Está en la página 1de 2

MD 01-02-03-04-05-06-08-09-11-12-16-20-24-30-35-40-50-60

AIR HANDLING UNITS


INDOOR / OUTDOOR INSTALLATION

AIR VOLUME: 1000-80000 m3/h

Technical Data 2012


AHU range no 07.09.344
Series MD

Features
1. Casing
1.1 Frame: The casing frame is constructed of heavy aluminum profiles, joined together by means of special synthetic corner pieces
Interklima MD series Air Handling Units are
made of solar radiation resistant glass reinforced polyamide, of excellent mechanical characteristics. The profiles are fixed on the
the result of a vast experience in the field of
corner pieces via galvanized allen head screws, that are completely hidden , thus creating an aesthetically perfect box. The
air treatment , of more than 30 years in
profiles themselves are thermally insulated, built in two pieces joined together by means of synthetic bars. Thus any metal contact
almost every market in the world. Interklima and therefore heat transfer between the internal part of the unit and the environment is completely blocked. Air tightness is
air handling units are successfully in ensured by a double gasket system . The internal gasket profile is inserted in the profile through a special slot and the internal part
operation for more than 30 years, in any of the panels are thus completely isolated. Another external EPDM gasket id used where panels are fixed on the casing. This
conceivable climatic conditions from -50° C double gasket system has been designed for both positive or negative pressures in the unit.
to +50° C and from 5% to 99% relative Three different types of profiles are used, one at the unit length and ends, one at the boxes junction and finally a panel separating
humidity. omega profile for lengthy boxes. The internal surface of the unit is completely flat and very easy to clean. There are no internal
frame or other projections.
The current MD line incorporates all
1.2 Panels: The unit panels are of the double wall type. A special synthetic EPDM profile completely insulates the external and the
knowledge accumulated over the years and internal panel walls, so that there is no metallic contact between them. That means that the internal panel wall cannot thermally
offers the best value for money in the affect the external wall. Insulation thickness is of 50 mm as standard. Thus perfect thermal and acoustical performance is
market. MD series is a multi-functional air achieved.
management system that can move, cool, There is a choice from two different types of insulating material :
heat, humidify, dehumidify and clean air to -Injected and expanded polyurethane having a density of 40 kg/m³ made of environmentally friendly materials.
the desirable conditions, regarding
-Mineral wool from 50 kg/m³ to 100 kg/m³.
temperature , humidity and filtration. A vast
The panels are fixed on the profiles by sheet metal screws, inserted on predrilled holes. The screws are guided by means of a
range of components can be fitted in a
synthetic well and closed by removable synthetic caps , so again there is no metallic contact between screws and panels.
precision manufactured modular casing,
1.3 Doors: Where frequent access to the internal components of the unit is required , door panels are provided. The construction is
offering complete air tightness and a high
similar to the standard fixed panels. The doors are equipped with handles and hinges to permit quick opening and access. The
degree of thermal insulation and energy
handles are installed on the door panel and are functioning externally, by means of a special latch installed on the profiles. Thus the
efficiency.
door panels are positively pressed on the frame and there is no piercing of the door that could create air leakages. Upon request ,
the handles can be equipped with a key lock, thus avoiding interference with the internal parts of the unit by unauthorized persons.
Also upon request a double wall polycarbonate window can be installed on doors or other panels.
1.4 Panels construction material: Standard panel construction is of galvanized steel sheets of suitable thickness. Upon request
panels can be provided with a powder coating of a thickness of 60 μ. The painting procedure is completely automated and consists
of cleaning, phosphating , drying, electrostatic powder coating and baking at 200 ° C. Standard colors used are RAL 9002 and
RAL 7042. This coating can be applied on one side only (usually the external wall) or both sides. Panels can also be manufactured
of stainless steel or aluminum, both sides or one side only.
1.5 Base: A heavy gauge steel base 100 mm high is provided as standard, to facilitate unit installation and leveling. Different base
heights can be provided , upon request. Also leveling screws can be provided upon request.
UNIT Fan Section Fan Coil Coil Section Electrical Simple Horizontal Vertical Bag Plate Rotary Laminar Sound
SIZE With Section Section With Filter Heating Mixing Mixing Mixing Filter Heat Heat Attenuator
Double With Element Box Box Box + Panel Exchanger Exchanger
Inlet Plug Fan Filter
Centrigugal
Fan

