Está en la página 1de 33

Lesson 6: Flow Control Valves

Lesson 6: Flow Control Valves

Basic Hydraulic Systems


• Hydraulic Tank
• Hydraulic Fluids
• Hydraulic Pumps and Motors
• Pressure Control Valves
• Directional Control Valves
• Flow Control Valves
• Cylinders

Introduction
Flow control consists of controlling the volume of oil flow in or out
of a circuit. Controlling flow in a hydraulic circuit can be
accomplished in several ways.
The most common way is by installing an orifice. When an orifice is
installed, the orifice presents a higher than normal restriction to the
pump flow. The higher restriction increases the oil pressure. The
increase in oil pressure causes some of the oil to take another path.
The path may be through another circuit or it may be over a relief
valve.
Also discussed are non-compensated and compensated flow control
valves.
Unit 3 3-6-2 Hydraulic Fundamentals
Lesson 6

Objectives
Upon completion of this lesson the student will:

1. State the function of the orifice, the needle valve, the flow
control valve, the pressure compensated flow control valve,
and the quick-drop valves.
2. Identify the ISO symbols for the various flow control valves.
Unit 3 3-6-3 Hydraulic Fundamentals
Lesson 6

Orifice
An orifice is a small opening in the oil flow path. Flow through an
orifice is affected by several factors. Three of the most common are:
1. The temperature of the oil.
2. The size of the orifice.
3. The pressure differential across the orifice.
Temperature
The oil viscosity changes with changes in temperature. Viscosity is a
measurement of the oil's resistance to flow at a specific temperature.
Hydraulic oil becomes thinner and flows more readily as the
temperature increases.
Orifice Size
The size of the orifice controls the flow rate through the orifice. A
common example is a hole in a garden hose. A small pin hole will
leak in the form of a drip or a fine spray. A larger hole will leak in
the form of a stream. The hole, whether small or large, meters a flow
of water to the outside of the hose. The amount of water metered
depend on the size of the hole (orifice).
The orifice size may be fixed or variable.

SPRING

CHECK
VALVE

HOUSING

ORIFICE
Fig. 3.6.1 Check Valve With Fixed Orifice

Check Valve With A Fixed Orifice


Figure 3.6.1 shows an example of a check valve with a fixed orifice
that is commonly used in construction equipment. The fixed orifice
is a hole through the center of the check valve. When oil flow is in
the normal direction, the valve opens and allows oil to flow around
the valve as well as through the orifice. When oil attempts to flow in
the reverse direction, the valve closes. All reverse flowing oil must
flow through the orifice which controls the flow rate.
Unit 3 3-6-4 Hydraulic Fundamentals
Lesson 6

VALVE STEM

VALVE
BODY
UNRESTRICTED
FLOW
VALVE TIP

RESTRICTED
FLOW
VALVE SEAT

Fig. 3.6.2 Variable Orifice

Variable Orifice
Figure 3.6.2 shows a variable orifice in the form of a needle valve.
In the needle valve, the size of the orifice is changed by the
positioning of the valve tip in relation to the valve seat.
The oil flow through the needle valve must make a 90° turn and pass
between the valve tip and the valve seat. The needle valve is one of
the most frequently used variable orifices.
When the valve stem is turned counter-clockwise, the orifice becomes
larger and the flow increases through the valve.
When the valve stem is turned clockwise, the orifice becomes smaller
and the flow decreases through the valve.
Unit 3 3-6-5 Hydraulic Fundamentals
Lesson 6

The schematic in Figures 3.6.3 and 3.6.4 consist of a positive


displacement pump, a relief valve and a variable orifice. The relief
valve is set at 3445 kPa (500 psi) and limits maximum pressure in
the system. The orifice may be adjusted to any flow between zero
and 5 gpm.

3445 kPa
(500 psi)
5 gpm 4 gpm

3445 kPa
(500 psi)
1 gpm

Fig. 3.6.3 Variable Orifice 4 gpm

In Figure 3.6.3, the variable orifice allows a flow of 4 gpm through


the orifice at a pressure of 3445 kPa (500 psi). Any increase in flow
through the orifice requires a pressure greater than 3445 kPa (500
psi). When the pressure exceeds 3445 kPa (500 psi), the relief valve
opens and the excessive oil (1 gpm) flows through the relief valve.
Unit 3 3-6-6 Hydraulic Fundamentals
Lesson 6

3445 kPa
(500 psi)
5 gpm 1 gpm

3445 kPa
(500 psi)
4 gpm

Fig. 3.6.4 Variable Orifice 1 gpm

In Figure 3.6.4, the variable orifice allows a flow of 1 gpm through


the orifice at a pressure of 3445 kPa (500 psi). Any increase in flow
through the orifice requires a pressure greater than 3445 kPa (500
psi). When the pressure exceeds 3445 kPa (500 psi), the relief valve
opens and the excessive oil (4 gpm) flows through the relief valve.

