Documentos de Académico
Documentos de Profesional
Documentos de Cultura
2-1987
0
IEEE Guide for the Application of
Gapped Silicon-CarbideSurge Arresters
for Alternating Current Systems
Published by The Institute of Electrical and Electronics Engineers, Inc 345 East 47th Street, New York, N Y 10017, USA
Sponsor
SurgeProtectiveDevicescommittee
of the
IEEE Power society
0 Copyright 1988 by
This guide supplements ANSIAEEE Std C62.1-1984, American National Standard for Surge
Arresters for Alternating Current Power Circuits, to assist users in the selection and application of
surge arresters.
This document is a revision of ANSI C62.2-1981. Revisions include:
1) A modification in the title of the guide, substituting “Gapped Silicon-Carbide” for “Valve-
Type,” t o distinguish i t from a guide for the application of metal-oxide surge arresters.
2) A new section 3.12, ”Protection of Gas-Insulated Substations,” h a s been added.
33 Sections 2.1.1, 3.10, 4.7, and 4.10 have been rewritten.
43 Appendix A has been updated, as well as Tables 1 and 6, which h a s been renumbered as Table
7 and modified t o include the Heavy Duty Distribution Surge Arrester.
5 ) Definitions 04.4 and D4.5 have been revised and renumbered D5.3 and D5.4 respectively (the
original D4.3 was deleted).
6) New references were added, consistent with new and revised sections.
7) A new Appendix E, “Coefficent of grounding (COG) Calculations,” h a s been added.
8) A new Appendix F, uArrester Stroke Currents-Arresters Connected to Distribution Lines,”
has been added.
This document was processed by Working Group 3.4.14 of the Application of Surge Protective
Devices Subcommittee, Surge Protective Devices Committee of the IEEE Power Engineering
Society .
At the time the work on the revision was completed, Working Group 3.4.14 consisted of the
following members:
* Deceased
Members of the Surge Protective Devices Committee and the Application of Surge Prc:e:::-,-e
Devices Subcommittee eligible to ballot on this revised Guide were a s follows:
When the IEEE Standards Board approved this standard on March 12,1987, i t had the following
membership:
*Member emeritus
.
contents
SECTION PAGE
3.4.3.3 Discharge Currents in Stations Where Lines are Not Shielded .......... 2
3.5 Locating Arresters and Determining Voltage at Protected Equipment . . . . . . . . . . . . . . . . . . . W
3.5.1 Locating Arresters in Nonshielded Installations.. .. . ... . . .... . . . . . . . . . . . . . . . . . . . . W ,
4.1 I n t r o d u c t i o n ....................................................................................... 31
4.2 General Procedure.. .. . . . ... . . . .. . . . . .... . . . ... . . . . . .... . . . . .......................... 31
4.2.1 Installation Practices Jeopardizing Insulation Coordination . . . . . . . . . . . . . 32
4.2.2 Applications Requiring Special Considerations ...... ....... . .... . ....
4.3 Selection of Arrester Ratings.. . .. . ... . . .. .. .. . . .. . ... . . .. . . .. . . . . . . .. . . .
4.3.1 Delta Systems . . . . .. . . .... . . . .... . . .... . . . . . . .. . .. . . . . . . . . . . . . . . . . . . . . . . . . , .
4.3.2 Three-Wire Unigrounded Wye Systems (Grounded a t So
4.3.3 Four-Wire Multigrounded Wye Systems (Including Spacer
4.4 Insulation Coordination .. . . . . ... . . .... . . . . .. ... . . . ... . . . ... . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . .32
4.5 Arrester Connections.. . ... . .. .... . ....... .... . .. . . .... .. . .... .. . ... . . . . . . .. .. .. . . .. . . .. . .. .. .. . .33
4.5.1 Effect of Connecting Lead Wires ..... . .. . .... . . .. . . .. . ... . . . .. . .. . . . .. . . . .. . . .. . . . . , . -33
4.5.2 Effect of Separation Distance.. .. . . ...... . . . ... . . . .. . . . . . . . . . . . . . . . .. . . . . . . . . . . . . . . .
SECTION PAGE
5. Bibliography ............................................................................................ 38
TABLES
FIGURES
Fig 1 Summary of Step-by-step Procedures for Arrester Selection and Insulation Coordination . 19
Fig 2 Coefficients of Grounding for Various System Conditions ...................................... 20
Fig 3 Typical Voltage-Time Curve for Coordination of Arrester Protective Levels with
Insulation Withstand Strength for Liquid-Filled Transformers .............................. 28
A? PE SDISE S
B4.2 Transients Where Only One or Two Sparkovers are Permitted ......................... 45
B4.3 Transients Where Temporary Overvoltages Approach Reseal Capability of the
Surge Arrester .................................................................................. 45
Appendix C Evaluation of Separation Effects in Simple Substations .............................. 47
C1 . References .............................................................................................. 47
C2 . Study Methods .......................................................................................... 47
C3. Parameters ............................................................................................. 47
C4 . C a l c u l a t i o n P r o c e d u r e ................................................................................. 48
C4.1 General .......................................................................................... 48
C4.2 Reduction of Station Configuration to Base Case ........................................... 48
C4.3 Formulas for Base Case Solution ............................................................. 48
C4.3.1 Formulas for Maximum Permissible Separation ................................. 49
C4.4 Example of Calculation of Separation Effects ............................................... 49
C4.5 Table for Allowable Separation ............................................................... 50
Appendix D D e f i n i t i o n s .................................................................................. 51
D1 . References .............................................................................................. 51
D2 . O v e r v o l t a g e s ............................................................................................ 51
D3 . I m p u l s e s ................................................................................................. 51
D4 . Standard Impulses ..................................................................................... 52
D5 . Insulation Coordination .............................................................................. 52
D6 . Arresters ................................................................................................ 53
D7 . System Voltages ........................................................................................ 53
Appendix E Coefficient of Grounding (COG) Calculations ......................................... 55
Appendix F Arrester Stroke Currents, Arresters Connected to Distribution Lines ............... 56
TABLES
FIGURES
9
ANSUIEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
[131 ANSI C92.1-1982, American National [241 ANSVIEEE Std (257.13-1978 (R19861, IEEE
Standard Voltage Values for Preferred Tran- S t a n d a r d Requirements for I n s t r u m e n t
sient Insulation Levels. Transformers.
[141 WITZKE, R. L., a n d BLISS, T. J. [251 ANSIAEEE Std C57.21-1981, IEEE Stan-
Coordination of Lightning Arrester Location dard Requirements, Terminology, and Test
with Transformer Insulation Level. A Z E E Code for Shunt Reactors Over 500 kVA.
Transactions. 1950, 69:964-975.
1261 ANSUIEEE Std C57.12.00-1987, IEEE
[151 SAKSHAUG, E. C. Current Limiting Gap Standard General Requirements for Liquid-
Arresters-Some Fundamental Considera- Immersed Distribution, Power, and Regulat-
tions. ZEEE Transactions on Power Apparatus i n g Transformers.
and Systems. 1971, PAS-90:1563-1573.
[27] ANSI/IEEE Std C57.12.90-1987, IEEE
[161 FLUGUM, R. W. Operation of Lightning Standard Test Code for Liquid-Immersed
Arresters on Abnormal Power Frequency Distribution, Power, and Regulating Trans-
Voltages. ZEEE Transactions on Power Appa- formers and IEEE Guide for Short-Circuit
ratus and Systems. 1970, PAS-89:1444-1451. Testing of Distribution and Power Trans-
formers.
[171 SHIE, A., and HUSE, J. Currents Through
Surge Arresters Due to Lightning with Main [281 ANSVIEEE Std C37.04-1979 (R1988), IEEE
Reference t o Distribution Systems. Electra. Standard Rating Structure for AC High-Volt-
10
ANSILEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
age Circuit Breakers Rated on a Symmetrical chines. Westinghouse Application Data 38-423.
Current Basis.
[391 HILEMAN, A. R. S u r g e Transfer
[291 AT31 C37.06-1987, AC High-Voltage Cir- Through 3 - P h a s e T r a n s f o r m e r s . A I E E
cuit Breakers Rated on a Symmetrical Cur- Transactions (Power Apparatus and Sys-
rent Basis-Preferred Ratings and Related tems). 1959, 77:1543-1551.
Required Capabilities.
[401 ARMSTRONG, H. R., HOWARD, S.B.,
:30: XSSI C37.0781-1972, American National a n d JOHNSON, I. B. Field Investigation of
Standard Schedule of Dielectric Test Values Surge Performance of Large Unit-Connected
for Outdoor AC High-Voltage Circuit Breaker Steam Turbine Generators. A I E E Transac-
External Insulation Rated on a Symmetrical tions (Power Apparatus and Systems). 1952,
Current Basis. 71:1023-1029.
:311 AYSI/IEEE C37.074-1972 (R1978), Ameri- [411 HAYWARD, A. P., DILLARD, J. K., and
can National S t a n d a r d Requirements for HILEMAN, A. R. Lightning Protection and
S w i t c h i n g - I m p u l s e Voltage I n s u l a t i o n Unit-Connected Turbine Generators-Field
Strength for AC High-Voltage Circuit Break- and Laboratory Studies. A I E E Transactions
ers Rated on a Symmetrical Current Basis (Power Apparatus and Systems). 1957, 75:
(362 kV and Above). 1370-1 378.
11
ANSIIEEE
C62.2-1987 IEEE GUIDE FOR "€€E! APPLICATION OF GAPPED SILICOS-C.lRBDE
1481 ERIKSSON, R., and HOLMLORN, H. for Distribution Circuits, Part 11: Application
Insulation coordination of insulated substa- and Evaluation. IEEE Transactions on Power
tions. Proceedings o f the International S y m - Apparatus and Systems. 1969, PAS-88:1241-
posium on Gaseous Dielectrics. March, 1978, 1247.
pp 314-337.
[581 MILLER, D. D., and WESTROM, A. C.
[491 YOST, A. G. Surge Protection in Power Traveling Wave Tests Yield New Protection
Systems. Gas-Insulated Substation ( G I s ) Alternatives for Underground Distribution.
Surge Arresters. IEEE Tutorial Course Text 79 Tulsa: EEI T&D Committee; Oct 7-8, 1976.
