Está en la página 1de 7

Construction and Building Materials, Vol. 9, No. 2, pp.

97-103, 1995
Copyright 0 1995 Elsevier Science Ltd
09504618(95)ooo02-x Printed in Great Britain. All rights reserved
09504618195 $10.00+0.00

Electrochemical behaviour of steel in plain and


blended cement concretes in sulphate and/or
chloride environments

Nezar R. Jarrah, Omar Saeed Baghabra Al-Amoudi, Mohammed Maslehuddin”,


Oluwatoyin A. Ashiru and Abdulaziz lbrahim Al-Mana

King Fahd University of Petroleum and Miner-a/s, Dhahran 31261, Saudi Arabia

Received 2 March 1994; revised 22 October 1994; accepted 21 November 1994

The electrochemical behaviour of reinforcing steel in plain and blended cement concrete speci-
mens placed in sulphate, chloride and sulphate-chloride environments was investigated. The effect
of cement composition and the exposure condition on the corrosion behaviour of reinforcing steel
was evaluated by measuring corrosion potentials at periodic intervals and conducting potentio-
dynamic scans after two and half years of exposure. The corrosion potential data indicated passive
corrosion in plain and blended cement concrete specimens placed in the pure sulphate environ-
ment. The time to initiation of reinforcement corrosion, however, was higher in blended cements
than plain cements in all chloride and chloride-sulphate environments. The concomitant presence
of suphate and chloride salts did not significantly influence the time to corrosion initiation. The
corrosion rate, however, was significantly influenced by the quantum of sulphate ions associated
with the chloride salts. The superior performance of silica fume blended cement, in terms of longer
time to corrosion initiation and lower corrosion rate, indicates its potential in enhancing the useful
service life of reinforced concrete structures placed in the chloride-sulphate environments.

Keywords: electrochemical behaviour; steel; concrete

In reinforced concrete, steel provides the much needed concrete through an accelerator, contaminated aggre-
tensile property, while concrete essentially takes care of gates and/or mixing water. Alternatively, they may
the compressive stresses. Furthermore, concrete penetrate the hardened concrete from the external envi-
provides both physical and chemical protection to the ronment. Deterioration of reinforced concrete bridge
reinforcing steel. The physical protection is provided by decks due to the use of de-icer salts in the temperate
its dense structure which retards the ingress of aggres- climates of the US and Europe is well documented.
sive species, such as oxygen, moisture and chloride ions Corrosion of reinforcement due to chloride salts is also
to the steel-concrete interface. The chemical protection a predominant durability problem in the coastal areas
is provided by the high alkalinity of the pore solution of the Arabian Gulf.
due to which a submicroscopically thin protective film The marine structures, both on-shore and off-shore,
of y-ferric oxide is formed on the steel surface. however, are subjected to both chloride-induced rein-
In spite of the inherent protection provided to the forcement corrosion and sulphate attack. The role of
steel by concrete, failures of concrete structures result- sulphate ions, when chlorides and sulphates are
ing from reinforcement corrosion are not uncommon. conjointly present, on corrosion of reinforcing steel is
The breakdown of the passive layer is attributed to two often a point of controversy. Holden et al.’ indicated
principal factors, namely (i) reduction in the pH of the that the concomitant presence of chlorides and
surrounding concrete due to carbonation and (ii) pene- sulphates increases the risk of corrosion significantly.
tration of aggressive ions like chlorides to the Al-Tayyib et al.* reported a seven-fold increase in corro-
steel-concrete interface. Reinforcement corrosion due sion activity on mild steel exposed to sulphate-contain-
to penetration of carbon dioxide may result in uniform ing calcium hydroxide solutions over those containing
corrosion and is predominant in industrial areas. The chloride salts. Cheng et ~1.~ investigated the effects of
chloride-induced reinforcement corrosion is basically chloride and sulphate ions on the electrochemical prop-
attributed to chlorides which are introduced into the erties of reinforcing steel using an AC impedance tech-
nique. Their results indicated that the presence of
*Correspondence to M. Maslehuddin, KFUPM Box 442, Dhahran
sulphate ions could modify the surface characteristics of
31261, Saudi Arabia reinforcing steel. Studies conducted by Al-Amoudi and

Construction and Building Materials 1995 Volume 9 Number 2 97


Electrochemical behaviour of steel: N. R. Jarrah et al.

