Introduction

S TRUCTURED G ROUND ™ GROUNDING SYSTEM C ATA LO G – W W - P CC B 04

Table of Contents
Introduction
INTRODUCTION
How to Use This Catalog . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
The Purpose of Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

GROUNDING ROADMAPS
Common Bonding Network (CBN) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Service Entrance Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Data Center Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Grounding
Data Center Rack Grounding (Raised Floor) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 Roadmaps
Telecommunications Room Grounding Roadmap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Telecommunications Room Rack Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

EQUIPMENT & RACK GROUNDING KITS


Features and Benefits — PANDUIT ® STRUCTUREDGROUND ™ System
for Data Center Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . .10
Rack Grounding Strip Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . .11 Equipment
& Rack
Common Bonding Network (CBN) to Rack Jumper Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . .11 Grounding
Equipment Jumper Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . .12 Kits
Paint Piercing Grounding Washer Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . .13
Electrostatic Discharge (ESD) Port Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . .13
Retrofit Rack Grounding Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . .14
Thread-Forming Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . .14
Bonding Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..... . . . . . . . . . . .14
Common
COMMON BONDING NETWORK (CBN) COMPONENTS Bonding
Network
BICSI/J-STD-607-A Telecommunications Grounding Busbars . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 (CBN)
Telecommunications Grounding and Bonding Conductor Label Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Components
Ring Terminal, Vinyl Expanded Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Code Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16-17
Flex Conductor, Two-Hole, Long Barrel with Window Lug . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Code/Flex Conductor HTAP Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Code/Flex Conductor HTAP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Clear Covers for HTCT HTAPs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Grounding Clamp, U-Bolt, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 Crimping
Grounding Clamp for Water Pipes, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23 Tools
Grounding Rod Clamp, Bronze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

CRIMPING TOOLS
Hand Operated Plier Type Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .24
CONTOUR CRIMP ™ Controlled Cycle Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .24
Die Type, Manual Hydraulic, 14 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .25
Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .26
Technical
CD-920 Crimping Dies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . .27 Information

TECHNICAL INFORMATION
® ™
PANDUIT STRUCTUREDGROUND System for Data Center Grounding Application Standards . . . . . . . . . . . . . . .28
Specification Layout for Data Center Grounding per BICSI TDM Manual, 10th Edition . . . . . . . . . . . . . . . . . . . .29
Recommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE)
per J-STD-607-A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Recommended Cable Sizes for Grounding Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Key Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Index

INDEX
Part Number Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Related Catalogs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
1
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

How to Use This Catalog


Introduction
Common Bonding Network (CBN) S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
page 4 Common Bonding Network (CBN)
• PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding is a complete, highly reliable line of products to ground
your building and network equipment in compliance with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942,
IEEE Std 1100 (IEEE Emerald Book), UL and CSA
Introduction

Telecommunications
Room
(see roadmap on page 8)

Grounding
Roadmaps

Equipment
& Rack
Grounding
Kits

Data Center
Grounding (see roadmap on page 6)

Roadmaps Common
Bonding
Network
(CBN)
Components

Crimping
Tools

Service Entrance
(see roadmap on page 5)

Technical
Information

Index

See page 28 for PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding Application Standards.
For more data center grounding information, see www.panduit.com/dcgrounding.

Equipment 4

& Rack
Grounding
Kits Grounding Roadmaps S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

pages 5-9 Data Center Grounding Roadmap


• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), UL
and CSA
• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity between
Data Center Rack Grounding (Raised Floor)

Introduction Introduction
metallic components and the grounded rack
• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet members Back of Rack Shown
to the rack grounding strip Paint Piercing Grounding
Washer Kit: RGW
Back of Racks Shown (see page 13)

3 Data Equipment Racks


Bonding Screws are used to
4 mount patch panels to the front of
Grounding Grounding
Roadmaps the rack: RGTBS (see page 14) Roadmaps

5
3 Equipment Jumper Kit 24" L, 90° Bent: RGEJ
(see page 12)

1
Equipment Electrostatic Discharge (ESD) Equipment
& Rack 3 Port Kit recommended for & Rack
Grounding use on front and back of rack: Grounding
Kits Kits
RGESD (see page 13)
AC Panel* 1
Common Telecommunications
Bonding Backbone
(TBB)

Bonding Common
Bonding
Network
Conduit
Rack Grounding Strip Kit: RGS
(see page 11) Common
Bonding
Network

Network (CBN)
Components
Building Steel 2
(CBN)
Components

(CBN)
Components Crimping
Tools
Common Bonding Network (CBN)
Equipment Jumper Kit 36" L, 90° Bent: RGEJ
(see page 12)
Crimping
Tools

Raised Floor Pedestal 2

Equipment Jumper Kit 24" L, 45° Bent: RGEJ


(see page 12)
Copper Compression HTAP and Telecommunications Grounding
1 Clear Cover: HTWC 4 Busbar (TGB) and Busbar Label
(see page 19) (see page 15)
Technical Technical
Information Information

Bronze, U-Bolt Grounding Clamp: GPL Telecommunications Grounding and Bonding


2 (see page 22) 5 Conductor Label Kit: LTYK Common Bonding Network (CBN) to
(see page 15) Rack Jumper Kit: RGCBNJ
(see page 11)
Copper Compression, Two-Hole, Long
3 Barrel with Window Lug: LCC-W
(see pages 16-17) Common Bonding Network – typically #2 AWG
Index Index
bare copper code conductor is used underfloor
*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.
A typical raised floor includes a multitude of metallic components which are connected together. It is the responsibility of the manufacturer and installer of the
raised floor to insure all the raised floor metallic components are bonded which means that they are connected together electrically in accordance with
applicable specifications. The PANDUIT Bonding/Grounding System does not insure required bonding of the raised floor metallic components.

6 For technical assistance in the U.S., call 866-405-6654 (outside the U.S., see inside back cover for directory) 7

Crimping
Tools

Detailed Product S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING Detailed Tool S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

Information Code/Flex Conductor HTAP Information Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool
• Two stage rapid advance hydraulic system minimizes • Tool provided with two, high capacity 12 VDC rechargeable
Introduction For Making Parallel and Multiple Tap Connections on Code and Flex Conductors Introduction

pages 11-23 pages 24-27


cycle time nickel-metal hydride batteries — provides for continuous
• Provides UL Listed and CSA Certified connections on operation and eliminates "memory" build-up, one hour
• Used to tap into continuous conductors as a • Tap grooves are separated from one another charge time
splice or pigtailing allowing them to function independently so PANDUIT ® PAN-LUG ™ copper and aluminum lugs and
HTAP can be used with a single or multiple splices and copper taps • Eight second crimp cycle time provides quick terminations,
• Each HTAP terminates a wide range of saves time
conductor sizes and combinations of code taps providing maximum design and • Open "C-Head" design allows easy loading of crimping
and flex conductors Class G, H, I and installation flexibility dies and connectors, saves time • Uses industry standard Makita* batteries and charger —
Locomotive to suit a variety of applications • Color coded and marked with PANDUIT die • Rubber boot on crimp head provides abrasion protection industry proven reliability easy to obtain from local
index numbers for proper crimp die selection retail sources
• Slotted design allows quick and easy • Ram automatically retracts when crimp cycle is complete
assembly of conductor to HTAP using 3 • Requires crimping tools and dies, see pages • Requires crimping dies, see page 27
Grounding Grounding
Roadmaps PANDUIT 94 V-0 cable ties included 25, 26 and 27 Roadmaps • Dies installed using spring loaded die retention pins — no
• UL Listed and CSA Certified for applications need for tools
HTAP up to 600V when crimped with PANDUIT • Crimp head rotates 360 degrees — provides versatility for
RUN
and specified competitor crimping tools and use in restricted spaces
PANDUIT crimping dies
• Tin plated to inhibit corrosion
TAP

Technical Equipment
& Rack
Grounding
W
RUN
W L
RUN
W L
Equipment
& Rack
Grounding

