Table of Contents
Introduction
INTRODUCTION
How to Use This Catalog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
The Purpose of Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
GROUNDING ROADMAPS
Common Bonding Network (CBN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Service Entrance Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Data Center Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Grounding
Data Center Rack Grounding (Raised Floor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Roadmaps
Telecommunications Room Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Telecommunications Room Rack Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
CRIMPING TOOLS
Hand Operated Plier Type Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .24
CONTOUR CRIMP ™ Controlled Cycle Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .24
Die Type, Manual Hydraulic, 14 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .25
Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .26
Technical
CD-920 Crimping Dies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .27 Information
TECHNICAL INFORMATION
® ™
PANDUIT STRUCTUREDGROUND System for Data Center Grounding Application Standards . . . . . . . . . . . . . . .28
Specification Layout for Data Center Grounding per BICSI TDM Manual, 10th Edition . . . . . . . . . . . . . . . . . . . .29
Recommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE)
per J-STD-607-A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Recommended Cable Sizes for Grounding Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Key Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Index
INDEX
Part Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Related Catalogs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
1
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Telecommunications
Room
(see roadmap on page 8)
Grounding
Roadmaps
Equipment
& Rack
Grounding
Kits
Data Center
Grounding (see roadmap on page 6)
Roadmaps Common
Bonding
Network
(CBN)
Components
Crimping
Tools
Service Entrance
(see roadmap on page 5)
Technical
Information
Index
See page 28 for PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding Application Standards.
For more data center grounding information, see www.panduit.com/dcgrounding.
Equipment 4
& Rack
Grounding
Kits Grounding Roadmaps S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
Introduction Introduction
metallic components and the grounded rack
• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet members Back of Rack Shown
to the rack grounding strip Paint Piercing Grounding
Washer Kit: RGW
Back of Racks Shown (see page 13)
5
3 Equipment Jumper Kit 24" L, 90° Bent: RGEJ
(see page 12)
1
Equipment Electrostatic Discharge (ESD) Equipment
& Rack 3 Port Kit recommended for & Rack
Grounding use on front and back of rack: Grounding
Kits Kits
RGESD (see page 13)
AC Panel* 1
Common Telecommunications
Bonding Backbone
(TBB)
Bonding Common
Bonding
Network
Conduit
Rack Grounding Strip Kit: RGS
(see page 11) Common
Bonding
Network
Network (CBN)
Components
Building Steel 2
(CBN)
Components
(CBN)
Components Crimping
Tools
Common Bonding Network (CBN)
Equipment Jumper Kit 36" L, 90° Bent: RGEJ
(see page 12)
Crimping
Tools
6 For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) 7
Crimping
Tools
Detailed Product S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING Detailed Tool S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Information Code/Flex Conductor HTAP Information Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool
• Two stage rapid advance hydraulic system minimizes • Tool provided with two, high capacity 12 VDC rechargeable
Introduction For Making Parallel and Multiple Tap Connections on Code and Flex Conductors Introduction
Technical Equipment
& Rack
Grounding
W
RUN
W L
RUN
W L
Equipment
& Rack
Grounding
Information
W RUN L
Kits RUN L Kits
Std.
H
Pkg.
H H H Part Number Part Description Qty.
CT-2931 Terminates PANDUIT ® PAN-LUG ™ Compression Connectors: 1
TAP 1 TAP 2
TAP 3 • Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor
TAP 1 TAP 1 TAP 2 TAP 1 • Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor
Common Common
Bonding HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250 Bonding • Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor
Network Network • Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor
(CBN) (CBN) • Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor
Components Figure Components • Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor
Copper Conductor Size Range Dimensions (In.) Wire • Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor
Wire PANDUIT PANDUIT Strip Std. • PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor
Strand Crimping Die Color Length Pkg.
Part Number Type Run Tap 1 Tap 2 Tap 3 L W H Tool & Die No. (In.) Qty. Warranty: 3 years
HTCT6-6-1 #6 - #10 #6 - #14 .61 .40 .99 CT-930, CT-2931 Orange, 11/16 1
Code AWG AWG PH6 CT-2931 includes:
— — • Tool
#6 - #10 #6 - #14 • Two 12 VDC, rechargeable NiMH batteries
Crimping Flex AWG AWG Crimping • One battery charger
Tools Tools • Steel tool case with storage for batteries, charger and crimp dies
HTCT2-2-1 #2 - #6 #2 - #6 AWG #8 - #14 #8 - #14 .76 .61 1.55 CT-930, CT-2931 Brown, 13/16 1
Code AWG STR/SOL AWG AWG PH2
STR/SOL For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.
#2 - #8 #2 - #8 AWG #8 - #14 #8 - #14 *Makita is a registered trademark of Makita Corporation in the United States.
Flex AWG AWG AWG
HTCT250-2-1 250 kcmil - #2 - #6 AWG #8 - #14 .92 .96 1.92 CT-930, CT-2931 Purple, 1 1
Code #2 AWG STR/SOL AWG PH25
—
4/0 - #2 #2 - #8 AWG #8 - #14
Flex AWG AWG
Technical Technical
Information HTCT250-250-1 250 kcmil - 250 kcmil - .90 .89 1.92 CT-930, CT-2931 Purple, 1 1 Information
Code #2 AWG #2 AWG PH25
— —
4/0 - #2 4/0 - #2
Flex AWG AWG
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
Index Index
Index 20 26
Technical Information — Includes Application Standards and BICSI TDM Manual, 10th Edition
pages 28-30
2
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
to handle expected currents safely, and one that directs these potentially damaging currents away
from sensitive communication equipment. Any metallic component that is part of the data center
infrastructure (such as equipment, racks, ladder racks, enclosures, cable trays, etc.) must be bonded
to the grounding system.
What are the effects of improper grounding? Equipment
& Rack
Decreased Efficiency Grounding
• Electrical noise is introduced on data cables when surges are not properly dissipated by the grounding system.They cause Kits
faulty data signals and dropped packets, thus decreasing the throughput and overall efficiency of your network.
Lower Reliability
• According to insurance industry data, improper grounding of communication systems leads to $500 million per year of
damage to property and/or equipment due to lightning. (1)
Common
• The Information Technology Industry Council states that grounding is the single-most important factor in reliable network Bonding
Network
equipment performance. (2) (CBN)
• More than 90% of problems in data communications equipment, including reboot, lockup, and data corruption, are Components
traced to problems with grounding. (3)
• Industry experts estimate that 27%-33% of damaged equipment in a user's facility is caused by electrostatic discharge.