Table 1 Chemical composition of cements and blending materials imens were covered with wet burlap for 24 h prior to
Constituent (wt. %) Fly Blast furnace Silica Type V Type I demoulding.
ash slag cement fume cement cement Test solutions. After demoulding, the specimens were
cured in potable water for a further period of 14 days
Silicon dioxide 52.3 27.7 92.5 22.0 20.5
Aluminium oxide 25.2 12.8 0.4 4.1 5.6 and then placed in the four test solutions. The compo-
Ferric oxide 4.6 1.2 0.4 4.2 3.8 sition of the test solutions is detailed below:
Calcium oxide 10.0 44.0 0.5 64.1 64.4
Magnesium oxide 2.2 8.8 0.9 2.2 2.1
Sulphur trioxide 0.6 3.1 0.5 2.0 2.1 Solution 1: 15.7% Cll (pure chloride environment)
Loss on ignition 0.4 0.9 2.6 0.8 0.7 Solution 2: 2.1% SO, - (pure sulphate environment)
Potassium oxide 0.3 0.3 Solution 3: 0.55% SO, -+ 15.7% Cl- (low sulphate-
Sodium oxide 0.2 0.2
54.6 56.7 chloride environment)
C,S
c,s 21.9 16.1 Solution 4: 2.1% SO, + 15.7% Cll (high sulphate-
_ _ 3.5 8.5
CA chloride environment)
C,AF 12.9 11.6

Test solutions 3 and 4 represent the concentration of


Maslehuddin4 showed that reinforcement corrosion chloride and sulphate ions commonly found in the
increases due to the conjoint presence of chloride and coastal and continental sabkha brines in the Arabian
sulphate salts as compared to those exposed to chloride Gulf, respectively5. Test solutions 1 and 2 represent the
salts. maximum chloride and sulphate concentrations in these
While the studies cited above provide an indication of solutions.
the role of sulphate ions on reinforcement corrosion, Sodium chloride was used to provide the chloride
there is a need to investigate the electrochemical behav- ions, while sodium sulphate and magnesium sulphate
iour of steel in concrete, particularly in blended cements were used to provide the sulphate ions. The latter two
which are commonly used these days to utilize the tech- salts were proportioned to provide 50% of the sulphate
nological benefits accrued from their use. concentration from each of them. The specimens were
This investigation was carried out to study the effect partially immersed in the solution contained in glass
of chloride and/or sulphate ions on the electrochemical fibre tanks. These tanks were covered with polyethylene
behaviour of steel in plain and blended cement sheets to minimize evaporation and the concentration
concretes. Two types of plain cements, namely ASTM C was adjusted each month.
150 Type V (C,A: 3.5%) and Type I (C,A: 8.5%) were Reinforcement corrosion. The reinforcement corrosion
used. The blended cements investigated utilized replace- was monitored by measuring the corrosion potentials at
ments of fly ash, silica fume and blast furnace slag. regular intervals using a high impedance voltmeter and
recording the potentials with respect to a saturated
Materials and techniques calomel electrode (SCE).
The electrochemical behaviour of steel in the concrete
Materials specimens was evaluated by conducting potentio-
The fly ash blended cement contained 20% fly ash, used dynamic scans after about two and half years of expo-
as a replacement of cement, while silica fume blended sure to the four test environments. A microprocessor-
cement contained 10% silica fume. The blast furnace based potentiostatigalvanostat was used for polarizing
slag cement concrete specimens contained 60% granu- the steel. A stainless steel frame placed outside the
lated blast furnace slag and 40% Type I cement. A specimen was used as a counter electrode, while a satur-
cementitious material content of 350 kg/m3 and water to ated calomel electrode was used as a reference electrode.
cementitious material ratio of 0.5 were kept invariant in Figure 1 is a schematic representation of the test set-up.
all the concrete mixes. The coarse aggregate was 19 mm A scan rate of 0.2 mVls was used. A positive feedback
maximum size crushed limestone, of bulk specific technique was used to compensate for the Ohmic drop
gravity 2.42 and average absorption of 3.77%. A coarse (IR) between the reference electrode and the reinforc-
to fine aggregate ratio of 1.6 by weight was kept invari- ing bar.
ant in all concrete mixes. Table I shows the chemical
composition of the cements and blending materials used
Results
in this investigation.
Corrosion potentials
Techniques The corrosion potentials of steel in concrete specimens
Reinforced concrete specimens. Concrete cylinders, 75 made with plain and blended cements and exposed to
X 150 mm with a centrally embedded 12 mm 0 rein- the four test environments are plotted against time of
forcing bar, were used. The bars were cleaned thor- exposure in Figures 2 to 5. Each point in these figures is
oughly using silicon carbide paper and degreased before an average of three readings taken on triplicate speci-
casting. They were also coated with epoxy coating at mens representing similar concrete constituents and
the concrete-air interface and the embedded end to exposure conditions. These corrosion potential-time
eliminate the crevice effect. The concrete ingredients curves were used to evaluate the time to initiation of
were mixed in a revolving mixer. After casting, the spec- corrosion based on the ASTM C 876 criterion of -350

