Está en la página 1de 2

KS SANITARY

PRESSURE TRANSDUCER
INSTRUCTION SHEET

m WARNING! READ m FREEZING:


Prohibit freezing of media in pressure port.
Noise
For minimum noise susceptibility, avoid
BEFORE INSTALLATION Unit should be drained (mount in vertical
position with electrical termination upward)
running the transducer’s cable in a con­
duit that contains high current ac power
1. GENERAL:
A failure resulting in injury or damage to prevent possible overpressure damage cables. Where possible avoid running the
may be caused by excessive overpres- from frozen media. cable near inductive equipment.
sure, excessive vibration or pressure 3. STATIC ELECTRICAL CHARGES: Shield Wiring
pulsation, excessive instrument tem- Any electrical device may be susceptible to Connect the braided shield to the guard
perature, corrosion of the pressure con- damage when exposed to static electrical terminal on the reading instrument (meter,
taining parts, or other misuse. Consult charges. To avoid damage to the trans- etc.) if available or to ground or to the
Ashcroft Inc., Stratford, Connecticut, ducer observe the following: power supply negative terminal.
USA before installing if there are any • Ground the body of the transducer Adjustment Potentiometers
questions or concerns. BEFORE making any electrical
The zero and span pots are accessible
2. OVERPRESSURE: ­c onnections.
through the top of the case. Loosen the
Pressure spikes in excess of the rated • When disconnecting, remove the ground four screws and separate the top carefully.
overpressure capability of the transduc- LAST! The zero pot is marked with a white dot.
er may cause irreversible electrical and/ Note: The shield and drain wire in the
or mechanical damage to the pressure Vent Tube
cable (if supplied) is not connected to the
measuring and containing elements. The cable will have a clear Teflon vent
transducer body, and is not a suitable
Fluid hammer and surges can destroy ground.
tube that's required at pressure below 500
any pressure transducer and must al- psi to provide atmospheric reference. The
ways be avoided. A pressure snubber Mounting open end should be placed in a dry area.
should be installed to eliminate the dam- Although the unit can withstand normal vi-
aging hammer effects. Fluid hammer bration without damage or significant output
occurs when a liquid flow is suddenly effects, it is always good practice to mount Load Limitations 4-20mA Output Only
stopped, as with quick closing solenoid the transducer where there is minimum (R LOOP )

valves. Surges occur when flow is sud- vibration. Be sure to use a gasket that does 1182
denly begun, as when a pump is turned not interfere with the sanitary diaphragm. If 1000
on at full power or a valve is quickly the gasket I.D. is smaller than 1.50 inches,
opened. an offset due to clamping force will occur.
750
Liquid surges are particularly damag- Power Supply
ing to pressure transducers if the pipe The supply voltage for the 1-5 and
is originally empty. To avoid damaging 500
1-6 Vdc output transducers must be within
surges, fluid lines should remain full (if
the range of 10 to 36 Vdc. The maximum OPERATING
possible), pumps should be brought 250
supply voltage for a 4-20mA current output REGION
up to power slowly, and valves opened
transducer is 36 Vdc while the minimum 0
slowly. To avoid damage from both fluid
hammer and surges, a surge chamber supply voltage is dependent upon the loop
0 10 20 30 36
should be installed. resistance of the circuit. The Load Limita-
tion Chart shows the minimum supply Vmin = 10V+ (.022A x R L)
Symptoms of fluid hammer and surge's RL = RS + RW
damaging effects:
voltage (Vmin) required for a given loop
­resistance (RLOOP). RL = Loop Resistance (ohms)
• Pressure transducer exhibits an output
Excitation (Ratiometric Output Only) RS = Sense Resistance (ohms)
at zero pressure (large zero offset).
For proper operation a voltage within RW = Wire Resistance (ohms)
• Pressure transducer output remains
the range of 5 to 10 Vdc must be
constant regardless of pressure
ap­plied between the transducer’s supply
• In severe cases, there will be no output.
terminals.

© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614, USA • Tel: 203-378-8281, Fax: 203-385-0402 • email: info@ashcrfoft.com, www.ashcroft.com.
All specifications subject to change without notice. All sales subject to standard terms and conditions of sale. I&M011-10124 (250-3110) Rev. A 5/11
KS Sanitary Transducers – Electrical Conn.
Dimensions
Voltage Output Units 1-5, 1-6 Vdc Ratiometric (mV/V)
A
Cable Type F2


Cable Type F2 Red = + Power
Red = + Power White = – Power
▲ White = Common Green = + Output
Green = Output Black = – Output

Cable Type C1 Cable Type C1


Red = + Power Red = + Power
White = Common White = – Power
Green = Output Green = + Output
Black = – Output

Hirschmann Type
B PIN-1 = + Power Bendix 4-Pin
PIN-2 = Common Pin A = +Power
PIN-4 = Output Pin B = +Output
Pin C = – Output
Pin D = – Power
Bendix 4-Pin, 6-Pin
Pin A = + Power
Pin B = Output Bendix 6-Pin
Pin D = Common Pin A = +Power
Pin D = – Power
▲ Pin B = +Output
Pin C = – Output
C Current Output Units 4-20 mA Pin E
Pin F
=
=
Shunt Cal.
Shunt Cal.
▼ ▼

Cable Type F2
Red = + Power
Black = – Power
D

Cable Type C1
Red = + Power
MODEL A B C D Black = – Power

S15 0.8 4.7 0.9 2.0 Hirschmann Type


PIN-1 = + Power
PIN-2 = – Power
S20 0.8 4.7 0.9 2.5
Bendix 4-Pin, 6-Pin
Pin A = + Power
Pin B = – Power

Wiring Diagrams for All Transducers

+ RED (+ Power)
POWER
SUPPLY WHITE (- Power)

TRANSDUCER
+ GREEN (+ Output)
BLACK (- Output)

METER
4-Wire Ratiometric (mV/V)

+ RED (+ Power)
POWER
SUPPLY WHITE (Common)

TRANSDUCER

GREEN (+ Output)
+
METER
3-Wire Voltage

POWER
SUPPLY
– +
RED (+)
POWER

TRANSDUCER

BLACK (–)
OUTPUT
– +
METER

4-20 mA

© 2011 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614, USA • Tel: 203-378-8281, Fax: 203-385-0402 • email: info@ashcrfoft.com, www.ashcroft.com.
All specifications subject to change without notice. All sales subject to standard terms and conditions of sale. I&M011-10124 (250-3110) Rev. A 5/11

También podría gustarte