The component cost of repairing damaged equipment is substantial for complex circuit boards, especially when labor
and downtime are considered. (4)
• According to the IEEE, the typical AC third prong ground is almost never sufficient to prevent damage to network equipment. (5)
Crimping
Safety Risks Tools
• Personal injury from electric shock caused by improper grounding can cause immeasurable human suffering and
significant expense.
• Potential fire hazards exist when heat is generated from electrical surges that find a high resistance path to ground.
Clearly the biggest cost of improper grounding is the inability to service customers properly.
PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding gives you what you need to properly protect
your investment.
1. Mike Holt, "Prevent Shocks in Your Communications: Understanding How the NEC Relies on Ground Resistance Theory Leads to a
Successful Application of Communications Grounding," Electrical Construction & Maintenance, September 2002.
2. Information Technology Industry Council (ITI, formerly CBEMA), Guidelines for Grounding Information Technology Equipment. Information
Letter, ITI, 15 February 1997. Index
3. Donald G. Pennington and Paul Holzer, "Doing Battle with Those Ground Transients," Electronic Engineering Times, 8 January 1996.
4. ESDA, "Fundamentals of ESD: Part 1 — An Introduction to ESD," 2001, <http://www.esda.org/basics/part1.cfm> (1 October 2004).
5. Institute of Electrical and Electronics Engineers, Inc., IEEE Recommended Practice for Powering and Grounding Electronic Equipment, IEEE
Std 1100-1999, 1999.
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 3
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Common Bonding Network (CBN)
• PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding is a complete, highly reliable line of products to ground
your building and network equipment in compliance with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942,
IEEE Std 1100 (IEEE Emerald Book), UL and CSA
Introduction
Telecommunications
Room
(see roadmap on page 8)
Grounding
Roadmaps
Equipment
& Rack
Grounding
Kits
Data Center
(see roadmap on page 6)
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
Service Entrance
(see roadmap on page 5)
Technical
Information
Index
See page 28 for PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding Application Standards.
For more data center grounding information, see www.panduit.com/dcgrounding.
4
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
Telecommunications Bonding
Backbone (TBB)**
2 2
Conduit
Grounding Equalizer (GE)
3
Grounding
1 Roadmaps
5
6
Earth Ground
3
7
Equipment
& Rack
Grounding
Kits
3
AC Panel*
4 Water Meter
4
Crimping
Tools
Copper Compression HTAP and Bronze, Grounding Rod Clamp: WB
1 Clear Cover: HTWC 5 (see page 23) connected by a cable to
(see page 19) 2 (U-Bolt Grounding Clamp)
*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.
**Specification J-STD-607-A specifies different size conductors based on the length of the Telecommunications Bonding Backbone (TBB). See page 30 for
Recommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE) Per J-STD-607-A.
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 5
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Data Center Grounding Roadmap
• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), UL
and CSA
• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity between
Introduction
metallic components and the grounded rack
• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet members
to the rack grounding strip
Back of Racks Shown
4
Grounding
Roadmaps
5
3
1
Equipment
& Rack 3
Grounding
Kits
AC Panel* 1
Telecommunications
Bonding Backbone
(TBB)
Common
Bonding
Network
Conduit
(CBN)
Components
Building Steel 2
6
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
Introduction
Technical
Information
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 7
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Telecommunications Room Grounding Roadmap
• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), UL
and CSA
• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity between
Introduction
metallic components and the grounded rack
• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet members
to the rack grounding strip
Back of Racks Shown
Grounding Equalizer (GE)
Grounding
Roadmaps
Conduit
5 1
3
4
Equipment
& Rack
Grounding
Kits
3
1
3 1
AC Panel*
Common
Bonding
Network Telecommunications
(CBN) Bonding Backbone
Components
(TBB)
Building Steel
Crimping
Tools
*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.
A typical overhead cabling system includes a multitude of metallic components which are connected together. It is the responsibility of the installer to insure all
of the metallic components are bonded, which means that they are connected together electrically in accordance with applicable specifications. The PANDUIT
Bonding/Grounding System does not insure required bonding of the overhead cabling system metallic components.
8
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
Introduction
Crimping
Tools
Technical
Equipment Jumper Kit 24" L, 45° Bent: RGEJ Information
(see page 12)
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 9
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Features and Benefits — PANDUIT ® STRUCTUREDGROUND ™ System for Data
Center Grounding
PANDUIT offers a variety of kits with premium components to ensure superior grounding with the highest reliability available.
Introduction • Provides highest reliability with an all-copper rack • Incorporates a flexible design that can be used with
grounding system to maintain data center system racks which meet EIA-310-D
performance and protect network equipment • Offers ease of installation — no paint scraping required to
• Complies with data center standard TIA-942 and is UL bond racks; factory terminated jumpers simply
Listed and CSA Certified bolt in place
C
Rack A
Paint Piercing Grounding Washer is Grounding
made from hardened steel and electro zinc Strip Kit
Common
C plated which inhibits corrosion to provide a (see page 11)
Bonding superior bond between frame members on
Network bolt-together racks
(CBN)
Components
Thread-Forming Screws are made from
D electro zinc plated steel and provide a bond to
the rack by removing paint from threaded
holes without creating metal shavings
B
Index C
G
Common Bonding Network (CBN)
to Rack Jumper Kit (see page 11)
10
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
Std.
Pkg.
Part Number Part Description Qty.
RGS134-1 Rack grounding strip; 78.65" length; .67" width; .05" thickness; 1 Grounding
provided with .16 oz (5cc) of antioxidant and three #12-24 x 1/2" Roadmaps
thread-forming screws*
RGS134-10-1 10 rack grounding strips; 78.65" length; .67" width; .05" thickness; 1
provided with .16 oz (5cc) of antioxidant and 30 #12-24 x 1/2"
thread-forming screws*
*An equal number of M6 x 12mm thread-forming screws also provided in each kit.
Equipment
& Rack
Grounding
Kits
Std. Std.
Pkg. Ctn.
Part Number Part Description Qty. Qty.
RGCBNJ660P #6 AWG jumper; 60" length; 45° bent lug on grounding strip side; 1 10
provided with .16 oz (5cc) of antioxidant, two #12-24 x 1/2" Crimping
thread-forming screws* and a copper compression HTAP** for Tools
connecting to the CBN in sizes ranging from #2 AWG to 250 kcmil
*An equal number of M6 x 12mm thread-forming screws also provided in each kit.
**HTAP also sold separately, see page 20.
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 11
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
3" or smaller
3" or larger
Select 24" equipment jumpers with 90° Select equipment jumpers with 45° lugs
lugs when equipment grounding connection for lower density applications or shallow
Index is close to the grounding strip. depth equipment to provide improved cable
management.