EH0144-6-PWR, Chapter 9.
[591 IEEE Committee Report. Surge Protection
[50] IEEE Working Group of Surge Protective of Cable-Connected Equipment on Higher-
Devices Committee. Voltage Rating Investi- Voltage Distribution Systems. IEEE Transac-
gation for Application of Lightning Arresters tions on Power Apparatus and Systems. 1981,
on Distribution Systems. IEEE Transactions PAS-10:154-1 57.
on Power Apparatus and Systems. 1972, PAS-
91:1067-1074. [SO] VALENTINE, W. W., DILLARD, J . K.,
and CLAYTON, J. M. Surge Attenuation in
[511 SAKSHAUG, E. C. Influence of rate of rise Power Cables. A I E E Transactions (Power
on distribution arrester protective character- Apparatus and Systems). 1955, 74:1115-1122.
istics. IEEE Transactions on Power Apparatus
and Systems. 1979, PAS-98:519-526. [611 AUER, G. G., and SCHULTZ, A. J . An
Analysis of 14.4124.9-kV Grounded-Wye
[521 IEEE Committee Report. Surge Protection Distribution System Overvoltages. A I E E
of Cable-Connected Distribution Equipment on Transactions (Power Apparatus and Sys-
Underground System s. IEEE Transact ions on tems). 1954, 73:1027-1031.
Power Apparatus and Systems. 1970, PAS-89:
263-26 7. E621 C R A " , L. B., and FLICKINGER, R. B.
Overvoltages of 14.4/24.9 kV Rural Distribu-
[531 KERSHAW, S . S., Jr., and CLINKEN- tion Systems. A I E E Transactions (Power
BEARD, C. R. Discharge voltage of arrester Apparatus and Systems). 1954,73:1208-1212.
connecting lead wires. IEEE Transactions on
[631 HOPKINSON, R. H. Ferroresonance
Power Apparatus and Systems. 1974, PAS- During Single-phase Switching of 3-Phase
93:226-232. Distribution Transformer Banks. I E E E
Transactions on Power Apparatus and Sys-
[541 ANSI C84.1-1982, American National tems. 1965,84:289-293.
Standard Voltage Ratings for Electric Power
Systems and Equipment (60 Hz). [641 KERSHAW, S . S., Jr, HUBER, W. J., and
HASSLER, S . P. Effect of Current Limiting
[551 GAIBROIS, G. L., HUBER, W. J., and Fuse Operation on Arrester Performance.
STOELTING, H. 0. Blowing of Distribution IEEE Underground Conference, Atlantic City,
Transformer Fuses by Lightning. Conference 1976.
Paper C73 421-5; IEEE Power Engineering
Society Summer Meeting; 1973. [651 OLIVE, W., and WESTROM, A. C.
Current Limiting Fuses With Tapered Wire
[561 Task Force Report. Investigation and Elements Provide Peak AC Voltage Control.
Evaluation of Lightning Protective Methods IEEE Underground Conference, 1974.
for Distribution Circuits, Part I: Model and
Study Analysis. IEEE Transactions on Power [661 IEEE Switchgear Committee and Surge
Apparatus and Systems. 1969, PAS-88:1232- Protective Devices Committee Working
1240. Group. Coordination of Lightning Arresters
and Current-Limiting Fuses. I E E E Transac-
[571 Task Force Report. Investigation and tions on Power Apparatus and Systems. 1972,
Evaluation of Lightning Protective Methods PAS-91:1075-1078.
12
ANSIAEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
13
ANSVIEEE
032.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-C.U?BIDE
Table 1
Lightning Stroke Current Data
!
I F*nstsxJke
Ekedimthe' 'Ile
SubIItstKIkes
% exceed in^ the Value
Parameter P p 95% 50%(M) 5% P P
Crest Current, kA 0.48 0.38 5 12.3 29 0.53 0.56
I
Minimum Linear 0.5 0.61 - 0.1 0.31 1.0 0.7l -
Front, ps
3.5
Time-to-Half Value, ps 133 77.5 I 200 0.58 - 7 30.2 140 0.93 -
other data. The resultant distribution is piece- the current in the stroke itself. In the case of
wise Log-Normal with parameters as follows: direct strokes t o lines, traveling waves are set
up in opposite directions from the point of
Range M P contact. Flashover of line insulation provides
20 kA and below 61 1.33 a parallel path t o ground, which diverts a
20 kA and above 33.3 0.605 portion of the stroke from the arrester. In the
case of strokes t o more than one conductor o r
The distribution may also be approximated
flashovers between conductors, two or more
[51 by the equation:
surge arresters may operate and share the
current. Only in the case of a direct stroke
very near to the terminal of the arrester where
no flashover occurs before arrester operation
where P(I) is the probability t h a t the crest is the arrester called upon t o discharge most of
current will equal o r exceed I (kA). the lightning stroke current. The probability
The lightning severity within a specific of such an occurrence can be significantly re-
area is generally specified by the ground flash duced by the use of shielding. Evaluation of
density, N g , in flashes per km2. However, at arrester currents is discussed in 3.4.2.
present within the USA, data on the average 2.1.1.2 Line Shielding. Overhead lines
N g is not generally available, a n d t h e may be protected against direct lightning
lightning severity m u s t be based on t h e strokes t o the conductors by the use of shield
a n n u a l keraunic level, o r the number of (overhead ground) wires, which are positioned
thunderstorm days per year, T d . In the USA, so a s to intercept lightning strokes and t o
these levels vary from five or less on the West direct them to ground via metallic tower o r
Coast t o greater than 100 in Florida, with an pole structures. Where wood pole structures
average between 35 and 40 [41. The value of Ng are used, low-impedance conductors connect
may be approximated from T d by the equation: the shield wires to ground.
I t h a s been found feasible t o eliminate all
Ng = 0.04 T"d except a small percentage of direct strokes to
where both N g and T d are average yearly line conductors by the use of shield wires.
values3 The coefficient of variation of both Ng When such a direct stroke (shielding failure)
and T d are large, about 60% for low values of does occur, line flashover is almost certain.
T d and about 30%for high values of T d [71. When a lightning stroke terminates on a
2.1.1.1 Arrester Currents Due to Light- shield wire, the stroke current is diverted t o
ning Strokes. As a general rule, arrester ground through the structure-connecting con-
currents due t o lightning strokes are less than ductors. The impedance of the current path
together with ground resistance results in a
3The exponent "a" for Tdis empirical-1.25 is used in voltage at the top of the line structure, a portion
[6], 1.35in [41. of which is coupled t o the phase conductor. The
14
ANSyIEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
15
ANSI/IEEE
C62.2-1987 E E E GUIDE FOR THE APPLICATION OF GAPPED SILICOX-C.lRBIDE
flow of discharge current and contribute to the Such operations a r e called “front-of-wave?
limitation of follow current at normal power- sparkovers (FOW). Most types of insulation
frequency voltage. If the voltage applied to the can withstand higher crest impulse levels as-
arrester is equal t o o r less t h a n its reseal sociated with front-of-wave sparkover because
voltage rating, the gap will interrupt the follow of the shorter duration of the impulse voltage.
current within one half of a cycle. Otherwise, For this reason, FOW sparkover is usually
the gaps may fail t o reseal and arrester failure coordinated with chopped-wave withstand (see
will occur. Arrester protective characteristics 3.6.1).
(sparkover and discharge voltage) increase as A sparkover characteristic curve similar to
a function of rating for a given arrester de- that of Fig 3 on page 28 can be obtained by test.
sign a s does reseal voltage rating. An itera- Maximum sparkovers for given times to
tive process (see Fig 1 on page 19) is used t o sparkover are shown. A band of data points
reconcile the conflicting demands of r e s e a l are obtained by making tests with impulses
capability and protective levels. with front times ranging from 1 to 2000 ps (see
2.2.1.1 Usual Operating Conditions. Ar- 2.2.4). The curve is drawn through or above the
resters are designed to operate properly at an maximum sparkover points, as shown in
ambient temperature not exceeding 40 “C and ANSIAEEE Std C62.1-1984 [l].
a t altitudes of 1800 m (6000 ft) or below. Power 2.2.3 Lightning Impulse Discharge Voltage
system frequency should be between 48 a n d (IR). I t is recognized t h a t discharge voltages
62 Hz (see ANSIAEEE C62.1-1984 U]). for surge arresters should be based upon
2.2.1.2 Unusual Conditions. In addition to discharge currents having wave shapes and
operation beyond the limits of 2.2.1 .l, exposure magnitudes t h a t represent those t o which the
t o damaging fumes or vapors, steam, dripping arresters will be subjected in service and t h a t
water, or salt spray require special considera- data on the lightning impulse strength level of
tion. Arresters must not be installed so t h a t apparatus to be protected by arresters should be
mechanical stresses are excessive. coordinated with the corresponding arrester
Arresters should not be subjected t o abnor- discharge voltage wave shapes.
mal vibrations or shocks. M a n u f a c t u r e r ’ s The discharge voltage wave shape of non-
recommended clearances must be maintained linear valve resistors typically h a s a shorter
between the arresters and nearby conducting front and longer tail than the discharge cur-
objects. rent wave. The discharge voltage resulting
2.2.2 Lightning Impulse Sparkover. Such from a discharge current having a standard
sparkovers are obtained by applying 1.2150 ps 8120 ps wave shape approximates the standard
impulses. For impulses below a certain crest 12/50 p s impulse reasonably well for current
value, no arrester sparkover occurs and a magnitudes between 5 kA and 20 kA.