TOO TOO
TH TH
PASTE PASTE

A B

Fig. 3.6.5 Pressure Differential

Pressure Differential
Flow through an orifice is affected by the pressure differential across
the orifice. The greater the pressure differential across the orifice, the
greater the flow through the orifice.
In Figure 3.6.5, pressure differential is illustrated using the two tubes
of tooth paste. When the tube of toothpaste is gently squeezed as in
A, the pressure difference between the inside of the tube and the
outside of the tube is small. Therefore, only a small amount of tooth
paste is forced out.
When the tube is squeezed with greater force as in B, the pressure
difference between the inside of the tube and the outside of the tube
increases and a larger amount of toothpaste is forced out.
INSTRUCTOR NOTE: At this time, perform Lab 3.6.1
Unit 3 3-6-7 Hydraulic Fundamentals
Lesson 6

5 gpm NO
LOAD

3445 kPa 0 kPa


(500 psi) (0 psi)

3445 kPa 0 gpm 5 gpm


(500 psi)

Fig. 3.6.6 Non-Compensated Flow Control Valve Schematic

Non-Compensated Flow Control Valve


The schematic in Figure 3.6.6 consists of a positive displacement
pump, a relief valve, a cylinder, a non-compensated flow control
valve, two pressure gauges and a three position, four-way, tandem
centered, lever operated directional control valve.
The non-compensated flow control valve consists of a variable orifice
and a check valve. When oil flows into the cylinder head end, the
check valve seats. The variable orifice controls oil flow into the head
end. When oil flows out of the cylinder head end, the check valve
opens, the oil follows the path of least resistance and flows
unrestricted through the check valve.
In a non-compensated flow control circuit, any change in the pressure
differential across the orifice will produce a corresponding change in
the flow through the orifice.
The relief valve is set at 3445 kPa (500 psi). The orifice is adjusted
to a flow of 5 gpm at 3445 kPa (500 psi) with no load on the
cylinder. The pressure differential across the orifice is
3445 kPa (500 psi). Total pump oil flows through the orifice to the
cylinder.
Unit 3 3-6-8 Hydraulic Fundamentals
Lesson 6

5 gpm
LOAD

3445 kPa 1378 kPa


(500 psi) (200 psi)

3445 kPa 2 gpm 3 gpm


(500 psi)

Fig. 3.6.7 Load and Pressure Increases

Load Increase
In Figure 3.6.7, the cylinder load is increased. The cylinder pressure
required to overcome the resistance of the load is 1378 kPa (200 psi).
The 1378 kPa (200 psi) is subtracted from the available 3445 kPa
(500 psi) upstream of the orifice. This reduces the pressure
differential across the orifice to 2067 kPa (300 psi). The 2067 kPa
(300 psi) causes the flow through the orifice to decrease to 3 gpm.
Any attempt to increase the flow through the orifice will cause the
system pressure to increase above the relief valve maximum setting
of 3445 kPa (500 psi). The remaining 2 gpm causes the system
pressure to increase above 3445 kPa (500 psi). The relief valve opens
and 2 gpm flows across the relief valve to the tank.
A decrease in the flow through the orifice causes a corresponding
decrease in the speed of the cylinder.
Unit 3 3-6-9 Hydraulic Fundamentals
Lesson 6

5 gpm
LOAD

3445 kPa 689 kPa


(500 psi) (100 psi)

3445 kPa 1 gpm 4 gpm


(500 psi)

Fig. 3.6.8 Load and Pressure Decreases

Load Decrease
In Figure 3.6.8, the cylinder load is decreased. The pressure required
to overcome the resistance of the load decreases to 689 kPa (100 psi).
The 689 kPa (100 psi) is subtracted from the available 3445 kPa (500
psi) upstream of the orifice. The new pressure differential across the
orifice is 2756 kPa (400 psi). The 2756 kPa (400 psi) causes the flow
through the orifice to increase to 4 gpm. Any attempt to increase the
flow through the orifice above 4 gpm will cause the system pressure
to increase above the relief valve maximum setting of 3445 kPa (500
psi). The remaining 1 gpm causes the system pressure to increase
above 3445 kPa (500 psi). The relief valve opens and 1 gpm flows
across the relief valve to the tank.
An increase in the flow causes a corresponding increase in the speed
of the cylinder.
In Figures 3.6.7 and 3.6.8, increasing the relief valve pressure setting
to 4823 kPa (700 psi) allows the pump to send the maximum flow of
5 gpm through the orifice as long as the cylinder load pressure is less
than 1378 kPa (200 psi). Therefore, the speed of the cylinder will
remain constant as the pressure changes between 1378 kPa (200 psi)
and 689 kPa (100 psi).
INSTRUCTOR NOTE: At this time, perform Lab 3.6.2
Unit 3 3-6-10 Hydraulic Fundamentals
Lesson 6

Compensated Flow Control Circuits


In a compensated flow control circuit, the pressure differential across
the orifice is not affected by a change in the load. The constant
pressure differential across the orifice will produce a constant flow
through the orifice.