Select 36" equipment jumpers with 90° lugs
when equipment grounding connection is on
the opposite side from the grounding strip.
12
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Std.
Pkg.
Part Number Part Description Qty.
RGW-12-1 12 paint piercing bonding washers for 3/8" stud size; .875 O.D.; provided 1
with .16 oz (5cc) of antioxidant; for use with standard equipment racks:
CMR19X84, CMR19X84S and CMR23X84
RGW-32-1 32 paint piercing bonding washers for 3/8" stud size; .875 O.D.; provided 1
with .16 oz (5cc) of antioxidant; for use with 4 post rack NF4PR84 and Grounding
data rack DR84 Roadmaps
RGW-100-1 100 paint piercing bonding washers for 3/8" stud size; .875 O.D.; provided 1
with .16 oz (5cc) of antioxidant
Equipment
& Rack
Electrostatic Discharge (ESD) Port Kit Grounding
Kits
• Accommodates standard ESD wrist strap 4mm plug • Bent 45°, acts as a hook to hold wrist strap
• Can be mounted to front or back of rack for • Barrel permanently marked with the protective earth
convenient access (ground) symbol
Std.
Pkg.
Part Number Part Description Qty. Common
RGESD-1 ESD port kit; provided with an ESD protection sticker, .16 oz (5cc) of 1 Bonding
antioxidant and one #12-24 x 1/2" thread-forming screw* Network
(CBN)
Contact your local electrical distributor for their selection of Electrostatic Discharge (ESD) wrist straps. Components
*One M6 x 12mm thread-forming screw also provided in each kit.
ESD port must be attached to a grounded member.
Crimping
Tools
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 13
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Grounding
Roadmaps
RGRKCBNJEJ RGRKCBNJ
Thread-Forming Screws
Crimping
Tools • Thread-forming, provides a bond to the rack by removing • Easily installed with 5/16" socket head wrench or flat
paint from threaded holes without creating metal shavings blade screwdriver
Std.
Pkg.
Part Number Part Description Qty.
RGTS-C Thread-forming grounding screw, #12-24 x 1/2" 100
RGTSM6-C Thread-forming grounding screw, M6 x 12mm 100
Technical
Information
Bonding Screws
• Creates an electrical bond between painted patch panels • Thread-forming, provides a bond to the rack by removing
and racks paint from threaded holes without creating metal shavings
• Serrations on bottom of screw remove paint from patch • Easily installed with Phillips screwdriver
panel, thus providing metal-to-metal contact
Std.
Pkg.
Index Part Number Part Description Qty.
RGTBS-C Thread-forming bonding screw, #12-24 x 1/2" 100
RGTBSM6-C Thread-forming bonding screw, M6 x 15mm 100
14
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
• Meets BICSI and J-STD-607-A requirements for network • Comes pre-assembled with brackets and insulators
systems grounding applications attached for quick installation
• Made of high conductivity copper and tin plated to • Use PANDUIT self-laminating laser/ink jet labels to identify
inhibit corrosion busbars to meet TIA/EIA-606-A
Common
Bonding
C200X100FJJ Network
(CBN)
Components
Std.
Pkg.
Part Number Part Description Qty.
LTYK Label kit includes printed tag and one flame retardant cable tie 10 Technical
Information
For additional label sizes, materials and print technologies and to see the complete line of PANDUIT identification
products, see the Identification Solutions Catalog SA-IDCB16.
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 15
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Common
Bonding
Network
(CBN)
Components
Index
16
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Grounding
Roadmaps
L
Figure 1 Figure 2: Slotted Lug Figure 3: Slotted Lug Figure 4: Slotted Lug
45°Bent 90°Bent
Stud Stud Wire
Figure
Copper Hole Hole PANDUIT PANDUIT Burndy T&B Strip Std.
Dimensions (In.)
Figure Conductor Size Spacing Crimping Die Color Die Die Length Pkg.
Part Number No. Size (In.) (In.) W B T L Tool & Die No. No. No. (In.) Qty.
LCC10-14JAW-L* 2 1/4 .50 – .63 .42 .53 .05 1.93 — — — 9/16 50 Equipment
#14 – #10 & Rack
LCC10-14JAWH-L* 3 AWG STR, 1/4 .50 – .63 .42 .53 .05 1.78 CT-100, — — — 9/16 50
Grounding
LCC10-14JAWF-L* 4 #12 – #10 1/4 .50 – .63 .42 .53 .05 1.56 CT-1570 — — — 9/16 50 Kits
LCC10-14BW-L* 1 AWG SOL 1/4 .75 .42 .53 .05 2.06 — — — 9/16 50
LCC8-10ABW-L 2 #10 .63 – .75 .41 .70 .08 2.14 Red P21 49 21 3/4 50
LCC8-14ABW-L 2 1/4 .63 – .75 .48 .70 .07 2.23 CT-1700, Red P21 49 21 3/4 50
#8 AWG CT-930,
LCC8-14DW-L 1 1/4 1.00 .48 .70 .07 2.48 Red P21 49 21 3/4 50
CT-2931
LCC8-38DW-L 1 3/8 1.00 .60 .70 .05 2.70 Red P21 49 21 3/4 50
LCC6-10ABW-L 2 #10 .63 – .75 .46 1.07 .08 2.52 Blue P24 7 24 1 1/8 50 Common
Bonding
LCC6-14JAW-L 2 1/4 .50 – .63 .48 1.07 .08 2.49 Blue P24 7 24 1 1/8 50 Network
LCC6-14JAWH-L (CBN)
3 1/4 .50 – .63 .48 1.07 .08 2.08 Blue P24 7 24 1 1/8 50
Components
LCC6-14JAWF-L 4 1/4 .50 – .63 .48 1.07 .08 1.66 CT-1700, Blue P24 7 24 1 1/8 50
#6 AWG CT-930,
LCC6-14BDW-L 2 1/4 .75 – 1.00 .48 1.07 .08 2.86 Blue P24 7 24 1 1/8 50