MD H W 3.1 3.2 3,3 3.1 3.2 3,3 L1 L2


01 610 712 1018 1171 712 1018 1324 865 1171 1477 712 406 865 559 1018 712 559 1324 1783 1324
02 712 712 1171 1171 712 1018 1324 865 1171 1477 712 406 865 559 1018 1018 559 1324 1783 1324
03 712 865 1171 1171 712 1018 1324 865 1171 1477 712 406 865 559 1018 1171 559 1324 1783 1324
04 865 865 1324 1171 712 1018 1324 865 1171 1477 712 406 865 559 1018 1171 559 1324 1783 1324
05 865 1018 1324 1171 712 1018 1324 865 1171 1477 712 406 865 559 1018 1171 559 1324 1783 1324
06 1018 1018 1477 1477 712 1018 1324 865 1171 1477 712 559 1171 712 1018 1324 559 1324 1783 1324
08 1018 1171 1477 1477 712 1018 1324 865 1171 1477 712 559 1171 712 1018 1324 559 1324 1783 1324
09 1171 1171 1630 1477 712 1018 1324 865 1171 1477 712 559 1171 712 1018 1324 559 1324 1783 1324
11 1171 1324 1630 1630 712 1018 1324 865 1171 1477 712 559 1171 712 1018 1783 559 1324 1783 1324
12 1324 1324 2089 1783 712 1018 1324 865 1171 1477 712 712 1477 865 1018 2089 559 1324 1783 1324
16 1324 1630 2089 1783 712 1018 1324 865 1171 1477 712 712 1477 865 1018 2089 559 1324 1783 1324
20 1630 1630 2089 1936 712 1018 1477 865 1171 1630 712 865 1783 1018 1018 2242 559 1324 1783 1324
24 1630 1936 2242 1936 712 1018 1477 865 1171 1630 712 865 1783 1018 1018 * 712 1324 1783 1324
30 1936 1936 2395 2089 712 1018 1477 865 1171 1630 712 1018 2089 1171 1018 * 712 1324 1783 1324
35 1936 2242 2395 2089 712 1018 1477 865 1171 1630 712 1018 2089 1171 1018 * 712 1324 1783 1324
40 2242 2242 2548 2548 712 1018 1477 865 1171 1630 712 1171 2395 1324 1018 * 712 1324 1783 1324
50 2242 2548 2548 2548 712 1018 1477 865 1171 1630 712 1171 2395 1324 1018 * 712 1324 1783 1324
60 2548 2548 2548 2548 712 1018 1477 865 1171 1630 712 1324 2701 1477 1018 * 712 1324 1783 1324
61Notes
2242 2854 2548 2548 712 1018 1477 865 1171 1630 712 1171 2395 1324 1018 * 712 1324 1783 1324

Notes
1. Above dimensions, are applied for 50mm insulation and they are typical. They can change depending on units size, installed components and complexity of the units.
2. Coil section : 3.1 = 1 coil + eliminators, 3.2 = 2 cois + eliminators, 3.3 = 2 coils + eliminators + spray humidifier.

SOUND ATTENUATOR SECTION LENGTH FOR ATTENUATION AT 250 Hz (db)


14 19 25 30 34 39 44
L1 1171 1477 1783 2089 2395 2701 3007
L2 712 1018 1324 1630 1936 2242 2548

61

mGB_AHUMD_02-2012

También podría gustarte