ORIFICE

FROM TO
PUMP SYSTEM

DUMP SPRING
VALVE TO TANK

Fig. 3.6.9 By-pass Pressure Compensated Flow Control Valve

By-pass Pressure Compensated Flow Control Valve


Figure 3.6.9 shows a illustration of a by-pass type pressure
compensated flow control valve. The by-pass type pressure
compensated flow control valve automatically adjusts to flow and
load changes.
Flow Change
The amount of flow through the valve depends on the size of the
orifice. Any change in oil flow through the orifice creates a change
in pressure on the upstream side of the orifice. The same pressure
change acts against the dump valve and spring.
When the pump flow is within the design flow of the orifice, the
force of the upstream oil pressure acting on the dump valve is less
than the combined force of the downstream oil pressure and the
spring. The dump valve remains closed and all of the pump oil flows
through the orifice.
When the pump flow is more than the design flow of the orifice, the
force of the upstream oil pressure acting on the dump valve is greater
than the combined force of the downstream oil pressure and the
spring. The dump valve opens and the excess oil flows through the
dump valve to the tank.
Unit 3 3-6-11 Hydraulic Fundamentals
Lesson 6

5 gpm NO
LOAD

2067 kPa 0 kPa


(300 psi) (0 psi)

5856 kPa
(850 psi) 3 gpm

2 gpm

Fig. 3.6.10 By-pass Pressure Compensated Flow Control Valve

No Load Pressure
Figure 3.6.10 shows the by-pass pressure compensated flow control
valve in a simple lifting circuit.
When the control valve is moved to the RAISE position, pump oil is
directed to the flow control valve. The flow control valve requires a
pressure differential of 1378 kPa (300 psi) to send 3 gpm through the
orifice. To send more than 3 gpm through the orifice, requires an
increase in the pressure differential. An increase in the pressure
differential of more than 1378 kPa (300 psi) opens the dump valve.
The excessive oil flows through the dump valve to the tank.

5 gpm INCREASED
LOAD

3445 kPa 1378 kPa


(500 psi) (200 psi)

5856 kPa
(850 psi) 3 gpm

2 gpm

Fig. 3.6.11 By-pass Pressure Compensated Flow Control Valve

Load Pressure Increases


When the load pressure increases, the pressure increases at the orifice
and in the dump valve spring chamber.
The increase in pressure at the orifice lowers the pressure differential
across the orifice and attempts to reduce the oil flow through the
orifice. However, at the same instance, the pressure is increased in
the dump valve spring chamber. The additional pressure closes the
dump valve and blocks oil flow to the tank. The blocked oil causes
Unit 3 3-6-12 Hydraulic Fundamentals
Lesson 6

the pressure on the pump side of the orifice to increase. The pressure
increases until the pressure differential across the orifice reaches
1378 kPa (300 psi). A pressure differential of 1378 kPa (300 psi)
sends 3 gpm through the orifice and 2 gpm across the dump valve.
This allows the flow control valve to respond instantly to any
increases or decreases in the load pressure.

METERED FLOW METERED FLOW

FROM FROM
PUMP PUMP

EXCESS OIL

Fig. 3.6.12 Bypass Pressure Compensated Flow Control Valve

Combine Orifice and Dump Valve


The more common type of flow control valve is shown in Figure
3.6.12. This valve combines the action of the orifice and dump valve
in one moving part. The pressure compensating operation is the same
as the by-pass pressure compensated flow control valve.
The graphic on the left shows flow through the valve that is either at
the flow rating or less than the flow rating of the valve.
The graphic on the right shows that flow is beginning to exceed the
flow rating of the valve, the pressure differential resulting from the
flow across the orifice becomes great enough to begin compressing
the spring and start dumping the excess oil as shown.
If the flow through the valve increases, the action of the orifice will
cause the spring to compress still more, and more flow will be
dumped. The controlled (metered) flow remains fairly constant as
flow to the valve increases or decreases.
Unit 3 3-6-13 Hydraulic Fundamentals
Lesson 6

GAUGE 1 GAUGE 2
4134 kPa (600 psi) 1378 kPa (200 psi)
GAUGE 3
0 kPa (0 psi)

COMPENSATOR NEEDLE
SPOOL ORIFICE 1 VALVE
SUPPLY
OIL CONTROLLED
OIL FLOW (2 gpm)

BIAS SPRING ORIFICE 2


1378 kPa (200 psi)

Fig. 3.6.13 Restrictor Type Pressure Compensated


Flow Control Valve

Restrictor Type Pressure Compensated Flow Control Valve


Figure 3.6.13 shows an illustration of a restrictor type pressure
compensated flow control valve. The controlled oil flow is set by
adjusting the needle valve.
The compensator spool and bias spring work like a pressure reducing
valve. The supply oil pressure is reduced to the pressure that sends
the correct oil flow pass the needle valve.
When the system is off, the spring moves the compensator spool
to the left.
At start up, the compensator spool is open to full oil flow and
pressure. When the oil flow becomes greater than the setting of the
needle valve, the needle valve restricts oil flow and causes the oil
pressure to increase as shown on gauge 2. The increase in oil
pressure is also sensed on the left side of the compensator spool.
When the force of the pressure on the left side of the compensator
spool overcomes the force of the spring, the compensator spool
moves to the right.
Although the supply pressure may continue to increase as shown on
gauge 1, orifice 1 reduces the oil pressure at the needle valve to the
force of the spring. The controlled oil flow pressure is 0 kPa (0 psi),
the pressure differential across the needle valve is 1378 kPa (200 psi)
which equals the force of the spring.
The needle valve is adjusted to allow 2 gpm through orifice 2 when
the pressure differential across the needle valve is 1378 kPa (200 psi).
Unit 3 3-6-14 Hydraulic Fundamentals
Lesson 6

