Está en la página 1de 5

PLUMBING LEGEND PLUMBING ABBREVIATIONS DRAWING INDEX

1. ALL WORK SHALL COMPLY WITH THE REQUIREMENTS OF TITLE 24 OF THE CALIFORNIA CODE OF SYMBOL ABBR DESCRIPTION ABBR DESCRIPTION ABBR DESCRIPTION DWG. NO. DESCRIPTION
REGULATIONS (C.C.R.), 2010 CPC.
AB.C ABOVE CEILING KW KILOWATTS P0.1 PLUMBING LEGEND AND NOTES
DETAIL NUMBER
2. ALL SYSTEMS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH ALL APPLICABLE CITY, COUNTY, FEDERAL DRAWING NUMBER AC AIR CONDITIONING LAB LABORATORY P2.0 PLUMBING WASTE & VENT
AND STATE CODES AND ORDINANCES, AND SHALL MEET ALL REQUIREMENTS OF ALL AUTHORITIES HAVING AFF ABOVE FINISHED FLOOR LBS POUNDS
JURISDICTION. P2.1 PLUMBING DOMESTIC WATER AND GAS
AG ABOVE GRADE LVL LEVEL
SECTION NUMBER P2.2 MECHANICAL ROOM PIPING DETAIL
3. DRAWINGS SHOWING THE LOCATIONS OF PLUMBING EQUIPMENT, PIPING, ETC. ARE DIAGRAMMATIC AND JOB DRAWING NUMBER AMP AMPERES LWT LEAVING WATER TEMPERATURE
CONDITIONS WILL NOT ALWAYS PERMIT THEIR INSTALLATION ON THE LOCATIONS SHOWN. THE PLUMBING P3.0 PLUMBING ISOMETRICS
ARCH ARCHITECTURAL MAX MAXIMUM
DRAWINGS SHOW THE GENERAL ARRANGEMENTS OF EQUIPMENT, PIPING, ETC. AND SHALL BE FOLLOWED
AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHER TRADES WILL PERMIT. THE BFF BELOW FINISHED FLOOR MBH THOUSAND BTU PER HOUR
ARCHITECTURAL DRAWINGS SHALL BE PART OF THE WORK INSOFAR AS THESE DRAWINGS FURNISH THE BG BELOW GRADE MIN MINIMUM
CONTRACTOR WITH INFORMATION RELATING TO DESIGN AND CONSTRUCTION OF THE BUILDING. BHP BRAKE HORSEPOWER MISC MISCELLANEOUS
BLDG BUILDING N/A NOT APPLICABLE
4. FURNISH AND INSTALL ANY INCIDENTAL WORK NOT SHOWN OR SPECIFIED WHICH ARE NECESSARY TO
PROVIDE A COMPLETE AND WORKABLE SYSTEM. BOF BOTTOM OF FOOTING NC NORMALLY CLOSED
BTU BRITISH THERMAL UNIT NIC NOT IN CONTRACT
5. PRIOR TO SUBMISSION OF BID, REVIEW FULL SET OF NEW CONSTRUCTION DRAWINGS (INCLUDING ALL
BTUH BRITISH THERMAL UNIT PER HOUR NIPW NOT IN PLUMBING WORK
OTHER TRADES). INCLUDE ANY ADDITIONAL PIPE OFF-SETS THAT ARE NOT CURRENTLY SHOWN ON
DRAWINGS BUT MAY BE REQUIRED TO CLEAR STRUCTURE, FINISHES OR WORK OF OTHER TRADES. NO CFH CUBIC FEET PER HOUR NO NORMALLY OPEN