Information
W RUN L
Kits RUN L Kits
Std.
H
Pkg.
H H H Part Number Part Description Qty.
CT-2931 Terminates PANDUIT ® PAN-LUG ™ Compression Connectors: 1
TAP 1 TAP 2
TAP 3 • Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor
TAP 1 TAP 1 TAP 2 TAP 1 • Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor
Common Common
Bonding HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250 Bonding • Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor
Network Network • Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor
(CBN) (CBN) • Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor
Components Figure Components • Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor
Copper Conductor Size Range Dimensions (In.) Wire • Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor
Wire PANDUIT PANDUIT Strip Std. • PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor
Strand Crimping Die Color Length Pkg.
Part Number Type Run Tap 1 Tap 2 Tap 3 L W H Tool & Die No. (In.) Qty. Warranty: 3 years
HTCT6-6-1 #6 - #10 #6 - #14 .61 .40 .99 CT-930, CT-2931 Orange, 11/16 1
Code AWG AWG PH6 CT-2931 includes:
— — • Tool
#6 - #10 #6 - #14 • Two 12 VDC, rechargeable NiMH batteries
Crimping Flex AWG AWG Crimping • One battery charger
Tools Tools • Steel tool case with storage for batteries, charger and crimp dies
HTCT2-2-1 #2 - #6 #2 - #6 AWG #8 - #14 #8 - #14 .76 .61 1.55 CT-930, CT-2931 Brown, 13/16 1
Code AWG STR/SOL AWG AWG PH2
STR/SOL For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.
#2 - #8 #2 - #8 AWG #8 - #14 #8 - #14 *Makita is a registered trademark of Makita Corporation in the United States.
Flex AWG AWG AWG
HTCT250-2-1 250 kcmil - #2 - #6 AWG #8 - #14 .92 .96 1.92 CT-930, CT-2931 Purple, 1 1
Code #2 AWG STR/SOL AWG PH25

4/0 - #2 #2 - #8 AWG #8 - #14
Flex AWG AWG
Technical Technical
Information HTCT250-250-1 250 kcmil - 250 kcmil - .90 .89 1.92 CT-930, CT-2931 Purple, 1 1 Information
Code #2 AWG #2 AWG PH25
— —
4/0 - #2 4/0 - #2
Flex AWG AWG
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.

Index Index

Index 20 26

Technical Information — Includes Application Standards and BICSI TDM Manual, 10th Edition
pages 28-30
2
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

The Purpose of Grounding


The grounding system is not just an insurance policy against a lightning strike. It is an active, Introduction
functioning system that provides protection for personnel and equipment. Proper grounding is
essential for efficient network performance.
The purpose of the grounding system is to create a low impedance path to earth ground for electrical
surges and transient voltages. Lightning, fault currents, circuit switching (motors turning on and off),
and electrostatic discharge are the common causes of these surges and transient voltages. An
effective grounding system minimizes the detrimental effects of these electrical surges.
Grounding
A properly designed grounding system is one that is intentional, visually verifiable, adequately sized Roadmaps

to handle expected currents safely, and one that directs these potentially damaging currents away
from sensitive communication equipment. Any metallic component that is part of the data center
infrastructure (such as equipment, racks, ladder racks, enclosures, cable trays, etc.) must be bonded
to the grounding system.
What are the effects of improper grounding? Equipment
& Rack
Decreased Efficiency Grounding
• Electrical noise is introduced on data cables when surges are not properly dissipated by the grounding system.They cause Kits

faulty data signals and dropped packets, thus decreasing the throughput and overall efficiency of your network.
Lower Reliability
• According to insurance industry data, improper grounding of communication systems leads to $500 million per year of
damage to property and/or equipment due to lightning. (1)
Common
• The Information Technology Industry Council states that grounding is the single-most important factor in reliable network Bonding
Network
equipment performance. (2) (CBN)
• More than 90% of problems in data communications equipment, including reboot, lockup, and data corruption, are Components
traced to problems with grounding. (3)
• Industry experts estimate that 27%-33% of damaged equipment in a user's facility is caused by electrostatic discharge.
The component cost of repairing damaged equipment is substantial for complex circuit boards, especially when labor
and downtime are considered. (4)
• According to the IEEE, the typical AC third prong ground is almost never sufficient to prevent damage to network equipment. (5)
Crimping
Safety Risks Tools

• Personal injury from electric shock caused by improper grounding can cause immeasurable human suffering and
significant expense.
• Potential fire hazards exist when heat is generated from electrical surges that find a high resistance path to ground.

Can you afford improper grounding?


Network equipment, such as switches, routers and storage devices, costs anywhere from thousands of dollars to hundreds of
Technical
thousands of dollars.The cost of proper grounding is only a tiny fraction of the cost of the equipment it is protecting. Information

Clearly the biggest cost of improper grounding is the inability to service customers properly.
PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding gives you what you need to properly protect
your investment.
1. Mike Holt, "Prevent Shocks in Your Communications: Understanding How the NEC Relies on Ground Resistance Theory Leads to a
Successful Application of Communications Grounding," Electrical Construction & Maintenance, September 2002.
2. Information Technology Industry Council (ITI, formerly CBEMA), Guidelines for Grounding Information Technology Equipment. Information
Letter, ITI, 15 February 1997. Index
3. Donald G. Pennington and Paul Holzer, "Doing Battle with Those Ground Transients," Electronic Engineering Times, 8 January 1996.
4. ESDA, "Fundamentals of ESD: Part 1 — An Introduction to ESD," 2001, <http://www.esda.org/basics/part1.cfm> (1 October 2004).
5. Institute of Electrical and Electronics Engineers, Inc., IEEE Recommended Practice for Powering and Grounding Electronic Equipment, IEEE
Std 1100-1999, 1999.
For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 3
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Common Bonding Network (CBN)
• PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding is a complete, highly reliable line of products to ground
your building and network equipment in compliance with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942,
IEEE Std 1100 (IEEE Emerald Book), UL and CSA
Introduction

Telecommunications
Room
(see roadmap on page 8)

Grounding
Roadmaps

Equipment
& Rack
Grounding
Kits

Data Center
(see roadmap on page 6)

Common
Bonding
Network
(CBN)
Components

Crimping
Tools

Service Entrance
(see roadmap on page 5)

Technical
Information

Index

See page 28 for PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding Application Standards.
For more data center grounding information, see www.panduit.com/dcgrounding.

4
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

Service Entrance Grounding Roadmap


• Complies with J-STD-607-A and IEEE Std 1100 (IEEE Emerald Book)
• Grounding Equalizer (GE) is required when two or more Telecommunications Bonding Backbones (TBB) are used within a
multi-story building; bond TBBs together with a GE at the top floor and at a minimum of every third floor in between Introduction

Telecommunications Bonding
Backbone (TBB)**
2 2
Conduit
Grounding Equalizer (GE)
3
Grounding
1 Roadmaps
5
6
Earth Ground
3
7
Equipment
& Rack
Grounding
Kits

3
AC Panel*

Cable Entrance Common


Bonding
Network
(CBN)
Components
AC Service Entrance
3

4 Water Meter
4

Crimping
Tools
Copper Compression HTAP and Bronze, Grounding Rod Clamp: WB
1 Clear Cover: HTWC 5 (see page 23) connected by a cable to
(see page 19) 2 (U-Bolt Grounding Clamp)

Bronze, U-Bolt Grounding Clamp: GPL Telecommunications Main


2 (see page 22) connected by a cable to 6 Grounding Busbar (TMGB) and
1 (HTAP) Busbar Label (see page 15)
Technical
Information

Copper Compression, Two-Hole, Long Telecommunications Grounding and Bonding


3 Barrel with Window Lug: LCC-W 7 Conductor Label Kit: LTYK
(see pages 16-17) (see page 15)

Bronze, Water Pipe Grounding Clamp: KP


4 (see page 23)
Index

*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.
**Specification J-STD-607-A specifies different size conductors based on the length of the Telecommunications Bonding Backbone (TBB). See page 30 for
Recommended Sizing of the Telecommunications Bonding Backbone (TBB) and Grounding Equalizer (GE) Per J-STD-607-A.