“full-wave” crest voltage is impressed on the 2.2.4 Switching Impulse Sparkover and
protected insulation, which must be designed Discharge Voltage. Values of switching im-
to withstand such impulses. If the crest is in- pulse sparkover and discharge voltages a r e
creased t o “let-through voltage” level (LT) determined by applying test impulses with
(refer t o D6.7.1 in Appendix D), sparkovers fronts ranging from 30 t o 2000 ps. On cer-
may occur occasionally, with t i m e s t o tain arrester designs, switching impulse dis-
sparkover of 3 ps o r more. In such cases, a charge levels may exceed sparkover.
chopped impulse followed by a discharge volt- 2.2.5 Reseal. A rule of long standing has
age (ZR)is let through to the insulation. I t is to been that the voltage rating of the arrester must
be expected, therefore, that the insulation must be at least equal t o the maximum expected
be able t o withstand either the discharge volt- temporary overvoltage (TOW in order to re-
age or an unmodified surge at l e t - t h r o u g h seal following an operation. The TOV was
level. A BIL (see 2.4) at least 20% greater than determined primarily by t h e line-to-ground
let-through would be required (see 3.7.1.1). As 60-Hz voltages on the unfaulted phases caused
crest values of 1.2/50 ps test impulses are in- by a line-to-ground fault on t h e remaining
creased above let-through, and sparkover oc- phase.
curs at successively shorter times and higher Arresters, particularly in the station class,
voltages until the impulse is chopped before the have been available with capability of operat-
prospective crest of the impulse can be reached. ing and resealing at voltages above rated
16
ANSVEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
voltage. The use of such arresters becomes (2) Basic Lightning Impulse Insulation
important in applications on systems operat- Level (BIL). Tests are made with full-wave
ing a t 300 kV and above. Refer t o Appendix B. 1.2/50-ps impulses a s specified in t h e
appropriate equipment standard.
2.3 P r o t e c t i v e Levels. The protective level of (3) Basic Switching Impulse Insulation
an arrester is the maximum crest value of Level (BSL). The test impulse depends on the
voltage t h a t appears across i t s terminals type of equipment.
under specified conditions of operation.
2.3.1 S p a r k o v e r Levels. There are three 2.5 Separation Effects. The voltage at the pro-
sparkover protective levels corresponding t o tected insulation will always be higher than a t
three points on the sparkover curve (see 2.2.2): the arrester terminals due to oscillations on
(1) Front-of-wave sparkover (FOW), which connecting leads [141. This rise in voltage is
is t h e maximum sparkover on a linearly called separation effect (SE).
rising impulse front. The rate of rise of the Separation effects increase with increasing
front increases with arrester r a t i n g (see rate of rise of the incoming surge and with
Appendix A). increasing distances between the arrester and
( 2 ) Let-through (1.2/50 ps) (LT) sparkover protected equipment. (Separation effect may be
(see 2.2.2 and D6.7.1). significant when the protective ratio, a s de-
( 3 ) Switching surge sparkover, which is the fined in 2.6, is less than 1.15.) For evaluation
maximum sparkover at a time t o sparkover of separation effects due t o lightning surges,
greater than 30 ps for impulses having times t o refer to Appendix C. Due t o the relatively slow
crest between 30 and 2000 ps. rates of rise of switching surges, separation
2.3.2 D i s c h a r g e Voltage Levels. There are effects need never be considered in applying
two discharge protective levels, lightning and the fundamental protective ratio formula t o
switching. switching surge withstand (BSL).
(1) Lightning discharge voltage levels (IR) Other considerations in locating arresters
are established by tests using 8/20-ps current are discussed in 3.5 and 4.5.
impulses (see ANSVIEEE Std C62.1-1984 [ll).
The particular IR must always be identified by 2.6 Insulation Coordination. Insulation coor-
the crest magnitude of the test current used to dination is defined in ANSI C92.1-1982 [131 as
establish it. “the process of correlating t h e insulation
strengths of electrical equipment with expected
NOTE: The greater of LT or ZR (at a specified current,) is
the lightning protective level (LPL).
overvoltages and with the characteristics of
surge protective devices.’’
(2) Switching impulse discharge voltage Degree of coordination is measured by the
level is established by tests a s described in protective ratio (PR). The fundamental defi-
ANSIAEEE Std C62.1-1984 [ll. The greater of nition of PR is:
either the switching surge sparkover o r the insulation withstand level
switching impulse discharge voltage is the voltage at protected e q u i p m e n t
switching surge protective level (SSP).
“Voltage a t protected equipment” includes
2.4 I n s u l a t i o n Withstand. Insulation strength separation effect, if significant. If not, i t is
is expressed in terms of the withstand voltage equal to arrester protective level, plus the line
that the equipment can tolerate without failure. and ground lead voltages.
The withstand voltages of interest in arrester There are three protective ratios in common
applications are taken from the list of pre- use, which compare protective levels with
ferred BILs and BSLs in ANSI C92.1-1982 [131. corresponding insulation with stands :
The following withstand levels for equip- C h o p p e d - W a v e W i t h s t a n d (CWW)
ment and bus insulation are of interest in Front-of-Wave S p a r k o v e r ( F O W )
arrester application:
Basic Impulse Insulation W i t h s t a n d (BIL)
(1) Chopped Wave (CWW). Tests are made
Lightning Protective Level (LPL)
with a 1.2/50-ps impulse chopped by the action
of a rod gap in a minimum time a s specified Switching Impulse Insulation W i t h s t a n d (BSL)
in the appropriate product standard. Switching S u r g e Protective Level (SSP)
17
ANSIlIEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
The protective margin (PM) in percent is Other sequences are equally acceptable. The
defined as: PM = [PR-l].lOO. PR and PM key step is insulation coordination evalua-
applications are covered in Sections 3 and 4. A tion. Withstand voltages may be selected to
graphical approach t o insulation coordination match the characteristics of certain arresters,
is also discussed in Section 3. o r arresters may be matched t o available
insulation.
3.2.2 Arrester Characteristics. Table 2
summarizes information applicable t o station
3. Protectionof Stations class and intermediate class arresters. Dis-
tribution class arresters are sometimes used
3.1 Introduction. The general procedures in stations. A iable containing information
given here are applicable where transformers applicable t o distribution arresters may be
and other equipment and station components found in Section 4.
have a chopped-wave voltage withstand level Protective levels are given in per-unit val-
at least 1.10 times the full-wave level. For this ues of crest arrester rating. As explained in
withstand level, the procedures for the selec- Table 2, per-unit values may be converted t o
tion and location of arresters in relation t o the kilovolts and used in preliminary selection of
insulation system t o be protected can gener- arresters. Values in the numbered columns
ally be reduced t o a series of steps. These are under ”Durability Characteristics” are spe-
summarized in 3.2 and elaborated upon in 3.3 cific requirements for the range of ratings
through 3.7. shown; see ANSUIEEE C62.1-1984. Additional
Applications such a s transformer series application information is found in notes
windings, nonloaded windings, a n d un- numbered t o correspond with the columns.
grounded neutrals are discussed in 3.8.
Where a lower chopped-wave insulation 3.3 Arrester Selection. As indicated in Fig 1,
level is specified in equipment such as dry- arrester selection involves the choice of a
type transformers, the protection procedures voltage rating and a class. Voltage rating is
are covered in 3.9. an index of the highest permissible temporary
Systems operating at voltage levels above overvoltage (TOV) a t the arrester terminals
242 kV to less than 1000 kV are referred t o as (see 3.3.1).
extra-high-voltage (EHV) systems; see ANSI Voltage ratings alone or in conjunction with
C92.1-1982 [131. For EHV applications, special class designations are used to specify test
considerations are necessary. These are dis- values a n d procedures, a s described in
cussed in Appendix B. ANSIDEEE C62.1-1984 [ l l . The class designa-
I t is t o be emphasized t h a t basic t o the tions are station, intermediate, distribution,
application theory presented by this guide are and secondary.
t h e presumptions (1) t h a t surge a r r e s t e r Station arresters are designed for heavy-
ground terminals are interconnected with the duty applications. They have the greatest
grounded parts of the protected equipment, and range of ratings (see Table 2 ) , the best protec-
(2) that both line and ground connections are tive characteristics, and the greatest durabil-
as short a s practical. ity. Intermediate arresters are designed for
moderate duty and only for applications a t 138
3.2 Step-by-StepProcedures and Generalized kV a n d below. Distribution arresters (see
Arrester Characteristics. Figure 1 and Table 2 Table 7) are used t o protect lower-voltage
are designed for ready reference in arrester transformers and lines where the system
application. imposed duty is minimal and there is a need
3.2.1 Selection of Arresters. Figure 1 pro- for a n economical design. Secondary ar-
vides a summary of the steps required to select resters are available for application to systems
arresters. The following sequence is used: operating at less than 1000 V (see Table A4 in
(1)Select arrester and determine its protec- Appendix A).
tive characteristics. 3.3.1 Determining the Maximum Tempo-
(2) Select (or determine) insulation with- rary Overvoltage (TOW. An arrester must be
stand. capable of resealing against the maximum
(3) Evaluate insulation coordination. anticipated TOV. The most common source of
18
ANSI/LEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
I.Tentatively select arrester (see 3.3) IV. Determine voltage at protected equipment
(1) Determine maximum temporary overvoltage (TOV) The voltage at protected equipment will be greater than
(see 3.3.1). that at the arrester (separation effect).
Calculate using Ro/Xl vs XdX, curves (Fig. 2) or (1) If the sum of the arrester lead length L and
calculations (see 3.3.1 .l). transformer lead length S is not greater than the values in
Evaluate effect of load rejection, switching, Table 5, separation effect can be ignored.
resonance, saturation, and possible loss of system, (2) Otherwise, evaluate voltage at equipment in
ground source (see 3.3.1.1 and 3.3.1.2). accordance with Appendix C.
Check for chance of frequent system operation at
vo’tages above “maximum system” !eve1 (see D7.2 V. Determine insulation withstand voltages (see 3.6)
of Appendix D), abnormal frequency, or discon- (1) Basic lightning impulse insulation levels (BIL) are
nec:ion of ground source (see 3.3.2.2). established for most types of equipment either by voltage
or by special test.
3II:E: Voltage ratings are usually equal to or greater than (2) Chopped-wave withstand voltages (CWW) for oil-
T O V (see 3.3.2). filled transformers are 1.1 to 1.15 times BIL (see 3.6.1).
WARNING: Even lower ratios apply to dry-type insulation at
(2) Select arrester class (see 3.3.3). Consider: short times (see 3.9).
( a ) Pressure relief rating equal to or greater than (3) Basic switching impulse insulation levels (BSL) are
system fault. 0.75-0.9 times BIL for transformers and 0.63-0.69 times
( b ) Lightning surge duty. BIL for breakers 362-765 kV.