CT-2931
LCC6-14EW-L 1 1/4 1.25 .48 1.07 .08 3.11 Blue P24 7 24 1 1/8 50
LCC6-56BW-L 1 5/16 .75 .56 1.07 .07 2.73 Blue P24 7 24 1 1/8 50
LCC6-38BDW-L 2 3/8 .75 – 1.00 .62 1.07 .06 3.08 Blue P24 7 24 1 1/8 50
LCC4-14ADW-L 2 1/4 .63 – 1.00 .55 1.05 .09 2.63 CT-1700, Gray P29 8 29 1 1/8 50
#4 – #3 Crimping
CT-930,
LCC4-38DW-L 1 AWG STR 3/8 1.00 .62 1.05 .08 3.09 Gray P29 8 29 1 1/8 50 Tools
CT-2931
LCC2-14AW-Q 1 1/4 .63 .60 1.16 .10 2.67 CT-1700, Brown P33 10 33 1 1/4 25
#2 AWG CT-930,
LCC2-38DW-Q 1 3/8 1.00 .66 1.16 .10 3.24 Brown P33 10 33 1 1/4 25
CT-2931
LCC1-14AW-E 1 1/4 .63 .70 1.36 .11 2.89 CT-1700, Green P37 11 37 1 7/16 20
#1 AWG CT-930,
LCC1-38DW-E 1 3/8 1.00 .70 1.36 .11 3.46 Green P37 11 37 1 7/16 20
CT-2931
LCC1/0-14AW-X 1 1/4 .63 .76 1.44 .12 3.07 CT-930, Pink P42 12 42 1 1/2 10
1/0 AWG
LCC1/0-38DW-X 1 3/8 1.00 .76 1.44 .12 3.57 CT-2931 Pink P42 12 42 1 1/2 10 Technical
Information
LCC2/0-14AW-X 1 1/4 .63 .85 1.50 .13 3.23 CT-930, Black P45 13 45 1 9/16 10
2/0 AWG
LCC2/0-38DW-X 1 3/8 1.00 .85 1.50 .13 3.67 CT-2931 Black P45 13 45 1 9/16 10
LCC3/0-38DW-X 1 3/8 1.00 .96 1.50 .13 3.70 Orange P50 14 50 1 9/16 10
CT-930,
LCC3/0-12W-X 1 3/0 AWG 1/2 1.75 .96 1.50 .13 4.87 Orange P50 14 50 1 9/16 10
CT-2931
LCC4/0-14AW-X 1 1/4 .63 1.06 1.56 .14 3.35 CT-930, Purple P54 15 54 1 5/8 10
4/0 AWG
LCC4/0-38DW-X 1 3/8 1.00 1.06 1.56 .14 3.81 CT-2931 Purple P54 15 54 1 5/8 10
LCC250-38DW-X 1 3/8 1.00 1.17 1.61 .14 3.89 CT-930, Yellow P62 16 62 1 11/16 10
250 kcmil
LCC250-12DW-X 1 1/2 1.00 1.17 1.61 .14 4.12 CT-2931 Yellow P62 16 62 1 11/16 10 Index
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
*Not tested to NEBS Level 3 requirements.
**Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000V.
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 17
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
• Meets J-STD-607-A requirements for • Can be used with code conductor and
network systems grounding applications flex conductor class: G, H, I, K, M and
• Requires crimping tools and dies, see pages Locomotive
24, 25, 26 and 27 • Long barrel maximizes number of crimps
• UL Listed for use up to 35KV**, temperature and provides premium wire pull-out strength
rated 90°C and CSA Certified to 600V when and electrical performance
crimped with PANDUIT and specified • Inspection window to visually assure full
Grounding competitor crimping tools and dies conductor insertion
Roadmaps
• Color coded barrels marked with PANDUIT • Generously beveled wire entry prevents
and specified competitor die index numbers bent back strands when inserting conductor
for proper crimp die selection into barrel
• Tin plated to inhibit corrosion
• Available with NEMA hole sizes and spacing
W W
HOLE HOLE
SPACING SPACING
Equipment L
L
& Rack INSPECTION B
Grounding B
WINDOW
Kits INSPECTION T
WINDOW
Flex Figure
Conductor Stud Stud Dimensions Wire
Size Code Hole Hole (In.) PANDUIT PANDUIT Strip Std.
Common
Bonding Figure Class Conductor Size Spacing Crimping Die Color Length Pkg.
Network Part Number No. G, H, I, K, M Locomotive Size (In.) (In.) W B T L Tool & Die No. (In.) Qty.
(CBN) LCCX8-10AB-L 2 #10 .63 – .75 .41 .70 .08 2.14 Red P21 3/4 50
Components CT-1700, Red P21
LCCX8-14AB-L 2 1/4 .63 – .75 .48 .70 .07 2.23 3/4 50
#8 AWG #8 AWG #8 AWG CT-930,
LCCX8-14D-L 1 1/4 1.00 .48 .70 .07 2.48 Red P21 3/4 50
CT-2931
LCCX8-38D-L 1 3/8 1.00 .60 .70 .05 2.70 Red P21 3/4 50
LCCX6-10B-L 1 #10 .75 .46 1.07 .08 2.52 Blue P24 1 1/8 50
LCCX6-14AB-L 2 1/4 .63 – .75 .48 1.07 .08 2.61 CT-1700, Blue P24 1 1/8 50
LCCX6-14D-L 1 #6 AWG #6 AWG #6 AWG 1/4 1.00 .48 1.07 .08 2.86 CT-930, Blue P24 1 1/8 50
LCCX6-38AC-L 2 3/8 .63 – .88 .62 1.07 .06 2.96 CT-2931 Blue P24 1 1/8 50
Crimping LCCX6-38D-L 1 3/8 1.00 .62 1.07 .06 3.08 Blue P24 1 1/8 50
Tools
LCCX4-14AB-L 2 1/4 .63 – .75 .55 1.05 .09 2.63 CT-1700, Gray P29 1 1/8 50
#5, #4, #3 #4 – #3
LCCX4-38BD-L 2 #4 AWG CT-930, Gray P29 1 1/8
AWG AWG STR 3/8 .75 – 1.00 .62 1.05 .08 3.09 50
CT-2931
LCCX2-38D-E 1 #2 AWG #2 AWG #2 AWG 3/8 1.00 .70 1.36 .11 3.46 CT-1700, Brown 1 7/16 20
CT-930, P33
CT-2931
LCCX1-14A-X 1 1/4 .63 .76 1.44 .12 3.07 CT-930, Green P37 1 1/2 10
#1 AWG #1 AWG #1 AWG
LCCX1-38D-X 1 3/8 1.00 .76 1.44 .12 3.57 CT-2931 Green P37 1 1/2 10
Technical LCCX1/0-14A-X 1 1/4 .63 .85 1.50 .13 3.23 CT-930, Pink P42 1 9/16 10
Information 1/0 AWG 1/0 AWG 1/0 AWG CT-2931 Pink P42 1 9/16
LCCX1/0-38D-X 1 3/8 1.00 .85 1.50 .13 3.67 10
LCCX2/0-14A-X 1 1/4 .63 .96 1.50 .13 3.27 CT-930, Black P45 1 9/16 10
2/0 AWG 2/0 AWG 2/0 AWG
LCCX2/0-38D-X 1 3/8 1.00 .96 1.50 .13 3.70 CT-2931 Black P45 1 9/16 10
LCCX3/0-38D-X 1 3/0 AWG 3/0 AWG 3/0 AWG 3/8 1.00 1.06 1.56 .14 3.81 CT-930, Orange 1 5/8 10
CT-2931 P50
LCCX4/0-38D-X 1 4/0 AWG 4/0 AWG 4/0 AWG 3/8 1.00 1.19 2.24 .16 4.55 CT-930, Purple 2 5/16 10
CT-2931 P54
LCCX250-38D-X 1 250 kcmil 262.6 kcmil — 3/8 1.00 1.28 2.24 .17 4.59 CT-930, Yellow P62 2 5/16 10