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 5
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Data Center Grounding Roadmap
• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), UL
and CSA
• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity between
Introduction
metallic components and the grounded rack
• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet members
to the rack grounding strip
Back of Racks Shown

3 Data Equipment Racks

4
Grounding
Roadmaps

5
3

1
Equipment
& Rack 3
Grounding
Kits
AC Panel* 1
Telecommunications
Bonding Backbone
(TBB)

Common
Bonding
Network
Conduit
(CBN)
Components
Building Steel 2

Crimping Common Bonding Network (CBN)


Tools

Raised Floor Pedestal 2

Copper Compression HTAP and Telecommunications Grounding


1 Clear Cover: HTWC 4 Busbar (TGB) and Busbar Label
(see page 19) (see page 15)
Technical
Information

Bronze, U-Bolt Grounding Clamp: GPL Telecommunications Grounding and Bonding


2 (see page 22) 5 Conductor Label Kit: LTYK
(see page 15)

Copper Compression, Two-Hole, Long


3 Barrel with Window Lug: LCC-W
(see pages 16-17)
Index
*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.
A typical raised floor includes a multitude of metallic components which are connected together. It is the responsibility of the manufacturer and installer of the
raised floor to insure all the raised floor metallic components are bonded which means that they are connected together electrically in accordance with
applicable specifications. The PANDUIT Bonding/Grounding System does not insure required bonding of the raised floor metallic components.

6
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

Data Center Rack Grounding (Raised Floor)

Introduction

Back of Rack Shown


Paint Piercing Grounding
Washer Kit: RGW
(see page 13)

Bonding Screws are used to


mount patch panels to the front of
Grounding
the rack: RGTBS (see page 14) Roadmaps

Equipment Jumper Kit 24" L, 90° Bent: RGEJ


(see page 12)

Electrostatic Discharge (ESD) Equipment


Port Kit recommended for & Rack
use on front and back of rack: Grounding
Kits
RGESD (see page 13)

Rack Grounding Strip Kit: RGS


(see page 11) Common
Bonding
Network
(CBN)
Components

Equipment Jumper Kit 36" L, 90° Bent: RGEJ


(see page 12)
Crimping
Tools

Equipment Jumper Kit 24" L, 45° Bent: RGEJ


(see page 12)

Technical
Information

Common Bonding Network (CBN) to


Rack Jumper Kit: RGCBNJ
(see page 11)

Common Bonding Network — typically #2 AWG


Index
bare copper code conductor is used underfloor

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 7
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Telecommunications Room Grounding Roadmap
• Complies with BICSI TDM Manual, 10th Edition and J-STD-607-A, TIA-942, IEEE Std 1100 (IEEE Emerald Book), UL
and CSA
• Bonding screws are recommended to mount all panels, equipment, shelves, etc. to ensure electrical continuity between
Introduction
metallic components and the grounded rack
• Can be used to ground equipment mounted in cabinets which meet EIA-310-D; installer should bond all cabinet members
to the rack grounding strip
Back of Racks Shown
Grounding Equalizer (GE)

Grounding
Roadmaps
Conduit

5 1
3
4
Equipment
& Rack
Grounding
Kits
3
1

3 1
AC Panel*
Common
Bonding
Network Telecommunications
(CBN) Bonding Backbone
Components
(TBB)

Building Steel
Crimping
Tools

Copper Compression HTAP and Telecommunications Grounding


1 Clear Cover: HTWC 4 Busbar (TGB) and Busbar Label
Technical (see page 19) (see page 15)
Information

Bronze, U-Bolt Grounding Clamp: GPL Telecommunications Grounding and Bonding


2 (see page 22) 5 Conductor Label Kit: LTYK
(see page 15)

Copper Compression, Two-Hole, Long


3 Barrel with Window Lug: LCC-W
Index (see pages 16-17)

*AC Panel should be grounded per NEC standards. Enclosure should be grounded per manufacturer’s specifications.
A typical overhead cabling system includes a multitude of metallic components which are connected together. It is the responsibility of the installer to insure all
of the metallic components are bonded, which means that they are connected together electrically in accordance with applicable specifications. The PANDUIT
Bonding/Grounding System does not insure required bonding of the overhead cabling system metallic components.

8
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

Telecommunications Room Rack Grounding

Introduction

Aisle Ground — typically #2 AWG insulated copper code


conductor is used overhead

Bonding Screws are used to


mount patch panels to the front of
the rack: RGTBS (see page 14) Grounding
Back of Rack Shown Roadmaps

Paint Piercing Grounding


Washer Kit: RGW
(see page 13)

Common Bonding Network (CBN) to


Equipment
Rack Jumper Kit: RGCBNJ & Rack
(see page 11) Grounding
Kits

Equipment Jumper Kit 24" L, 90° Bent: RGEJ


(see page 12)

Electrostatic Discharge (ESD)


Common
Port Kit recommended for Bonding
use on front and back of rack: Network
RGESD (see page 13) (CBN)
Components

Rack Grounding Strip Kit: RGS


(see page 11)

Crimping
Tools

Equipment Jumper Kit 36" L, 90° Bent: RGEJ


(see page 12)

Technical
Equipment Jumper Kit 24" L, 45° Bent: RGEJ Information
(see page 12)

Index

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 9
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING
Features and Benefits — PANDUIT ® STRUCTUREDGROUND ™ System for Data
Center Grounding
PANDUIT offers a variety of kits with premium components to ensure superior grounding with the highest reliability available.
Introduction • Provides highest reliability with an all-copper rack • Incorporates a flexible design that can be used with
grounding system to maintain data center system racks which meet EIA-310-D
performance and protect network equipment • Offers ease of installation — no paint scraping required to
• Complies with data center standard TIA-942 and is UL bond racks; factory terminated jumpers simply
Listed and CSA Certified bolt in place
C

Grounding Rack Grounding Strip is made from high


Roadmaps conductivity, low resistance wrought copper
A and tin plated to inhibit corrosion, providing C F
the lowest impedance path to ground

Jumper has UL, VW-1 flame rated green Electrostatic E


insulation and is factory terminated with Discharge (ESD)
copper compression, two-hole, long barrel Port Kit
Equipment with window lug; lug is UL Listed, CSA (see page 13)
& Rack
B Certified and meets NEBS Level 3 with a single
Grounding stud hole and slot which allows mounting for
D
Kits
½" to 5/8" hole spacing and accommodates
stud sizes ¼", #12 and 6mm

Rack A
Paint Piercing Grounding Washer is Grounding
made from hardened steel and electro zinc Strip Kit
Common
C plated which inhibits corrosion to provide a (see page 11)
Bonding superior bond between frame members on
Network bolt-together racks
(CBN)
Components
Thread-Forming Screws are made from
D electro zinc plated steel and provide a bond to
the rack by removing paint from threaded
holes without creating metal shavings

Crimping Electrostatic Discharge (ESD) Port is made


Tools
E from high conductivity, low resistance copper
and tin plated to inhibit corrosion plus it D
functions as an ESD wrist strap hanger
B D
Electrostatic Discharge (ESD) Protection Equipment
Sticker is provided in black and yellow for
F high visibility and easy identification as an
Jumper Kit
(see page 12)
ESD port C
Technical
Information
Copper Compression HTAP is UL Listed and C
CSA Certified; used to make a highly reliable,
G permanent bond between the common
bonding network and common bonding
network (CBN) to rack jumper kit

B
Index C

G
Common Bonding Network (CBN)
to Rack Jumper Kit (see page 11)
10
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

Equipment & Rack Grounding Kits


Introduction

Rack Grounding Strip Kits


• Bonds up to 44 RU per rack • EIA Universal mounting hole pattern

Std.
Pkg.
Part Number Part Description Qty.
RGS134-1 Rack grounding strip; 78.65" length; .67" width; .05" thickness; 1 Grounding
provided with .16 oz (5cc) of antioxidant and three #12-24 x 1/2" Roadmaps
thread-forming screws*
RGS134-10-1 10 rack grounding strips; 78.65" length; .67" width; .05" thickness; 1
provided with .16 oz (5cc) of antioxidant and 30 #12-24 x 1/2"
thread-forming screws*
*An equal number of M6 x 12mm thread-forming screws also provided in each kit.

