE GAUGE
ON A CHARGED CONTAINER.
READ AND FOLLOW ALL INSTRUCTIONS WITHIN
THE INSTALLATION MANUAL. SAFETY PROCEDURES
INDICATED IN THE MANUAL MUST BE FOLLOWED
IN EXACT SEQUENCE BEFORE INSTALLING AND
REMOVAL OF CONTAINERS. SYSTEM USERS/OWNER
MUST CHECK PRESSURE ON THE GAUGE WEEKLY.
FULL SYSTEM SERVICE AND MAINTENANCE TO
BE CARRIED OUT AT 6 MONTHLY INTERVALS BY
TRAINED SERVICE PERSONNEL.
SP PELIGRO
CONTENDOR DE ALTA PRESIÓN, SUSCEPTIBLE DE
DESCARGA VIOLENTA. EXTREMADAMENTE
PELIGROSO. PUEDE OCASIONAR LESIONES GRAVES. PRESSURE/TEMPERATURE CHART ( INERGEN )
NO RETIRE EL MANÓMETRO CUANDO EL CONTENDOR
ESTÉ CARGADO. 375
300 bar system @ 15˚C
LEA Y SIGA LAS INSTRUCCIONES QUE APARECEN 350 200 bar system @ 15˚C
EN EL MANUAL DE INSTALACIÓN. ANTES DE LA
INSTALACIÓN Y RETIRADA DE LOS CONTENDORS 325
DEBEN SEGUIRSE LOS PROCEDIMIENTOS DE SEGURIDAD
EN EL MISMO ORDEN EN EL QUE ESTÁN INDICADOS 300
EN EL MANUAL. EL PROPIETARIO O LOS USUARIOS

Pressure (bar g)
DEL SISTEMA DEBEN COMPROBAR LA PRESIÓN EN 275
EL MANÓMETRO SEMANALMENTE. EL SERVICIO Y
MANTENIMIENTO COMPLETOS DEL SISTEMA DEBEN 250
LLEVARSE A CABO EN INTERVALOS DE 6 MESES

Standard Contacted
Y POR PERSONAL DE SERVICIO DEBIDAMENTE 225
INSTRUIDO.
200
FR DANGER
CONTENEUR À HAUTE PRESSION, RISQUE DE VIOLENTES 175
DÉCHARGES. EXTRÊMEMENT DANGEREUX. PEUT
CAUSER DE GRAVES BLESSURES. NE PAS RETIRER LE 150
MANOMÈTRE D’UN CONTENEUR CHARGÉ.
125
LIRE ET SUIVRE TOUTES LES INSTRUCTIONS
CONTENUES DANS LE MANUEL D’INSTALLATION. -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60
LES PROCÉDURES DE SÉCURITÉ INDIQUÉES DANS LE
MANUEL DOIVENT ÊTRE EFFECTUÉES DANS L’ORDRE Temperature (oC)
EXACT AVANT L’INSTALLATION ET LE RETRAIT DES
CONTENEURS. LES UTILISATEURS/ LE PROPRIÉTAIRE

Container INERGEN INERGEN


DU SYSTÈME DOIVENT VÉRIFIER LA PRESSION
VIA LE MANOMÈTRE DE FAÇON HEBDOMADAIRE.
L’ENTRETIEN ET LA MAINTENANCE COMPLETS DU
SYSTÈME DOIVENT ÊTRE OPÉRÉS TOUS LES 6 MOIS
PAR DU PERSONNEL D’ENTRETIEN FORMÉ. EXTINGUISHING AGENT SPECIFICATION
GEFAHR INERGEN
HOCHDRUCK-BEHÄLTER. PLÖTZLICHER STARKER
GASAUSTRITT MÖGLICH! SEHR GEFÄHRLICH! KANN NITROGEN = 52%
SCHWERE VERLETZUNGEN VERURSACHEN. BEI ARGON = 40%
UNTER DRUCK STEHENDER BEHÄLTER KEINE CARBON DIOXIDE = 8%
DRUCKMESSGERÄT .
NOMINAL COMPOSITION (REFER TO ISO 14520)
LESEN UND BEFOLGEN SIE ALLE ANWEISUNGEN
IN DER AUFBAUANLEITUNG. IN DER ANLEITUNG UN1956 Tyco Fire Protection Products
VORGESCHRIEBENE SICHERHEITSABLÄUFE SIND

Part Pressure Pressure Pressure


USBAU VON BEHÄLTER Burlingham House Hewett Road
IN DER ANGEGEBENEN REIHENFOLGE STRIKT ZU
BEFOLGEN. SY TREIBER Gapton Hall Industrial Estate
MÜSSEN DEN DRUCK WÖCHENTLICH MITHILFE DER Great Yarmouth NR31 0NN United Kingdom
MANOMETER KONTROLLIEREN. EINE VOLLSTÄNDIGE
INSTANDHALTUNG UND WARTUNG DES SYSTEMS Tel: +44 1493 417 600
MUSS HALBJÄHRLICH DURCH AUSGEBILDETES
SERVICEPERSONAL ERFOLGEN. Approved System Fax: +44 1493 417 700