BARKLEY AVENUE, WALNUT CREEK, CA 94597


EXTRA PAYMENT WILL BE ALLOWED FOR WORK RESULTING FROM LACK OF PROPER INITIAL APPRAISAL OF CLG CEILING NTS NOT TO SCALE
ENTIRE SCOPE OF WORK. SUBMIT REQUESTS FOR INFORMATION (RFIs) AS REQUIRED TO ANSWER ANY
QUESTIONS THAT MAY ARISE DURING BIDDING PHASE. CLEARLY INDICATE SCOPE INCLUSION AND CONC CONCRETE OC ON CENTER
EXCLUSION IN BID. COTG CLEAN OUT TO GRADE OD OUTSIDE DIAMETER
DIA DIAMETER PD PRESSURE DROP
6. FOR PLUMBING PIPING PENETRATING THRU, UNDER AND PARALLEL TO WOOD JOISTS, WOOD BEAMS AND
(E) EXISTING POC POINT OF CONNECTION
FOOTINGS, SEE STRUCTURAL DETAILS. PIPE INSTALLATION OTHER THAN SHOWN ON STRUCTURAL DETAILS
SHALL BE APPROVED BY THE STRUCTURAL ENGINEER. EA EACH PSI POUNDS PER SQUARE INCH
EFF EFFICIENCY PSIG POUNDS PER SQUARE INCH GAUGE

PLEASANT CREEK HOMES


7. FOR EXACT LOCATIONS OF PLUMBING FIXTURES, SEE ARCHITECTURAL DRAWINGS.
ELEC ELECTRICAL SL SLOPE
8. FOR EXACT LOCATIONS OF ROOF DRAINS SEE ARCHITECTURAL DRAWINGS AND DETAILS. EWT ENTERING WATER TEMPERATURE SP STATIC PRESSURE
FD FLOOR DRAIN SPECS SPECIFICATIONS
9. COORDINATE WITH CIVIL DRAWINGS FOR SITE CONNECTIONS TO THE COLD WATER, GAS, SANITARY SEWER
AND STORM DRAIN STUBOUTS. FT FOOT OR FEET STD STANDARD
FU FIXTURE UNIT STOR STORAGE
10. PROVIDE CLEANOUTS ON DRAINAGE LINES IN ACCORDANCE WITH THE CALIFORNIA PLUMBING CODE AND AS GA GAUGE STRUCT STRUCTURAL
INDICATED ON THE DRAWINGS.
GAL GALLON TEMP TEMPERATURE
11. ALL SANITARY SEWER PIPING SHALL BE SLOPED AT 1/4" PER FOOT UNLESS NOTED OTHERWISE. GALV GALVANIZED TYP TYPICAL
GPH GALLONS PER HOUR UF UNDERFLOOR
12. ALL PLUMBING DRAINAGE AND SANITARY VENT TERMINATIONS SHALL TERMINATE IN ACCORDANCE WITH
THE CALIFORNIA PLUMBING CODE. GPM GALLONS PER MINUTE UG UNDERGROUND
HD HEAD UON UNLESS OTHERWISE NOTED
13. ALL PLUMBING EQUIPMENT SHALL BE SECURELY FASTENED TO THE BUILDING STRUCTURES. HP HORSEPOWER V VENT OR VOLTS
14. WHERE MAIN PIPE SIZE IS NOT INDICATED BETWEEN BRANCH CONNECTIONS ON THE DRAWING, THE PIPE HVAC HEATING, VENT & AIR CONDITIONING VR VENT RISER
SIZE SHALL BE OF THE LARGER PRECEDING PIPE SIZE. ID INSIDE DIAMETER VTR VENT THROUGH ROOF
IE INVERT ELEVATION W WATTS
15. ALL VALVES AND ACCESSORIES SHALL BE FULL LINE SIZE. PROVIDE ALL NECESSARY UNIONS, REDUCERS
IN INCH WT WEIGHT
AND STOPS AS REQUIRED WHEN CONNECTING TO EACH FIXTURE AND/OR EQUIPMENT.

16. KEEP ALL PLUMBING PIPING AS HIGH AS POSSIBLE TO THE STRUCTURE ABOVE AND OFFSET PIPING AS NOTE: NOT ALL SYMBOLS OR ABBREVIATIONS APPLY NOTE: NOT ALL SYMBOLS OR ABBREVIATIONS APPLY
REQUIRED.

17. CLOSELY COORDINATE WORK WITH ALL TRADES.

18. CHANGES IN THE DIRECTION OF DRAINAGE FLOW SHALL BE PER CALIFORNIA PLUMBING CODE.

19. ALL SANITARY VENTS SHALL TERMINATE AT LEAST 6" ABOVE ROOF AND AT LEAST 12" FROM ANY VERTICAL
SURFACE. PROVIDE MINIMUM 10' CLEARANCE FROM VENT TERMINATIONS TO OUTSIDE AIR INLETS OR
OPENINGS IN THE BUILDING.