Equipment
& Rack
Grounding
Kits

Common Bonding Network (CBN) to Rack Jumper Kit


Common
• Bonds the rack grounding strip to the CBN • HTAP is UL Listed and CSA Certified for applications up to Bonding
• HTAP, included in kit, requires crimping tool and die; see 600V when crimped with PANDUIT and specified Network
the CT-930 crimping tool on page 25, the CT-2931 crimp- competitor crimping tools and PANDUIT crimping dies; (CBN)
see the Termination Solutions Catalog SA-TMCB02 for the Components
ing tool on page 26 and the CD-930H-250 crimping die on
page 27 complete line of PANDUIT crimping tools

Std. Std.
Pkg. Ctn.
Part Number Part Description Qty. Qty.
RGCBNJ660P #6 AWG jumper; 60" length; 45° bent lug on grounding strip side; 1 10
provided with .16 oz (5cc) of antioxidant, two #12-24 x 1/2" Crimping
thread-forming screws* and a copper compression HTAP** for Tools
connecting to the CBN in sizes ranging from #2 AWG to 250 kcmil
*An equal number of M6 x 12mm thread-forming screws also provided in each kit.
**HTAP also sold separately, see page 20.

Technical
Information

Index

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 11
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

Equipment Jumper Kits


Introduction • Bonds network equipment to rack grounding strip • Use jumpers with 45° bent lugs, on grounding strip side, for
• Jumper kit available with both ends factory terminated to improved cable management
provide a bolt on solution • Use 24" jumpers when network equipment ground point is
• Jumper kit available with one end factory terminated to located near the grounding strip side of the rack
attach to the rack grounding strip; free end accommodates • Use 36" jumpers when network equipment ground point is
unique equipment terminations located away from the grounding strip side of the rack
• Use jumpers with 90° bent lug, on grounding strip side, for
high density grounding requirements up to one ground
point per RU
Grounding
Roadmaps
Std. Std.
Pkg. Ctn.
Part Number Part Description Qty. Qty.
#10 AWG equipment jumpers factory terminated on both ends
RGEJ1024PH #10 AWG jumper; 24" length; 45° bent lug on grounding strip side 1 10
to straight lug on equipment; provided with .16 oz (5cc) of
antioxidant and four #12-24 x 1/2" thread-forming screws*
Equipment RGEJ1024PF #10 AWG jumper; 24" length; 90° bent lug on grounding strip side 1 10
& Rack to straight lug on equipment; provided with .16 oz (5cc) of
Grounding antioxidant and four #12-24 x 1/2" thread-forming screws*
Kits
RGEJ1024PF RGEJ1036PF #10 AWG jumper; 36" length; 90° bent lug on grounding strip side 1 10
to straight lug on equipment; provided with .16 oz (5cc) of
antioxidant and four #12-24 x 1/2" thread-forming screws*
#6 AWG equipment jumpers factory terminated on both ends
RGEJ624PH #6 AWG jumper; 24" length; 45° bent lug on grounding strip side to 1 10
straight lug on equipment; provided with .16 oz (5cc) of antioxidant
Common and four #12-24 x 1/2" thread-forming screws*
Bonding
Network RGEJ624PF #6 AWG jumper; 24" length; 90° bent lug on grounding strip side to 1 10
(CBN) straight lug on equipment; provided with .16 oz (5cc) of antioxidant
Components and four #12-24 x 1/2" thread-forming screws*
RGEJ636PF #6 AWG jumper; 36" length; 90° bent lug on grounding strip side to 1 10
straight lug on equipment; provided with .16 oz (5cc) of antioxidant
and four #12-24 x 1/2" thread-forming screws*
#10 AWG equipment jumper factory terminated on one end
RGEJ1057PF #10 AWG jumper; 57" length; 90° bent lug on grounding strip side; 1 10
provided with .16 oz (5cc) of antioxidant and two #12-24 x 1/2"
Crimping thread-forming screws*
Tools
#6 AWG equipment jumper factory terminated on one end
RGEJ657PF #6 AWG jumper; 57" length; 90° bent lug on grounding strip side; 1 10
provided with .16 oz (5cc) of antioxidant and two #12-24 x 1/2"
thread-forming screws*
RGEJ1057PF
*An equal number of M6 x 12mm thread-forming screws also provided in each kit.

How to Select the Appropriate Equipment Jumper


Technical
Information

3" or smaller

3" or larger

Select 24" equipment jumpers with 90° Select equipment jumpers with 45° lugs
lugs when equipment grounding connection for lower density applications or shallow
Index is close to the grounding strip. depth equipment to provide improved cable
management.
Select 36" equipment jumpers with 90° lugs
when equipment grounding connection is on
the opposite side from the grounding strip.

12
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING

Paint Piercing Grounding Washer Kits


• Bonds frame members on bolt-together racks • Green color coding to indicate bonding application
Introduction
• No paint scraping required

Std.
Pkg.
Part Number Part Description Qty.
RGW-12-1 12 paint piercing bonding washers for 3/8" stud size; .875 O.D.; provided 1
with .16 oz (5cc) of antioxidant; for use with standard equipment racks:
CMR19X84, CMR19X84S and CMR23X84
RGW-32-1 32 paint piercing bonding washers for 3/8" stud size; .875 O.D.; provided 1
with .16 oz (5cc) of antioxidant; for use with 4 post rack NF4PR84 and Grounding
data rack DR84 Roadmaps

RGW-100-1 100 paint piercing bonding washers for 3/8" stud size; .875 O.D.; provided 1
with .16 oz (5cc) of antioxidant

Equipment
& Rack
Electrostatic Discharge (ESD) Port Kit Grounding
Kits
• Accommodates standard ESD wrist strap 4mm plug • Bent 45°, acts as a hook to hold wrist strap
• Can be mounted to front or back of rack for • Barrel permanently marked with the protective earth
convenient access (ground) symbol

Std.
Pkg.
Part Number Part Description Qty. Common
RGESD-1 ESD port kit; provided with an ESD protection sticker, .16 oz (5cc) of 1 Bonding
antioxidant and one #12-24 x 1/2" thread-forming screw* Network
(CBN)
Contact your local electrical distributor for their selection of Electrostatic Discharge (ESD) wrist straps. Components
*One M6 x 12mm thread-forming screw also provided in each kit.
ESD port must be attached to a grounded member.

Crimping
Tools

Technical
Information

Index

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 13
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

Retrofit Rack Grounding Kits


Introduction
• Provides a dedicated ground system to maintain system • Provides a complete system of matched components that
performance and protect network equipment when RGS can be easily selected to save cost and labor
rack grounding strip kit cannot be used (see page 11) • Thread-forming screws eliminate the need to manually
• Optimized for installation on 19" racks that meet EIA-310-D, remove paint from the rack
with functioning equipment, and are deployed in the field

Grounding
Roadmaps

RGRKCBNJEJ RGRKCBNJ

Lug Std. Std.


Network (see pages Pkg. Ctn.
Equipment 16-18) Part Number Part Description Qty. Qty.
RGRKCBNJEJ Rack grounding kit to ground the rack and one piece of equipment; 1 10
includes one RGRB19 busbar, one HTCT250-2-1 HTAP and two
Equipment RGREJ696 grounding jumpers
Rack
& Rack Grounding RGRKCBNJ Rack grounding kit to ground the rack; includes one RGRB19 1 10
Grounding Kit busbar, one HTCT250-2-1 HTAP and one RGREJ696
Kits Rack RGRKCBNJEJ grounding jumper
Grounding
Busbar RGRB19 Rack grounding busbar; can be positioned anywhere on the rack; 1 10
RGRB19 Grounding 19" length; tin plated; 14 holes arranged for flexibility in mounting;
Jumper mounting hole sets have 1/2" spacing; provided with two
HTAP RGREJ696
(see #12-24 x 1/2" thread-forming screws* for mounting
or
page 20) RGREJ696 Grounding jumper; #6 AWG; 96" length; one end factory 1 10
RGREJ1096
terminated to lug; provided with .16 oz (5cc) of antioxidant and four
Common #12-24 x 1/2" thread-forming screws* and other mounting hardware
Bonding
Network as appropriate
(CBN) RGREJ1096 Grounding jumper; #10 AWG; 96" length; one end factory 1 10
Components Grounding
Jumper terminated to lug; provided with .16 oz (5cc) of antioxidant and four
RGREJ696 #12-24 x 1/2" thread-forming screws* and other mounting hardware
as appropriate
Rack Grounding Kit
*An equal number of M6 x 12mm thread-forming screws also provided in each kit.
RGRKCBNJ

