Documentos de Académico
Documentos de Profesional
Documentos de Cultura
3 Measurement of impedance of
R-L, R-C,R-L-C & study of
resonance phenomena
APPARATUS REQUIRED:-
Voltmeter 0 -300V, MI; ammeters 10A, 5A, 5A, MI; single –phase
inductive variable load, rheostat 100 ,5A; variac 230V, 10A.
THEORY:-
I1
I3
Power factor,
Cos = I12-I22-I32/2I2I3………………………….. (1.3)
I2 = V/R [R is a known resistance]……………… (1.4)
Now from eq. 1.1
I3Cos = P/V
Put this value in eq. 1.2
I12= I22+I32+2I2I3Cos
I12= I22+I32+2I2P/V
or P= (I12-I22-I32)V/2I2
Eqs.1.3 and 1.5 show that we can find the power and power factor in an a.c.
circuits by using 3- single phase ammeters, instead of a wattmeter.
PROCEDURE:-
OBSERVATION:-
CALCULATION:-
For each set of observation calculate the power consumed (Eq 1.5) and the
power factor (Eq 1.3). Next take the average of all the set of calculation for
cos i.e., power factor; and P i.e., power consumed in the load.
RESULT:-
The power factor of the circuit and the power consumed in circuit should be
recorded here.
PRECAUTIONS:-
Apparatus Required:-
Theory:-
Wattmeter has two coils, one is called “current coil” and other is
“pressure coil”. The current coil carries the load current and pressure coil
carries a current proportional to and in phase with supply voltage. The
deflection of wattmeter depends upon the currents in the two coil and upon
the P.F. of the circuit.
In the wattmeter the current coil are arranged for different ratings i.e.
2.5,5 Amp.etc. and similarly voltage coils are rated for 125 V, 250V,
500Vetc. While doing the experiment the proper range should be selected
according to the load voltage and current.
The reading should be multiplied by a factor called the “Multiplying
Factor”.
Active power:-
It is the power, which is actually dissipated in the circuit
Resistance.
P = I2 R = VI COS watts
Reactive Power:-
It is the power developed in the inductive reactance of
the circuit.
Q = I 2X L
Circuit Diagram:-
From diagram:-
It is clear
Sin = XL/Z
Or,
ZSin =XL
Q = I2XL = I*I*XL
Q = I*I*ZSin
Q = V*I*Sin
Power Triangle:-
VI COS
VI
SIN
VI
Impedance Triangle:- R
XL
Z = (R2) + (XL2)
Procedure:-
Observation Table:-
Calculation: -
Report: -
Precautions: -
Following precautions should be taken care of while performing this
experiment.
1. All connections should be tight.
2. The zero setting of all the meters should be checked before connecting
them in the circuit.
3. The current through ammeter should never be allowed to exceed the
current rating of rheostat and load used.
4. Do not increase the current beyond the rated value of wattmeter.
5. The wattmeter should be connected properly in the circuit.
Measurement
Of
Impedance of
R-L, R-C,R-L-C & study of
resonance phenomena
Object :-
Apparatus Required :-
Theory :-
Vr = I R and V L = I XL
2 2 2 2
VS = (Vr + VL ) = (I R)2 + (I XL) = I (R)2 + (XL)
2
I = V / R2 + XL = V/Z
Where,
Z = R2 + XL 2 is the impedance of the circuit
XL = 2 f L is the inductive reactance of the circuit
L = XL/ (2 f)
XL = VL / I
(B) Series R – C Circuit :- It consist of R – Ohm and C – Farads connected in
series with source.