CT-2931
Index For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
**Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000V.
18
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
Equipment
& Rack
Grounding
Kits
W L W L
W RUN
W RUN L RUN
RUN L
H H H
H
Common
TAP 2 Bonding
TAP 1
TAP 3 Network
TAP 1 TAP 1 TAP 2 TAP 1 (CBN)
Components
HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250
Catalog SA-TMCB02.
See pages 20 and 21 for more information on HTAPs and clear covers, including crimping tools.
Labels for clear covers are sold separately and are printed with the PANDUIT LS7 Printer. For information on the LS7 Printer and to see the complete line of
PANDUIT identification products, see the Identification Solutions Catalog SA-IDCB16.
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 19
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Equipment
& Rack W L W L
W RUN
Grounding RUN
W RUN L
Kits
RUN L
H H H
H
TAP 1 TAP 2
TAP 3
TAP 1 TAP 1 TAP 2 TAP 1
Common
Bonding HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250
Network
(CBN)
Components Figure
Copper Conductor Size Range Dimensions (In.) Wire
Wire PANDUIT PANDUIT Strip Std.
Strand Crimping Die Color Length Pkg.
Part Number Type Run Tap 1 Tap 2 Tap 3 L W H Tool & Die No. (In.) Qty.
HTCT6-6-1 #6 – #10 #6 – #14 .61 .40 .99 CT-930, CT-2931 Orange, 11/16 1
Code AWG AWG PH6
— —
#6 – #10 #6 – #14
Crimping Flex AWG AWG
Tools
HTCT2-2-1 #2 – #6 #2 – #6 AWG #8 – #14 #8 – #14 .76 .61 1.55 CT-930, CT-2931 Brown, 13/16 1
Code AWG STR/SOL AWG AWG PH2
STR/SOL
#2 – #8 #2 – #8 AWG #8 – #14 #8 – #14
Flex AWG AWG AWG
HTCT250-2-1 250 kcmil – #2 – #6 AWG #8 – #14 .92 .96 1.92 CT-930, CT-2931 Purple, 1 1
Code #2 AWG STR/SOL AWG PH25
—
4/0 – #2 #2 – #8 AWG #8 – #14
Flex AWG AWG
Technical
Information HTCT250-250-1 250 kcmil – 250 kcmil – .90 .89 1.92 CT-930, CT-2931 Purple, 1 1
Code #2 AWG #2 AWG PH25
— —
4/0 – #2 4/0 – #2
Flex AWG AWG
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
Index
20
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
• Made of high impact plastic to provide high impact strength • Incorporate molded in flash barriers which encompass the
and 360° inspections of crimped connection to assure the HTAP installation providing protection against electrical
crimp is complete and the correct die was used flash over
• Incorporate dual self-latching spring loaded latches and • UL 94 V-0 flame rating and oxygen index of 28 providing
supplied with two PANDUIT UL 94 V-0 cable ties — allow self-extinguishing, flame retardant properties
for easy snap-on assembly and ensure covers are secured • Part number, voltage rating, temperature rating and HTCT
• Low profile design minimizes space requirements part number molded into cover for easy identification
Grounding
• Each cover half supports installation information labels • Flexible fingers located at each end of cover prevent Roadmaps
inside plastic retainer strips to allow labels to be viewed foreign objects from entering cover and are made from
on either side of cover and to protect labels from ductile plastic material that allows easy installation and
being removed will not damage conductor insulation
H
Common
Bonding
Network
Shown Assembled (CBN)
Components
Crimping
Tools
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 21
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
C UL
R US Grounding Clamp, U-Bolt, Bronze
Introduction • Used to ground copper conductor parallel or at a right • Accommodates a wide range of pipe, tube, rod and
angle to a rod, tube or pipe conductor sizes — minimizes inventory
• Made from high strength, electrolytic cast bronze • UL Listed for grounding and bonding and suitable for direct
• High strength silicon bronze hardware provides long term burial in earth or concrete
reliable assembly
Grounding H
Roadmaps
W L
Common
Bonding
Network
(CBN)
Components
Crimping
Tools
Technical
Information
Index
22
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
L W
Equipment
& Rack
Grounding
Kits
Catalog SA-TMCB02.
Technical
Information
H
W L
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 23
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Crimping Tools
Introduction
Std.
Pkg.
Part Number Part Description Qty.
Grounding CT-100 Crimps most PANDUIT #26 – #10 AWG insulated and non-insulated 1
Roadmaps
terminals, disconnects and splices. Cuts #4, #6, #8 and #10 screw sizes.
Cuts and strips wire. Excellent all-around application tool of heat treated
finished steel with comfortable cushioned plastic grip handles.
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
Equipment
& Rack
Grounding
Kits
CONTOUR CRIMP ™ Controlled Cycle Tools
• Specifically designed for the installation of PAN-TERM ® • Superior crimp performance
terminals, disconnects and splices • Reliable — backed by a two year warranty
• Low handle effort — increases productivity
Common
Bonding Std.
Network
(CBN)
Pkg.
Components Part Number Part Description Qty.
CT-1550 Crimps most PAN-TERM ® #22 – #10 AWG nylon and vinyl insulated 1
terminals, splices and disconnects. The CT-1550 has the red/blue pocket
CT-1550 closest to the pivot which provides a reduced crimp effort for those who
make red/blue terminations.
CT-1570 Crimps most PAN-TERM ® #22 – #10 AWG and .5-6.0mm non-insulated 1
terminals and disconnects. Crimps PANDUIT #22 – #10 AWG and
.5-6.0mm non-insulated splices, and #10 AWG compression lugs.
Crimping CT-1700 Crimps PANDUIT #8 – #2 AWG non-insulated tubular terminals (S 1
Tools
series), #8 – #1 AWG copper lugs and splices, #6 – #4 AWG aluminum
CT-1570
lugs and splices and CTAPF copper taps for #14 – #3 AWG. Includes 5
position, color coded rotating die.