Size Quantity Quantity


Number (bar) Gauge Gauge
(Litres) (m3) (kg)
Fitted Fitted
73130006H 300 80 No Yes 23.0 33.1
73130007H 300 80 Yes No 23.0 33.1
74106020H 300 140 No Yes 40.2 57.9
74106021H 300 140 Yes No 40.2 57.9
73131025H 200 80 No Yes 16.5 23.8
73131026H 200 80 Yes No 16.5 23.8
74106018H 200 140 No Yes 28.9 41.6
74106019H 200 140 Yes No 28.9 41.6
025294
73130032* 300 80 No Yes 23.0 33.1
73130029** 300 80 No Yes 23.0 33.1
74106044** 300 140 No Yes 40.2 57.9 Fig 3 Container and Valve Assembly
(Showing Dimensions - See Table 9)
  Table 8  Filling Details for iFLOW INERGEN Technical Specification
Container and Valve Assemblies
Dimensions and weights for each assembly are shown in Minimum Test Pressure: 450 bar (300 bar system
Table 9. 300 bar (200 bar system)
(2010/35/EC)
Containers are designed, manufactured and marked in Nominal Working Pressure: 300 bar and 200 bar (at 15 °C)
accordance with 2010/35/EC and are pressure tested to 300 Nominal Working Pressure: 358 bar and 235 bar (at 50 °C)
or 450 bar.
Labels providing safety, maintenance and pressure

Container Dimension Dimension Dimension Tare Gross


Pressure Dimension A
Size B C D Weight Weight
(bar) (mm)
(Litres) (mm) (mm) (mm) (kg) (kg)

80 300 269 1780 1825 1955 103 136


140 300 360 1745 1790 1920 215 273
80 200 269 1780 1825 1955 93 117
140 200 360 1745 1790 1920 202 244

  Table 9  Dimensions and weights for iFLOW INERGEN Container and Valve Assemblies
PAGE 22 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.9 PILOT CONTAINER - STANDARD Height Diameter
Max Pipe
Con- Max. No. Length
Part Dimension Dimension
tainer Containers (6mm
(Part No. 70100075H, 70100082H and 70121011H) Number A B
Size Operated tube)
(mm) (mm)
mtrs
There are three sizes of pilot container 3 litre (Part No. 70100075H 3 litre 635 100 40 50
70100075H), 13 litre (Part No. 70100082H) and 50 litre (Part 70100082H 13 litre 1210 140 150 125
No. 70121011H). Each size of pilot container is charged with 70121011H 50 litre 1620 229 200 165
Nitrogen to 100 bar. 70100084* 3 litre 635 100 40 50
These pilot containers are used to pneumatically operate an 70100083** 13 litre 1210 140 150 125
70121012** 50 litre 1620 229 200 165
iFLOW system. They can also operate Selector valves if fitted
to the system.
Table12 Pilot Container Details
The maximum number of iFLOW containers that can be *Australian Approved Market Only
operated by these pilot containers are shown in table 12. **PESO (INDIA) Approved Market Only
The solenoid valve is factory-fitted and must not be Technical Specification
removed on site for testing purposes.
Gas Type: Nitrogen
Container Pressure: 100 bar
Container Test Pressure: 300 bar
Pressure Gauge: 0 to 160 bar
Working Temperature Range: -20 °C to 50 °C
Actuation Method: Manual / Electrical
Bracket Type: Wall Mounted
Weight: 10.6 kg

The pilot container is supplied with a solenoid, manual


actuator, contacted pressure gauge, mounting bracket,
outlet adaptor, 700mm hose, ¼ BSPT Male to 6mm
compression adaptor and a bleed valve.

PUL L

0-160bar pressure gauge


complete with a contact
switch set to signal if the
container pressure drops to
90 bar.

025307

Fig. 19 iFLOW Pilot Container Details

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 35 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.15 iFLOW 140 LITRE CONTAINER BRACKETS Please note:
Manifold brackets and ‘U Bolts’
(Part Nos. as shown below)
are ordered separately
The 140 litre iFLOW container brackets are supplied in
sets. They are single row two containers, single row three
containers. Each set is detailed in Table 15.

2
1

025314

Fig. 29 iFLOW Single Row 140 Litre Container Brackets

Part
Item Number Description
Number
1 30602100 Single Row (2 Containers)
30603100 Single Row (3 Containers shown )
30621010 Modular bracket (1 Container)
2 30680006 Manifold Support Single
3 30600060 U Bolt ( 1 in.)
30600090 U Bolt (2 in. )
30600110 U Bolt (3 in. )
30600120 U Bolt ( 4 in. )

Table 15 140 Litre Container Bracket Details


Larger container bank configurations are created by using
the above bracket sets multiple times, for example a five
container single row system requires 1 x 30602100 and 1 x
30603100.
Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 43 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.15 iFLOW 140 LITRE CONTAINER BRACKETS Please note:
Manifold brackets and ‘U Bolts’
(Part Nos. as shown below)
are ordered separately
The 140 litre iFLOW container brackets are supplied in sets.
They are double row four containers and double row six
containers. Each set is detailed in Table 16.

3
1
2

Fig. 30 iFLOW Double Row 140 Litre Container Brackets


025338

Part
Item Number Description
Number
1 3060410D Double Row (4 Containers shown)
3060610D Double Row (6 Containers)
2 30680006 Manifold Support Single
3 30600060 U Bolt ( 1 in.)
30600090 U Bolt (2 in. )
30600110 U Bolt (3 in. )
30600120 U Bolt ( 4 in. )

Table 16 140 Litre Container Bracket Details

Larger container bank configurations are created by using


the above bracket sets multiple times, for example a five
container single row system requires 1 x 3060410D and 1 x
3060610D.