GAUGE 1 GAUGE 2
4134 kPa (600 psi) 2756 kPa (400 psi)
GAUGE 3
1378 kPa (200 psi)

COMPENSATOR NEEDLE
SPOOL ORIFICE 1
VALVE
SUPPLY
OIL CONTROLLED
OIL FLOW (2 gpm)

BIAS SPRING ORIFICE 2


1378 kPa (200 psi)

Fig. 3.6.14 Controlled Oil Pressure

Controlled Oil Pressure


In Figure 3.6.14, the controlled oil pressure is 1378 kPa (200 psi) as
shown on gauge 3. The oil pressure in the valve spring chamber is
also 1378 kPa (200 psi). The force of the spring chamber oil pressure
is added to the force of the spring. The combined forces move the
compensator spool to the left. When the compensator spool moves to
the left, orifice 1 opens. Orifice 1 allows the oil pressure to increase
at the upstream side of the needle valve.
The increase in oil pressure is also sensed on the left side of the
compensator spool. The increase in pressure moves the compensator
spool to the right against the combined force of the spring and
controlled oil pressure. The compensator spool moves to a new
position that allows 2756 kPa (400 psi) through orifice 1. The
increase in gauge 2 pressure to 2756 kPa (400 psi) on the upstream
side of the needle valve maintains a pressure differential of 1378 kPa
(200 psi) across the needle valve (gauge 2 minus gauge 3).
The pressure differential of 1378 kPa (200 psi) across the needle
valve sends 2 gpm through orifice 2.
The pressure compensated flow control valves offer more precise
cylinder speed control than non-pressure compensated valves. The
pressure compensated valves automatically adjust to keep the flow
rate constant as load conditions vary.
The pressure compensated valves are usually installed when cylinder
operating loads are 6890 kPa (1000 psi) and over.
At this time, perform Lab 3.6.3
Unit 3 3-6-15 Hydraulic Fundamentals
Lesson 6

ORIFICE

TO
LIFT/LOWER POPPET
CONTROL VALVE
VALVE
SPRING
FROM
CYLINDER
ROD END
FROM
LIFT/LOWER
CONTROL
VALVE

TO CYLINDER
HEAD END

Fig. 3.6.15 Quick-Drop Valve

Quick-Drop Valve "Quick-Drop Mode"


Figure 3.6.15 shows an illustration of a quick-drop valve. The quick-
drop valve is commonly installed on the dozer lift cylinder. When
activated, the quick-drop valve allows the dozer blade to rapidly drop
to the ground.
When the dozer blade is raised and the operator moves the lift/lower
control to the QUICK-DROP position, the lift/lower control valve
allows the lift cylinder rod end oil to flow to the tank. The
gravitational forces acting on the dozer blade pulls the rod out of the
cylinder and causes the piston to move independent of the force of
the pump oil pressure. This action greatly increases the oil flow
through the quick-drop valve orifice and creates a vacuum in the head
end of the lift cylinder. The increase in oil flow through the orifice
causes the pressure up stream of the orifice to increase. The
increased oil pressure opens the poppet valve. The open poppet valve
connects the passage from the cylinder rod end to the passage to the
cylinder head end. The oil from the rod end of the cylinder flows
through the open poppet valve, joins the oil from the control valve
and flows to the head end of the cylinder.
A small amount of oil flows through the orifice to the lift/lower
control valve and to the tank.
When the blade strikes the ground, the movement of the rod out of
the cylinder cease. This causes a rapid decrease in the oil flow
through the orifice. The pressure caused by flow through the orifice
decreases and the spring closes the poppet valve. All oil flow to the
head end, now comes from the lift/lower control valve.
Unit 3 3-6-16 Hydraulic Fundamentals
Lesson 6

ORIFICE

FROM
LIFT/LOWER POPPET
CONTROL VALVE
VALVE

SPRING
TO
CYLINDER
ROD END

TO
LIFT/LOWER
CONTROL
VALVE

FROM CYLINDER
HEAD END

Fig. 3.6.16 Quick-Drop Valve

Quick-Drop Valve "Blade RAISE Mode"


Figure 3.6.16 shows the quick-drop valve when the blade is being
raised.
When the operator moves the lift/lower control to the blade RAISE
position, pump oil flows from the lift/lower control valve, through the
orifice and to the rod end of the lift cylinder. The orifice creates a
restriction to the oil flow which increases the upstream pressure. The
higher pressure oil flows through the passage to the spring chamber
behind the poppet valve. The pressurized oil assists the spring and
holds the valve closed when pressure is applied to the rod end of the
cylinder.
Oil from the head end flows through the quick-drop valve and the
control valve to the tank.
Unit 3 3-6-17 Hydraulic Fundamentals
Lesson 6

FIXED ORIFICE VARIABLE ORIFICE


(NEEDLE VALVE)

PRESSURE COMPENSATED PRESSURE COMPENSATED


FLOW CONTROL VALVE FLOW CONTROL VALVE
WITH BY-PASS

Fig. 3.6.17 Flow Control ISO Symbols

ISO Symbols
Figure 3.6.17, shows the ISO symbols for the basic flow control
components.
The non-pressure compensated flow control ISO symbols are the
fixed orifice and the variable orifice.
The pressure compensated flow control devices are the pressure
compensated flow control valve and the pressure compensated flow
control valve with by-pass.
The ISO symbol does not give any information on the actual physical
structure of the component.
Unit 3 -1- Hydraulic Fundamentals
Instructor Copy Lab 3.6.1