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
CT- 1700
Technical
Information
Index
24
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
Std.
Pkg.
Part Number Part Description Qty.
CT-930 Terminates PANDUIT ® PAN-LUG ™ Compression Connectors: 1 Equipment
& Rack
• Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor Grounding
• Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor Kits
• Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor
• Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor
• Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor
• Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor
• Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor
• PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor
Crimping
Tools
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 25
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Equipment
& Rack
Grounding
Kits
Std.
Pkg.
Part Number Part Description Qty.
CT-2931 Terminates PANDUIT ® PAN-LUG ™ Compression Connectors: 1
• Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor
Common • Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor
Bonding • Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor
Network • Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor
(CBN) • Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor
Components • Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor
• Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor
• PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor
Warranty: 3 years
CT-2931 includes:
• Tool
• Two 12 VDC, rechargeable NiMH batteries
Crimping • One battery charger
Tools • Steel tool case with storage for batteries, charger and crimp dies
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.
*Makita is a registered trademark of Makita Corporation.
Technical
Information
Index
26
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
Grounding
Roadmaps
Die Number
Used to Install PANDUIT Compression Lug & Splice Sizes Std. Equipment
Pkg. & Rack
Part Number Copper Code Conductor Size and Die Color & Die No. Qty. Grounding
Kits
CD-920-8 #8 AWG, Red P21 1
CD-920-6 #6 AWG, Blue P24 1
CD-920-4 #4 AWG, Gray P29 1
CD-920-2 #2 AWG, Brown P33 1
CD-920-1 #1 AWG, Green P37 1
CD-920
CD-920-1/0 1/0 AWG, Pink P42 1
Common
CD-920-2/0 2/0 AWG, Black P45 1 Bonding
CD-920-3/0 3/0 AWG, Orange P50 1 Network
(CBN)
CD-920-4/0 4/0 AWG, Purple P54 1 Components
CD-920-250 250 kcmil, Yellow P62 1
Technical
Information
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 27
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
The Telecommunications Industry Association is a leading U.S. TIA-942 states that electrical continuity is required throughout the
non-profit trade association serving the communications and rack materials. Adhering to these principles protects network
Equipment information technology industry. TIA represents providers of equipment and maintains system performance. PANDUIT ®
& Rack communications and information technology products and services STRUCTUREDGROUND ™ System for Data Center Grounding meets
Grounding for the global marketplace through its core competencies in TIA-942 requirements by incorporating an all-copper grounding path.
Kits standards development. Paint piercing grounding washers ensure metal to metal contact of
rack members and two-hole compression lugs for a permanent and
reliable connection.
The Institute of Electrical and Electronics IEEE Std 1100-1999 (IEEE Emerald Book) – IEEE
Engineers, Inc. (IEEE) Recommended Practice for Powering and Grounding
Electronic Equipment
Common The IEEE promotes the engineering process of creating,
Bonding developing, integrating, sharing, and applying knowledge about The main objective of the Emerald Book is to provide a consensus of
Network electro and information technologies and sciences for the benefit recommended practices to address electronic equipment
(CBN) of humanity and the profession. performance issues while maintaining a safe installation, as
Components specified in the National Electrical Code ® (NEC ®) (NFPA 70-1999)
and recognized testing laboratories' standards.
NEBS Level 3 Approval as Tested by Telcordia Technologies NEBS Level 3 Criteria is the minimum level of
environmental compatibility needed to provide maximum
Telcordia Technologies, formerly known as Bellcore, serves as the assurance of equipment operability within the network
testing agency for the Regional Bell Operating Companies. Network facility environment.
Equipment-Building Systems (NEBS) was developed by Bellcore
Crimping and is currently maintained by Telcordia Technologies. NEBS was The Level 3 Criteria is the highest assurance of product operability.
Tools developed to standardize requirements for Central Office Equipment Products that meet NEBS Level 3 Criteria are suited for equipment
and to develop criteria for personal safety, protection of property and applications which demand minimal service interruptions over the life
operational continuity. span of the equipment. PANDUIT is the first in the industry to have a
system of copper compression lugs and splices (#8 AWG – 1,000
kcmil) and crimping tools physically and rigorously tested by
Telcordia Technologies to meet NEBS Level 3 compliance.
28
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
Specification Layout for Data Center Grounding per BICSI TDM Manual,
10th Edition
Introduction
Roof
Red
iron
Backbone pathway
Suspended ceiling area
TR TR Grounding
GE GE Roadmaps
Building steel
Building steel
TGB TGB
Red Equipment
iron & Rack
Grounding
Exterior building wall
(TBB)
TBB Common
Bonding
TGB TGB Network
(CBN)
Components
Sleeve Red
iron
Backbone pathway
Suspended ceiling area
ACEG Crimping
Panel Tools
Primary
(TBB)
board
cable
protection
TMGB TGB
Electrical
EF
GEC
BCT Source: BICSI TDM Manual, 10th Edition Technical
Grounding ACEG = Alternating current equipment ground Information
electrode BC = Bonding conductor
system BCT = Bonding conductor for telecommunications
EF = Entrance facility
ER = Equipment room
GE = Grounding equalizer
GEC = Grounding electrode conductor
TBB = Telecommunications bonding backbone
TGB = Telecommunications grounding busbar
TMGB = Telecommunications main grounding busbar
TR = Telecommunications room Index
For more technical grounding information, please see the Data Center Grounding White Paper at www.panduit.com/dcgrounding.
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 29
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
The TBB shall be a copper conductor. The minimum conductor size shall be a No. 6 AWG. The TBB
shall be sized at 2 kcmil per linear foot of conductor length up to a maximum size of a 3/0 AWG. The
TBB may be insulated. The Bonding conductor for Telecommunications (BCT) shall be, as a minimum,
the same size as the TBB.(1)
Common
Bonding Recommended Cable Sizes for Grounding Applications
Network
(CBN) Use the
Components Following
Purpose Code Cables
Other connections to the TGB and TMGB, #6 AWG, green insulated
including building steel, main water pipe, etc.
Underfloor CBN #2 AWG, bare
Connections to Underfloor CBN from pipes, #6 AWG, bare
ventilation ducts, etc.
Connection from Underfloor CBN to TGB 2/0 AWG, bare
Crimping
Tools
Key Terminology
Ground A conducting connection, whether intentional or
accidental, by which an electric circuit or equipment is
connected to the earth, or to some conducting body of
Technical relatively large extent that serves in place of the earth.
Information
Common Bonding Network (CBN) The principal means for affecting bonding and earthing
Index
inside a building.
1. Telecommunications Industry Association, Commercial Building Grounding (Earthing) and Bonding Requirements For Telecommunications, J-STD-607-A,
October 2002.