PAGE 44 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.12 iFLOW DISCHARGE HOSE
(Part No. 91116026, 91116030, 91116045 and 91116046)
Discharge hose connecting the container to manifold. Part Length Container
End Thread
Number Dimension A Size
¾ in. nominal diameter made of synthetic rubber with one
91116026 G 3/4 in. ISO228 350 mm 80 L
mid metal braid (R1) and an outer layer of synthetic rubber
91116030 G 3/4 in. ISO228 590 mm 80 L
resistant to weathering.
91116045 G 3/4 in. ISO228 450 mm 140 L
Working pressure of 155 bar and burst pressure of 620 bar. 91116046 G 3/4 in. ISO228 690 mm 140 L

Table.13 Discharge Hose Details

025312

Fig. 25 iFLOW Discharge Hose

Technical Specification Location on System


Connected between Check Valve
Internal Hose Inner Diameter: 19 mm
Installation Instructions
Connection Inner Diameter: 16 mm
See section 4.4 of the manual.
Maximum Working Pressure: 155 bar
Test Pressure: 233 bar Operating Instructions
Minimum Burst Pressure: 620 bar The discharge hose is a pressure connector and requires no
Minimum Bend Radius: 175 mm operating instructions.
Maximum Bend Angle: 360 °
Weight: 0.63 kg (Part No. 91116026) Maintenance Instructions
0.79 kg (Part No. 91116030) In case of faults or suspected faults contact customer
0.68kg (Part No. 91116045)
services to organize replacement.
0.82kg (Part No. 91116046)
Approvals: LPCB, VdS
Certification: EN 12094-8
CE Certification Number: 0768-CPD-30123
Year of CE Marking: 2013
CE Marking Requirements: Manufacturer, Part Number,
Batch No, Working Pressure, Hose
Type, CE0768
Method of Marking: Engraving

PAGE 40 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.11 iFLOW CHECK VALVE
(Part No. 21114011)
The iFLOW check valve is supplied with a 3/4 in. male
coupling and dowty seal. It is interconnected with two
hoses (Part No. 91116026 and 91116030). The male end if this
hose is sealed by a bonded seal and the female end of the
hose connects to the 3/4 in. male coupling supplied with
the iFLOW check valve. The inlet to the iFLOW check valve is
fitted with a female swivel nut which fits directly on to the
outlet of the iFLOW container valve. When necessary a blind
cap (Part No. 30390160) is used to blank off any unused
ports, see figure 8. This blind cap is sealed with a dowty seal
(Part No. 95108010).

21114011

Fig. 23 Part No. 21114011 iFLOW Check Valve

PAGE 38 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
iFLOW CHECK VALVE (CONTINUED)

Technical Specification Location on System


Connected between the discharge hoses.
Body: Brass
Cap: Brass Installation Instructions
Piston: Brass Refer to section 4.3 of the manual.
Nut: Brass
Spring: Stainless Steel Operating Instructions
Inlet Connection Thread: W.21.7 DIN477 The manifold check valve will automatically open on
Outlet Connection Thread: 6. 3/4 in. ISO228 system discharge and close at end of discharge and
Typical Working Pressure: 60 bar at 20 °C therefore requires no operating instructions.
Maximum Working Pressure: 140 bar
Test Pressure: 140 bar
Cross Sectional Area: 113 mm²
Weight: 0.70 kg
Approvals: LPCB, VdS
Certification: EN 12094-13
CE Certification Number: 0786-CPD-30138
Year of CE Marking: 2011
CE Marking Requirements: Manufacturer, Part Number, DNXX,
Working Pressure, Direction of
Flow, Serial No, CE0786
Method of Marking: Engraving
Overall Size: 81 mm x Dia 52 mm

3/4 in. Blind Cap


(Part No. 30390160)

Male coupling
(Part No. 35116260)

Male end of hose


3/4 in. Dowty Seal
(Part no. 95108010)
Female end of hose

3/4 in. Dowty Seal


(Part no. 95108010)

025311

Fig. 24 iFLOW Hose Connection Details

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 39 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.20.2 LOCK OFF ASSEMBLY
(Part No. 302.200.072)

The Lock-off unit can be used to lock the extinguishing


mmediately.
processThe warnings
and to in theThe
release it again. Operating Instructions
Lock-off unit consists of a for
2/2-directional ball valve with a relief bore hole and built-on
parts. Two switches can be built onto the device to monitor
the two positions. The padlock enclosed with the product
can be used to secure each of the end positions. The ball
valve must be installed so that it points in the correct
direction. A fixing bracket and screws are enclosed in the
package, together with two adapters.

An adaptor (Part No. 309.010.005) is included with the


assembly to provide a connection between the lock off unit
and the 6mm copper nickel pipe actuation arrangement.

Technical Specification

Nominal diameter: DN 8
Operating pressure: 200 bar
Max. operating pressure: 240 bar
Test pressure: 315 bar
Outlet Adaptor: 1/4 in. NPT Female
Material: steel, nickel-plated
Weight: 0.8 kg
Approval: VdS
Identification marking: CE
Certification body: 0786-VdS

Maintenance Instructions
If the Lock off unit is used properly, it requires no
maintenance. Damaged Lock-off units must be replaced
immediately. The warnings in the Operating Instructions for
the extinguishing system must be followed.
In case of faults or suspected faults contact customer
services to organize replacement.

025059

Fig. 40 Lock Off Assembly

PAGE 52 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.19 DECOMPRESSION SCREW
(Part No. 30027301)
After actuation of a container bank the pneumatic acuation
line retains pressure from the pilot container. To enable safe
release of the pressure a decompression screw is fitted to
the last pneumatic cone in place of the normal pneumatic
cone fixing screw. The pneumatic cone has a blanking
plate fitted and this must be removed prior to installing the
decompression screw.

