Smart Positioners YT-3300 / YT-3350 / YT-3301 / YT-3303

Torque motor technology with communications

Design features • Auto / Manual switch. Enables closed-loop automatic


valve position control or manual positioning via the A/M
• Auto calibration. Simple menu structure with options to switch. The manual mode is useful for troubleshooting,
auto calibrate all parameters or zero and end points only. calibration, system testing or as a manual bypass.
• LCD display. Alphanumeric digital display for process • HART communication. Allows commands, position
values and calibration. feedback and diagnostics to be sent digitally over the
• Partial Stroke Test (PST). Fully adjustable Partial current loop.
Stroke Test. All functionality can be performed and • Front panel pushbuttons for configuration. 4 robust
selected locally, through push buttons, or remotely with and positive acting pushbuttons for field configuration.
communication protocol. • Remote Mounting Option (YT-3301 model).
• Feedback signal. Analogue and Digital feedback signals Remote sensor via cable to enable the positioner to be
with 4 to 20 mA, mechanical and proximity switch options mounted away from extreme temperature.
(Limit switch options for YT-3300 and YT-3350 models).
• PID control. Pre-calibrated and user configurable
variables via front panel pushbutton menu. SIL ®
SIL LEVEL 2

YT-3300 Aluminium Enclosure

Adapter Type Lever

(0.08)

(1.04) (1.18)
26.5 30
2
(3.67)
93.1

105.3
(4.15)
YT-3350 STS316 Enclosure

(2.11)
53.5
10
196.8
(0.39)
(775) 107.8
240
(4.24)
(9.45)

Dimensions: mm (Inches ")

YT-3301 Remote Mounting Option


Cable Connector
(0.98)
25
(4.13)
105

(2.91)
74

91.5
(3.60)

YT-3303 Left Side Mounting Option 16


(0.63)
(5.82)
147.8

202.8 111.8
(7.98) (4.40)

14 Valve Positioners and Accessories


Smart Positioners YT-3300 / YT-3350 / YT-3301 / YT-3303

Item Type YT-3300 YT-3303 YT-3350 YT-3301 Product Code


YT-3301 - L - S - N - 2 - 4 - 2 - 4 - S - (1)
Input Signal 4 - 20 mA DC

Supply Pressure 0.14 - 0.7 MPa (1.4 - 7 bar)


Linear Model
10 - 150 mm
Type YT-3300 = Aluminium housing
Stroke
Rotary YT-3301 = A
 luminium housing with
0 - 90°
Type remote sensor
Impedance Max. 500 Ω @ 20 mA DC YT-3303 = A
 luminium housing with
right side lever
Air Connection PT(NPT,G)1/4 NPT1/4 PT(NPT,G)1/4 YT-3350 = Stainless steel housing

Gauge Connection PT(NPT)1/8 NPT1/8 PT(NPT)1/8 Motion Type


L = Linear
G(PF,NPT)1/2,
Conduit G(PF,NPT)1/2, M20 G(PF)1/2 R = Rotary
M20
Standard Acting Type
-30 - 85 °C (-22 - 185 °F)
Type S = Single
Low D = Double
Temp. -40 - 85 °C (-40 - 185 °F)
Area Protection
Operating Type N = Safe Area
Temp. LCD -30 - 85 °C (-22 - 185 °F) I = Intrinsically Safe ATEX, IECEx. NEPSI, KCs
Explosion -40 - 60 °C (T5) A = Intrinsically Safe CSA, FM
Temp. -40 - 40 °C (T6) Lever Type
Remote -40 - 120 °C Linear Rotary
-
Sensor (-40 - 248 °F) 0 = 10-40 mm 1 = M6 x 34L

fork type
Linearity ±0.5% F.S. 1 = 20-100 mm 2 = M6 x 63L
2 = 90-150 mm 3 = M8 x 34L
Hysteresis ±0.5% F.S. 3 = 16-30 mm 4 = M8 x 63L

roller type
4 = 16-60 mm 5 = NAMUR
Sensitivity ±0.2% F.S. 5 = 16-100 mm
6 = 90-150 mm
Repeatability ±0.3% F.S.
Conduit & Air Connection
Air Consumption Below 2 LPM (sup = O.14 MPa) 1 = G1/2 - PT1/4
Flow Capacity 70 LPM (sup = O.14 MPa) 2 = G1/2 - NPT1/4
3 = G1/2 - G1/4
Output 4 = M20 - NPT1/4
Linear, EQ%, Quick Open user set (18 Point)
Characteristics 5 = NPT1/2 - NPT1/4
Aluminium Stainless Aluminium
Material Communications
Diecasting Steel 316 Diecasting
0 = NONE
Ingress Protection IP66 2 = HART protocol communication
ATEX, IECEx
Output Options
Ex ia IIC T5/T6 Gb, EX iaD IIIC T100°C/T85°C Db
0 = NONE
IP66
1 = 4-20 mA feedback
NEPSI 2 = Limit Switch - Mechanical Type (YT-3300 and YT-3350 only)
Ex ia llC T5/T6 3 = Limit Switch - Proximity Type (YT-3300 and YT-3350 only)
KCs 4 = 4-20 mA + Limit Switch - Mechanical Type
Ex ia IIC T5/T6, EX iaD IIIC T100°C/T85°C (YT-3300 and YT-3350 only)
Explosion 5 = 4-20 mA + Limit Switch - Proximity Type
Protection CSA (YT-3300 and YT-3350 only)
Type Certification in progress
Operating Temp.
FM S = -30 to 85°C
Class I, Div 1, Groups ABCD L = -40 to 85°C
Class I, Zone 0 AEx ia IIC
Class II/III, Div 1, Groups EFG Cable Length (YT-3301 only)
Class I, II, III, Div 2, Groups ABCDEFG Option for YT-3301 only. Standard cable length is 5 m.
NEMA Type 4X IP66 1 = 5 m
AMBIENT TEMP: -40 - 60°C (T5) / -40 - 40°C (T6) 2 = 10 m
Communication 3 = 15 m
HART (ver.7) 4 = 20 m
(Option)
AC 125 V, AC 125 V,
Mechanical 3A 3A
- -
Type (Omron) DC 30 V, DC 30 V,
L/S 2A 2A
Rating
Proximity DC 8.2 V DC 8.2 V
- -
Type (P&F) 8.2 mA 8.2 mA

5.1 kg
Body 2 kg (4.4 lb) 2 kg (4.4 lb)
(11.2 lb)
Weight
Remote