The PQ1000-V is a portable instrument for measuring and logging electrical parameters. It
belongs to the higher performance and accuracy category, according to the requirements
of IEC 61000-4-30 - Class A
Applications
• Power Quality Analysis.
• Studies and detection of electrical network troubleshooting.
• Voltage and Current Harmonic Spectra Analysis.
• Harmonic Power Flow.
• Voltage Flicker Analysis.
• Detection and studies of emitted perturbations.
• Historical logs of voltage and current events analysis.
• Trend graphics of RMS values during voltage events: dips, swells and interrupts.
• Trend graphics of RMS values during current events: inrush, under loads and no load.
• Symmetrical components and unbalance factors analysis.
• Measurement of electric power flow quantities under sinusoidal, nonsinusoidal,
balanced and unbalanced conditions
The PQ1000-V logs more than 1400 electrical parameters over 10 minutes interval for more than 60 days. It has 4 voltage
channels up to 600 Volt and 4 current channels. The PQ1000-V implants a nonvolatile solid state memory. It applies current
transducers TI-Flex Ecamec ® batteries or auxiliary power sources required. The internal UPS provides more than 2 hours of use
without mains power connected.
The touch screen interface is characterized by being intuitive and easy to use
SISTEMA ECAMEC 2.0
Ecamec System 2.0 is the developed software that provides the
communication interface between Ecamec’s instruments - PC and the
processing tools of the large volumes of information generated by the last
generating instrument.
Harmonic Analysis
• Voltage and current spectral analysis
• Trends of harmonics and inter-armonics
Trend Analysis
• Urms and Irms
• Harmonic and Inter-harmonics RMS values
• THD% and TID%
• Flicker PST y PLT.
• Derating Factors.
• Arbitrary selection and cross correlation between electrical parameters.
Polar Diagrams
• Phasor diagramo voltage and current. The event classification based on ITIC – CBEMA –
• 4 quadrant power diagram. SEMI F47 curves provide useful information about
the compatibility level of the electrical network.
The bar graphs shows harmonic spectra schemes of each measurement interval, providing
information about harmonics RMS values and signed active and reactive harmonic power.
Log capacity > 60 days at 10 minutes interval with more than 1400 parameters
Programmable Time Length Measurement Calendar between dates, number of intervals or combination.
Size: 4,3"
INPUTS CHARACTERISTICS
VOLTAGE INPUTS:
Input impedance 6 MΩ
VOLTAGE
CURRENT
MAXIMA and MINIMA 0 to FS < ±0,10% • Characteristic values updated at each measurement
(depends on CT) (depends on CT) interval.
FREQUENCY
POWER
ENERGY
FLICKER
VOLTAGE EVENTS
CURRENT EVENTS
MACHINES FACTORS
CURRENT TRANSDUCERS
TI-Q 6A 0 to 6 A CLAMP
TI-Q 60 A 0 to 60 A CLAMP
Measurement inputs: CAT IV - 600V, CAT III - 1000V, According to IEC 61010-1
Electric Field Immunity Test 25 V/m - 10 MHz a 2700 MHz - IEC 61000-4-3.
REFERENCE CONDITIONS
Temperature: 23 ºC ± 2ºC
Humidity: 30%
Waveform: Sinusoidal
INTERFACES
GPRS/GSM (Optional): Wireless TCP/IP transmission of instantaneous values and logged data. Reada-
ble from multiple users. Remote log start.
Bluetooth SPP (Optional): Radio communication: 2.4 GHz - Class 2: 20m (66ft.) or Class 1: 100m (330ft.)
VISUALIZATION MODES
DISPLAY
COLOR TOUCH SCREEN
Instantaneous values, diagrams and bar graphs on color touch screen with three second refresh rate and availability of pausing data.
Allows to set new measurement logs through the touch screen without requiring a PC.
Instantaneous measurements • True RMS values: Phase-Neutral Voltage, Phase to Phase Voltage and Current.
• Total Harmonic and Inter-harmonic Distortion: THD y TID
• Power P-Q-D-S
• Power Factor - Cos φ
• Flicker: PST - PLT - iFLK
• Symmetrical Components
• Unbalance factors
Voltage and Frequency Quality • Bar graphics with voltage and frequency deviations from nominal values.
On Line Wiring Assistance • On line wiring assistance for each power system configuration.
• Instantaneous voltage and current values of each channel.
• Instantaneous diagnosis - Wiring warnings:
Negative power flow directions.
Negative phase sequence.
Lack of voltage - current phases correspondence.
ON LINE MEASUREMENT
SOFTWARE: Sistema Ecamec 2.0 - Econnect Module
Screen values refreshed each 3 second for 8 measurement channels.
Phasor diagram
IEC 61000-4-30 Ed.2008-10. Clase A. EMC - Part 4-30: Testing and measurement techniques – Power quality measurement methods.
IEC 61000-4-7 Ed.2002. EMC - Part 4-7: Testing and measurement techniques – General guide on harmonics and interharmonics
measurements and instrumentation, for power supply systems and equipment connected thereto.
IEC 61000-4-15 Ed.2010-08. EMC - Part 4-15: Testing and measurement techniques – Flickermeter – Functional and design specifications.
IEC 62053-21 Ed.2003-01. Electricity metering equipment (a.c.) - Particular requirements - Part 21: Static meters for active energy
(classes 1 and 2).
IEC 62053-23 Ed.2003-01. Electricity metering equipment (a.c.) - Particular requirements - Part 23: Static meters for reactive energy
(classes 2 and 3).
IEEE Std 459-2000 IEEE Standard Definitions for the Measurement of Electric Power Quantities Under Sinusoidal, Nonsinusoi-
dal, Balanced, or Unbalanced Conditions
IEC 61010-1. Safety requirements for electrical equipment for measurement, control, and laboratory use – Part 1: General
requirements.
IEC 61326-1. Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 1: General
requirements.
IEC 61000-4-3. Electromagnetic compatibility (EMC) - Part 4-3: Testing and measurement techniques - Radiated,
radio-frequency, electromagnetic field immunity test.
EN 55011. Industrial, scientific and medical equipment - Radio-frequency disturbance characteristics - Limits and
methods of measurement.
IEC 60068-2-2. Environmental testing - Part 2-2: Tests - Test B: Dry heat
IEC 60068-2-13. Environmental testing Part 2: Tests - Test M: Low air pressure
Due to Ecamec continuous improvement policy the present datasheet parameters may vary and actual product may differ from the pictures shown.