Decompression Screw

Fig. 35 Part No. 30027301 Decompresssion Screw

Pneumatic Cone
30027201

Following a discharge the following procedure is used to


release the Nitrogen trapped in the pneumatic actuation
line:
i) Remove cap (7)
ii) Using a flat screwdriver remove internal
cap (5).
iii) Reverse the internal cap (5) and re-install in Technical Specification
the decompression screw. The hexagon will
be facing outwards. Fit cap (7) back onto the Body: Brass
unit and begin to tighten using a 6mm Allen Internal Parts: Nitrile
wrench. As you tighten pressure will begin to Connection: 1/4 in. BSPP
escape from the pneumatic actuation line. Test Pressure: 420 bar
iv) When all internal pressure has been vented Working Pressure: 140 bar
unscrew cap (7) remove internal cap (5) and Overall Size: 68mm x 23.5mm0mm
re-install in its original orientation. (hex. 22mm )
v) Re-fit cap (7) checking that its o-ring is still Weight: 0.23 kg
retained in its groove.

025354

PAGE 48 of 100
iFLOW INERGEN Total Flood Fire SECTION 3 – SYSTEM COMPONENTS
Suppression System Manual
(Part No. 14A-23H-03) 2017-JAN-04    REV. 3    PAGE 3-16

PNEUMATIC ACTUATOR
(Part No. 30118APB)
The pneumatic actuator can be installed on to the iFLOW
valve. It comprises of an internal piston complete with firing
pin. Following actuation by pressure the firing pin moves ! !WARNING
CAUTION
forward and ruptures a burst disc in the iFLOW valve causing
it to operate. It can be fitted with up to three actuating hoses. Failure to reset the actuator prior to fitting onto the
It is supplied with a ¼ in. blind cap which can be fitted to the container valve will result in the immediate operation of the
unit to blank off one of the inlets (if required by the container container valve and the potentially hazardous discharge of
bank configuration). the container.

The actuator requires a minimum pressure of 60 bar to cause


operation.

35116429

025302A

30116APBmod

FIG. 3-16 PART NO. 30118APB  PNEUMATIC ACTUATOR

Technical Specification Location on System


Connected to the port on the container discharge valve.
Body: Brass
Actuator Pin: Stainless Steel Installation Instructions
Pipe Connection: M30 x 1.5 Female Refer to page 4-12.
Inlet Connections: 1/4 in. BSPP Note the 35mm-60mm ‘C’ Spanner is required (Part No.
Maximum Working Pressure: 370 bar 35017401)
Minimum Trigger Pressure: 60 bar
Nominal Trigger Pressure: 100 bar (with pilot container) Operating Instructions
300 bar (without pilot The pneumatic actuator is operated by pressure via a hose
container) connection from either the master container or pilot container.
Maximum Trigger Pressure: 370 bar Once operated the pneumatic actuator will require manual
Weight: 0.37 kg resetting before re-fitting to the iFLOW container valve.
Working Temperature Range: -20 °C to 50 °C
Maintenance Instructions
Testing of Actuator: Possible
Approvals: LPCB, VdS Refer to Section 6.
Certification: EN 12094-4
CE Certification Number: 0786-CPD-30139
Year of CE Marking: 2011
CE Marking Requirements: Manufacturer, Part Number,
Serial No, Working Pressure,
CE0786
Method of Marking: Engraving
Overall Size: 64 mm x 50 mm
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.23 ACTUATION PIPING

(Part No. as shown in table)


Part
Description Unit of Measure
Number
308.002.00 6mm half hard copper tube 3 metres long
30804060 Copper Pipe 6mm O/D 1 metre long
30880007 Copper Pipe Coupling (1/4 in. x 6mm) N/A
30880015 Equal Tee (6 mm) N/A
30880008 Hose Connector N/A
(1/4 in. Pilot hose - female/female)
31199813 1/4 in. Dowty Seal N/A

Table 23 Actuation Piping Part Numbers

PNEUMATIC ACTUATION COMPONENTS (CONTINUED)


6mm Copper Nickle Pipe 6mm Half Hard Pipe
(Part No. 30804060) (Part No. 308.002.000)
The copper nickle pipe (suitable for bending) is used to Where extensive actuation runs are required, 6mm half hard
connect pressure activated devices to the system, e.g. slave copper pipe can be used. This is supplied in 3m lengths and
container, pressure switch, etc. is not suitable for bending.

30804068 025023

Fig. 44 Part No. 30804060 6mm O.D. Copper Nickle Pipe Fig. 45 Part No. 308.002.000 6mm O.D. Copper Half Hard
Technical Specification Technical Specification 025023

Material: Copper Nickel Alloy Material: Phosphorous De-Oxidised Copper


Specification: CN102 Specification: BS6017 Grade Cu-DHP
Maximum Working Pressure: 149.5 bar Maximum Working Pressure: 149.5 bar
Supplied Length: 1m Supplied Length: 3m
Weight: 0.078 kg/m Weight: 0.078 kg/m

PAGE 56 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
PNEUMATIC ACTUATION COMPONENTS (CONTINUED)

6mm Compression Tee ¼ in. BSPT x 6 mm Stud Coupling


(Part No. 30880015) (Part No. 30880007)
This is used primarily for connecting pilot lines from one This is used in the pilot line when using copper nickel pipe
slave container to the next. and fits into the manual-pneumatic actuator (Part No.
302.207.003).

