PLANILLA DE HIERROS CASA

DIAM. TIPO DE DIMENSIONES (M) LONG. DE PESO LONG. PESO


MARCA No. OBSERV.
(MM) DOBLADO a b c d CORTE (M) (KG/M) TOTAL (M) TOTAL (KG)

COLUMNAS
201 12 C 32 4.90 0.20 5.30 0.89 169.60 150.6

A 202 10 O 196 0.20 0.20 0.12 1.04 0.62 203.84 125.7 A


203 10 C1 392 0.20 0.12 0.44 0.62 172.48 106.3
VIGAS
301 12 C 4 3.00 0.20 3.40 0.89 13.60 12.1
302 10 O 37 0.15 0.20 0.12 0.94 0.62 34.78 21.4
302 10 O 49 0.15 0.20 0.12 0.94 0.62 46.06 28.4
303 12 C 4 4.20 0.20 4.60 0.89 18.40 16.3
302 10 O 52 0.15 0.20 0.12 0.94 0.62 48.88 30.1
304 12 C 4 4.50 0.20 4.90 0.89 19.60 17.4
302 10 O 54 0.15 0.20 0.12 0.94 0.62 50.76 31.3
305 12 C 4 4.67 0.20 5.07 0.89 20.28 18.0
LOSA
401 12 C 9 1.00 0.15 1.30 0.89 11.70 10.4
402 12 C 9 1.48 0.15 1.78 0.89 16.02 14.2
403 12 C 16 1.60 0.15 1.90 0.89 30.40 27.0
404 12 I 6 4.50 0.10 4.50 0.89 27.00 24.0 Ganchos a 135°
405 12 I 2 1.85 0.10 1.85 0.89 3.70 3.3
406 12 I 4 3.50 0.10 3.50 0.89 14.00 12.4
407 12 I 5 4.20 0.10 4.20 0.89 21.00 18.6
B ZAPATAS B
601 12 C 72 0.90 0.20 1.30 0.89 93.60 83.1
CADENAS
701 12 I 4 14.70 14.70 0.89 58.80 52.2
702 10 O 148 0.15 0.15 0.12 0.84 0.62 124.32 76.6

TOTAL (NO INCLUYE DESPERDICIOS) 879.6


NOTA: LAS LONGITUDES DE CORTE DEBERAN SER VERIFICADAS Y LAS CANTIDADES REALES DEBERAN SER COMPROBADAS EN OBRA

PLANILLA DE HIERROS DUCTOS

DIAM. TIPO DE DIMENSIONES (M) LONG. DE PESO LONG. PESO


MARCA No. OBSERV.
(MM) DOBLADO a b c d CORTE (M) (KG/M) TOTAL (M) TOTAL (KG)

DUCTOS A-A
901 8 I 10 0.78 0.78 0.39 7.80 3.1
902 8 O 3 1.15 1.10 0.10 4.70 0.39 14.10 5.6
903 8 I 3 1.15 1.15 0.39 3.45 1.4
SUBTOTAL 10.0
DUCTOS B-B
904 8 I 10 4.60 4.60 0.39 46.00 18.2
C 905 8 O 16 1.15 1.45 0.10 5.40 0.39 86.40 34.1 C
906 8 I 32 1.15 1.15 0.39 36.80 14.5
SUBTOTAL 66.8
DUCTOS C-C
907 8 I 4 19.00 19.00 0.39 76.00 30.0
908 8 O 4 0.70 0.25 0.10 2.10 0.39 8.40 3.3
909 8 I 63 0.55 0.55 0.39 34.65 13.7
SUBTOTAL 47.0

DIAM. TIPO DE DIMENSIONES (m) LONG. DE PESO LONG. PESO


MARCA No. OBSERV.
(mm) DOBLADO a b c d CORTE (m) (kg/m) TOTAL (m) TOTAL (kg)

CIMENTACIÓN BANCO DE CAPACITORES


750 12 L 48 1.10 0.20 1.30 0.89 62.40 55.4
751 10 O 88 0.40 0.19 0.10 1.38 0.62 121.44 74.9
752 10 0 44 0.40 0.40 0.10 0.90 0.62 39.60 24.4
753 12 C 32 1.10 0.20 1.50 0.89 48.00 42.6
SUBTOTAL 197.3
NOTA: LAS LONGITUDES DE CORTE DEBERAN SER VERIFICADAS Y LAS CANTIDADES REALES DEBERAN SER COMPROBADAS EN OBRA

D D

E E

EMPRESA ELÉCTRICA QUITO

F SUBESTACIÓN PEREZ GUERRERO F


CASA DE CONTROL Y DUCTOS

DISEÑADO: Ing. Karina Ruiz ESCALA: LAS INDICADAS

DIBUJADO: Ing. Xavier Orellana APROBADO:


Ing. David Carrera
REVISADO: Ing. Juan Pablo Idrovo

FECHA: AGOSTO 2017 REF: EEQ-DCOC-SE-005