Instructor Copy: Lab 3.6.1


Name _________________________

SYSTEM
PRESSURE
GAUGE

1 2

SYSTEM
RELIEF
VALVE 2

BACKUP
RELIEF
VALVE 1 1

PUMP

TANK

Fig 3.6.18 Hydraulic Circuit

LAB 3.6.1: NEEDLE VALVE

Purpose
To install and operate a needle valve in simple hydraulic circuits.
Materials needed
1. Basic Hydraulic Training Unit
Procedure
1. Build the circuit shown in Figure 3.6.18.
2. Turn the needle valve adjustment knob clockwise until the valve closes completely.
3. Adjust system pressure to 5856 kPa (850 psi).
4. Turn ON the training unit.
5. Monitor the pressure gauge and flow meter. Record the readings in the "Chart 1"
(Figure 3.6.19). The pressure gauge and flow meter readings will change with changes in hose
length and oil temperature.
6. Open the needle valve one-half (1/2) turn at a time. Monitor the pressure gauge and flow
meter. Record the readings in the "Chart 1" (Figure 3.6.19).
7. Continue to open the needle valve 1/2 turn at a time. Monitor the pressure gauge and flow
meter. Record the readings in the "Chart 1" (Figure 3.6.19) until the valve is fully open.
8. Turn OFF the training unit and close the needle valve (turn clockwise).
Unit 3 -2- Hydraulic Fundamentals
Instructor Copy Lab 3.6.1

LAB 3.6.1: NEEDLE VALVE (continued)

CHART 1 CHART 2
Number Pressure kPa Flow Rate Number Pressure kPa Flow Rate
of Turns (PSI) (GPM) of Turns (PSI) (GPM)
5856 kPa 5856 kPa
0 0 0
(850 psi) 0 (850 psi)
5374 kPa 5615 kPa
1/2 (780 psi) .4 1/2 (815 psi) .3
3307 kPa 3721 kPa
1 (480 psi) .8 1 (540 psi) .8
1378 kPa 1481 kPa
1 1/2 (200 psi) .85 1 1/2 (215 psi) .85
1102 kPa 999 kPa
2 (160 psi) .85 2 (145 psi) .85
965 kPa 896 kPa
2 1/2 (140 psi) .85 2 1/2 (130 psi) .85
827 kPa 792 kPa
3 (120 psi) .85 3 .85
(115 psi)
827 kPa 792 kPa
3 1/2 (120 psi) .85 3 1/2 .85
(115 psi)
Fig. 3.6.19

9. Reverse the hoses to the top and bottom of the needle valve.
10. Turn ON the training unit.
11. Monitor the pressure gauge and flow meter. Record the readings in the "Chart 2" (Figure
3.6.19).
12. Continue to open the needle valve 1/2 turn at a time. Monitor the pressure gauge and flow
meter. Record the readings in the "Chart 2" (Figure 3.6.19) until the valve is fully open.
13. Compare the two sets of data and explain what you have found.
The flow characteristics across a needle valve in one direction are different from the flow
characteristics across the same needle valve in the opposite direction.
These differences in flow characteristics cause different readings at the pressure gauges and
flow meters.
14. Turn OFF the training unit.
Unit 3 -1- Hydraulic Fundamentals
Student Copy Lab 3.6.1

Student Copy: Lab 3.6.1


Name _________________________

SYSTEM
PRESSURE
GAUGE

1 2

SYSTEM
RELIEF
VALVE 2

BACKUP
RELIEF
VALVE 1 1

PUMP

TANK

Fig. 3.6.18 Hydraulic Circuit

LAB 3.6.1: NEEDLE VALVE

Purpose
To install and operate a needle valve in simple hydraulic circuits.
Materials needed
1. Basic Hydraulic Training Unit
Procedure
1. Build the circuit shown in Figure 3.6.18.
2. Turn the needle valve adjustment knob clockwise until the valve closes completely.
3. Adjust system pressure to 5856 kPa (850 psi).
4. Turn ON the training unit.
5. Monitor the pressure gauge and flow meter. Record the readings in the "Chart 1"
(Figure 3.6.19). The pressure gauge and flow meter readings will change with changes in hose
length and oil temperature.
6. Open the needle valve one-half (1/2) turn at a time. Monitor the pressure gauge and flow
meter. Record the readings in the "Chart 1" (Figure 3.6.19).
7. Continue to open the needle valve 1/2 turn at a time. Monitor the pressure gauge and flow
meter. Record the readings in the "Chart 1" (Figure 3.6.19) until the valve is fully open.
8. Turn OFF the training unit and close the needle valve (turn clockwise).
Unit 3 -2- Hydraulic Fundamentals
Student Copy Lab 3.6.1

LAB 3.6.1: NEEDLE VALVE (continued)

CHART 1 CHART 2
Number Pressure kPa Flow Rate Number Pressure kPa Flow Rate
of Turns (PSI) (GPM) of Turns (PSI) (GPM)
5856 kPa 0 5856 kPa
0 0
(850 psi) (850 psi)
1/2 1/2

1 1

1 1/2 1 1/2

2 2

2 1/2 2 1/2

3 3

3 1/2 3 1/2

Fig 3.6.19

9. Reverse the hoses to the top and bottom of the needle valve.
10. Turn ON the training unit.
11. Monitor the pressure gauge and flow meter. Record the readings in the "Chart 2" (Figure
3.6.19).
12. Continue to open the needle valve 1/2 turn at a time. Monitor the pressure gauge and flow
meter. Record the readings in the "Chart 2" (Figure 3.6.19) until the valve is fully open.
13. Compare the two sets of data and explain what you have found.