60.0
025025
025024

Fig. 46 Part No. 30880015 Compression Tee Fig. 48 Part No. 30880007 6mm Coupling Stud (BSPT)
Technical Specification Technical Specification

Material: Brass Material: Brass


Connection: 6mm DIN 2353 Compression Fittings Connection: 1/4 in. BSPT
Overall Size: 60 mm x 37.5 mm Overall Size: 33.5 mm x 16 mm
Weight: 0.064 kg Weight: 0.024 kg

1/4 in. BSP Socket


Dowty Seal 1/4 in. Part No. 31199813
(Part No. 30880008)
On systems using both 6mm copper nickle pipe and flexible
actuation hose a 1/4 in. BSP socket is used to make the
connection. One side of the socket connects to the pilot
hose (Part No. 30506014(550mm) or 30522001(700mm).
The other side of the socket connects to the pilot line
copper nickle pipe via the 1/4 in. BSPT x 6mm stud coupling
(Part No. 30880007).

025070

Fig. 47 Part No. 30880008 Socket (1/4 in. BSP)

Technical Specification

Material: Brass
Type: 3000lb Fitting
Connection: 1/4 in. BSPP Female
Overall Size: 36.3 mm x Dia 20 mm
Weight: 0.057 kg

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 57 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.16 iFLOW ACTUATION HOSES
Part Length
Container
(Part 30506014, 30522001 ) Number Dimension A
1/4 in. diameter Teflon hoses fitted with brass ends are 30506014 580 mm Slave to Slave 80 litre
used to connect the pneumatic actuators together and to Pilot Actuated
transmit the pressure from the pilot container to operate 30522001 700 mm Slave to Slave 140 litre
the iFLOW container, and to connect the manual pneumatic Pilot Actuated
actuators. They come in two lengths, see table 17 . 30522001 700 mm Pilot to Slave
The hose has male swivel ends and when fitting to the
pneumatic cones no sealing tape is required. Care must be Table 17 Actuation Hose Details
taken to avoid twisting the hose during installation.

025315

Fig. 31 iFLOW Actuation Hoses


Technical Specification Location on System
Fitted between pneumatic cones.
Hose Construction: Stainless Steel Wire Braid
PTFE Liner Installation Instructions
Connection: 1/4 in. BSPP Male Swivel Union Refer to section 4.5.10 of the manual.
(Brass)
Internal Hose Inner Diameter: 5.8-6.2mm Operating Instructions
Connection Inner Diameter: 4 mm The iFLOW actuation hose is a pressure connector and
Working Pressure: 260 bar requires no operating instructions.
Maximum Working Pressure: 420 bar
Minimum Burst Pressure: 780 bar Maintenance Instructions
Bend Angle: 360 ° In case of faults or suspected faults contact customer
Minimum Bend Radius: 30 mm services to organize replacement.
Approvals: VdS
Certification: EN 12094-8
CE Certification Number: 0786-CPD-30099
Year of CE Marking: 2009
CE Marking Requirements: Manufacturer, Part Number,
Batch No, Working Pressure,
Hose Type, CE0786
Method of Marking: Engraving
Weight: 0.13 kg (Part No. 30506014)
0.14 kg (Part No. 30522001)

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 45 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.18.2 PILOT LINE NON RETURN VALVE
(Part No. 20006020)
The pilot line non return valve is used when there is a Technical Specification
requirement to either maintain pressure in a particular
section of the pilot line or to ensure that nitrogen pressure Body: Brass
from the pilot container is operating the correct iFLOW Size ¼ in.
INERGEN containers. Typical Working Pressure: 100 bar @ 20 °C
Working Temperature Range: -20 °C to 50 °C
For example, a system using Selector valves where differing
numbers of containers are required for each risk will use Approvals: VdS
the pilot line non return to ensure that pilot pressure opens Certification: EN 12094-13
only the correct bank of containers and the correct selector
valve.
Various adaptors are available to fit the pilot line non return
valve and these are detailed in the installation section of
this manual.

MALE ADAPTOR 1/4” DOWTY SEAL


(PART OF ASSEMBLY)

Fig. 34 Part No. 20006020 Pilot Line ! !WARNING


WARNING
Non Return Valve DO NOT REMOVE THE MALE ADAPTOR AS SUPPLIED

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 47 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
4.5.6 RELEASE SYSTEMS FOR SELECTOR VALVES

Pilot Line Non Return Valve Configurations

Configuration Parts Required Comments

Inlet to pilot line non return 1 x P/No. 20006020 pilot line non return valve No additional components required
valve is an actuation hose;
outlet fitted directly to a
pneumatic actuator*
Inlet to pilot line non return 1 x P/No. 20006020 pilot line non return valve Fit P/No 3088007 to the inlet of the
valve is 6 mm o/d copper 1 x P/No. 30880007 6 mm o/d tubing male pilot line non return valve
tubing ; outlet fitted directly adaptor
to a pneumatic actuator*
Inlet to pilot line non return 1 x P/No. 20006020 pilot line non return valve Fit P/No 30880059 to the outlet of the
valve is an actuation hose; 1 x 30880059 female/female actuation hose pilot line non return valve
outlet is an actuation hose coupling
Inlet to pilot line non return 1 x P/No. 20006020 pilot line non return valve Remove adaptor supplied fitted to the
valve is 6 mm o/d copper 2 x P/No. 30880007 6 mm o/d tubing male pilot non return valve outlet and fit P/
tubing ; outlet is 6mm o/d adaptor No. 30880007 to both inlet and outlet
copper tubing of the pilot container non return valve

Table 25 Release System Components

PAGE 72 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.17 1/4 in. BLEED VALVE 3.18.1 PILOT VALVE ADAPTOR
(Part No. 20007020) (Part No. 35116381)
The bleed valve is used in the actuation line of systems The Pilot Container Valve Adaptor is used to connect the
where an unintentional build-up of pressure, perhaps Valve to the Pilot Actuation Hose or Tubing and Bleed Valve.
through a leak, could be problematic.
The device will automatically relieve pressure caused
by small leaks but will seal to completely prevent loss of
actuation pressure when, typically, the pilot container
operates.
As an option on single hazard system. This can be fitted on
the last pneumatic cone.