98 Construction and Building Materials 1995 Volume 9 Number 2


Electrochemical behaviour of steel: N. R. Jarrah et al.

: 0.55% !504 +
15.70% Cl

.o
0
;TIC ANK

Threshold Potential

I I I I
01 I I
b75mm_I &AL, BRIDGE 0 100 200 300 LOO 500 600 ‘0
Period of Immersion, Days
Figure 1 Schematic representation of the electrochemical test set-up
Figure 3 Corrosion potentials on steel in plain and blended cement
concrete specimens exposed to a low sulphate-chloride environment
- + - Type 1 Cement
900 - - -z- - Type Y Cement
900 - --+--Type I Cement
- -O- - Flv Ash Cement
......Q--... 5l1ca Fume Cement
- -%-Type Y Cement Test Environment :15.7% Cl
-+-- Blast Slag Cement @ 800 - + -Fly Ash Cement
-.,.-.o.--..- Stka Fume Cement
‘” 700
<
1 600
G_
6 500
z
a 100

o~_~
2
‘: 300
5

2 200
a ,_. .Ja”‘”
ET==-
100 ‘..&3_.~.__.~.Q 6
...... ...
-ww
T&t Enyironmen! : 2.1% ?I4 + 15.7;~ CL
1
0 100 200 300 400 500 600 700
0 I I I L I I
Period of Immersion. Days 0 100 200 300 400 500 600 100

Figure 2
Corrosion potentials on steel in plain and blended cement Period of Immersion, Days
concrete specimens exposed to a high sulphate-chloride environment
Figure 4 Corrosion potentials on steel in plain and blended cement
concrete specimens exposed to a pure chloride environment