Vr = I R and V C = I XC
2 2 2 2
VS = (Vr + VC ) = (I R)2 + (I XC) = I (R)2 + (XC)
2
I = V / R2 + XC = V/Z
Where,
Z = R2 + XC 2 is the impedance of the circuit
XC = 1 / 2 f C is the capacitance reactance of the circuit
C = 1/2 f XC
XC = VC / I
Vr = I R VC = I XC VL = I XL
2 2 2
VS = Vr + (VL - VC) = (I R)2 + (I XL - I XC)
2
=I R2 + (XL - XC)
Where,
2
Z = R2 + (XL - XC) is the impedance of the circuit
XL = 2 f L is the inductive reactance of the circuit
L = XL/ (2 f)
XL = VL / I
XC = 1 / 2 f C is the capacitance reactance of the circuit
C = 1/2 f XC
XC = VC / I
Vr = I R
R = Vr /I
Resonance: -
Resonance in R-L-C series circuit:
When capacitive reactance XC is equal to the inductive reactance XL then the circuit is said
to be in resonance. The current will maximum, power factor is unity and lie in to phase
with the supply voltage.
2 2 2
VS = Vr + (VL - VC) = (I R)2 + (I XL - I XC) = I R2 + (XL
2
- XC)
Now, XL = WC XC= 1 / WC
WL= 1 / WC , 2 f L= 1/2 fC
Fr = 1/2 LC
Fr = Resonance Frequency
Procedure :-
(1) Connect the circuit diagram connecting R-L, R-C & R-L-C Series as shown in the
circuit diagram.
(2) The Auto-Transformer to zero position and switch on supply.
(3) Adjust the Auto-Transformer till a suitable voltage is applied.
(4) Take the reading from the voltage for VR ,VL , VC & VS respectively.
(5) Note the reading of ammeter.
(6) Repeat step (3) Varying the supply voltage and record the reading in observation
table.
Observation Table :-
Result:-
(1)Resistance (R) = ------------------
(2)Capacitance Reactance = -------------------
(3)Inductive Reactance = --------------------
(4)Inductor (L) = -------------------- Henry
(5)Capacitor (C) = -------------------- F
Precaution :-
Apparatus Required:-
D.C. Machines model.
Theory:-
A d.c. machine is an Electro-Mechanical energy conversion device .
It can convert mechanical power into d.c. electrical power and is known
as a d.c. generator. On the other hand, when it converts d.c. electrical
power into mechanical power it is known as d.c. motor.
Contructional Details:-
There are two main parts of a d.c. machine:-
(A) Field System: -
(i) Electromagnetic Poles
(ii) Yoke
(iii) Field Winding
(B) Armature: -
(i) Armature Core
(ii) Armature Winding
(iii) Commutator
Usually, the pole core and pole shoes are made of thin cast steel.
(5) Commutator:-
It is the most important part of d.c. machine and serves the following
purposes:-
(i) It connects the rotating armature conductors to the stationary
external circuit through brushes.
(ii) It convert the alternating current induced in the armature
conductor into unidirectional current in the external load circuit
in generator action whereas, it converts the alternating torque
into unidirectional torque produced in the armature motor action.
The commutator is of cylindrical shape and is made up of wedge-
shaped hard drawn copper segments. The segments are insulated from
each other by a thin sheet of mice. The segments are held together by
means of 2 V-shaped rings that fit into the V-grooves cut into the
segments. Each armature coil is connected to the commutator segment
through riser.
(6) Brushes:-
The brushes are pressed upon the commutator and from the
connecting link between the armature winding and the external
circuit. They are usually made of high grade carbon because carbon is
conducting material and the same time in powdered form provides
lubricating effect on the commutator surface. The brushes are held in
particular position around the commutator by brush holders.
(7) End housings:-
End housings are attached to the ends of the main frame and support
bearings. The front housing supports the bearing and the brush
assemblies whereas the rear housing usually supports the bearing
only.
(8) Bearings:-
The ball or roller bearings are fitted in the end housings. The function
of the bearings is to reduce friction between the rotating and
stationary parts of the machine. Mostly high carbon steel is used for
the construction of bearings as it is very hard material.
(9) Shaft :-
The shaft is made of mild steel with a maximum breaking strength.
The shaft is used to transfer mechanical power from or to the
machine. The rotating parts like armature core, commutator, cooling
fan etc. are keyed to the shaft.