13. Turn OFF the training unit.


Unit 3 -1- Hydraulic Fundamentals
Instructor Copy Lab 3.6.2

Instructor Copy: Lab 3.6.2


Name _________________________

IN-LINE
PRESSURE
GAUGE
SYSTEM
PRESSURE
GAUGE
1 2

1 2

SYSTEM
RELIEF
VALVE 2

BACKUP
RELIEF
VALVE 1 1

PUMP

TANK

Lab. 3.6.20 Flow Control Valve

LAB 3.6.2: NON-PRESSURE COMPENSATED FLOW CONTROL VALVE

Purpose
To install and operate in a hydraulic circuit a non-pressure compensated flow control valve with reverse
flow check.
Materials needed
1. Basic Hydraulic Training Unit
Procedure
1. Build the circuit in Figure 3.6.20.
2. Adjust system pressure to 5856 kPa (850 psi).
3. Open the flow control valve and the needle valve fully counter-clock wise.
4. Turn on the training unit.
5. Monitor the gauges and flow meter. The flow meter should read 0.9 gpm.
6. Record the pressure gauges and the flow meter readings in the chart (Figure 3.6.21).
7. Adjust the flow control valve so that the flow meter reading is .5 gpm.
8. Monitor the gauges and flow meter. Record the data on the chart (Figure 3.6.21).
9. Adjust the needle valve so that the load on the system is 1378 kPa (200 psi). Pressure is shown
on the in-line pressure gauge.
10. Monitor the flow meter and pressure gauges. Record the data on the chart (Figure 3.6.21).
11. Increase the load pressure in increments of 345 kPa (50 psi) up to 2756 kPa (400 psi). After
each increase, record the flow meter and pressure gauges readings on the chart (Figure 3.6.21).
Unit 3 -2- Hydraulic Fundamentals
Instructor Copy Lab 3.6.2

LAB 3.6.2: NON-PRESSURE COMPENSATED FLOW CONTROL VALVE (continued)

System In-Line
Pressure Flow Rate
Test Pressure
kPa (PSI) (GPM)
kPa (PSI)
1550 kPa 1034 kPa
1 (225 psi) (150 psi) .9
5271 kPa 413 kPa
2 (765 psi) (60 psi) .5
5443 kPa 1378 kPa
3 (790 psi) (200 psi) .45
5512 kPa 1723 kPa
4 (800 psi) (250 psi) .42
5546 kPa 2067 kPa
5 (805 psi) (300 psi) .41
5615 kPa 2412 kPa
6 (815 psi) (350 psi) .39
5719 kPa 2756 kPa
7
(830 psi) (400 psi) .35
Fig. 3.6.21

13. Turn OFF the training unit and review the complete set of data.
The pressure gauge and flow meter readings will change with changes in hose length and
oil temperature.
14. How does changing the load affect the flow rate as indicated on the flow meter?
Changing the load directly affects the flow rate. As the load increases the flow rate decreases.
Likewise, as the load decreases, the flow rate increases.
15. Based on your experience, what would happen in you switched the hoses on the ports to the
flow control valve? Think about the effect of the change on flow control.
Reversing the hoses on the non-pressure compensated flow control valve would permit free
flow in what is now the controlled flow direction. Changing the settings on the flow control
valve would have no effect on the in-line pressure.
16. Disconnect hoses from training unit.
Unit 3 -1- Hydraulic Fundamentals
Student Copy Lab 3.6.2.

Student Copy: Lab 3.6.2


Name _________________________

IN-LINE
PRESSURE
GAUGE
SYSTEM
PRESSURE
GAUGE
1 2

1 2

SYSTEM
RELIEF
VALVE 2

BACKUP
RELIEF
VALVE 1 1

PUMP

TANK

Fig. 3.6.20 Pressure Reducing Valve Circuit

LAB 3.6.2: NON-PRESSURE COMPENSATED FLOW CONTROL VALVE

Purpose
To install and operate in a hydraulic circuit a non-pressure compensated flow control valve with reverse
flow check.
Materials needed
1. Basic Hydraulic Training Unit