mV CSE, i.e. -270 mV SCE. The corrosion initiation


times based on the potential-time records for concrete and blended cements. Due to this reducing environ-
specimens exposed to the four environments are ment, the potentials may be low. The corrosion rate,
summarized in Table 2. Initiation of reinforcement however, remains low.
corrosion was indicated in Type I and Type V cement The time to initiation of reinforcement corrosion in
concrete specimens placed in the high sulphate-chloride Type I and Type V cement concrete specimens exposed
environment after 162 and 106 days, respectively to the low sulphate-chloride environment was 108 and
(Figure 2). Initiation of reinforcement corrosion was 80 days (Figure 3). The time to initiation of corrosion of
indicated in fly ash blended cement concrete specimens steel in fly ash and silica fume blended cement concrete
after 210 days of exposure. The corrosion specimens was 152 and 548 days, respectively. The
potential-time curve for steel in silica fume blended corrosion potentials of steel in blast furnace slag cement
cement concrete specimens crossed the -270 mV SCE concrete specimens were more negative than -270 mV
threshold line after about 552 days of exposure. The SCE.
corrosion potentials of steel in blast furnace slag cement The corrosion potential-time curves for specimens
concrete specimens were lower than -270 mV SCE even placed in the pure chloride environment are presented
before placement in the test environment. The high in Figure 4. Initiation of reinforcement corrosion in
corrosion potentials in the BFS cement concrete speci- Type I and Type V cement concrete specimens was indi-
mens may be attributed to the reducing effects of cated after 175 and 107 days, respectively, and in fly ash
sulphur species, namely S--, S,O,, etc., derived from the and silica fume cement concretes after 220 and 631 days
slag6. These sulphur species in the BFS cement create a of exposure. The potential-time curve for steel in the
more reducing environment than in the other Portland blast furnace slag cement concrete specimens indicated

Construction and Building Materials 1995 Volume 9 Number 2 99


Electrochemical behaviour of steel: N. R. Jarrah et al.

700 . 0 BOO
I-
Test Environment : 2.10% SO4
~~BFS
w 600 -4 0 600 TEST ENVIRONMENT 2.1% SO,+15 7% Cl
y FA
=:
> 500 - :;;
t *mu- rype I cement
+ Type V Cement -;I; )I:
SF -
- LOO - a- -Fly Ash Cement
0
:
: 81hra Fume Cement
m
A Blast Slag Cement
j$ 300 - Threshold Potential

TYPE I

0
0 600
0 100 200 300 100 500 600 700 800

Period of Immersion. Days

Figure 5 Corrosion potentials on steel in plain and blended cement


concrete specimens exposed to a pure sulphate environment

Table 2 Time to initiation of corrosion in plain and blended


cements Figure 6 Potentiodynamic plot for steel in plain and blended cement
concrete specimens exposed to a high sulphate-chloride environment
Time to reinforcement corrosion initiation (days) in
Cement Table 3 Electrochemical data for steel in plain and blended cement
Pure Low-sulphate High-sulphate Pure concrete specimens placed in a high sulphate-chloride environment
chloride chloride chloride sulphate
Cement type RP Corrosion rate
Type 1 175 108 162 Passive (kR.cm*) (mpy)
Type V 107 80 106 Passive
Fly ash 220 152 210 Passive Type 1 4.9 4.113
Silica fume 631 548 552 Passive Type V 4.4 5.632
Type I + fly ash 6.4 3.002
*Indicates passivity Type I + B.F. slag 17.1 1.367
Type I + silica fume 29.7 0.902

a trend similar to that observed in the two sulphate-


chloride environments. 0 800
BFS7
The corrosion potential-time curves for specimens o 6oo _ TEST ENVlRONMENT:0.55%SOL+15.7%CI
placed in the pure sulphate environment indicated no
corrosion initiation even after about two years of expo- 0 400 -
sure (Figure 5).
g 0 200 -
In summary, the data in Table 2 indicate that the -
performance, in terms of time to initiation of reinforce- ’ 0 000 -
ment corrosion, of silica fume cement concrete was <
significantly superior to fly ash and plain cement F -0 200 -
iz
concretes. However, the performance of fly ash cement
$ -0 400 I-
concrete was better than plain cements. In plain
cements, Type I cement performed better than Type V -0 600 -
cement in all chloride and chloride-sulphate environ-
-0 800 -
ments. Further, these data also indciated that sulphate
ions alone do not initiate reinforcement corrosion and 1 000 1R I I
_)
I
, c
10" 10' 10' 10' lo* 10' 106
that the time to initiation of reinforcement corrosion
CURRENT DENSITY, nA/cm'
was not significantly affected by the concentration of
the sulphate ions associated with chloride ions. Figure 7 Potentiodynamic plot for steel in plain and blended cement
concrete specimens exposed to a low sulphate-chloride environment
The potentiodynamic plots for steel embedded in
plain and blended cement concrete specimens exposed
to the high sulphate-chloride environment are shown in environment are shown in Table 3. These data indicate
Figure 6. The polarization current density was observed higher corrosion activity in plain cement concrete
to be higher in plain cements than in blended cements. specimens than that in blended cement concrete speci-
Higher corrosion activity was measured in Type V mens. Minimum corrosion activity, as measured by the
cement (C,A: 3.5%) than that in Type I cement (C,A: corrosion rate, was indicated in silica fume blended
8.5%). The potential-current curve for steel in silica cement concrete specimens followed by blast furnace
fume blended cement concrete specimens tended to be slag and fly ash blended cement concrete specimens.
more cathodic as compared to the corresponding curves The potentiodynamic plots for steel in concrete spec-
for other blended cement concrete specimens. imens placed in the low sulphate-chloride environment
The electrochemical data for steel in plain and are plotted in Figure 7. These curves indicated a trend
blended cements placed in the high sulphate-chloride similar to that in Figure 6. However, the following