Perform load test
On
a single phase transformer
Object: -
To perform load test on a single-phase transformer & to determine the
following:
(a)- Efficiency at different loads & to plot graph between efficiency Vs
load currents.
(b)- Regulation of the transformer & to plot graph between regulation
Vs load currents.
Apparatus Required:-
Theory: -
Wattmeter has two coils ,one is called “current coil” & other is
called as “pressure coil”. The current coil carries the load current & the
pressure coil carries a current proportional to and in phase with supply
voltage. The deflection of wattmeter depends upon the currents in the
two coils and upon the P.F. of circuit.
In the wattmeter the current coils are arranged for different ratings i.e.
2.5,5 Amp etc. and similarly voltage coils are rated for 125V, 250V,
and 500V etc. While doing the experiment the proper range should be
selected according to the load voltage & current.
The reading should be multiplied by a factor called the “Multiplying
factor”.
Observation table:-
Report:-
The efficiency of the transformer on full load =
The regulation of the transformer =
Precaution:-
1)-Connection should be tight.
2)-Load on the transformer should nit increase beyond its capacity.
Study of transformer name plate
Rating &
Determination of ratio
OBECT:
1. Study & construction of single phase transformer.
2. Name plate rating of single phase transformer
3. Determination of transformation ration.
APPARATUS REQUIRED:
THEORY:
The name plate rating of a power transformer : The name plate rating of a
power transformer usually contains
TRANSFORMATION RATIO:
The turn ratio of the single phase transformer can be found by measuring the
primary & secondary voltage. Let V1 &V2 is the primary and secondary voltage at
on load.
1/K = V1/ V2 = N1/N2 = I2/I1 = Turn Ratio
Induced E.M.F. in primary winding, E1 =4.44f N1 Volts
Induced E.M.F. in secondary winding, E2 =4.44f N2 Volts
For ideal transformer E1 = V1 and E2 = V2
Hence, Transformation Ratio K = V2/ V1 = N2/ N1 = I1/ I2
PROCEDURE:
1. Connect the circuit as per figure & set up auto transformer to zero position.
2. Switch on A .C. supply and adjust the Auto transformer till a suitable voltage.
3. Record voltage, V1 across the primary and V2 across the secondary winding.
4. Vary the Auto transformer and repeat above step,take at least 3 readings.
5. switch off the supply.
OBSERVATION:
PRECAUTION:
1. Connection should be tight.
2. Do not touch on live wire.
3. Load on the transfer should not increase beyond its capacity.
Open circuit
&
Transformer
OBECT:
APPARATUS REQUIRED:
THEORY:
In this test voltmeter, Ammeter & Wattmeter are connected on low voltage side of
transformer.The high voltage is left open circuited.The rated voltage applied to the
primary.The ammeter reads no load current, or the exciting I0.Since I0 is quite small
(2 to 6% of rated current) the primary leakage impedance drop is almost negligible
and for all practical purpose the applied voltage V1,is equal to induced E.M.F
V1.The input power (iron loss) is given by wattmeter reading,consist of core loss
and ohmic loss.Since the exciting current is very small, the ohmic losses during
open circuit test is negligible as compared to normal core loss.
CIRCUIT DIAGRAM: -
CALCULATION:
The low voltage side of the transformer of the transformer is short circuited &
instrument are placed on H.V. side. Apply the low voltage on H.V. side & with the
help of autotransformer go on increasing the applied voltage till the rated current
starts flowing in the short circuited winding(L.V. side).The primary voltage 10% to
12% of its rated value is sufficient to circulate the rated current in short circuited
winding. Since the core flux induces the voltage, which is 1% to 6% of its rated
value hence core loss can be neglected. The wattmeter records only the ohmic loss
is both, the primary & secondary winding.
CALCULATION:
Vsc, Isc & Psc are the voltmeter ammeter & wattmeter reading
RSC = PSC/I2SC
Load x P.F.