Procedure
1. Build the circuit in Figure 3.6.20.
2. Adjust system pressure to 5856 kPa (850 psi).
3. Open the flow control valve and the needle valve fully counter-clock wise.
4. Turn on the training unit.
5. Monitor the gauges and flow meter. The flow meter should read 0.9 gpm.
6. Record the pressure gauges and the flow meter readings in the chart (Figure 3.6.21).
7. Adjust the flow control valve so that the flow meter reading is .5 gpm.
8. Monitor the gauges and flow meter. Record the data on the chart (Figure 3.6.21).
9. Adjust the needle valve so that the load on the system is 1378 kPa (200 psi). Pressure is shown
on the in-line pressure gauge.
10. Monitor the flow meter and pressure gauges. Record the data on the chart (Figure 3.6.21).
11. Increase the load pressure in increments of 345 kPa (50 psi) up to 2756 kPa (400 psi). After
each increase, record the flow meter and pressure gauges readings on the chart (Figure 3.6.21).
Unit 3 -2- Hydraulic Fundamentals
Student Copy Lab 3.6.2

LAB 3.6.2: NON-PRESSURE COMPENSATED FLOW CONTROL VALVE (continued)


System In-Line
Pressure Flow Rate
Test Pressure
kPa (PSI) (GPM)
kPa (PSI)
1

Fig. 3.6.21

13. Turn OFF the training unit and review the complete set of data.
The pressure gauge and flow meter readings will change with changes in hose length and
oil temperature.
14. How does changing the load affect the flow rate as indicated on the flow meter?

15. Based on your experience, what would happen in you switched the hoses on the ports to the
flow control valve? Think about the effect of the change on flow control.

16. Disconnect hoses from training unit.


Unit 3 -1- Hydraulic Fundamentals
Instructor Copy Lab 3.6.3

Instructor Copy: Lab 3.6.3


Name _________________________

IN-LINE
PRESSURE
GAUGE
SYSTEM
PRESSURE
GAUGE
1 2

1 2

SYSTEM
RELIEF
VALVE 2

BACKUP
RELIEF
VALVE 1 1

PUMP

TANK

Fig. 3.6.22 Reverse Flow Check

LAB 3.6.3: PRESSURE COMPENSATED FLOW CONTROL VALVE WITH


REVERSE FLOW CHECK

Purpose
To install and operate in a hydraulic circuit a pressure compensated flow control valve with reverse
flow check.
Materials needed
1. Basic Hydraulic Training Unit
Procedure
1. Build the circuit shown in Figure 3.6.22.
2. Adjust system pressure to 5856 kPa (850 psi).
3. Open the flow control valve and the needle valve fully counter-clock wise.
4. Turn on the training unit.
5. Monitor the gauges and flow meter. The flow meter should read 0.9 gpm.
6. Record the pressure gauges and the flow meter readings in the chart (Figure 3.6.23).
7 Adjust the flow control valve so that the flow meter reading is .5 gpm.
8. Monitor the gauges and flow meter. Record the data on the chart (Figure 3.6.23).
9. Adjust the needle valve so that the load on the system is 1378 kPa (200 psi). Pressure is shown
in-line pressure gauge.
10. Monitor the flow meter and pressure gauges. Record the data on the chart (Figure 3.6.23).
11. Increase the load pressure in increments of 345 kPa (50 psi) up to 2756 kPa (400 psi). After
each increase, record the flow meter and pressure gauges readings on the chart (Figure 3.6.23).
Unit 3 -2- Hydraulic Fundamentals
Instructor Copy Lab 3.6.3

LAB 3.6.3: REVERSE FLOW CHECK (continued)

System In-Line
Test Flow Rate
Pressure Pressure
(GPM)
kPa (PSI) kPa (PSI)
1378 kPa 861 kPa
1 (200 psi) (125 psi) .85

5168 kPa 413 kPa


2 (750 psi) (60 psi) .5

5168 kPa 1378 kPa


3 (750 psi) (200 psi) .5

5168 kPa 1723 kPa


4 (750 psi) (250 psi) .5

5168 kPa 2067 kPa


5 (750 psi) (300 psi) .5

5168 kPa 2412 kPa


6 (750 psi) (350 psi) .5

5168 kPa 2756 kPa


7 (750 psi) (400 psi) .5

Fig. 3.6.23

12. Turn off the training unit and review the complete set of data.
The pressure gauge and flow meter readings will change with changes in hose length and
oil temperature.
13. How does changing the load affect the flow rate as indicated on the flow meter?
Changing the load has no effect whatsoever on the flow rate or the system pressure.
14. Based on your experience, what would happen in you switched the hoses on the ports to the
flow control valve? Think about the effect of the change on flow control.
Reversing the hoses on the pressure compensated flow control valve would permit free flow
in what is now the controlled flow direction. Changing the settings on the flow control valve
would then have no control over in-line pressure.
15. When the system was throttled to .5 GPM, the pump still pumped 0.9 GPM. Based on your
previous experiences and knowledge of the system, what is the flow path of the 0.4 GPM not
used by the system?
The 0.4 GPM not directed through the system is passing directly over the system relief valve
and returning to the reservoir.
16. Disconnect hoses from training unit.
Unit 3 -1- Hydraulic Fundamentals
Student Copy Lab 3.6.3.