025316
025357

Fig. 32 Part No. 20007020 1/4 in. Bleed Valve Fig. 33 Part No. 35116381 Pilot Valve Adaptor

Technical Specification Technical Specification

Body: Brass Body: Steel (Zinc Coated )


Internal Parts: Brass and Stainless Steel Internal Parts: Steel (Zinc Coated )
Connection: 1/4 in. BSPP Connection: 1/4 in. BSPP
Minimum Activation Pressure: 20 bar Maximum Working Pressure: 120 bar
Maximum Working Pressure: 240 bar Overall Size: 53.5 mm x 39 mm
Overall Size: 50 mm x xx mm Weight: 0.26 kg
Weight: 0.14 kg

PAGE 46 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.7 DISCHARGE PRESSURE SWITCH
(Part No. 30330010)
The pressure switch is mounted in the distribution pipework The pressure switch requires to be manually reset following
and may be used to provide an electrical indication of the operation.
release of agent or to perform ventilation shut-downs or
A minimum pressure of 10 bar is required to ensure
other interlock functions.
satisfactory operation

025305

Fig. 16 Part No. 30330010   Pressure Switch

Technical Specification Location on System


Connected to either the manifold or the discharge
Locking System: Brass pipework.
Electrical Box System: Duraluminium
Connection: 1/2 in. BSPT
Installation Instructions
Mechanical Installation:
Set Point: 10 bar Rising at 20 °C
(with Manual Reset) Refer to section 4.6.1 of the manual.
Working Temperature Range: -25 °C to 80 °C Electrical Installation:
Maximum Working Pressure: 370 bar The switch has normally open and normally closed contacts.
Weight: 0.41 kg
Maximum Current: 6A
Operating Instructions
The discharge pressure switch is designed to work within
Maximum Voltage: 250 v dc
the pre-determined system operating conditions. The
Ingress Protection Class: IP67
switch requires to be manually reset following operation.
Conforms to: EN 12094-10, UL-580
Marking Requirements: Manufacturer, Part Number,
Maintenance Instructions
Serial No, 10 bar rising
To reset after activation pull and release the knob on the
Method of Marking Engraving
side of the unit
Overall Size: 126 mm x 30.3 mm
x 32.4 mm

PAGE 32 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
SELECTOR VALVE (CONTINUED)
Location on System Technical Specification
Fitted to the manifold
Valve Bore Size: 20mm (3/4 in.) - 100mm (4 in.)
Installation Instructions Valve Construction: Steel
Refore to section 4.5.4 of the manual. Valve Connection (Threaded): Threaded NPT Female Inlet NPT
male outlet
Maintenance Instructions Pneumatic Port Connection 1/4 in. BSPP
In case of faults or suspected faults contact customer Working Temperature Range: -20 °C to 50 °C
services to organize replacement. Mounting Position: Horizontal or Vertical
Nominal Actuation Pressure: 100 bar
Approvals: LPCB, VdS
Certification: EN 12094-5
CE Certification Number: 0786-CPD-30052
Year of CE Marking: 2010
CE Marking Requirements: Manufacturer, Part Number,
DNXX, Serial No, CE0786

Selector Valve Size Outlet Pneumatic Fittings Dimensions Weight


Assembly Union (length x width) (Kg)
21100050 20mm (3/4 in.) 30888001 30880007 Stud Cou- 555 x 171 7.5
21100060 25mm (1 in. ) 30888002 pling 1/4 in. BSPT x 565 x 182 8.8
6mm (2 required per
21100070 30mm (1 1/4 in. ) 30888003 579 x 179 11.5
selector valve assy)
21100080 38mm (1 1/2 in. ) 30888004 584 x 180 13.0
21100090 50mm (2 in. ) 30888005 612 x 228 17.0
62116006 60mm (2 1/2in.) 30888006 660 x 185 27.5
62116004 75mm (3in.) 30888007 699 x 188 33.9
62116005 100mm (4in. ) 30888008 871 x 242 58.0

Table 18 Selector Valve


Note:
For each selector valve assembly the appropriate outlet
union and (2 x) pneumatic fittings must be ordered sepa-
rately. (See table 18). Additionally selector valve solenoid
and brackets must be ordered separately (see section
3.20.1).

Selector Valve Ancillaries.


A selector valve microswitch (Part No. 30116011) is available
and when fitted, will electronically signal that the selector
valve has operated.
A lever (Part No. 20010013) is available to manually close
the selector valve after operation. When mounting the
selector valve sufficient clearance must be allowed for
operating the manual lever.

PAGE 50 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.20.1 SELECTOR VALVE SOLENOID AND BRACKETS
30130250 (Solenoid with Manual Release) or Technical Specification
30130251 (Solenoid only with blind cap)
The selector valve solenoid is installed between the pilot Actuation Type: Solenoid (normally closed)
container and selector valve and allows pneumatic release Reset Method: Manually
on receipt of electrical signal from control panel. Connection: 6mm Stud Coupling
Selector valve solenoids are offered as standard with Voltage: 24 V dc ± 15%
manual release or solenoid operation only. Maximum working Pressure : 170 bar (2465 psi)
Consumption: 13 W
Min Duration of Trigger Signal: Continuous Duty
Electrical Connection: DIN Plug
Protection IP 65
Working Temperature Range: -20 °C to 50 °C
Weight: 0.25 kg
Approvals: LPCB, VdS
Certification: EN 12094-4
CE Marking Requirements: Manufacturer, Serial No, Voltage,
Current, CE0786
Method of Marking: Stamp