100 Construction and Building Materials 1995 Volume 9 Number 2


Electrochemical behaviour of steel: N. R. Jan-ah et al.

Table 4 Electrochemical data for steel in plain and blended cement Table 5 Electrochemical data for steel in plain and blended cement
concrete specimens placed in a low sulphate-chloride environment concrete specimens placed in a pure chloride environment

Cement type Corrosion rate Cement type Corrosion rate


(mpy) fmpy)

Type I 4.8 3.338 Type 1 14.3 1.612


Type V 3.5 5.032 Type V 12.1 1.738
Type I + fly ash 9.8 2.291 Type I + fly ash 12.6 1.533
Type I + B.F. slag 19.3 1.134 Type I + B.F. slag 32.1 0.759
Type I + silica fume 27.7 0.582 Type I + silica fume 62.7 0.338

0 800 0.800
I TEST ENVIRONMENT : 2.10% SO‘ , .TYPE P

0.600 -

0.400 -

\ I’
-0.600 - /
-._-..---a-~~._\_
_/”
-0.800
‘-A
-1000 I I 1 1 I
t ‘\
-1.000’ I
I I I t

100 10' 102 103 106 105 106 10° lo’ lo* lo3 104 10S 106
CURRENT DENSITY, “A/cm2 CURRENT DENSKY. nA/cm2
Figure 8 Potentiodynamic plot for steel in plain and blended cement Figure 9 Potentiodynamic plot for steel in plain and blended cement
concrete specimens exposed to a pure chloride environment concrete specimens exposed to a pure sulphate environment

at a potential of -50 mV SCE. Silica fume and fly ash


features differentiate the behaviour of reinforcing steel cement concretes indicated superior performance in
placed in this solution from those placed in the high inhibiting reinforcement corrosion compared to plain
sulphate-chloride environment: cements. The performance of blast furnace slag cement
concrete was marginally better than that of plain
(9 a passive region was indicated for steel in silica cement concretes. The potential-current density plot for
fume cement concrete specimens, in the range of Type V cement concrete tended to be more anodic
-650 to -200 mV SCE; compared to Type I cement concrete.
(ii) the anodic portions of the potential-current The electrochemical data for steel in plain and
density plots for the blast furnace slag and silica blended cement concrete specimens exposed to the pure
fume cement concrete specimens tended to merge chloride environment are shown in Table 5. These data
together, indicating no superior performance of also indicated a superior performance by silica fume
the silica fume as compared to blast furnace slag cement concrete in inhibiting reinforcement corrosion.
in this environment; The potential-current density curves for steel in
(iii) the possibility of pitting corrosion is discernible concrete specimens placed in the pure sulphate solution
for steel in Type V cement concrete specimens are plotted in Figure 9. These curves indicated uniform
beyond -300 mV SCE. corrosion in all the specimens exposed to this environ-
ment. The silica fume cement concrete specimens indi-
The electrochemical data for steel in plain and cated superior performance in this environment as well.
blended cement concrete specimens placed in a low The current-potential curve for steel in blast furnace
sulphate-chloride environment are shown in Table 4. slag cement concrete tends to shift towards a more
These data indicated a trend more or less similar to that anodic region as compared to plain cement concrete
exhibited in Table 3. However, comparison of data in specimens.
Tab&s 3 and 4 indicated higher corrosion activity in The electrochemical data for steel in concrete speci-
specimens placed in the high sulphate-chloride environ- mens placed in this solution are presented in Table 6.
ment than in specimens placed in the low sulphate- These data indicate minimal corrosion activity on steel
chloride environment. in silica fume cement concrete specimens placed in this
The potentiodynamic curves for steel in plain and environment. The corrosion rate of steel in both plain
blended cement concrete specimens placed in the pure and blended cement concrete specimens placed in this
chloride environment are shown in Figure 8. Uniform environment was much lower than in the corresponding
corrosion was observed on steel in all the cements specimens placed in either chloride or sulphate-chloride
except Type I cement in which pitting corrosion occurs environments.