( c ) Switching surge duty (station and intermediate
only). VI. Evaluate coordination (see 3.7)
( d ) Reliability requirements. (1) When separation effect (see IV in this figure) can be
disregarded, each of the following criteria must be met:
RULE: Class must be available in voltage rating selected and
must meet durability and system reliability requirements. PR(1): CWWlFOW 2 1.2
PR(2): BlLlLPL 2 1.2
II. Determine protection characteristics of selected arrester PR(3): BSUSSP ? 1.15
(see 3.4) Alternatively, coordination curves can be used (see
3.7.3.1 ).
RULE: Use manufacturer’s data for arrester selected where (2) If separation effects cannot be disreaarded:
available. Find voltage at equipment, €,, using methods of
Appendix C. Where front is such that sparkover
(1) Use Table 2 or Appendix A for general studies. For occurs in I 2 ps, base E; on FOW sparkover and
selection of lightning discharge currents, see 3.4.2. use formula PR(1S) in (b) below. Otherwise, base
(2) Establish three standard arrester protective levels €,on LPL in accordance with ll(2b) above, and use
(see 3.7): formula PR(2S) in (b) below.
(a) Front-of-wave sparkover (FOW). All of the following criteria must be met:
( b ) The greater of 1.2150-ps sparkover (LT) or
lightning discharge voltage at selected current PR( 1S): cWWIE;> 1.15
(LPL); see 3.4.1. PR(2S): BILE;? 1.15 or
( c ) The greater of switching surge sparkover or PR(3S): BSUSSP ? 1.15
discharge voltage (SSP); see 3.4.1.
(3) Use in VI(1) or V1(2), as applicable. (3) If criteria of VI(1) or V1(2b), as applicable, cannot be
met (see 3.7.3):
111. Locate arresters with respect to equipment ( a ) Use arrester with lower lightning or switching
(1) Nonshielded incoming lines. Locate arresters as close surge protective levels.
as possible to transformers. Consider use of line entrance ( b ) Change arrester location to reduce separation.
gaps or arresters (see 3.5.1). ( c ) Use higher withstand voltage.
(21 Shielded incomina lines. Locate arresters to Drovide ( d ) Improve shielding.
cpiiGum protection to alrequipment (see 3.5.2). ’ ( e ) Add arresters.
\ I
Fig 1
Summary of Step-by-StepProcedures for Arrester Selection and Insulation Coordination
19
ANSIlLEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICOS-C.QBKDE
- 4
< D
oz
0
1 2 3 4 5 6 I 2 3 4 5 6
XO’X I XO’X I
Voltage conditions neglecting positive- and
negative-sequence resistance: R, = R2 = 0 Voltage conditions for R, = R, = 0.LX2
Fig 2
Coefficients of Gmundingfor Various System Conditions
ANSI/LEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
ANSVIEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
TOV is voltage rise on unfaulted phases dur- be chosen at least equal5 t o the maximum
ing a line-to-ground fault. phase-to-ground temporary overvoltage in
In many cases only TOV due t o line-to- order to interrupt the power follow current. It is
ground faults must be considered. However, recommended t h a t an arrester voltage rating
there are other sources of TOV and operating at least 25% higher t h a n t h e maximum
conditions t h a t affect arrester operation, as operating phase-to-ground voltage be selected
discussed in 3.3.1.1, 3.3.1.2, and 3.3.2. for stations when possible. Use of an arrester
3.3.1.1 Fault Conditions. The curves of with too low a voltage rating may result in an
Fig 2 may be used t o quickly determine tem- excessive failure r a t e of the arresters in
porary overvoltages during fault conditions service.
on applications involving short lines operat- Special conditims that should be considered
ing a t voltages through 242 kV. The numbers in choosing the arrester voltage rating are a s
adjacent t o each of the curves in Fig 2 are the follo w s :
coefficients of grounding in percent (see 33.2.1 Abnormal System Operating Volt-
D2.3.3 of Appendix D). From known values of ages. The selection of arrester voltage ratings
RdXl and XOfX1 determine the corresponding based on maximum system voltages assumes
coefficient of grounding, interpolating be- that, in service, the maximum system voltage
tween curves as necessary. Multiply the coef- is exceeded only under abnormal operating
ficient of grounding by maximum system conditions, and t h a t the probability of a coin-
phase-to-phase operating voltage t o determine cidental arrester operation is very small.
the temporary overvoltage t o ground at the However, if maximum system voltages used
point of fault. Alternatively, the voltage can be in determining temporary overvoltages, a s in
calculated using equivalent system imped- 3.3.1.1, are likely t o be exceeded frequently,
ances a s seen from the fault location. The increasing the probability of arrester opera-
effect of s h u n t reactors, shunt and series tions during such conditions, it may be neces-
capacitances, and distributed line capaci- sary t o use an arrester with a higher voltage
tances must be included in the calculations rating. Other causes of TOV, a s listed in
where significant. This applies particularly t o 3.3.1.2, require consideration on an individ-
applications involving long lines and EHV ual basis; no general rules are applicable.
lines [ l o ] . Where the s h u n t capacitance of 3.3.2.2 Abnormal System Frequency.
lines is large, there may be additional voltage Normal system frequency less than 48 or more
rises due t o line charging currents, harmon- than 62 Hz may require special consideration
ics due t o transformer saturation, and (less in the design or application of surge arresters
frequently) resonance effects.4 and should be a subject of discussion between
3.3.1.2 Other Causes of Temporary the user and the manufacturer.
Over~oltage.~ Other causes of TOV include: If any grounding source could be discon-
nected by sectionalizing, check the effect on
(1) Loss of neutral ground on a normally the coefficient of grounding and the arrester
grounded system. rating.
(2) Sudden loss of load or generator overspeed, 3 3 3 Choosing the Proper Class of Arrester.
or both. Choose the proper class of arrester based on
( 3 ) Resonance effects a n d induction from the protective characteristics summarized in
parallel circuits. Table 2 and the following:
(4) Accidental contact with conductors of a (1) Available voltage ratings.
higher voltage system. (2) Pressure relief current limits, which
33.2 Choosing the Tentative Arrester Volt- should not be exceeded by the system's avail-
age Rating. Choose the tentative arrester volt- able short-circuit current a t the arrester lo-
age rating based on the maximum phase-to- cation.
ground temporary overvoltage determined a s (3) Durability characteristics (see Table 2)
indicated in 3.3.1. This voltage rating should that are adequate for system requirements.
M
LL
ANSUIEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
23
ANSI/IEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
3.4.3.2 Discharge C u r r e n t s Where Lines shielded, the surges entering the station are
Are Shieldedf o r a Short Distance Adjacent to much less severe than those from unshielded
Station. Where shielding does not include the lines. Consequently, arrester protective levels
entire line, increased arrester discharge cur- are lower.
rents become more probable. In assessing the As a general rule, there is always some rise
probability of a n arrester discharge current, it in voltage between arrester terminals and
is necessary t o consider (a) strokes per unit protected equipment (see 2.5 and Appendix C).
area per mile, (b) probability of strokes t o line Therefore, i t is always good practice t o reduce
exceeding a selected value, and (c) percentage separation between a r r e s t e r a n d major
of total stroke current t h a t discharges through equipment t o a minimum. However, i t is
the arrester. Items (a) and (b) can be evaluated sometimes possiVe t o protect more than one
using the methods of Brown and Thunander piece of equipment with a single arrester
[IS]. It will be found conservative t o use the installation, provided t h a t rates of rise can be
following table [171 for item (c): restricted, as in the case where both the station
and all overhead feeder lines are shielded.
Distance Percent of Stroke 3.5.1 Locating Arresters in Nonshielded
Line Shielding Current Discharged Installations. Such installations are subjected
Extends from Station Through Arrester t o the highest lightning currents and voltage
0.5 mi (0.8 km) 50 rates of rise. The very minimum possible
1.0 mi (1.6 km) 35 separation i s recommended for installations
1.5 mi (2.4 km) 25
where complete shielding is not used.
3.5.1.1 Single U n s h i e l d e d Incoming
3.4.3.3 D i s c h a r g e C u r r e n t s in Stations O v e r h e a d L i n e . An arrester with a single
Where Lines Are Not Shielded. As discussed unshielded incoming overhead line should be
in 2.1.1.1, arrester currents due to lightning located as near a s possible to the terminals of
strokes are generally less than stroke cur- the equipment (usually a tranformer) to be
rents. Despite the fact t h a t stations with non- protected.
shielded lines can be subjected t o extremely 3.5.1.2 M u l t i p l e U n s h i e l d e d O v e r h e a d
high rates of rise from incoming surges and to L i n e s . When several unshielded incoming
high currents resulting from flashovers close overhead lines meet in the station, the incom-
t o the arrester, the effect of station bus, line ing overvoltage waves are reduced by reflec-
arrangement, and equipment is such t h a t the tion. However, consideration should be given
arrester current is significantly less than the t o the case where one o r more of the lines are
stroke currents discussed in 2.1.1. In general, disconnected by switching. When one or more
the discharge level for stations with un- circuit breakers o r disconnecting switches are
shielded lines should not be less than 20 000 A. open in such a station, the corresponding line
In severe thunderstorm areas (ie, keraunic entrances o r certain parts of the station may be
level 40 o r above), higher levels may be left without protection from the arresters at the
desirable. transformers. Lightning flashover of insula-
tion on a de-energized line i s unlikely t o
3.5 L o c a t i n g Arresters and D e t e r m i n i n g cause damage, but other insulation in equip-
Voltage at Protected Equipment. A major de- ment such a s circuit breakers, potential
termining factor in locating arresters is the transformers, and current transformers con-
shielding (if any) provided (see 2.1.1.3 and nected on the line side might be damaged. If
2.1.1.4). I t is usually feasible t o provide such cases are recognized t o require addi-
shielding for the substation proper even though tional protection, valve-type arresters or gaps
the associated lines are unshielded. This will can be installed at the respective line en-
reduce or eliminate direct lightning strokes to trances.
the station with accompanying steep fronts 35.2 Locating Arresters in Shielded Instal-
and extreme magnitudes. l a t i o n s . Incoming surge voltages from
However, i t should be recognized t h a t the shielded lines are limited in amplitude and
majority of strokes will be t o the lines, which steepness. In many cases, this will permit
will create surges t h a t travel along the line some separation between the arresters and the
and into the station 181. If t h e lines are insulation t o be protected.