20. ALL PIPING PENETRATION THROUGH RATED WALLS AND FLOORS SHALL BE SEALED WITH UL-LISTED AND
CALIFORNIA FIRE MARSHAL LISTED SEALANTS. SEE ARCHITECTURAL DRAWINGS FOR ALL LOCATIONS.

21. PROVIDE DIELECTRIC INSULATING CONNECTIONS BETWEEN ALL DISSIMILAR METALS.

22. HOT AND COLD WATER PIPING SHALL BE COPPER TYPE K OR L.

23. SANITARY SEWER AND VENT PIPING SHALL BE ABS, COPPER OR CAST IRON.

24. CONDENSATE DRAIN SHALL BE AS SANITARY SEWER OR COPPER TYPE M.

25. NATURAL GAS PIPING ABOVE GROUND SHALL BE SCHEDULE 40 BLACK STEEL.
2-WAY COTG
(IE=18" BFF)

HB-1

1" CW 1/2" CW

G G

BARKLEY AVENUE, WALNUT CREEK, CA 94597


G
G
3/4" HW 1-1/4" G
1-1/4" G
1/2" CW

PLEASANT CREEK HOMES


2" SS AB.C
IWH-1

WB-1 3/4" G
3" SS 3/4" HW

3/4" HW 3/4" CW 3" SS

2" VTR 3/4" CW 2" VTR KS-1 3/4" CW


3" SS
1" CW 3/4" HW
3/4" HW
L-1
WCO (TYP)
L-1 T-1 3/4" CW
BT-1
2" VTR
2" VTR
T-1
HB-1 3"

3"

2-BEDROOM ROOF PLAN 2-BEDROOM SECOND FLOOR PLAN 2-BEDROOM FIRST FLOOR PLAN

GENERAL NOTES REFERENCE SHEET NOTES


IWH-1
FURNACE (60 MBH) SS LINES TO BE SLOPED TO AT LEAST 1.4" PER FOOT. PLUMBING LINES UNDER WINDOW.
(199 MBH) 4F
T T
2F COORDINATE LOCATION (AND SLOPE IF REQUIRED) OF ALL PIPE ABOVE FIRST FLOOR CEILING PLUMBING LINES UNDER COUNTER.
WITH STRUCTURAL REQUIREMENTS OF FLOOR FRAMING.
SS DROP BETWEEN 1ST AND 2ND FLOOR.
9 FT

2" VENT RISER BETWEEN 1ST AND 2ND FLOOR.


3F
T
1" CW RISER BETWEEN 1ST AND 2ND FLOOR.

CLOTHES DRYER (35 MBH) 3/4 HW RISER BETWEEN 1ST AND 2ND FLOOR.
FT G
47 FURNACE IN ATTIC. REFER TO MECHANICAL PLANS.

3/4" SS RISER UP TO ATTIC. PROVIDE AIR GAP FITTING (MIN 1" CLEARANCE) FOR CONNECTION
G TO CONDENSATE DRAIN.

1-1/4" G RISER BETWEEN 1ST AND 2ND FLOOR.


G
PROVIDE HW AND SS CONNECTION FROM KS-1 TO DISHWASHER WITH AIR GAP FITTING.

CLOTHES WASHER/DRYER PROVIDED BY OCCUPANT.

LOCATE VTR MINIMUM 10 FEET FROM OPENING INTO THE BUILIDING.

NATURAL GAS METER RECESSED IN WALL. COORDINATE EXACT LOCATION WITH PG&E.

REFER TO CIVIL DRAWINGS FOR CONTINUATION.


G

PROVIDE DIRT LEG WITH REMOVABLE CAP AT NATURAL GAS CONNECTIONS TO EQUIPMENT.