Construction and Building Materials 1995 Volume 9 Number 2 101


Electrochemical behaviour of steel: N. R. Jarrah et al.

Table 6 Electrochemical data for steel in plain and blended cement 6,


concrete specimens placed in a pure sulphate environment

Cement type Corrosion rate


(lcZm2) (mpy)

Type I 23.4 0.867


Type V 126.1 0.151
Type I + fly ash 131.6 0.183
Type I + B.F. slag 24.5 0.880
Type I + silica fume 224.6 0.065

Discussion
The time to initiation and propagation of reinforcement
corrosion are the two components of the service life
model presented by Tuutti’ and Brownes. The initiation
period represents the time for the diffusion of aggressive
substances through concrete to the steel-concrete inter- 0 0.02 0.04 0.06 0.08 0.1 0.12 0.11,
SULFATE / CHLORIDE RATIO
face to cause activation of the corrosion process. The
propagation time represents the time before loss of Figure 10 Effect of sulphate ion concentration on reinforcement
corrosion in sulphate-chloride environments
serviceability or damage prevents the structure from
being used for its intended function. The data developed
in this investigation are discussed in the light of this with the earlier results on the effect of sulphate-chloride
model. environments on reinforcement corrosion in paste speci-
The data on time to initiation of reinforcement corro- mens made with Type I cement4.
sion, presented in Table 2, indicated a superior perfor- A comparison of corrosion rate data, Figure IO, with
mance by the blended cements, particularly silica fume that on time to initiation of corrosion (Table 2) indi-
cement in inhibiting reinforcement corrosion. The time cates that while sulphate ions do not contribute to the
to initiation of reinforcement corrosion in plain cement initiation of reinforcement corrosion, their presence at
concrete specimens placed in a pure chloride environ- the steel-concrete interface, once corrosion is initiated,
ment was in the range of 107 to 175 days, while for the increases the corrosion activity. This increase in the
specimens placed in sulphate-chloride environments it corrosion activity due to the conjoint presence of chlo-
was in the range of 80 to 160 days. The time to initia- ride and sulphate salts as compared to that due to the
tion of reinforcement corrosion in fly ash and silica presence of only chloride ions may be attributed to the
fume cement concrete specimens ranged from 220 to decrease in the electrical resistivity which aids in the
631 and from 152 to 552 days in the chloride and flow of the corrosion current from the anodic to the
sulphate-chloride environments, respectively. cathodic site and vice versa.
The data in Table 2, however, do not indicate a The superior performance of blended cements, partic-
systematic trend with regard to the role of sulphate ions ularly silica fume blended cement, over plain cements in
on the time to initiation of reinforcement corrosion. sulphate, chloride and sulphate-chloride environments,
The insignificant role of sulphate ions on time to initia- indicates the technologica1 benefits that can be accrued
tion of reinforcement corrosion may be attributed to the due to their use. The higher time to initiation of rein-
fact that chloride ions diffuse much faster than sulphate forcement corrosion in blended cements, particularly in
ions into hardened cement matrix9 and hence totally silica fume cement concrete specimens, may be attrib-
dominate the initiation of reinforcement corrosion. Rio uted to the dense and impermeable structure of these
and Turriziani’O observed that the chloride penetration cements compared to plain cements. Mineral admix-
depth was about twice as much as that for SO,--. This is tures react with calcium hydroxide (CH) liberated by
consistent with the diffusivity data of Barnes and Roy” the hydration of the tricalcium silicate (C,S) and dical-
who found in salt-containing mixtures (containing fly cium silicate (C,S) in the Portland cement forming
ash and/or slag) consistently lower diffusion rates by a secondary calcium silicate hydrate14J5. The secondary
factor of 2 to 5 for SO,- than Na’ and other cations. C-S-H phase, although less dense than the primary C-S-
Based on an extensive literature review, Oberholster” H formed in the plain cements, nevertheless effectively
reported that the diffusion of chloride is generally 10 to fills up the large voids in the hydrated Portland-
100 times faster than that of sulphates. The greater pozzolan cement concretes. Li and Royi indicated that
penetration of chlorides compared to sulphates was also the diffusion of aggressive agents, chloride ions in
observed by Stratful13, who indicated that concrete particular, is affected not only by the pore structure of
retained 14 times more chlorides than sulphates. the materials but also by the diffusion mechanism.
The effect of sulphate concentration on reinforcement According to them, a reduction in chloride transport
corrosion in sulphate-chloride environments is plotted rate also occurs due to the change in chemical composi-
in Figure IO. As shown in this figure, the corrosion tion beyond that caused by physical factors. It is
activity increases with the concentration of sulphate assumed that because of the pozzolanic reaction a
ions associated with chloride salts. This trend is in line significant amount of gel is produced during hydration