24
ANSI/IEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
25
ANSI/LEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
26
ANSVIEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
Table 5
Maximum Allowable Separation
1 2 3 4
Allowable Separation, D t
PR(l)$(feet) (meters) (feet) (meters) (feet) (meters) (feet) (meters)
1.2 10 3 14 4.3 18 5.5 22 6.7
1.4 14 4.3 al 6.1 26 7.9 32 9.8
1.6 a0 6.1 29 8.8 39 12 50 15
1.8 33 9.1 46 14 64 a0 8Q %
1.9 37 11.3 a 19 88 ZI 118 40
2.0 49 14.9 8Q 26 130 40 167 83
2.1 68 20.7 132 40 234 n 397 121
*After Rules 2 and 3 (see C3.2 in Appendix C) have been applied.
t D = arrester lead length L + transformer lead length S (where L and S are measured from their junction with the path of
the incoming surge; see Fig C1 in Appendix C).
$This table is based on the use of CWW = 1.15 BIL. If surge front is reduced by the multiple-line effect (see Rule 5, C3.2)
such that sparkover occurs after 2 ps, the table should not be used.
NOTE: Table separations are calculated using a n incoming surge with a rate of rise of 8.33 crest kV/ps/kV (rms) of
arrester rating. For other rates of rise, use the methods of Appendix C.
Five standard protective ratios (PR) and 3.7.1.3 Significant Separation. As dis-
protective margins (PM) are identified a s cussed in 2.5 and 2.6, separation effects may
follow s:6 become significant when the protective ratio
(1)Where separation is not significant: (see 2.6) is less than 1.15. Table 5 gives the
maximum separation that can be used without
PR(1) = CWW/FOW PM(1) = [ P R ( l ) - 111 0 0
violating the 1.15 minimum limit for PR(1S)
PR(2) = B I U L P L PM(2) = [PR(2) - 11 1 0 0
a s defined in 3.7.1.1.
PR(3) = B S U S S P PM(3) = (PR(3) - 11 1 0 0
CAUTION: If the third footnote to Table 5 applies, use the
(2) Where there is significant separation detailed method of Appendix C, since the table may not be
valid.
(refer t o 3.7.1.3):
PR(1S) = CWW/Ei PM(1S) = [ P R ( l S ) - 11 1 0 0 3.7.1.4 Satisfactory Performance. Insu-
PR(2S) = BlL'Ei PM(2S) = [PR(2S) - 11 100 lation coordination is considered satisfactory
PR(3) = B S U S S P PM(3) = [PR(3) - 13 1 0 0 when all of the criteria of 3.7.1.1 or 3.7.1.2 (as
applicable) are met.
3.7.1.1 Protective Ratio Limits for Coordi-
3.7.2 Coordination Curve Comparison
nation. The PR limits for coordination are a s
Method [lo]. I t should be recognized that data
follows :
from t h e four (at most) generally available
PR(1) 2 1 . 2 PR(1S) t 1.15 insulation tests can be used to develop only an
PR(2) t 1.2 PR(2S) t 1 . 1 5 approximate insulation volt-time curve. A
PR(3) 2 1.15 curve plotted in accordance with the instruc-
tions given in the notes for Fig 3 is no more
3.7.1.2 Protective Margin Limits for than a graphical interpretation of the test re-
Coordination. The PM limits for coordination sults presented in a highly conventionalized
are a s follows: manner as an aid to insulation coordination.
PM(1) 2 20 PM(1S) t 1 5 It is not a true volt-time curve for the trans-
PM(2) 2 20 PM(2S) 2 15 former. On t h e other hand, t h e arrester-
PM(3) 2 15 PM(3) t 1 5 sparkover curve is an accurate representation
of an arrester's response to impulses.
%WW, chopped-wave withstand (see 2.4) Evaluation of insulation coordination by the
BIL, basic impulse insulation level (see 2.4)
BSL, basic switching impulse insu!ation level (see 2.4) curve method is made in accordance with Note
FOW, front-of-wave arrester sparkover (see 2.3.1) 3 to Fig 3.
LPL, lightning protective level (see 2.3.1 and 2.3.23 3.7.3 When Coordination Cannot Be
SSP, switching surge protective level (see 2.3.1 a n d
2.3.2) Achieved. If coordination cannot be achieved
Ei, voltage a t transformer ( s e e 3.7.1.3 and Appendix C) with the arrester tentatively select.ed in 3.3, i t
ANSUTEEE
C62.2-1987 E!EE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
I 5
14
13
12
I I
I O
09
08
07
06
0 5
NOTES: (1) F o r the transformer curve, plot four points for about 30 to 2000 ps. Connect t h e points with a curve of
t h e following withstand voltages a s obtained from t h e approximately the shape shown. If a m a n u f a c t u r e r ' s
manufacturer or standards: (a) front of wave (if avail- voltage-time sparkover curve is available, it may be used
able), (b) chopped wave, (c) full wave (BIL) a t about 8 ps, instead of the approximation. (b) Draw a ladder of lines,
and (d) switching surge a t about 300 p.Connect the points each extending from 5 pi to 10 ps a t levels corresponding to
with a dotted or dashed line showing disjointed curves a t 5 kA, 10 kA, and 20 kA discharge voltage. Add a similar
the chopped-wave point extending the full-wave voltage a s line passing through the 1.2/50-ps sparkover.
a straight line from about 8 to 50 ps and the switching surge
withstand voltage a s a straight line extending from ap- (3) To use the curve:
proximately 50 to 2000 ps and passing through the plotted ( a ) Locate the point between 0.5 and 50 ps where the
300-ps point. It is not possible to interpolate exactly between separation between withstand and arrester curve(s) is
points on t h e curve. Good experience has been obtained minimum. (Treat 1.2/50-ps sparkover and selected
with the assumptions implicit in the preceding rules: (a) discharge kA lines a s separate curves.) Calculate
The full BIL strength will apply for front times between 8 PM = [(withstand voltage)/(arrester voltage) - 11 x 100.
and 50 ps. (b) Minimum switching surge withstand occurs PM must be 2 20 a t this point. When separation effect
between 50 and 2000 ps. has been evaluated, PM must be 2 15%.
(b) Make a similar check between 50 and 2000 ps. P M
(2) F o r the arrester curve, approximate t h e sparkover must be 2 15%.
curve a s follows: (a) Plot three points for the following (c) If separation is significant (see 3.7.1.3), evaluate
published sparkover voltages for the specific arresters to be voltage a t protected equipment (Appendix C). Plot point
installed: front of wave, 1.2/5O-ps sparkover (at 8 ps), and at 3 ps if sparkover occurs in less than 2 ps; otherwise,
switching surge protective level a s a straight line from plot at 8 ps .
Fig 3
m i d Voltage-Time Curve for Coordination of Arrester Protective Levels
with Insulation Withstand Strength for Liquid-FilledTransformers
ANSIlIEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
29
ANSIllEEE
C62.2-1987 LEEE GUIDE FOR TKE APPLICATION OF GAPPED SILICON-CARBIDE
Delta and ungrounded-wye capacitor banks (2) Select the capacitors on the basis of ma-
have very small values of capacitance t o chine voltage rating and connection in
ground, and a lightning surge on one phase accordance with manufacturer's recom-
will tend t o charge the other phases through the mendations.
phase-to-phase capacitance. Therefore, light- (3) Determine the minimum permissible BIL
ning surges can be hazardous and these banks of t h e insulation by multiplying the
should be protected. Grounded-wye banks have lightning impulse protective level (LPL) of
their full capacitance from line t o ground and the arrester by 1.2 (see 3.7.1).
tend to reduce the magnitude of surge voltages (4) Select the voltage r a t i n g a n d class of
reaching their terminals. In some instances, arrester as directed in 3.3.3.
these banks are self-protecting. This is not 3.11.2 Machines Connected to Overhead
always the case, however, and thus arresters Lines Through Transformers. For machines
should be considered for each capacitor bank connected to overhead lines through trans-
application. formers L39-421 protection a s described in
Severe duty is imposed on arresters adjacent 3.11.1 may not be required, or the capacitors
t o shunt capacitor banks due t o high energy may possibly be omitted [43,441. It is possible t o
discharges during bank switching, regard- make a n investigation of resultant surge
less of whether the arresters were installed for voltages using a recurrent surge generator.
protection of the capacitor or other equipment. However, i t i s suggested t h a t Dillard and
Of particular concern is prestriking o r re- Hileman [431 and Abetti, Johnson, and Schultz
striking of t h e switching device during [441 be reviewed before proceeding to perform
switching operations. F o r switched capacitors, such tests.
surge arresters are recommended near the When arresters are definitely t o be installed
switching device on the capacitor side of the a t the machine terminals, follow the procedure
switch. The arrester manufacturer should be in 3.11.1.
consulted for aid in selecting arresters suit-
able for the duty. 3.12 Protection of Gas-InsulatedSubstations.
3.10.2 D u t y on Arresters. Duty on arresters Becausz all insulation within a gas-insulated
connected t o terminals of large capacitance substation (GIS) must be considered non-self
cables is similar t o t h a t caused by shunt restoring, surge protection should be provided
capacitor switching 134, 351 see 3.5.3. and must be coordinated with all elements of
the station. The most critical protective case
3.11 Protection of Rotating Machines. At for the line entrance arrester is coordination
present a guide for the protection of rotating with a GIS open switch o r circuit breaker and a
machines is in preparation (ANSIDEEE Std steep-front incoming lightning surge. Two
C62.21). This section will not be applicable approaches have been taken in the arrester
when the new guide becomes available. protection of existing stations connected to
3.11.1 Machines Connected to Overhead overhead lines: (1) conventional arresters a t
Lines Directly or Through n Short Length of t h e line entrance, a n d (2) special gas-
Cable. For machines connected to overhead insulated surge a r r e s t e r s a t more ideal
lines, either directly or through a short length protective locations within the GIS.
of cable, perform the following [36-381: The dominant design criterion in the insu-
(1) Install a s close a s practical to the machine lation coordination and surge protection of a
terminals, between phase and ground, GIS is related to lightning overvoltages. Most
surge protective capacitors to reduce the estimates of the increase (turnup) of GIS insu-
slope of the wave front and arresters to lation strength for waves with short front
limit t h e magnitude of the incoming times down to approximately a microsecond
surge. Also, connect arresters on the range from none a t all t o very modest. Steep-
overhead lines ahead of t h e machine front reflections from surge impedance dis-
location o r a t an overhead line-cable continuities within the GIS-most notably an
junction point. Capacitors may not be open switch-can lead t o significant differ-
required for installations involving ma- ences between surge arrester protective level
chines with single-turn coils where there and surge voltage magnitude at substation
is no turn-to-turn stress. locations remote from the arrester.