Fig 38 Selector Valve Solenoid c/w Manual Release


Part No. shown 30130250
Solenoid Only with Blind Cap Part No. 30130251

(Part No. 30650013, 30650014 and 30650022)


Brackets are available to mount the selector valve solenoid.

res
330 cent

025320mod

Fig. 39 iFLOW Selector Valve Solenoid Brackets


Part
Description
Number
30650022 Selector Valve Solenoid Mounting Bracket (2 Solenoids)
30650013 Selector Valve Solenoid Mounting Bracket (3 Solenoids)
30650014 Selector Valve Solenoid Mounting Bracket (4 Solenoids)

Table.19 Selector Valve Solenoid Mounting Bracket Part Numbers


Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 51 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.20 SELECTOR VALVE
(Part No. 21100050, 21100060, 21100070, 21100080, 21100090, 62116006, 62116004 and 62116005)
The selector valve is used in applications where multiple
areas require to be protected from a single bank of
containers.
The valves are pneumatically operated by a pilot container
(see section 3.9).
The pressure enters through the inlet port (see figure 36) Inlet Port
and when the selector valve is fully open the contained
pressure exits through the outlet port. Pressure from the
bottom port is connected via a suitable pilot line to operate
the appropriate number of containers required to protect a
particular hazard.
A typical selector valve system is shown in figure 37.
OutletPort
The operation of a typical system is as follows:
The fire detection system in one of the protected hazards
operates. A fire signal is sent to the solenoid on the pilot
container and it operates. At the same time a signal operates
a second solenoid which is connected to the pilot line from
the pilot container. This second solenoid opens and allows
pilot container pressure to pass to the appropriate selector
valve. The selector valve piston operates and opens the
selector valve. When the piston is at its fullest travel the
selector valve is fully open, pressure then passes from
a port in the bottom of the piston to the container bank.
This pressure operates the container bank and INERGEN
discharges through the selector valve into the hazard. The
unit is supplied with a non-return valve.
025319A
Fig. 36 iFLOW Selector Valve

025351
Fig. 37 iFLOW Selector Valve System (Unequal Size Risks)

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 49 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
SELECTOR VALVE (CONTINUED)
Location on System Technical Specification
Fitted to the manifold
Valve Bore Size: 20mm (3/4 in.) - 100mm (4 in.)
Installation Instructions Valve Construction: Steel
Refore to section 4.5.4 of the manual. Valve Connection (Threaded): Threaded NPT Female Inlet NPT
male outlet
Maintenance Instructions Pneumatic Port Connection 1/4 in. BSPP
In case of faults or suspected faults contact customer Working Temperature Range: -20 °C to 50 °C
services to organize replacement. Mounting Position: Horizontal or Vertical
Nominal Actuation Pressure: 100 bar
Approvals: LPCB, VdS
Certification: EN 12094-5
CE Certification Number: 0786-CPD-30052
Year of CE Marking: 2010
CE Marking Requirements: Manufacturer, Part Number,
DNXX, Serial No, CE0786

Selector Valve Size Outlet Pneumatic Fittings Dimensions Weight


Assembly Union (length x width) (Kg)
21100050 20mm (3/4 in.) 30888001 30880007 Stud Cou- 555 x 171 7.5
21100060 25mm (1 in. ) 30888002 pling 1/4 in. BSPT x 565 x 182 8.8
6mm (2 required per
21100070 30mm (1 1/4 in. ) 30888003 579 x 179 11.5
selector valve assy)
21100080 38mm (1 1/2 in. ) 30888004 584 x 180 13.0
21100090 50mm (2 in. ) 30888005 612 x 228 17.0
62116006 60mm (2 1/2in.) 30888006 660 x 185 27.5
62116004 75mm (3in.) 30888007 699 x 188 33.9
62116005 100mm (4in. ) 30888008 871 x 242 58.0

Table 18 Selector Valve


Note:
For each selector valve assembly the appropriate outlet
union and (2 x) pneumatic fittings must be ordered sepa-
rately. (See table 18). Additionally selector valve solenoid
and brackets must be ordered separately (see section
3.20.1).

Selector Valve Ancillaries.


A selector valve microswitch (Part No. 30116011) is available
and when fitted, will electronically signal that the selector
valve has operated.
A lever (Part No. 20010013) is available to manually close
the selector valve after operation. When mounting the
selector valve sufficient clearance must be allowed for
operating the manual lever.

PAGE 50 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.25 MANUAL RELEASE CAUTION PLATE
(Part No. 63013030)
The Manual Release Caution Plate provides instructions to Technical Specification
personnel on the use of manual controls.
Material: PVC
One plate is to be fixed adjacent to all positions from where Sign Size: 210 mm x 75 mm
INERGEN can be released manually. Font Type: Helvetica Medium
Colours: Black and Red

Fig. 50 Manual Release Caution Plate


(Part No. 63013030)

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 59 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.26 DOOR CAUTION PLATE - LOCK-OFF
(Part No. 63013031) Technical Specification
The Door Caution Plate (lock-off) provides instructions to
personnel who may enter an area protected with INERGEN. Material: PVC
Sign Size: 210 mm x 210 mm
This version of the caution plate is used when it is necessary
Font Type: Helvetica Medium
to instruct personnel to place the system on manual control
Colours: Black and Yellow
before entering the protected area.
One plate is to be fixed to all entrance doors into an INERGEN
protected area.