METER

2-BEDROOM GAS ISOMETRIC PLAN


2-WAY COTG
(IE=15" BFF)

3"SS

1"CW
HB-1

BARKLEY AVENUE, WALNUT CREEK, CA 94597


1-1/4" G

G G

PLEASANT CREEK HOMES


1/2" G 3/4" G
3/4" CD

G
2" SS AB.C

1-1/4" G

G
WB-1

3/4"HW

G
2" VTR

WCO (TYP)
L-1 1"CW 1"HW
KS-1

G
3/4"CW 3/4"HW 3/4"CW
3/4"HW
L-1 T-1
2" VTR BT-1
2" VTR 3/4"CW T-1 3/4"CW 3"SS 1"CW IWH-2

3"SS
2" VTR COTG
HB-1

3-BEDROOM ROOF PLAN 3-BEDROOM SECOND FLOOR PLAN 3-BEDROOM FIRST FLOOR PLAN

GENERAL NOTES REFERENCE SHEET NOTES


FURNACE
(60 MBH) FT SS LINES TO BE SLOPED TO AT LEAST 1.4" PER FOOT. PLUMBING LINES UNDER WINDOW.
2 F T
15 36 G
FT IWH-2 COORDINATE LOCATION (AND SLOPE IF REQUIRED) OF ALL PIPE ABOVE FIRST FLOOR CEILING 3" SS DROP BETWEEN 1ST AND 2ND FLOOR.
(199 MBH) WITH STRUCTURAL REQUIREMENTS OF FLOOR FRAMING.
CLOTHES 2" VENT RISER BETWEEN 1ST AND 2ND FLOOR.
DRYER
(35 MBH) 3/4" CW RISER BETWEEN 1ST AND 2ND FLOOR.
G

3/4 HW RISER BETWEEN 1ST AND 2ND FLOOR.


18 FT

FURNACE IN ATTIC. REFER TO MECHANICAL PLANS.

3/4" SS RISER UP TO ATTIC. PROVIDE AIR GAP FITTING (MIN 1" CLEARANCE) FOR CONNECTION
TO CONDENSATE DRAIN.
FT
34 3/4" G RISER BETWEEN 1ST AND 2ND FLOOR.
G
PROVIDE HW AND SS CONNECTION FROM KS-1 TO DISHWASHER WITH AIR GAP FITTING.

CLOTHES WASHER/DRYER PROVIDED BY OCCUPANT.

LOCATE VTR MINIMUM 10 FEET FROM OPENING INTO THE BUILIDING.

LOCATE CW, HW AND G SHUTOFF VALVES FOR WATER HEATER IN CABINET.

NATURAL GAS METER. COORDINATE EXACT LOCATION WITH PG&E.

REFER TO CIVIL DRAWINGS FOR CONTINUATION.


METER
PROVIDE DIRT LEG WITH REMOVABLE CAP AT NATURAL GAS CONNECTIONS TO EQUIPMENT.

COORDINATE LOCATION AND SLOPE OF SS PIPE BELOW FLOOR WITH STRUCTURAL


REQUIREMENTS OF FLOOR FRAMING.

3-BEDROOM GAS ISOMETRIC PLAN


2-WAY COTG
(IE=15" BFF)

HB-1

G G

3"SS

BARKLEY AVENUE, WALNUT CREEK, CA 94597


1-1/4" G AB.C

1" CW AB.C

PLEASANT CREEK HOMES


3/4" SS AB.C
3/4" G
3/4" CD AB.C

G
1-1/4" G AB.C

G
G
1"CW AB.C
WB-1 3/4" CW AB.C KS-1
3/4" CW
3/4"HW AB.C
2" VTR 1""HW AB.C 1" HW 3/4"HW AB.C
2" SS BT-1 1"CW AB.C
BT-1
3/4"CW WCO (TYP)
AB.C T-1
2" VTR
2" VTR 2" VTR T-1 L-1 3" SS
L-1 G

1/2" G 2"SS
AB.C IWH-2 1-1/4" G AB.C
HB-1

3"SS
COTG (TYP)

4-BEDROOM ROOF PLAN 4-BEDROOM SECOND FLOOR PLAN 4-BEDROOM FIRST FLOOR PLAN

GENERAL NOTES REFERENCE SHEET NOTES


FURNACE
(80 MBH)
SS LINES TO BE SLOPED TO AT LEAST 1.4" PER FOOT. PLUMBING LINES UNDER WINDOW.