30
ANSI/IEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
coordination becomes a primary considera- cases the voltage on the unfaulted phases
tion for higher-voltage systems (particularly must be calculated t o determine arrester
when reduced BIL values are used), for line rating).
protection (see 4.6), and for protection of On systems where i t is possible to backfeed a
underground distribution systems (see 4.10). portion of the circuit through devices such as
4.2.1 Installation practices jeopardizing in- transformers o r capacitors connected t o the
sulation coordination. circuit after a phase has been interrupted, the
(1) Long lead wires between line and ar- arrester rating should be at least equal t o the
rester line terminal and between arrester maximum phase-to-phase voltage.
ground terminal and ground (see 4.5.1). 4.3.3 Four-Wire M u l t i g r o u n d e d Wye Sys-
(2) Large separation distances between the tems (Including Spacer-Cable Circuits). Since
arrester and the protected equipment (see most distribution systems are of the four-wire
4.5.2). multigrounded wye type, arrester ratings used
( 3 ) Failure t o interconnect the arrester and have been established by many years of
equipment ground terminals (see 4.5.4). operating experience.
4.2.2 Applications Requiring Special Con- This long-term experience is not available
s i d e r a t i o n s . Applications that require special for the higher-voltage distribution systems
considerations, either in regard t o duty re- being installed o r for spacer-cable circuits,
quirements imposed on the arrester or in re- and a method for establishing arrester ratings
gard t o protection requirements include: is required. In a generally accepted method
(1) Arrester protection of s h u n t capacitor [501, the nominal phase-to-ground operating
banks (see 4.7). voltage of the system is multiplied by:
(2) Arrester protection of switches, reclosers, (1) 1.25 for four-wire multigrounded wye
etc (see 4.8). open-wire circuits;
(3) Arrester protection of voltage regulators (2) 1.50 for spacer cable circuits.
(see 4.9). These multiplying factors take into account
(4) Arrester protection of underground cir- voltage regulation and the effect of connected
cuits (see 4.10). distribction transformers magnetizing reac-
(5) Arrester application in contaminated at- tance. For open-wire systems having operat-
mospheres (see 4.11). ing voltages not listed in Table 6 , the 1.25
factor is recommended t o determine arrester
4.3 Selection of Arrester Ratings. Systems to rating; for spacer-cable circuits, the 1.5 factor
be protected by distribution arresters are (1) can be used a s a guide, but it is recognized that
delta connected, (2) three-wire wye uni- this results in conservative minimum a r -
grounded at the source, or ( 3 ) four-wire multi- rester ratings.
ground wye. Construction includes open wire,
spacer cable, and underground. 4.4 I n s u l a t i o n C o o r d i n a t i o n . Distribution
Voltage ratings of arresters usually applied system insulation coordination is normally
to distribution systems are listed in Table 6. based on the following protective margins:
General characteristics of distribution ar-
PM(1) = (CWWE'OW - 1 ) l O O
resters are shown in Tables 7a and 7b. PM(2) = ( B I M R - 1 ) l O O
4.3.1 D e l t a S y s t e m s . The arrester rating
should be equal t o or greater than the maxi- For oil-filled, a i r , and solid (inorganic)
mum phase-to-phase voltage. insulation, CWW can be assumed to be
4.3.2 T h r e e - W i r e U n i g r o u n d e d Wye Sys- 1.15 x BIL; for dry-type (organic) insulation,
tems ( G r o u n d e d at S o u r c e Only). In lieu of the CWW i s assumed to be the same a s
calculations t o determine phase-to-ground the BIL.
voltages during single line-to-ground faults, The general rule is t h a t PM(1) and PM(2)
i t is generally acceptable t o use an arrester must both be a t least 20%.However, experience
rating a t least equal t o 80% of the maximum with surge protection of distribution systems
phase-to-phase voltage with no fault on the (15 kV and less) has been gained with protec-
system. (The 80% rule is usually not ap- tive margins greatly in excess of 20%. By
plicable when these unigrounded systems are connecting ilistribution a r r e s t e r s directly
grounded through an impedance. In these across overh(bad equipment insulation, sepa-
32
ANSIlIEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
ration effects (SE) a r e minimized and con- at which interconnection is made t o the pro-
sideration of PM(1) can usually be neglected. tected equipment ground (minus the length of
However, PM(1) must be considered when the arrester). A commonly accepted voltage
arresters are used for line protection (see 4.6), value t o be added t o the arrester discharge
underground systems protection (see 4.1 01, or voltage is 1.6 kV/ft of lead wire [521. Based on
dry-type insulation protection. A PM(1) of at tests, this voltage develops from a 20 kA
least 20% is recommended for dry-type insu- discharge current (4 x 1 0 ps wave) for lead
lation. lengths under 5 ft [531 Although the lead wire
The discharge voltage of an arrester is voltage developed at insulation coordination
greater for less frequent high crest lightning levels of 1 0 and 20 kA (8/20-ps wave) are
surges and increases with higher rates of rise approximately one-fourth a n d one-half the
of lightning current [511. I t is the usual prac- value of 1.6 kV ft [531 , it is important to keep
tice t o select a reference value of discharge lead lengths a s short as possible. Higher
current t h a t will be exceeded infrequently. lightning currents, faster rising current
The discharge voltage at this reference level waves, a n d long lead lengths produce sub-
is used t o calculate PM(2). Obviously, the stantially higher voltages. Excessive lead
selection of a higher reference level for wire lengths can eliminate the safety factor
any given arrester will result in a smaller allowed for by the protective margin PM(2).
PM(2). 4.5.2 Effect of Separation Distance. Distri-
There is no universally accepted surge cur- bution arresters are often used to protect a
rent level on which t o base insulation coordi- single piece of equipment and, therefore,
nation, although currents in the 10-20 kA should be connected a s close as possible to the
range are often used. [The range of arrester equipment. This reduces separation effects
discharge voltage values at 1 0 kA (8/20-ps (see Section 2 and Appendix C). Arresters used
wave) is shown in column 5 of Table 7a.l Ref- to protect equipment should not be installed on
erence currents above 20 kA can be considered separate poles (a pole span away from the
t o take into account lightning currents with equipment t o be protected), especially where
faster rates of rise than the standard test waves only one arrester is used and the transformer
used t o make discharge voltage measure- is connected to a line t h a t runs in two direc-
ments 1513 or where severe lightning is com- tions from the tap point. In effect, surges ap-
mon. (Arrester discharge voltage values can proaching equipment from the side where no
be obtained from the manufacturer for cur- arrester is installed are not limited and may
rents greater than 20 kA.) Strict application of cause equipment failure. Surges approaching
the 20% margin rule will then favor the use of from the arrester side are limited by arrester
arresters with low discharge voltages. PM(2) action, but separation effect is very high.
does not include a n allowance for voltage de- 4.5.3 Location of Arresters with Respect to
veloped across arrester connecting lead wires Equipment Fuses. In general, it is a good
(see 4.5.1). The arrester discharge voltage practice t o connect fuses between the arrester
characteristic t o be used for insulation coordi- and the transformer or other equipment being
nation purposes is the total of the arrester protected. This minimizes the magnitude of
discharge voltage plus the connecting lead lightning current carried by the fuse during
wire voltage. Maintaining lead wires a s arrester operation and the possibility of fuse
short as possible is particularly impor- damage or blowing. Where fuses must be
t a n t when protecting underground systems connected ahead of arresters (for instance, to
(see 4.10). keep arrester lead wires short when protecting
underground cable equipment), i t is recom-
4.5 Arrester Connections mended that the surge withstand characteris-
4.5.1 Effect of Connecting Lead Wires. tics of the fuse be evaluated [551.
Lightning currents discharging through the 45.4 Interconnection of Grounds
inductance of connecting wires produce a 4.5.4.1 Primary and Secondary Ground.
voltage t h a t adds t o the arrester discharge I t i s recommended t h a t primary and sec-
voltage. The total length of these wires is ondary grounds of the distribution trans-
measured from the point at which the arrester former be interconnected with the arrester
line connection is made t o the line t o the point ground terminal.
33
ANSI/IEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
34
ANSVIEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
Table 6
Commonly Applied Voltage Ratings of Arresters on Distribution Systems
System Voltage Usually Applied Arrester Ratings
(kV rms) (kV rms)
Four-Wire Three-Wire
Maximum Multigrounded Unigrounded Delta and Spacer-
Nominal Voltage Neutral Neutral Ungrounded Cable
Voltage Range B* Wye Wye Wye Circuits?
2403 2540 3
416OYl2400 44ooY12540 3 6 3
4160 4400 6
4800 5080 6
6900 7260 9 or 9 A O
8320Y/4800 8800Y15080 6 9 or 9 A O 6
12 00OYl6930 12 700Yl7330 9 or 9 A O 9 A O o r 10 SA0 or 10
12 470Yi7200 13 200Yi7620 9 or 9 A O 12 9DO or 10
13 200Yl7620 1 3 97OYl8070 9 A O or 10 12 9 A O or 10
13 8OOYl7970 14 52OYl8380 N O , 10, or 12 12 12
13800 14 520 15
20 78OYD2 OOO 22 OOOYA2 700 15 18 18
22 860YA3 200 24 200YA3 970 18 zl a
Boo0 24340 25
24 94OYD4 400 26 400YA5 240 18 a 2l
34 m m 9 9x1 36 510Y/2180 25 or 27 30 30
34500 36 n o 36$ or37$
*See ANSI (34.1-1982 [54].
t T h e use of spacer cables a t most system voltages has had limited application, reducing t h e experience factor in
establishing arrester ratings usually applied. Where experience is a factor, arrester ratings lower t h a n 1.5 x nominal
system line to gmund voltage [50] have been used. This is taken into account for the voltage ratings listed.