Thread-Forming Screws
Crimping
Tools • Thread-forming, provides a bond to the rack by removing • Easily installed with 5/16" socket head wrench or flat
paint from threaded holes without creating metal shavings blade screwdriver
Std.
Pkg.
Part Number Part Description Qty.
RGTS-C Thread-forming grounding screw, #12-24 x 1/2" 100
RGTSM6-C Thread-forming grounding screw, M6 x 12mm 100

Technical
Information
Bonding Screws
• Creates an electrical bond between painted patch panels • Thread-forming, provides a bond to the rack by removing
and racks paint from threaded holes without creating metal shavings
• Serrations on bottom of screw remove paint from patch • Easily installed with Phillips screwdriver
panel, thus providing metal-to-metal contact
Std.
Pkg.
Index Part Number Part Description Qty.
RGTBS-C Thread-forming bonding screw, #12-24 x 1/2" 100
RGTBSM6-C Thread-forming bonding screw, M6 x 15mm 100

14
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING

Common Bonding Network (CBN) Components


C UL
R US BICSI/J-STD-607-A Telecommunications Grounding Busbars Introduction

• Meets BICSI and J-STD-607-A requirements for network • Comes pre-assembled with brackets and insulators
systems grounding applications attached for quick installation
• Made of high conductivity copper and tin plated to • Use PANDUIT self-laminating laser/ink jet labels to identify
inhibit corrosion busbars to meet TIA/EIA-606-A

No. of 5/16" No. of 7/16" Can Be Clearly Std.


hole sets, hole sets, Identified with PANDUIT Pkg. Grounding
Part Number Bar Size 5/8" spacing 1" spacing Laser/Ink Jet Label* Qty. Roadmaps

Telecommunications Grounding Busbars (TGB)


GB2B0304TPI-1 1/4" x 2" x 10" 4 3 1
GB2B0306TPI-1 1/4" x 2" x 12" 6 3 C200X100FJJ 1
TGB GB2B0312TPI-1 1/4" x 2" x 20" 12 3 1
Telecommunications Main Grounding Busbars (TMGB)
GB4B0612TPI-1 1/4" x 4" x 12" 12 6 1
C200X100FJJ Equipment
GB4B0624TPI-1 1/4" x 4" x 20" 24 6 1 & Rack
Grounding
For additional label sizes, materials and print technologies and to see the complete line of PANDUIT identification
Kits
products, see the Identification Solutions Catalog SA-IDCB16.
*Busbar labels sold separately.
TMGB

Common
Bonding
C200X100FJJ Network
(CBN)
Components

Telecommunications Grounding and Bonding Conductor Label Kit


• Meets labeling requirements of J-STD-607-A; each • Kit includes everything needed to properly label cables; one
telecommunications grounding and bonding conductor shall flame retardant cable tie and one rigid plastic yellow tag Crimping
Tools
be labeled as close as practicable to its point of termination in printed with “IF THIS CONNECTOR OR CABLE IS LOOSE
a readable position OR MUST BE REMOVED, PLEASE CALL THE BUILDING
• Can be applied as a wrap-around marker (parallel to cable) or TELECOMMUNICATIONS MANAGER”
flag marker (45° or 90°) to cable

Std.
Pkg.
Part Number Part Description Qty.
LTYK Label kit includes printed tag and one flame retardant cable tie 10 Technical
Information
For additional label sizes, materials and print technologies and to see the complete line of PANDUIT identification
products, see the Identification Solutions Catalog SA-IDCB16.

Index

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 15
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

Ring Terminal, Vinyl Expanded Insulation


Introduction • Expanded wire entry allows for large O.D. wire insulation or • Brazed seam assures a reliable crimp
multiple wire crimps within one wire barrel • Insulation support
• Industry standard color coding to indicate wire range • Requires crimping tools, see page 24

Figure PANDUIT Std. Std.


Part Wire Color Stock Max. Stud Dimensions (In.) Crimping Pkg. Ctn.
Number Range Code Thickness Ins. Size L W C Tool Qty.** Qty.
PV14-6RX-C .03 .200 #6 .96 .31 .25 100 500
Grounding PV14-8RX-C 16-14 .03 .200 #8 .96 .31 .25 CT-100‡, 100 500
Roadmaps Blue
PV14-10RX-C AWG .03 .200 #10 .96 .31 .25 CT-1550‡ 100 500
PV14-14RX-C .03 .200 1/4" 1.16 .46 .37 100 500
PV10-6RX-L .04 .250 #6 1.10 .31 .30 50 500
PV10-8RX-L 12-10 .04 .250 #8 1.10 .31 .30 CT-100‡, 50 500
Yellow
PV10-10RX-L AWG .04 .250 #10 1.10 .31 .30 CT-1550‡ 50 500
PV10-14RX-L .04 .250 1/4" 1.29 .52 .39 50 500
L For additional sizes and configurations and to see the complete line of PAN-TERM ® Terminals, see the Termination
Equipment Solutions Catalog SA-TMCB02.
& Rack ‡UL and CSA approved tooling/product combinations. For crimping tools see page 24.
Grounding W
**To order in bulk, replace -C in the part number with -M for a bulk package of 1000 and replace -L with -D for a
Kits bulk package of 500.
C

Common
Bonding
Network
(CBN)
Components

Code Conductor, Two-Hole, Long Barrel with Window Lug


For Use with Stranded Copper Conductors
Crimping
Tools • Meets J-STD-607-A requirements for • Color coded barrels marked with PANDUIT
network systems grounding applications and specified competitor die index numbers
• Tested by Telcordia — meets NEBS for proper crimp die selection
Level 3 • Long barrel maximizes number of crimps
• Requires crimping tools and dies, see and provides premium wire pull-out strength
pages 24, 25, 26 and 27 and electrical performance
• UL Listed for use up to 35KV**, temperature • Inspection window to visually assure full
rated 90°C and CSA Certified to 600V when conductor insertion
crimped with PANDUIT and specified • Tin plated to inhibit corrosion
Technical competitor crimping tools and dies
Information • Available with NEMA hole sizes and spacing
• UL Listed and CSA Certified for wire
range-taking capability when crimped with
PANDUIT ® UNI-DIE ™ dieless crimping tools

Index

16
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING

Code Conductor, Two-Hole, Long Barrel with Window Lug (continued)


Introduction
W W W INSPECTION
W WINDOW
HOLE HOLE HOLE
SPACING SPACING SPACING HOLE
L SPACING
L
INSPECTION B B
T
WINDOW
B
INSPECTION T 90˚
INSPECTION
WINDOW WINDOW
45˚
T
T
L
B