COORDINATE LOCATION (AND SLOPE IF REQUIRED) OF ALL PIPE ABOVE FIRST FLOOR CEILING 3" SS DROP BETWEEN 1ST AND 2ND FLOOR.
WITH STRUCTURAL REQUIREMENTS OF FLOOR FRAMING.
T
8F 2" VENT RISER BETWEEN 1ST AND 2ND FLOOR.
G
IWH-2 3/4" CW RISER BETWEEN 1ST AND 2ND FLOOR.
G

G (199 MBH)
16 FT

3/4" HW RISER BETWEEN 1ST AND 2ND FLOOR.


FT G 18
29 FT
FURNACE IN ATTIC. REFER TO MECHANICAL PLANS.

G CLOTHES 3/4" SS RISER UP TO ATTIC. PROVIDE AIR GAP FITTING (MIN 1" CLEARANCE) FOR CONNECTION
FT DRYER TO CONDENSATE DRAIN.
43 G (35 MBH)
3/4" G RISER BETWEEN 1ST AND 2ND FLOOR.

PROVIDE HW AND SS CONNECTION FROM KS-1 TO DISHWASHER.


G
CLOTHES WASHER/DRYER PROVIDED BY OCCUPANT.

LOCATE VTR MINIMUM 10 FEET FROM OPENING INTO THE BUILIDING.

LOCATE CW, HW AND G SHUTOFF VALVES FOR WATER HEATER IN CABINET.

NATURAL GAS METER. COORDINATE EXACT LOCATION WITH PG&E.

REFER TO CIVIL DRAWINGS FOR CONTINUATION.

METER PROVIDE DIRT LEG WITH REMOVABLE CAP AT NATURAL GAS CONNECTIONS TO EQUIPMENT.

4-BEDROOM GAS ISOMETRIC PLAN


GENERAL SHEET NOTES REFERENCE SHEET NOTES
REFER TO FLOOR PLAN FOR SIZES. PLUMBING LINES UNDER WINDOW.

PLUMBING LINES UNDER COUNTER.

SS DROP BETWEEN 1ST AND 2ND FLOOR.

VENT RISER BETWEEN 1ST AND 2ND FLOOR.

VTR VTR VTR 3/4" SS FOR FURNACE IN ATTIC SPACE.

WALL CLEANOUT.

LOCATE VTR MINIMUM 10 FEET FROM OPENING INTO THE BUILIDING.

2" SS BFF.

VTR VTR
VTR CW RISER BETWEEN 1ST AND 2ND FLOOR.
BT-1
HW RISER BETWEEN 1ST AND 2ND FLOOR.

T-1 BT-1 PROVIDE HW AND SS CONNECTION FROM KS-1 TO DISHWASHER.


T-1
KS-1

BARKLEY AVENUE, WALNUT CREEK, CA 94597


BT-1

L-1 L-1
T-1

KS-1 WB-1 COTG WB-1

L-1

PLEASANT CREEK HOMES


KS-1 T-1
WB-1 T-1
T-1 L-1
2-WAY
COTG 2-WAY
L-1 COTG
2-WAY L-1
COTG
SS OUT THE BUILDING BT-1 SS OUT THE BUILDING

SS OUT THE BUILDING

SANITARY WASTE & VENT ISOMETRIC 4-BEDROOM SANITARY WASTE & VENT ISOMETRIC 3-BEDROOM SANITARY WASTE & VENT ISOMETRIC 2-BEDROOM

IWH-1
BT-1

WB-1
T-1
BT-1

KS-1 T-1 L-1

IWH-2

IWH-2 L-1
WB-1 L-1
KS-1 T-1 BT-1

HB-1
HB-1

T-1
WB-1 T-1
KS-1
HB-1
L-1

L-1
CW LINE INTO BUILDING L-1
BT-1

HB-1
HB-1
CW LINE INTO BUILDING

HB-1
CW LINE INTO BUILDING

T-1

COLD & HOT WATER ISOMETRIC 4-BEDROOM COLD & HOT WATER ISOMETRIC 3-BEDROOM COLD & HOT WATER ISOMETRIC 2-BEDROOM