$Nonstandard distribution arrester voltage ratings.
Table 7a
Distribution Arrester Protective Characteristics
~~ ~~ ~
Protective Levels
Per-Unit Crest Arrester R a t s
Range of Front-of-W ave Sparkover Discharge
Application Without With With
Rating Maximum System External External 10 kA
(kV) Voltage (kV) Gap (kV) Gap (kV) 8120-ps Wave
3 2.6-4.5 3.30-5.89 5.66-8.95 2.71-3.25
6 4.5-7.8 3.18-4.12 5.30-6.71 2.65-3.06
9-1 2 7.8-1 4.3 2.83-3.77 4.30-5.97 2 55-3.22
15-21 18-25.8 2.12-3.54 3.70-5.42 2.45-3.09
25-30 38 2.02-3.54 2.36-2.75
*The per-unit values shown are maximum industry values from tables in Appendix A. For specific values, consult
manufacturer's literature.
NOTE: Protective level (kV) = per-unit level x rating x f i . For example, range of FOW sparkover for a 12-kV arrester is
(2.83 tu 3.77) x 1 5 2 = 48 tu 64 kV.
Table 7b
Distribution Arrester Durability Characteristics*
(1) (2) (3)
Duty Cycle Low-Current
Initiating Long-Duration High-Current
Arrester Surge Withstand Withstand
Class (Cres<(A)) (Crest (A)) (ps) (Crest (A))
Normal Duty 5Ooo 75 m 65oo0
Heavy Duty 10ooo 2-53 m 100 ooo
-
*This refers to the ability of the arrester to protect itself against the stresses resulting from:
I
(1) Cumulative power-follow current and surge discharge operations (which also determine the ability to reseal
against a voltage equal to the arrester rating).
(2) Long-duration lightning.
(3) Severe lightning discharges.
35
ANSI/LEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
36
ANSI/IEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
37
ANSVIEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
tection of a failed arrester from ground level that arrester damage does occur, an arrester
may be difficult, b u t close inspection will with a higher voltage rating than what would
usually reveal a burn mark or bubble of metal normally be applied would be required. The
on the arcing horn from the passage of abnor- higher sparkover voltage reduces the chance of
mally high power frequency current. sparkover, and the higher discharge voltage
In the case of a n arrester equipped with a reduces the duty on the arrester if sparkover
disconnector, operation of the disconnector does occur. Additional information on t h e
physically separates t h e arrester ground effects of current-limiting fuses can be found
connection from the failed arrester and t h u s in Kershaw, Huber, a n d Hassler 1641, Olive
gives a visual indication of failure. Care m u s t and Westrom [651, a n d I E E E Switchgear
be taken t o provide enough clearance t o ensure Committee and Surge Protection Devices
t h a t the separated ground lead is not thrown Committee Working Group, Coordination of
into a n energized conductor. Lightning Arresters a n d Current-Limiting
NOTE: In certain designs, operation of the disconnector is Fuses [661.
achieved by the detonation of a small explosive charge
when follow current is abnormal. No attempt should be
made to unload o r disassemble a disconnector.
5. Bibliography
4.14 Current-Limiting Fuses. Current-limit-
ing fuses are used t o protect and isolate faulted BECK, E. Lightning protection for electric
single-phase laterals and some three-phase systems. New York: McGraw-Hill; 1954.
laterals in addition t o transformer isolation.
Since some current-limiting fuses can gener- GREENWOOD, A. Electric Transients i n
ate a high arc voltage with peak magnitudes Power Systems. New York: Wiley Inter-
exceeding system voltage, care must be exer- science, 1971.
cised t o ensure proper coordination between the
fuse and the arrester. ANSI C92.2-1987, American National Stan-
Although experience with these applications dard fc r Power System s-AI t e r n a t i n g- C u r -
is limited, distribution arrester damage a s a rent Electrical Systems and Equipment Oper-
result of current-limiting fuse operation h a s ating at Voltages Above 230 kV Nominal-
not been an application problem. In the event Preferred Voltage Ratings.
38
ANSI/IEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
Appendixes
(These Appendixes are not a part of American National Standard Guide for the Application of Gapped Silicon-Carbide
Surge Arresters for Alternating-Current Systems, ANSI/IEEE C62.2-1987, but are included for information only.)
Appendix A
Protective Characteristics of Surge Arresters
In lieu of specific data on protective charac- should be used for more accurate insulation
teristics of available surge arresters, Tables coordination. Among the various columns of
A1 through A6, which a r e compiled from protective characteristics, the highest or the
domestic manufacturers' catalog informa- lowest maximum values of sparkover and
tion, can be used as a guide in general discharge voltage are not necessarily related
insulation coordination studies. I t should be to the same arrester. For example, a particular
recognized t h a t these data are the range of the 12 kV arrester whose front-wave sparkover
maxima listed in manufacturers' catalog is identical t o the lowest maximum value
information for each type of arrester, result- shown in one of the tables does not neces-
ing in certain apparent inconsistencies in the sarily possess t h e lowest maximum value
tables. Therefore, the specific manufacturer's shown for discharge voltage in the 10 000 A
information on the arrester being applied column.
ANSI/LEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
ANSI/IEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
ANSUIEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
42
ANSI/IEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
Table A5
Protective Characteristicsof Gapped Silimn-CarbideDistribution Arresters for the Pmtection of
Rotating Machines and Dry-Type Transformers
oulse Soarkover Voltage Tee Voltaee for W20-u~Discharge Current Value
100 k V l p
Vo 1t age l o p to per12 kV 1.2/50-ps kV Crest kV Crest kV Crest kV Crest kV Crest
Rating of Sparkover of Rating Crest for1500A for3000A for5000A for10000A for20000A
Arrester (Range of (Range of (Range of (Range of (Range of (Range of (Range of (Range of
(kV rms) Maxima) Maxima) Maxima) Maxima) Maxima) Maxima) Maxima) Maxima)
3 12-16 11-16 11-16 9-9.5 9.5-10.5 10-11 11-12 12-13.5
4.5 16.5-18 16.5-19 17-18 13.5-15 14.5-17 15-17.5 16.5-19 17.5-21.5
6 22-24 21-24 22 -25 14-19 19-21 20-22 22-24 23.5-27
7.5 26-26 26-26.5 26-26.5 22.5-25 24-27 25-29 27-31 29.5-35
9 30-32 32-32 31-32 27-28 29-32 30-33 32.5-36 3540
12 3941 3941 39-41 36-38 38.542 404 434 47-54
15 4749 4647 4649 4245 46.448 50-51 54-55 58.5-62
Table A6
Pmtective Characteristicsof Gapped Silicon-CarbideStation Arresters for the
Protection of Rotating Machines and Dry-- Transformers
-Jmoulse Soarkover Voltape -Discharee Voltaee for 8120-us Dischame Current Value
100 kV1p
Voltage lop to per12 kV 1.2/50-ps kV Crest kV Crest kV Crest kV Crest kV Crest
Rating of Sparkover of Rating Crest for 1500 A for 3000 A for 5000 A for 10 WO A for 20 OOo A
Arrester (Range of (Range of (Range of (Range of (Range of (Range of (Range of (Range of
(kV rms) Maxima) Maxima) Maxima) Maxima) Maxima) Maxima) Maxima) Maxima)
3 10-12 10-13 a 12 4.7-5 5.3-5.8 64.4 6.7-7.3 7.7-8.3
4.5 13-14 1416.5 12.5-15 7-7.5 8-8.7 8.9-9.5 10-10.8 11.5-12.3
6 iaia 19-19 1&18 93-10 10.6-11.5 11.9-12.0 13.4-14.3 15.3-16.3
7.5 23-24 24-25 20-23 11.6-12.2 13-14.3 14.8-15.7 16.7-17.7 19-20.3
9 26-28 28.540 24-26 13.9-14.6 16-17.1 17.8-18.8 20-21.2 22.9-24.3
12 35-36 3641 3236 18.5-19.5 21.3-22.7 23.5-24.9 26.7-28.1 30.1-32.1
15 43-43 4.551 40-43 23.1-24.2 26.6-28.2 29.5-31 33.4-35 38.2-40
16.5 - - 44-46 - - - - -
18 48-41 5240 4749 27.7-28.9 31.9-33.7 35-37.1 40-41.8 45.8-47.8
19.5 - - 52-52 - - - - -
21 54-59 63-70 54-56 32.3-33.7 37.2-39.3 41-43.2 46.8-48.7 53.4-55.5
22.5 - - - - - - - -
w 62-65 n-78 6244 36.9-38.5 42.8-44.8 4749.2 53.4-55.5 6143.5
25.5 - - - - - - - -
27 69-73 80-86 69-75 41.5-43.1 47.8-50.3 53-55.3 60-62.5 68.7-71.2
43
ANSYLGEE
C62.2-1987 LEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
AppendixB
44
ANSI/IEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
~~
I. Surges where several sparkovers are permitted (7) Energizing, deenergizing, or load dropping of line
(see B4.1) transformer unit (harmonic overvoltages)
(1) Prestriking when energizing capacitive circuits with (8) Voltage magnification on closing
disconnecting switches (9) Restriking circuit breaker when deenergizing line
(2) Restriking when deenergizing capacitive circuits with (10) Switching capacitor banks or long cables
disconnecting switches. (1 1) Chopping inductive current by circuit breakers
II. Surges where only one or two sparkovers are permitted 111. Surges where temporary overvoltages approach reseal
(see B4.2) capability of surge arrester (see B4.3)
(3) Energizing line or line transformer (1 2) Clearing line-to-ground faults at one end of line
(4) Energizing line with shunt compensation (13) Clearing overspeeding ac machines
(5) Reclosing on line with trapped charge (14) Closing when out of phase
(6) Reclosina., shunt-comDensated line with trawed
\ I , , (15) Linear resonance effects
..
rharnp
-. Y- ~ -, Ferroresonance
i l Si - . - . . . oscillations
.- . .. -
NOTE This figure lists some switching surges that often reqLlre special consideratoon The list IS not exhaustive [BA
Fig B1
Causes of Switching Surges that Mect Arrester Applications
46
ANSVLEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
AppendixC
47
ANSVLEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
(REMOVED)
(RULE 3)
(RULE 4 )
675 kV/ws
ARR S = 29ft
TI
h
(REMOVED) L = 71ft
(RULE I ) D = 100 f t
4
w ARR
TI T2 -
TRANSFORMERS
550 kV BIL
(a 1 (b)
Fig C1
Station Configuration anc Equivalent Base
49
ANSIAEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
AppendixD
Definitions
: D 3 ] XYSI C92.1-1982, American National D2.4 Traveling Wave. The resulting wave
Standard i’oltage Values for Preferred Tran- when an electrical variation in a circuit such
sient Insulation Levels. a s a transmission line t a k e s t h e form of
translation of energy along a conductor, such
energy being always equally divided between
D2 Overvoltages current and potential forms; see ANSUIEEE
SM 100-1988 [D21.