Grounding
Roadmaps
L

Figure 1 Figure 2: Slotted Lug Figure 3: Slotted Lug Figure 4: Slotted Lug
45°Bent 90°Bent
Stud Stud Wire
Figure
Copper Hole Hole PANDUIT PANDUIT Burndy T&B Strip Std.
Dimensions (In.)
Figure Conductor Size Spacing Crimping Die Color Die Die Length Pkg.
Part Number No. Size (In.) (In.) W B T L Tool & Die No. No. No. (In.) Qty.
LCC10-14JAW-L* 2 1/4 .50 – .63 .42 .53 .05 1.93 — — — 9/16 50 Equipment
#14 – #10 & Rack
LCC10-14JAWH-L* 3 AWG STR, 1/4 .50 – .63 .42 .53 .05 1.78 CT-100, — — — 9/16 50
Grounding
LCC10-14JAWF-L* 4 #12 – #10 1/4 .50 – .63 .42 .53 .05 1.56 CT-1570 — — — 9/16 50 Kits
LCC10-14BW-L* 1 AWG SOL 1/4 .75 .42 .53 .05 2.06 — — — 9/16 50
LCC8-10ABW-L 2 #10 .63 – .75 .41 .70 .08 2.14 Red P21 49 21 3/4 50
LCC8-14ABW-L 2 1/4 .63 – .75 .48 .70 .07 2.23 CT-1700, Red P21 49 21 3/4 50
#8 AWG CT-930,
LCC8-14DW-L 1 1/4 1.00 .48 .70 .07 2.48 Red P21 49 21 3/4 50
CT-2931
LCC8-38DW-L 1 3/8 1.00 .60 .70 .05 2.70 Red P21 49 21 3/4 50
LCC6-10ABW-L 2 #10 .63 – .75 .46 1.07 .08 2.52 Blue P24 7 24 1 1/8 50 Common
Bonding
LCC6-14JAW-L 2 1/4 .50 – .63 .48 1.07 .08 2.49 Blue P24 7 24 1 1/8 50 Network
LCC6-14JAWH-L (CBN)
3 1/4 .50 – .63 .48 1.07 .08 2.08 Blue P24 7 24 1 1/8 50
Components
LCC6-14JAWF-L 4 1/4 .50 – .63 .48 1.07 .08 1.66 CT-1700, Blue P24 7 24 1 1/8 50
#6 AWG CT-930,
LCC6-14BDW-L 2 1/4 .75 – 1.00 .48 1.07 .08 2.86 Blue P24 7 24 1 1/8 50
CT-2931
LCC6-14EW-L 1 1/4 1.25 .48 1.07 .08 3.11 Blue P24 7 24 1 1/8 50
LCC6-56BW-L 1 5/16 .75 .56 1.07 .07 2.73 Blue P24 7 24 1 1/8 50
LCC6-38BDW-L 2 3/8 .75 – 1.00 .62 1.07 .06 3.08 Blue P24 7 24 1 1/8 50
LCC4-14ADW-L 2 1/4 .63 – 1.00 .55 1.05 .09 2.63 CT-1700, Gray P29 8 29 1 1/8 50
#4 – #3 Crimping
CT-930,
LCC4-38DW-L 1 AWG STR 3/8 1.00 .62 1.05 .08 3.09 Gray P29 8 29 1 1/8 50 Tools
CT-2931
LCC2-14AW-Q 1 1/4 .63 .60 1.16 .10 2.67 CT-1700, Brown P33 10 33 1 1/4 25
#2 AWG CT-930,
LCC2-38DW-Q 1 3/8 1.00 .66 1.16 .10 3.24 Brown P33 10 33 1 1/4 25
CT-2931
LCC1-14AW-E 1 1/4 .63 .70 1.36 .11 2.89 CT-1700, Green P37 11 37 1 7/16 20
#1 AWG CT-930,
LCC1-38DW-E 1 3/8 1.00 .70 1.36 .11 3.46 Green P37 11 37 1 7/16 20
CT-2931
LCC1/0-14AW-X 1 1/4 .63 .76 1.44 .12 3.07 CT-930, Pink P42 12 42 1 1/2 10
1/0 AWG
LCC1/0-38DW-X 1 3/8 1.00 .76 1.44 .12 3.57 CT-2931 Pink P42 12 42 1 1/2 10 Technical
Information
LCC2/0-14AW-X 1 1/4 .63 .85 1.50 .13 3.23 CT-930, Black P45 13 45 1 9/16 10
2/0 AWG
LCC2/0-38DW-X 1 3/8 1.00 .85 1.50 .13 3.67 CT-2931 Black P45 13 45 1 9/16 10
LCC3/0-38DW-X 1 3/8 1.00 .96 1.50 .13 3.70 Orange P50 14 50 1 9/16 10
CT-930,
LCC3/0-12W-X 1 3/0 AWG 1/2 1.75 .96 1.50 .13 4.87 Orange P50 14 50 1 9/16 10
CT-2931
LCC4/0-14AW-X 1 1/4 .63 1.06 1.56 .14 3.35 CT-930, Purple P54 15 54 1 5/8 10
4/0 AWG
LCC4/0-38DW-X 1 3/8 1.00 1.06 1.56 .14 3.81 CT-2931 Purple P54 15 54 1 5/8 10
LCC250-38DW-X 1 3/8 1.00 1.17 1.61 .14 3.89 CT-930, Yellow P62 16 62 1 11/16 10
250 kcmil
LCC250-12DW-X 1 1/2 1.00 1.17 1.61 .14 4.12 CT-2931 Yellow P62 16 62 1 11/16 10 Index
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
*Not tested to NEBS Level 3 requirements.
**Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000V.

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 17
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

Flex Conductor, Two-Hole, Long Barrel with Window Lug


Introduction For Use with Flexible, Extra-Flexible and Code Stranded Copper Conductors

• Meets J-STD-607-A requirements for • Can be used with code conductor and
network systems grounding applications flex conductor class: G, H, I, K, M and
• Requires crimping tools and dies, see pages Locomotive
24, 25, 26 and 27 • Long barrel maximizes number of crimps
• UL Listed for use up to 35KV**, temperature and provides premium wire pull-out strength
rated 90°C and CSA Certified to 600V when and electrical performance
crimped with PANDUIT and specified • Inspection window to visually assure full
Grounding competitor crimping tools and dies conductor insertion
Roadmaps
• Color coded barrels marked with PANDUIT • Generously beveled wire entry prevents
and specified competitor die index numbers bent back strands when inserting conductor
for proper crimp die selection into barrel
• Tin plated to inhibit corrosion
• Available with NEMA hole sizes and spacing
W W

HOLE HOLE
SPACING SPACING
Equipment L
L
& Rack INSPECTION B
Grounding B
WINDOW

Kits INSPECTION T
WINDOW

Figure 1 Figure 2: Slotted Lug

Flex Figure
Conductor Stud Stud Dimensions Wire
Size Code Hole Hole (In.) PANDUIT PANDUIT Strip Std.
Common
Bonding Figure Class Conductor Size Spacing Crimping Die Color Length Pkg.
Network Part Number No. G, H, I, K, M Locomotive Size (In.) (In.) W B T L Tool & Die No. (In.) Qty.
(CBN) LCCX8-10AB-L 2 #10 .63 – .75 .41 .70 .08 2.14 Red P21 3/4 50
Components CT-1700, Red P21
LCCX8-14AB-L 2 1/4 .63 – .75 .48 .70 .07 2.23 3/4 50
#8 AWG #8 AWG #8 AWG CT-930,
LCCX8-14D-L 1 1/4 1.00 .48 .70 .07 2.48 Red P21 3/4 50
CT-2931
LCCX8-38D-L 1 3/8 1.00 .60 .70 .05 2.70 Red P21 3/4 50
LCCX6-10B-L 1 #10 .75 .46 1.07 .08 2.52 Blue P24 1 1/8 50
LCCX6-14AB-L 2 1/4 .63 – .75 .48 1.07 .08 2.61 CT-1700, Blue P24 1 1/8 50
LCCX6-14D-L 1 #6 AWG #6 AWG #6 AWG 1/4 1.00 .48 1.07 .08 2.86 CT-930, Blue P24 1 1/8 50
LCCX6-38AC-L 2 3/8 .63 – .88 .62 1.07 .06 2.96 CT-2931 Blue P24 1 1/8 50
Crimping LCCX6-38D-L 1 3/8 1.00 .62 1.07 .06 3.08 Blue P24 1 1/8 50
Tools
LCCX4-14AB-L 2 1/4 .63 – .75 .55 1.05 .09 2.63 CT-1700, Gray P29 1 1/8 50
#5, #4, #3 #4 – #3
LCCX4-38BD-L 2 #4 AWG CT-930, Gray P29 1 1/8
AWG AWG STR 3/8 .75 – 1.00 .62 1.05 .08 3.09 50
CT-2931
LCCX2-38D-E 1 #2 AWG #2 AWG #2 AWG 3/8 1.00 .70 1.36 .11 3.46 CT-1700, Brown 1 7/16 20
CT-930, P33
CT-2931
LCCX1-14A-X 1 1/4 .63 .76 1.44 .12 3.07 CT-930, Green P37 1 1/2 10
#1 AWG #1 AWG #1 AWG
LCCX1-38D-X 1 3/8 1.00 .76 1.44 .12 3.57 CT-2931 Green P37 1 1/2 10
Technical LCCX1/0-14A-X 1 1/4 .63 .85 1.50 .13 3.23 CT-930, Pink P42 1 9/16 10
Information 1/0 AWG 1/0 AWG 1/0 AWG CT-2931 Pink P42 1 9/16
LCCX1/0-38D-X 1 3/8 1.00 .85 1.50 .13 3.67 10
LCCX2/0-14A-X 1 1/4 .63 .96 1.50 .13 3.27 CT-930, Black P45 1 9/16 10
2/0 AWG 2/0 AWG 2/0 AWG
LCCX2/0-38D-X 1 3/8 1.00 .96 1.50 .13 3.70 CT-2931 Black P45 1 9/16 10
LCCX3/0-38D-X 1 3/0 AWG 3/0 AWG 3/0 AWG 3/8 1.00 1.06 1.56 .14 3.81 CT-930, Orange 1 5/8 10
CT-2931 P50
LCCX4/0-38D-X 1 4/0 AWG 4/0 AWG 4/0 AWG 3/8 1.00 1.19 2.24 .16 4.55 CT-930, Purple 2 5/16 10
CT-2931 P54
LCCX250-38D-X 1 250 kcmil 262.6 kcmil — 3/8 1.00 1.28 2.24 .17 4.59 CT-930, Yellow P62 2 5/16 10
CT-2931
Index For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.
**Consult cable manufacturer for voltage stress relief instructions with applications greater than 2000V.