The efficiency at any load, = X 100 %
Load x P.F.+ Wo+ Io2Ro
1. Connect the circuit diagram as shown in figure and set up the autotransformer at
zero position .
2. Adjust the supply voltage with the help of autotransformer to 230 volts with
secondary winding terminal open.
3. Record the ammeter, voltmeter ,wattmeter reading.
4. Vary the supply voltage with the help of the auto transformer and enter the reading
in observation table.
1. Connect the circuit diagram as shown in figure and set up the autotransformer at zero
position .
2. Adjust the supply voltage with the help of autotransformer (keep in mind that 10-12%
of rated voltage is sufficiency) with secondary winding terminal short circuited and
circulate full rated current in short circuited winding.
3. Record the ammeter, voltmeter ,wattmeter reading.
4. Vary the supply voltage with the help of the auto transformer and enter the reading in
observation table.
5. Three readings adjust at 50% ,86.6% & 100% rated full load current.
OBSERVATION TABLE FOR SHORT CIRCUIT TEST
RESULT:
PRECAUTION:
1. In open circuit test, the H.V. side should be open circuited(left side).
2. In open circuit test, low voltage should be apply to the H.V. side & it should be
increased gradually to circulate the rated current in H.V. side.
3. Connection should be tight.
4. Do not touch on livewire.
Measurement of power
in 3 phase
APPARATUS REQUIRED:
THEORY:
Two wattmeter method can be employed to measure power in a 3- phase,3 wire star
or delta connected balance or unbalanced load. In this method, the current coils of
the wattmeters are connected in any two lines say R and Y and potential coil of
each wattmeters is joined across the same line and third line i.e. B.
Then the sum of the power measured by two wattmeters W1 and W2 is equal to the
power absorbed By the 3 load
OBSERVATION TABLE
S.NO. Voltmeter Ammeter Wattmeter Reading Total power Total reactive Power factor
Readings Readings in watt P=(W1+W2)* power Cos =
V in volts I in Amp. M.F. P=
3(W1+W2)* (W1+W2)M.F
M.F, 3 VLIL
W1 W2
1
2
3
4
5
CALCULATION:
RESULT:
The power measured in the circuit and there corresponding power factors in
observation table.
1. Proper currents and voltage range must be selected before putting the
instruments in the circuit.
2. If any Wattmeter reads backward, reverse its pressure coil connection and
the reading as negative.
3. As the supply voltage Fluctuates it is not possible to observe the readings
correctly.
Study of
Three Point
&
Four point starter
OBJECT:
THEORY:
When a motor is stationary, there is no back E.M.F. and the armature behaves as a
low resistance circuit. If the motor is switched on across the supply, it draws a
heavy current from the mains. This may result
To limit the starting current, a starter is used which reduces the voltage
applied to the armature during the starting period.
THREE-POINT STARTER:
The total current drawn by the motor passed through the winding of a small
electromagnet OC known as overload release. This magnet in the event of overload
attracts a soft iron armature P that in turn short circuits the terminals X and Y of the
no volt coil through contact ‘C’. The distance between the magnet and P is usually
adjustable and is so adjusted that P gets attracted only when current drawn by the
motor also flowing through the overload release coil exceeds a preset value.
Therefore when the motor is overloaded, this electromagnetic short circuit the
holding coil terminals and the starter handle swings back to “off” position,
automatically switching off the motor. Since it prevents continuous operation of the
motor on overload, it is known as overload release.
FOUR POINT STARTER:
In a three point starter, the field current of the motor flows through the holding
coils. When the resistance is inserted in a field circuit to increase the speed beyond
a certain limit, the holding coil current may reduce to such an extend that the
electromagnetic pull of the holding coil is no longer sufficient to overcome the
handle spring tension. In such a case, the starter is not suitable for wide range of
speed control by field weakening method is desired. For such application a four-
point starter is used.
Therefore 4 point starter has a holding coil connected across the d.c. supply in
series with the starting resistance instead of being connected in series with the field
winding.