30
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction
C L P
CD-920-1 . . . . . . . . . . . . . . . . . . . . .27 LCC1-14AW-E . . . . . . . . . . . . . . . . . .17 PV10-10RX-L . . . . . . . . . . . . . . . . . .16
CD-920-1/0 . . . . . . . . . . . . . . . . . . . .27 LCC1-38DW-E . . . . . . . . . . . . . . . . .17 PV10-14RX-L . . . . . . . . . . . . . . . . . .16
CD-920-2 . . . . . . . . . . . . . . . . . . . . .27 LCC1/0-14AW-X . . . . . . . . . . . . . . . .17 PV10-6RX-L . . . . . . . . . . . . . . . . . . .16
CD-920-2/0 . . . . . . . . . . . . . . . . . . . .27 LCC1/0-38DW-X . . . . . . . . . . . . . . . .17 PV10-8RX-L . . . . . . . . . . . . . . . . . . .16
CD-920-250 . . . . . . . . . . . . . . . . . . .27 LCC10-14BW-L . . . . . . . . . . . . . . . . .17 PV14-10RX-C . . . . . . . . . . . . . . . . . .16 Grounding
CD-920-3/0 . . . . . . . . . . . . . . . . . . . .27 LCC10-14JAW-L . . . . . . . . . . . . . . .17 PV14-14RX-C . . . . . . . . . . . . . . . . . .16 Roadmaps
CD-920-4 . . . . . . . . . . . . . . . . . . . . .27 LCC10-14JAWF-L . . . . . . . . . . . . . . .17 PV14-6RX-C . . . . . . . . . . . . . . . . . . .16
CD-920-4/0 . . . . . . . . . . . . . . . . . . . .27 LCC10-14JAWH-L . . . . . . . . . . . . . . .17 PV14-8RX-C . . . . . . . . . . . . . . . . . . .16
CD-920-6 . . . . . . . . . . . . . . . . . . . . .27 LCC2-14AW-Q . . . . . . . . . . . . . . . . .17
CD-920-8 . . . . . . . . . . . . . . . . . . . . .27 LCC2-38DW-Q . . . . . . . . . . . . . . . . .17
CD-920H-2 . . . . . . . . . . . . . . . . . . . .27 LCC2/0-14AW-X . . . . . . . . . . . . . . . .17 R
CD-920H-6 . . . . . . . . . . . . . . . . . . . .27 LCC2/0-38DW-X . . . . . . . . . . . . . . . .17 RGCBNJ660P . . . . . . . . . . . . . . . . . .11
CD-930H-250 . . . . . . . . . . . . . . . . . .27 LCC250-12DW-X . . . . . . . . . . . . . . . .17 RGEJ1024PF . . . . . . . . . . . . . . . . . .12
CLRCVR1-1 . . . . . . . . . . . . . . . . . . .21 LCC250-38DW-X . . . . . . . . . . . . . . . .17 RGEJ1024PH . . . . . . . . . . . . . . . . . .12 Equipment
CLRCVR2-1 . . . . . . . . . . . . . . . . . . .21 LCC3/0-12W-X . . . . . . . . . . . . . . . . .17 RGEJ1036PF . . . . . . . . . . . . . . . . . .12 & Rack
Grounding
CLRCVR3-1 . . . . . . . . . . . . . . . . . . .21 LCC3/0-38DW-X . . . . . . . . . . . . . . . .17 RGEJ1057PF . . . . . . . . . . . . . . . . . .12 Kits
CT-100 . . . . . . . . . . . . . . . . . . . . . . .24 LCC4-14ADW-L . . . . . . . . . . . . . . . . .17 RGEJ624PF . . . . . . . . . . . . . . . . . . .12
CT-1550 . . . . . . . . . . . . . . . . . . . . . .24 LCC4-38DW-L . . . . . . . . . . . . . . . . . .17 RGEJ624PH . . . . . . . . . . . . . . . . . . .12
CT-1570 . . . . . . . . . . . . . . . . . . . . . .24 LCC4/0-14AW-X . . . . . . . . . . . . . . . .17 RGEJ636PF . . . . . . . . . . . . . . . . . . .12
CT-1700 . . . . . . . . . . . . . . . . . . . . . .24 LCC4/0-38DW-X . . . . . . . . . . . . . . . .17 RGEJ657PF . . . . . . . . . . . . . . . . . . .12
CT-2931 . . . . . . . . . . . . . . . . . . . . . .26 LCC6-10ABW-L . . . . . . . . . . . . . . . . .17 RGESD-1 . . . . . . . . . . . . . . . . . . . . .13
CT-930 . . . . . . . . . . . . . . . . . . . . . . .25 LCC6-14BDW-L . . . . . . . . . . . . . . . . .17 RGRB19 . . . . . . . . . . . . . . . . . . . . . .14
LCC6-14EW-L . . . . . . . . . . . . . . . . . .17 RGREJ1096 . . . . . . . . . . . . . . . . . . .14
Common
LCC6-14JAW-L . . . . . . . . . . . . . . . . .17 RGREJ696 . . . . . . . . . . . . . . . . . . . .14 Bonding
G LCC6-14JAWF-L . . . . . . . . . . . . . . . .17 RGRKCBNJ . . . . . . . . . . . . . . . . . . .14 Network
GB2B0304TPI-1 . . . . . . . . . . . . . . . .15 LCC6-14JAWH-L . . . . . . . . . . . . . . . .17 RGRKCBNJEJ . . . . . . . . . . . . . . . . .14 (CBN)
GB2B0306TPI-1 . . . . . . . . . . . . . . . .15 LCC6-38BDW-L . . . . . . . . . . . . . . . . .17 RGS134-1 . . . . . . . . . . . . . . . . . . . . .11 Components
GB2B0312TPI-1 . . . . . . . . . . . . . . . .15 LCC6-56BW-L . . . . . . . . . . . . . . . . . .17 RGS134-10-1 . . . . . . . . . . . . . . . . . .11
GB4B0612TPI-1 . . . . . . . . . . . . . . . .15 LCC8-10ABW-L . . . . . . . . . . . . . . . . .17 RGTBS-C . . . . . . . . . . . . . . . . . . . . .14
GB4B0624TPI-1 . . . . . . . . . . . . . . . .15 LCC8-14ABW-L . . . . . . . . . . . . . . . . .17 RGTBSM6-C . . . . . . . . . . . . . . . . . . .14
GPL-14-X . . . . . . . . . . . . . . . . . . . . .22 LCC8-14DW-L . . . . . . . . . . . . . . . . . .17 RGTS-C . . . . . . . . . . . . . . . . . . . . . .14