Student Copy: Lab 3.6.3


Name _________________________

IN-LINE
PRESSURE
GAUGE
SYSTEM
PRESSURE
GAUGE
1 2

1 2

SYSTEM
RELIEF
VALVE 2

BACKUP
RELIEF
VALVE 1 1

PUMP

TANK

Fig. 3.6.22 Hydraulic Circuit

LAB 3.6.3: PRESSURE COMPENSATED FLOW CONTROL VALVE WITH


REVERSE FLOW CHECK

Purpose
To install and operate in a hydraulic circuit a pressure compensated flow control valve with reverse
flow check.
Materials needed
1. Basic Hydraulic Training Unit
Procedure
1. Build the circuit shown in Figure 3.6.22.
2. Adjust system pressure to 5856 kPa (850 psi).
3. Open the flow control valve and the needle valve fully counter-clock wise.
4. Turn on the training unit.
5. Monitor the gauges and flow meter. The flow meter should read 0.9 gpm.
6. Record the pressure gauges and the flow meter readings in the chart (Figure 3.6.23).
7 Adjust the flow control valve so that the flow meter reading is .5 gpm.
8. Monitor the gauges and flow meter. Record the data on the chart (Figure 3.6.23).
9. Adjust the needle valve so that the load on the system is 1378 kPa (200 psi). Pressure is shown
in-line pressure gauge.
10. Monitor the flow meter and pressure gauges. Record the data on the chart (Figure 3.6.23).
11. Increase the load pressure in increments of 345 kPa (50 psi) up to 2756 kPa (400 psi). After
each increase, record the flow meter and pressure gauges readings on the chart (Figure 3.6.23).
Unit 3 -2- Hydraulic Fundamentals
Student Copy Lab 3.6.3.

LAB 3.6.3: REVERSE FLOW CHECK (continued)

System In-Line
Test Flow Rate
Pressure Pressure
(GPM)
kPa (PSI) kPa (PSI)
1

Fig. 3.6.23

12. Turn OFF the training unit and review the complete set of data.
13. How does changing the load affect the flow rate as indicated on the flow meter?

14. Based on your experience, what would happen in you switched the hoses on the ports to the
flow control valve? Think about the effect of the change on flow control.

15. When the system was throttled to .5 GPM, the pump still pumped 0.9 GPM. Based on your
previous experiences and knowledge of the system, what is the flow path of the 0.4 GPM not
used by the system?

16. Disconnect hoses from training unit.


Unit 3 -1- Hydraulic Fundamentals
Instructor Copy Quiz 3.6.1

Instructor Copy: Quiz 3.6.1


Name _________________________
FLOW CONTROL FUNCTIONS AND VALVES QUIZ

Fill in the blanks or circle the best answer.


1. The orifice presents a higher than normal restriction to pump flow.
A. True
B. False
2. The orifice size has little effect on the flow rate through the orifice..
A. True
B. False
3. Oil flows in a straight line through the needle valve.
A. True
B. False
4. A decrease in the pressure differential across an orifice, will cause a decrease in the flow
through the orifice.
A. True
B. False
5. The oil temperature has no effect on oil flow through an orifice.
A. True
B. False
The following statements refer to:

A. Needle valve.
B. By-pass type pressure compensated flow control valve.
C. Restrictor type pressure compensated flow control valve.

A 6. The valve consist of a threaded stem which can be adjusted.

B 7. The oil flow that exceeds the orifice rating increases the pressure and opens the dump
valve.

A,C 8. The oil flow that exceeds the orifice rating increases the pressure and opens the relief
valve.

B 9. Orifice and dump valve in one movable part.


Unit 3 -2- Hydraulic Fundamentals
Instructor Copy Quiz 3.6.1

FLOW CONTROL FUNCTIONS AND VALVES QUIZ

Name _________________________

Complete the following sentences.

11. The quick-drop valve is commonly found on the dozer lift cylinder.

12. The weight of the dozer blade forces oil from the rod end of the lift cylinder.

A B C D

Name the ISO symbols.

13. A Orifice

14. B Needle Valve

15. C Pressure Compensated Flow Control Valve

16. D Pressure Compensated Flow Control Valve, By-pass Type


Unit 3 -1- Hydraulic Fundamentals
Student Copy Quiz 3.6.1

Student Copy: Quiz 3.6.1


Name _________________________
Name _________________________
FLOW CONTROL FUNCTIONS AND VALVES QUIZ

Fill in the blanks or circle the best answer.

1. The orifice presents a higher than normal restriction to pump flow.


A. True
B. False
2. The orifice size has little effect on the flow rate through the orifice..
A. True
B. False
3. Oil flows in a straight line through the needle valve.
A. True
B. False
4. A decrease in the pressure differential across an orifice, will cause a decrease in the flow
through the orifice.
A. True
B. False
5. The oil temperature has no effect on oil flow through an orifice.
A. True
B. False
The following statements refer to:

A. Needle valve.
B. By-pass type pressure compensated flow control valve.
C. Restrictor type pressure compensated flow control valve.

6. The valve consist of a threaded stem which can be adjusted.

7. The oil flow that exceeds the orifice rating increases the pressure and opens the dump
valve.

8. The oil flow that exceeds the orifice rating increases the pressure and opens the relief
valve.

9. Orifice and dump valve in one movable part.


Unit 3 -2- Hydraulic Fundamentals
Student Copy Quiz 3.6.1

FLOW CONTROL FUNCTIONS AND VALVES QUIZ

Complete the following sentences.

11. The valve is commonly found on the dozer lift cylinder.

12. The weight of the dozer blade forces oil from the of the lift cylinder.

Name the ISO symbols.

A B C D

13. A

14. B

15. C

16. D

También podría gustarte