102 Construction and Building Materials 1995 Volume 9 Number 2


Nectrochemical behaviour of steel: N. R. Jarrah et al.

in the pozzolanic materials; the critical point is that the 7 The longer time to initiation of reinforcement corro-
gel-type hydrates are located to block the pores instead sion and lower corrosion rate observed in the silica
of just forming a layer on the solid pore surfaces. The fume cement concrete exposed to chloride and/or
lower amount of Ca(OH), in the pozzolanic cement sulphate environments reflects its usefulness in
pastes, and their higher silica and alumina contents, are enhancing the useful-service life of reinforced
of benefit for these kinds of cementitious materials to concrete structures.
minimize the penetration of chloride ions. Further, the
pore channels in these cements have a high tortuosity
compared to plain cement pastes. Also, the chloride Acknowledgements
ions may be inhibited by interaction of these secondary The authors wish to acknowledge the Research Institute
hydrates formed, by the pozzolanic reactions, with and the Department of Civil Engineering, King Fahd
other ions as they pass through these channels. University of Petroleum and Minerals for support of
The dense pore structure of blended cements also this research.
impedes the flow of moisture and oxygen to the
steel-concrete interface, thereby retarding the anodic
reaction. Moreover, the electrical resistivity of blended References
cements being higher than that of plain cementsr7, prop- 1 Holden, W.R., Page, C.L. and Short, N.R. The influence of
agation of corrosion current will be hampered in these chlorides and sulfates on concrete durability. Corrosion of
Reinforcement in Concrete Construction, ed. Crane, A.P., Society
cements compared to plain cements. The lower corro-
of Chemical Industry, London, 1983, pp 143-149
sion activity in blended cements as compared to plain 2 Al-Tayyib, A.J., Somuah, SK., Boah, J.K., Lublanc, P. and Al-
cements may be attributed to these factors, namely the Mana, AI., Laboratory study on the effect of sulfate ions on
dense microstructure, lower oxygen and moisture diffu- rebar corrosion. Cem. Concr. Res. 1988, 18(5), 774-782
3 Cheng, T., Lee, J. and Tsai, W. Corrosion of reinforcement in
sion as well as increased electrical resistivity.
artificial sea water and concentrated sulfate solution. Cem.
Concr. Res. 1990, 20(2), 243-252
4 Al-Amoudi, O.S.B. and Maslehuddin, M. The effect of chloride
Conclusions and sulfate ions on reinforcement corrosion. Cem. Concr. Res.
1993, 23(l), 139-146
The corrosion potential-time curves for steel in 5 Johnson, H., Kamal, M.R., Pierson, G.O. and Ramsay, J.B.
plain and blended cement concrete specimens placed Sabkhas of Eastern Saudi Arabia. In Quaternary Period in Saudi
in a pure sulphate environment, for about two years, Arabia, eds Al-Sayyari and Zotl, Springer-Verlag, Austria, 1978,
indicated passivity. pp 84-93
6 Macphee, D.E. and Cao, H.T. Theoretical description of impact
The data on time to initiation of corrosion did not of blast furnace slag (BFS) on steel passivation in concrete.