D2.1 Overvoltage. Abnormal voltage between
t w o points of a system that is greater than the
highest value appearing between the same two D3. Impulses
points u n d e r normal service conditions.
Overvoltages may be low-frequency, tempo- D3.1 Impulse. A surge of unidirectional
rary, and transient (surge). polarity.
D2.2 Surge. A transient wave of current, D3.2 Crest (Peak) Value of an Impulse. The
potential, o r power in an electric circuit; see maximum value t h a t an impulse attains.
ANSVIEEE Std C62.1-1984 [Dl].
D2.2.1 Lightning Surge. A transient D3.3 Wave Front of an Impulse. That part of
electrical disturbance in a n electric circuit an impulse that occurs prior t o the crest value.
caused by lightning; see ANSUIEEE S t d
C62.1-1984 [Dl]. D3.4 Wave Tail of an Impulse. That part
D2.2.2 Lightning Overvoltage. The crest between crest value and the end of the impulse;
voltage appearing across an a r r e s t e r o r see ANSVIEEE Std C62.1-1984 [Dll.
insulation caused by a lightning surge.
D3.5 Wave Shape of an Impulse Test Wave.
D2.3 Switching Overvoltage. Any combina- The graph of the wave a s a function of time;
tion of switching surge(s) and temporary see ANSIAEEE Std C62.1-1984 [Dll.
overvoltage(s) associated with a single
switching episode. D3.6 Wave Shape Designation of an Impulse
D2.3.1 Switching Surge. A heavily damped D3.6.1 The wave shape of an impulse (other
transient electrical disturbance associated than rectangular) of a current o r voltage is
with switching. System insulation flashover designated by a combination of two numbers.
(see D5.7) may precede or follow the switching The first, an index of wave front, is the virtual
in some cases but not all. duration of the wave front in microseconds a s
D2.3.2 Temporary Overvoltage. An oscil- defined in D3.8. The second, an index of the
latory overvoltage associated with switching wave tail, is the time in microseconds from
of relatively long duration, which is un- virtual zero t o the instant a t which one-half of
damped o r slightly damped. the crest value is reached on the wave tail.
51
ANSUlEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILICON-CARBIDE
Examples are 1.2150 ps and 8120 ps waves; see D4.2.2. Transformer Products. For trans-
ANSIIIEEE Std C62.1-1984 [Dl]. former products: 100 x 1000 ps.
D3.6.2 The wave shape of a rectangular D4.2.3. Arrester Sparkover Tests. For ar-
impulse of current or voltage is designated by rester sparkover tests:7
two numbers. T h e f i r s t designates t h e (1) 30-60 x 90-180 ps
minimum value of current or voltage t h a t is (2) 150-300 x 450-900 ps
sustained for t h e time i n microseconds (3) 1000-2000 x 3000-6000 ps
designated by the second number. An example
is the 75 A x 1000 ps wave; see ANSVIEEE Std
C62.1-1984 [Dl]. D5.Insulation Coordination
D3.7 Virtual Zero Point of an Impulse. The D5.1 Coordination of Insulation. The process
intersection with the zero axis of a straight of correlating the insulation strengths of
line drawn through points on the front of the electric equipment with expected overvoltages
current wave at 1 0 and 90% crest value, o r and with the characteristics of surge protective
through points on the front of the voltage wave devices; see ANSI C92.1-1982 [Dll.
a t 30 and 90% crest value; see ANSIIIEEE
C62.1-1984 [Dl]. D5.2 Withstand Voltage. The voltage t h a t
electric equipment is capable of withstanding
D3.8 Virtual Duration of Wave Front of an without failure or disruptive discharge when
Impulse. The virtual value for the duration of tested under specified conditions; see ANSI
the wave front is as follows: C92.1-1982 [Dl].
(1) For voltage waves with wave front
durations less than 30 ps, either full or chopped D5.3 Basic Lightning Impulse Insulation
on the front, crest, or tail, 1.67 times the time Level. The electrical strength of insulation
€or the voltage to increase from 30 t o 90% of its expressed in terms of the crest value of a stan-
crest value. dard lightning impulse. The basic lightning
(2) For voltage waves with wave front impulse insulation level (BIL) may be either a
durations of 30 ps or more, the time taken by statistical BIL or a conventional BIL, defined
the voltage t o increase from actual zero t o as follows (see ANSI C92.1-1982 [Dll).
maximum crest value. D5.3.1 Statistical BIL. Applicable specifi-
(3) For current waves, 1.25 times the time for cally t o self-restoring insulations. The crest
the current t o increase from 10 t o 90% of crest value of a standard lightning impulse for
value. which the insulation exhibits a 90% probability
of withstand (or a 10% probability of failure)
D3.9 Nominal Rate of Rise (of an Impulse.) under specified conditions.
For a wave front, the slope of the line t h a t de- D5.3.2 Conventional BIL. Applicable spe-
termines the virtual zero. I t is usually ex- cifically t o nonself-restoring insulations.
pressed in volts o r amperes per microsecond. The crest value of a standard lightning im-
pulse for which the insulation shall not exhibit
disruptive discharge when subjected t o a spe-
D4. Standard Impulses cific number of applications of this impulse
under specified conditions.
D4.1 Standard Lightning Impulse. The wave
shape of standard impulse used (when it is D5.4 Basic Switching Impulse Insulation
not in conflict with product standards) is Level. The electrical strength of insulation
1.2150 ps. expressed in terms of the crest value of a stan-
dard switching impulse. The basic switching
D4.2 Standard Switching Impulses. The wave impulse insulation level (BSL) may be either a
shapes of standard impulse tests depend on statistical BSL or a conventional BSL, defined
equipment being tested. a s follows (see ANSI C92.1-1982 [DlI).
D4.2.1 Air Insulation and Switchgear. For
air insulation and switchgear: 250 x 2500 ps; 7The tail duration is not critical; see ANSIlIEEE C62.1-
see ANSI C92.1-1982 [Dll. 1984 [ll.
52
ANSI/IEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
D6.1 Surge Arrester. A protective device for D6.8 Follow (Power) Current. The current
limiting surge voltages on equipment by dis- from the connected power source t h a t flows
charging or bypassing surge current; i t pre- through an arrester during and following the
vents continued flow of follow current t o passage of discharge current; see ANSVIEEE
ground, a n d is capable of repeating these C62.1-1984.
functions as specified; see ANSVIEEE C62.l-
1984 D11. D6.9 Arrester Recovery Voltage. The crest
voltage t h a t occurs across the terminals of an
D6.2 Valve Arrester. An arrester that includes arrester following a unit operation.
a valve element; see ANSVIEEE C62.1-1984.
D6.2.1 Arrester Rating. The designated D6.10 Reseal Voltage Rating of an Arrester.
maximum permissible operating voltage The maximum arrester recovery voltage per-
between an arrester's terminals at which i t is mitted for a specified time following one or
designed t o perform its duty cycle. I t is the more unit operation(s) with discharge cur-
voltage rating specified on the nameplate; see rents of specified magnitude and duration.
ANSVIEEE C62.1-1984 [Dl].
D6.4 Valve Element. A resistor that, because of D7.2 Maximum System Voltage. The highest
its nonlinear current-voltage characteristic, rms phase-to-phase voltage t h a t occurs on the
limits t h e voltage across t h e a r r e s t e r system under normal operating conditions,
ANSVIEEE
C62.2-1987 IEEE GUIDE FOR THE APPLICATION OF GAPPED SILJCON-CARBIDE
and the highest rms phase-to-phase voltage for nated, a n d to which certain o p e r a t i n g
which equipment and other system compo- characteristics of t h e system a r e related.
nents are designed for satisfactory continuous (The nominal voltage of a system is near the
operation without derating of any kind. (This voltage level a t which the system normally
voltage excludes voltage transients and tem- operates a n d provides a per-unit base
porary overvoltages caused by abnormal sys- voltage for system study purposes. To allow
tem conditions such a s faults, load rejection, for operating contingencies, systems gen-
and so forth.) erally operate a t voltage levels about 5 to
10% below the maximum system voltage
D7.3 Nominal System Voltage. The system for which t h e system components a r e
voltage by which the system may be desig- de sign e d. 1
54
ANSI/IEEE
SURGE ARRESTERS FOR ALTERNATING-CURRENT SYSTEMS C62.2-1987
AppendixE
Coefficientiof-Grounding(COG)Calculations
As an aid to users of Fig 2, the following The curves in Fig 2 include the effects of
equations can be used to calculate the coeffi- fault resistance. For each point, a fault
cients of grounding (COG). The equations are resistance was chosen t h a t produced t h e
applicable for 21 =Z2,a s are the curves in maximum COG. In general, however, fault
Fig 2. resistance tends to reduce the COG, except in
Single line-to-ground (SLG) f a u l t on low-resistance systems. To include fault
phase a: resistance R f , the definition of k above would
1 d3k
7
AppendkF
Arrester Stroke Currents-Arresters C o ~ e ~tot Distribution
d Lines
The magnitude of lightning stroke currents, .08% will exceed 100 kA
discharged through distribution surge ar- .41% will exceed 61 kA
resters, was investigated in an Electric Power 1.8% will exceed 40 kA
Research Institute (EPRI) study, EPRI EL- 3.4% will exceed 30 kA
1140, Study of Lightning Current Magnitude 9.3% will exceed #) kA
through Distribution Arresters. Sept, 1979. 23.3% will exceed 10 kA
Values obtained are tabulated: 45.4% will exceed 5 kA
56