18
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

Code/Flex Conductor HTAP Kit


• Includes all components to make a complete HTAP and • Matching clear covers are made from high impact plastic Introduction
cover installation: HTCT HTAP, matching CLRCVR clear and provide high impact strength and 360° viewing of
cover and cable ties installed HTAP
• Each HTCT HTAP designed to terminate a wide range of • Clear covers have a UL 94 V-0 flame rating and an
copper code and flex conductor combinations to oxygen index of 28 providing self-extinguishing, flame
accommodate a variety of applications retardant properties
• HTAPs incorporate a unique slotted design that allows for • Requires crimping tools and dies, see pages 25, 26 and
quick and easy installation using supplied PANDUIT cable 27
ties; saves time and cost • UL Listed and CSA Certified for applications up to 600V
when crimped with PANDUIT and specified competitor Grounding
Roadmaps

Equipment
& Rack
Grounding
Kits
W L W L
W RUN
W RUN L RUN
RUN L

H H H
H

Common
TAP 2 Bonding
TAP 1
TAP 3 Network
TAP 1 TAP 1 TAP 2 TAP 1 (CBN)
Components
HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250

Components Copper Conductor Size Range


Clear Wire Std.
HTAP Cover Strand Pkg.
Part Number Part No. Part No. Type Run Tap1 Tap 2 Tap 3 Qty.
HTWC6-6-1 HTCT6-6-1 CLRCVR1-1 Code #6 – #10 AWG #6 – #14 AWG 1
— — Crimping
Flex #6 – #10 AWG #6 – #14 AWG Tools
HTWC2-2-1 HTCT2-2-1 CLRCVR2-1 #2 – #6 AWG #2 – #6 AWG #8 – #14 AWG #8 – #14 AWG 1
Code STR/SOL STR/SOL
Flex #2 – #8 AWG #2 – #8 AWG #8 – #14 AWG #8 – #14 AWG
HTWC250-2-1 HTCT250-2-1 CLRCVR3-1 250 kcmil – #2 #2 – #6 AWG #8 – #14 AWG 1
Code AWG STR/SOL —
Flex 4/0 – #2 AWG #2 – #8 AWG #8 – #14 AWG
HTWC250-250-1 HTCT250-250-1 CLRCVR3-1 250 kcmil – #2 250 kcmil – #2 1
Code AWG AWG — —
Flex 4/0 – #2 AWG 4/0 – #2 AWG Technical
Information
For additional sizes and configurations and to see the complete line of PAN-LUG Power and Grounding Connectors, see the Termination Solutions

Catalog SA-TMCB02.
See pages 20 and 21 for more information on HTAPs and clear covers, including crimping tools.
Labels for clear covers are sold separately and are printed with the PANDUIT LS7 Printer. For information on the LS7 Printer and to see the complete line of
PANDUIT identification products, see the Identification Solutions Catalog SA-IDCB16.

Index

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 19
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

Code/Flex Conductor HTAP


Introduction For Making Parallel and Multiple Tap Connections on Code and Flex Conductors
• Used to tap into continuous conductors as a • Tap grooves are separated from one another
splice or pigtailing allowing them to function independently so
• Each HTAP terminates a wide range of HTAP can be used with a single or multiple
conductor sizes and combinations of code taps providing maximum design and
and flex conductors Class G, H, I and installation flexibility
Locomotive to suit a variety of applications • Color coded and marked with PANDUIT die
• Slotted design allows quick and easy index numbers for proper crimp die selection
Grounding assembly of conductor to HTAP using 3 • Requires crimping tools and dies, see
Roadmaps PANDUIT 94 V-0 cable ties included pages 25, 26 and 27
• UL Listed and CSA Certified for applications
HTAP up to 600V when crimped with PANDUIT
RUN and specified competitor crimping tools and
PANDUIT crimping dies
• Tin plated to inhibit corrosion
TAP

Equipment
& Rack W L W L
W RUN
Grounding RUN
W RUN L
Kits
RUN L

H H H
H

TAP 1 TAP 2
TAP 3
TAP 1 TAP 1 TAP 2 TAP 1
Common
Bonding HTCT6-6 HTCT2-2 HTCT250-2 HTCT250-250
Network
(CBN)
Components Figure
Copper Conductor Size Range Dimensions (In.) Wire
Wire PANDUIT PANDUIT Strip Std.
Strand Crimping Die Color Length Pkg.
Part Number Type Run Tap 1 Tap 2 Tap 3 L W H Tool & Die No. (In.) Qty.
HTCT6-6-1 #6 – #10 #6 – #14 .61 .40 .99 CT-930, CT-2931 Orange, 11/16 1
Code AWG AWG PH6
— —
#6 – #10 #6 – #14
Crimping Flex AWG AWG
Tools
HTCT2-2-1 #2 – #6 #2 – #6 AWG #8 – #14 #8 – #14 .76 .61 1.55 CT-930, CT-2931 Brown, 13/16 1
Code AWG STR/SOL AWG AWG PH2
STR/SOL
#2 – #8 #2 – #8 AWG #8 – #14 #8 – #14
Flex AWG AWG AWG
HTCT250-2-1 250 kcmil – #2 – #6 AWG #8 – #14 .92 .96 1.92 CT-930, CT-2931 Purple, 1 1
Code #2 AWG STR/SOL AWG PH25

4/0 – #2 #2 – #8 AWG #8 – #14
Flex AWG AWG
Technical
Information HTCT250-250-1 250 kcmil – 250 kcmil – .90 .89 1.92 CT-930, CT-2931 Purple, 1 1
Code #2 AWG #2 AWG PH25
— —
4/0 – #2 4/0 – #2
Flex AWG AWG
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.

Index

20
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

Clear Covers for HTCT HTAPs


For Use with PANDUIT HTCT HTAPs Introduction

• Made of high impact plastic to provide high impact strength • Incorporate molded in flash barriers which encompass the
and 360° inspections of crimped connection to assure the HTAP installation providing protection against electrical
crimp is complete and the correct die was used flash over
• Incorporate dual self-latching spring loaded latches and • UL 94 V-0 flame rating and oxygen index of 28 providing
supplied with two PANDUIT UL 94 V-0 cable ties — allow self-extinguishing, flame retardant properties
for easy snap-on assembly and ensure covers are secured • Part number, voltage rating, temperature rating and HTCT
• Low profile design minimizes space requirements part number molded into cover for easy identification
Grounding
• Each cover half supports installation information labels • Flexible fingers located at each end of cover prevent Roadmaps
inside plastic retainer strips to allow labels to be viewed foreign objects from entering cover and are made from
on either side of cover and to protect labels from ductile plastic material that allows easy installation and
being removed will not damage conductor insulation

Figure Dimensions Std.