Fig. 51 Door Caution Plate - Lock-off


(Part No. 63013031)

PAGE 60 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.27 DOOR CAUTION PLATE - NO LOCK-OFF
(Part No. 63013032)
The Door Caution Plate (no lock-off) provides instructions to Technical Specification
personnel who may enter an area protected with INERGEN.
Material: PVC
This version of the caution plate is used when it is permit-
Sign Size: 210 mm x 210 mm
ted to leave the system on automatic control even while the
Font Type: Helvetica Medium
area is occupied.
Colours: Black and Yellow
One plate is to be fixed to all entrance doors into an INERGEN
protected area.

Fig. 52 Door Caution Plate - No Lockoff


(Part No. 63013032)

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 61 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.3 DISCHARGE NOZZLES

These discharge nozzles are available in a 180º and 360º The discharge nozzle consists of a steel discharge head
patterns and are designed to uniformly distribute agent containing an orifice plate. The orifice is specifically drilled
throughout the hazard area. All nozzles are specifically according to the flow calculation determined for each
drilled to suit the individual design requirements. hazard area.
Where the size of any hazard enclosure determines that A nozzle/pipe sealing plate (cover plate) is available (part
one nozzle does not provide coverage within the above numbers 30410320-30410920)
parameters the hazard should be theoretically sub divided
into appropriately sized modules. orifice plate (part no. 3044032 to 30440092

025352

Fig. 8 iFLOW Discharge Nozzles

Technical Specification Location on System


At end of discharge pipework.
Material: Steel F-2112
Finish Chrome Plate Installation Instructions
Thread Type: According to ISO 228 Before connection, ensure the pipework supports have
Nozzle Thread Sizes: 3/8 in., 1/2 in., 3/4 in., been fitted at the correct intervals and are
1 in., 1¼ in., 1½ in. adequate for purpose. For connection to pipe work, apply
and 2 in. suitable pipe sealant to the inlet and tighten securely.
Nozzle Types: 360° or 180° Ensure that the nozzle is fitted in accordance with the
Coverage: 7 x 7 m (360°) design requirements and are aimed in the correct
7 x 7 m (180°) alignment away from obstructions or barriers that could
Protection Height: 0.5 m - 5 m prevent adequate distribution/mixing of the
Max Distance from Ceiling: 0.3 m agent.
Max Coverage Area Per Nozzle: 49 m2
Maximum Working Pressure: 142 bar Operating Instructions
Orientation: Pendant / Upright The discharge nozzles are designed to work within the pre-
Approvals: VdS Approved Nozzle determined system operating conditions.
Coefficients
Drilling increment: 0.1.mm Min 3.0 mm Maintenance Instructions
dia to Max 80% of The nozzles should be inspected for dust and debris every
pipe c.s.a. six months, and cleaned out where necessary. If any doubt
exists concerning the integrity of the pipework, arrange for
it to be purged. Remove the nozzle(s) and the nozzle filter
mesh to check that they are free of debris following the
purge.
In case of faults or suspected faults contact customer
services to organize replacement.

PAGE 26 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.3.1 360° DISCHARGE NOZZLES
(Part Nos. as shown below)
The 360º discharge nozzle is either an 18 port or 24 port
nozzle, depending upon its size.

025299

Fig. 9 iFLOW 360º Discharge Nozzle Details

Dia Thread Part Dimension Diameter Dimension Dimension Number of Drill Diameter
(BSPP) Number A B C D Ports E
(mm) (mm) (mm) (mm) (mm)
3/8 in. 30400000 23 25 40 20 18 3
1/2 in. 30400001 30 33 50 22 18 4
3/4 in. 30400002 35 38 55 23 24 5
1 in. 30400003 40 44 64 28 24 6.5
1-1/4 in. 30400004 50 55 75 32 24 9
1-1/2 in. 30400005 60 66 90 35 24 10
2 in. 30400006 80 88 105 38 24 13

Table 10  360º Nozzle Details

4.85 m

Fig. 10 iFLOW 360º Discharge Nozzle Coverage

360° Nozzle

Copyright © 2015 Tyco Fire Products LP. All rights reserved PAGE 27 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.3.2 180° DISCHARGE NOZZLES
(Part Nos. as shown below)
The 180º discharge nozzle is an 18 port nozzle.

025300

Fig. 11 iFLOW 180º Discharge Nozzle Details

Dia Thread Part Dimension Diameter Dimension Dimension Drill Diameter


(BSPP) Number A B C D E
(mm) (mm) (mm) (mm) (mm)
3/8 in. 30400007 23 25 40 20 3
1/2 in. 30400008 30 33 50 22 4
3/4 in. 30400009 35 38 55 23 5
1 in. 30400010 40 44 64 28 6.5
1-1/4 in. 30400011 50 55 75 32 9
1-1/2 in. 30400012 60 66 90 35 10
2 in. 30400013 80 88 105 38 13

Table 11  180º Nozzle Details

7.83 m
Fig. 12 iFLOW 180º Discharge Nozzle Coverage

180° Nozzle

PAGE 28 of 100
EQUIPMENT: iFLOW
PUBLICATION: 14A-23H
ISSUE No. 02
DATE: 2015-02
3.24 SPECIAL TOOLS

(Part No. as shown in table)


Special tools are required to attach and or tighten various
components.

Part
Description
Number
35017401 ‘C’ Spanner Dia 35 mm-60 mm, Pin Dia 4 mm
35017402 ‘C’ Spanner Dia 60 mm-90 mm, Pin Dia 5 mm
35017403 ‘C’ Spanner Dia 90 mm-155 mm, Pin Dia 6 mm
35017404 ‘C’ Spanner Dia 165 mm-230 mm, Pin Dia 10 mm

Table 24 Special Tools Part Numbers

025355

Fig. 49 ‘C’ Spanner

PAGE 58 of 100