indicate a clear and systematic trend on the role of Mag. Concr. Res. 1993, 45(162), pp 63-69
sulphate ions in corrosion activation. I Tuutti, K. Service life of structures with regard to corrosion of
The potentiodynamic curves for steel in plain and embedded steel. ACI SP-65, American Concrete Institute,
Detroit, 1980, pp 223-236
blended cements generally indicated uniform corro- 8 Browne, R.D. Design for durability. Proc. 7th European Ready
sion in all exposure conditions. These plots indicated Mixed Concrete Congress, Institute of Concrete Technology,
active corrosion in plain cements compared to London, 1983
9 Roy, D.M. Mechanism of cement paste degradation due to
blended cements,
chemical and physical factors. Proc. 8th International Congress
Increasing the sulphate concentration from 0 to on the Chemistry of Cement, Rio de Janeiro, 1986, pp 362-380
2.1% in 15.7% chloride solution increased the corro- 10 Rio, A. and Turriziani, R. II Cemento, 1983, 80(l), pp 37-48
sion current density. This trend was observed in 11 Barnes, M. and Roy, D.M. Leaching of salt stones containing fly
ash and slag. Internal Report, 1985
both plain and blended cement concrete specimens. 12 Oberholster, R.E. Pore structure, permeability and diffusivity of
The increase in corrosion activity associated with hardened cement paste and concrete in relation to durability:
increasing sulphate concentration may be attributed status and prospects. Proc. 8th International Congress on the
Chemistry of Cement, Rio de Janeiro, Sub-Theme 4.1, September
to the decrease in the electrical resistivity of concrete
1986, pp 323-335
due to the presence of sulphate ions. 13 Stratful, R.F. Effect on reinforced concrete in sodium chloride
The superior performance of blended cements, and sodium sulfate environments. Mater. Protect. December
particularly silica fume blended cement, in both the 1964, 3(12), pp 74-80
14 Mehta, P.K. and Aitcin, P.C. Principles underlying the produc-
chloride and sulphate-chloride environments, is
tion of high performance concrete. Cem. Concr. Aggreg. 1990,
attributable to the dense pore structure which 12(2), 70-78
inhibits the diffusion of chloride, oxygen and mois- 15 Feldman, R.F. Pore structure formation during hydration of fly
ture to the steel-concrete interface. The lower corro- ash and slag cement blends. Proc. Symposium on Fly Ash
Utilization in Cement and Concrete, Material Research Society,
sion rates in these cements are also attributable to Boston, 1981, pp 124-133
the higher electrical resistivity of these cements than 16 Li, S. and Roy, D.M. Investigation of relations between poros-
in the plain cements. The higher electrical resistivity ity, pore structure, and Cl- diffusion of fly ash and blended
impedes the flow of electrons from the anodic to the cement pastes. Cem. Concr. Res. 1986, 16(3), pp 749-759
17 Gjorv, O.E. Durability of concrete containing condensed silica
cathodic sites, thus retarding the propagation of the fume. ACI SP-79, American Concrete Institute, Detroit, Vol. 2,
corrosion process. 1983, pp 695-708

Construction and Building Materials 1995 Volume 9 Number 2 103

También podría gustarte