GPL-15-X . . . . . . . . . . . . . . . . . . . . .22 LCC8-38DW-L . . . . . . . . . . . . . . . . . .17 RGTSM6-C . . . . . . . . . . . . . . . . . . . .14
GPL-8-Q . . . . . . . . . . . . . . . . . . . . . .22 LCCX1-14A-X . . . . . . . . . . . . . . . . . .18 RGW-100-1 . . . . . . . . . . . . . . . . . . . .13
LCCX1-38D-X . . . . . . . . . . . . . . . . . .18 RGW-12-1 . . . . . . . . . . . . . . . . . . . . .13
Crimping
LCCX1/0-14A-X . . . . . . . . . . . . . . . .18 RGW-32-1 . . . . . . . . . . . . . . . . . . . . .13 Tools
H LCCX1/0-38D-X . . . . . . . . . . . . . . . .18
HTCT2-2-1 . . . . . . . . . . . . . . . . . . . .20 LCCX2-38D-E . . . . . . . . . . . . . . . . . .18
HTCT250-2-1 . . . . . . . . . . . . . . . . . .20 LCCX2/0-14A-X . . . . . . . . . . . . . . . .18 W
HTCT250-250-1 . . . . . . . . . . . . . . . .20 LCCX2/0-38D-X . . . . . . . . . . . . . . . .18 WB12-L . . . . . . . . . . . . . . . . . . . . . . .23
HTCT6-6-1 . . . . . . . . . . . . . . . . . . . .20 LCCX250-38D-X . . . . . . . . . . . . . . . .18 WB34-X . . . . . . . . . . . . . . . . . . . . . .23
HTWC2-2-1 . . . . . . . . . . . . . . . . . . . .19 LCCX3/0-38D-X . . . . . . . . . . . . . . . .18 WB58-Q . . . . . . . . . . . . . . . . . . . . . .23
HTWC250-2-1 . . . . . . . . . . . . . . . . . .19 LCCX4-14AB-L . . . . . . . . . . . . . . . . .18
HTWC250-250-1 . . . . . . . . . . . . . . . .19 LCCX4-38BD-L . . . . . . . . . . . . . . . . .18
HTWC6-6-1 . . . . . . . . . . . . . . . . . . . .19 LCCX4/0-38D-X . . . . . . . . . . . . . . . .18 Technical
LCCX6-10B-L . . . . . . . . . . . . . . . . . .18 Information
LCCX6-14AB-L . . . . . . . . . . . . . . . . .18
K LCCX6-14D-L . . . . . . . . . . . . . . . . . .18
KP1-C . . . . . . . . . . . . . . . . . . . . . . .23 LCCX6-38AC-L . . . . . . . . . . . . . . . . .18
KP2-L . . . . . . . . . . . . . . . . . . . . . . . .23 LCCX6-38D-L . . . . . . . . . . . . . . . . . .18
LCCX8-10AB-L . . . . . . . . . . . . . . . . .18
LCCX8-14AB-L . . . . . . . . . . . . . . . . .18
LCCX8-14D-L . . . . . . . . . . . . . . . . . .18
LCCX8-38D-L . . . . . . . . . . . . . . . . . .18
LTYK . . . . . . . . . . . . . . . . . . . . . . . . .15
Index
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 31
PANDUIT is a global leader in cabling and communication products,
delivering end-to-end solutions in support of
demanding electrical and networking requirements.
PANDUIT Catalogs
!PAN-TY ® Cable Ties !CONTOUR-TY ® Cable Ties !PAN-TERM ® Terminals !Crimping Tools and Dies
!PAN-TY Clamp Ties
®
!DURA-TY Cable Ties
™
!PAN-TERM ® Disconnects !PAN-LUG ™ Mechanical Connectors
!PAN-TY Push Mount Ties
®
!BELT-TY In-Line Cable Ties
™
!PAN-TERM Splices
®
!PAN-LUG ™ Grounding Connectors
!PAN-TY Marker Ties
®
!TAK-TY Hook & Loop Cable Ties
®
!PAN-TERM Ferrules
®
!Support Products
!DOME-TOP ® Barb Ty Cable Ties !STA-STRAP ® Cable Ties !PAN-LUG ™ Compression
!DOME-TOP ® Barb Ty Clamp Ties !Cable Tie Installation Tools Connectors
!DOME-TOP Barb Ty Marker Ties
®
!Custom Hot Stamping
!Adhesive Backed Cable Tie !Grommet Edging !PAN-STEEL ® Stainless Steel !PAN-STEEL® System Accessories
Mounts !Braided Expandable Sleeving Cable Ties !PAN-STEEL® System
!Screw Applied Cable Tie Mounts !Corrugated Loom Tubing !PAN-STEEL ® Stainless Steel Permanent Identification
!Flat Cable Mounts and Fittings Strapping
!Fixed Diameter Clamps !Heat Shrink Tubing !Installation Tools
!Harness Board Accessories !Non-Shrink PVC Tubing
!Spiral Wrap !PAN-WRAP ™ Split Harness Wrap
!Hand-Held Printers !Lockout/Tagout Products !Office Furniture Raceway !Faceplates, Surface Mount Outlet
!Desktop Printers !Voltage Markers !Cove Raceway Boxes & Labeling Administration
!Labeling Software !Warning Labels !PAN-WAY TG-70 Surface Raceway
® !PAN-WAY ® LD Profile Surface
Raceway
!Computer Printable Labels !Safety Signs and Tags !PAN-WAY ® T-70 & Twin-70
Surface Raceway !PAN-WAY ® T130 Surface Raceway
!Wire Markers !Letters and Numbers
!PAN-WAY ® T-45 Surface Raceway !PAN-POLE ™ Outlet Poles
!ULTIMATE ID ® Network
Labeling System
!PANDUCT ® Slotted Wall !PANDUCT ® Hinged Slotted Wall !Modules !Racks & Cable Management
Wiring Duct Wiring Duct !ULTIMATE ID ® System !Grounding and Bonding
!PANDUCT ® Solid Wall Raceway !PANDUCT ® Flexible Wiring Duct !Work Area !Fiber Routing
!PANDUCT ® Halogen Free Slotted !PANDUCT ® Low Smoke Slotted !Zone Cabling !Surface Raceway
Wall Wiring Duct Wall Wiring Duct
!Patch Panels, Copper Patch !Labeling & Administration
!PANDUCT ® Flush Cover Round !Wiring Duct Accessories and Cords & Punchdowns !Cable Ties & Accessories
Hole Wiring Duct Installation Tools
!Fiber Connectors, Enclosures &