Use With HTAP (In.) Pkg.
Part Number Part Number L W H Qty.
CLRCVR1-1 HTCT6-6 4.48 1.41 1.20 1 Equipment
CLRCVR2-1 HTCT2-2 5.10 1.66 1.40 1 & Rack
Grounding
CLRCVR3-1 HTCT250-2, HTCT250-250 5.35 2.16 1.40 1 Kits
For additional sizes and configurations and to see the complete line of PAN-LUG ™ Power and Grounding
Connectors, see the Termination Solutions Catalog SA-TMCB02.
Labels for clear covers are sold separately and are printed with the PANDUIT LS7 Printer. For information on the
LS7 Printer and to see the complete line of PANDUIT identification products, see the Identification Solutions
L W
Catalog SA-IDCB16.

H
Common
Bonding
Network
Shown Assembled (CBN)
Components

Crimping
Tools

Technical
Information

Index

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 21
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

C UL
R US Grounding Clamp, U-Bolt, Bronze
Introduction • Used to ground copper conductor parallel or at a right • Accommodates a wide range of pipe, tube, rod and
angle to a rod, tube or pipe conductor sizes — minimizes inventory
• Made from high strength, electrolytic cast bronze • UL Listed for grounding and bonding and suitable for direct
• High strength silicon bronze hardware provides long term burial in earth or concrete
reliable assembly

Grounding H
Roadmaps

W L

Ground Iron Figure Dimensions Bolt Hex Tightening Std.


Rod Size Pipe Size Conductor (In.) Dia. Size Torque Pkg.
Part Number (In.) (In.) Size Range L W H (In.) (In.) (In.-Lbs.) Qty.
GPL-8-Q 7/8 or 1 1/2 or 3/4 #8 SOL – #4 STR 2.38 1.38 2.63 3/8 9/16 110 25
Equipment GPL-14-X — 1 #8 SOL – #4 STR 2.63 1.38 2.75 3/8 9/16 110 10
& Rack
Grounding GPL-15-X — 1 #4 SOL – 2/0 STR 2.63 1.63 2.75 3/8 9/16 180 10
Kits For the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions Catalog SA-TMCB02.

Common
Bonding
Network
(CBN)
Components

Crimping
Tools

Technical
Information

Index

22
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

Grounding Clamp for Water Pipes, Bronze


• Used to ground copper code conductor to water pipe or • Accommodates a wide range of pipe, tube, rod and Introduction
copper tube conductor sizes — minimizes inventory
• Cast from high strength, electrolytic bronze to provide • UL Listed for grounding and bonding and suitable for direct
reliable grounding connections burial in earth or concrete
• Plated steel screws provide high strength and
inhibit corrosion

Water Pipe Figure Tightening Torque Std.


Range Conductor Dimensions (In.) (In.-Lbs.) Pkg.
Grounding
Part Number (In.) Size Range L W Conductor Clamp Qty. Roadmaps
KP1-C 1/2 – 1 #10 SOL – #2 STR 2.28 .66 50 50 100
KP2-L 1 1/4 – 2 #10 SOL – #2 STR 3.58 .73 50 50 50
For the complete line of PAN-LUG ™ Power and Grounding Connectors, see the Termination Solutions
Catalog SA-TMCB02.

L W

Equipment
& Rack
Grounding
Kits

Grounding Rod Clamp, Bronze Common


Bonding
• Used for grounding copper conductor parallel to • Accommodates a wide range of rod and conductor Network
(CBN)
ground rods sizes — minimizes inventory Components
• Made from high strength, seamless electrolytic bronze to • UL Listed and CSA Certified for grounding and bonding
provide long term durability and suitable for direct burial in earth and concrete
• High strength silicon bronze hardware provides long term
reliable assembly
Ground Figure Hex Tightening Std.
Rod Conductor Size Dimensions (In.) Size Torque Pkg.
Part Number Size Range L W H (In.) (In.-Lbs.) Qty. Crimping
WB12-L 1/2 #2 – #10 STR .88 .84 1.28 1/2 180 50 Tools
#10 SOL
WB34-X 5/8 1/0 – #8 STR 1.03 1.06 1.54 1/2 180 10
3/4 #2 – #8 STR
WB58-Q 5/8 1/0 – #8 STR 1.04 .92 1.40 1/2 180 25
For the complete line of PAN-LUG Power and Grounding Connectors, see the Termination Solutions

Catalog SA-TMCB02.

Technical
Information
H

W L

Index

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 23
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

Crimping Tools
Introduction

Hand Operated Plier Type Tool


• Plier type • Installer controlled crimp

Std.
Pkg.
Part Number Part Description Qty.
Grounding CT-100 Crimps most PANDUIT #26 – #10 AWG insulated and non-insulated 1
Roadmaps
terminals, disconnects and splices. Cuts #4, #6, #8 and #10 screw sizes.
Cuts and strips wire. Excellent all-around application tool of heat treated
finished steel with comfortable cushioned plastic grip handles.
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.

Equipment
& Rack
Grounding
Kits
CONTOUR CRIMP ™ Controlled Cycle Tools
• Specifically designed for the installation of PAN-TERM ® • Superior crimp performance
terminals, disconnects and splices • Reliable — backed by a two year warranty
• Low handle effort — increases productivity

Common
Bonding Std.
Network
(CBN)
Pkg.
Components Part Number Part Description Qty.
CT-1550 Crimps most PAN-TERM ® #22 – #10 AWG nylon and vinyl insulated 1
terminals, splices and disconnects. The CT-1550 has the red/blue pocket
CT-1550 closest to the pivot which provides a reduced crimp effort for those who
make red/blue terminations.
CT-1570 Crimps most PAN-TERM ® #22 – #10 AWG and .5-6.0mm non-insulated 1
terminals and disconnects. Crimps PANDUIT #22 – #10 AWG and
.5-6.0mm non-insulated splices, and #10 AWG compression lugs.
Crimping CT-1700 Crimps PANDUIT #8 – #2 AWG non-insulated tubular terminals (S 1
Tools
series), #8 – #1 AWG copper lugs and splices, #6 – #4 AWG aluminum
CT-1570
lugs and splices and CTAPF copper taps for #14 – #3 AWG. Includes 5
position, color coded rotating die.

For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.

CT- 1700

Technical
Information

Index

24
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

Die Type, Manual Hydraulic, 14 Ton, Crimping Tool


• Two-stage rapid advance hydraulic system minimizes • Open “C-Head” design allows easy loading of crimping dies
number of pumps required to complete a crimp — and connectors, saves time Introduction
saves time • Requires crimping dies, see page 27
• Cushioned grip prevents hands from slipping on tool — • Dies installed using spring loaded die retention pins, no
reduces fatigue need for tools
• Provides UL Listed and CSA Certified connections on • Rubber boot on crimp head provides abrasion protection
PANDUIT ® PAN-LUG ™ copper and aluminum lugs and
splices and copper taps • Audible “pop-off” valve indicates crimp completion
• Crimp head rotates 180°, provides versatility for use in
restricted spaces
Grounding
Roadmaps

Std.
Pkg.
Part Number Part Description Qty.
CT-930 Terminates PANDUIT ® PAN-LUG ™ Compression Connectors: 1 Equipment
& Rack
• Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor Grounding
• Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor Kits
• Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor
• Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor
• Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor
• Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor
• Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor
• PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor

Warranty: 5 years Common


Bonding
Network
CT-930 includes: (CBN)
• Tool Components
• Plastic tool case with die storage
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.

Crimping
Tools

Technical
Information

Index

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 25
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

Die Type, Battery Powered Hydraulic, 12 Ton, Crimping Tool


• Two stage rapid advance hydraulic system minimizes • Tool provided with two, high capacity 12 VDC rechargeable
Introduction
cycle time nickel-metal hydride batteries — provides for continuous
• Provides UL Listed and CSA Certified connections on operation and eliminates “memory” build-up, one hour
PANDUIT ® PAN-LUG ™ copper and aluminum lugs and charge time
splices and copper taps • Eight second crimp cycle time provides quick terminations,
• Open “C-Head” design allows easy loading of crimping saves time
dies and connectors, saves time • Uses industry standard Makita* batteries and charger —
• Rubber boot on crimp head provides abrasion protection industry proven reliability easy to obtain from local
retail sources
• Ram automatically retracts when crimp cycle is complete
• Requires crimping dies, see page 27
Grounding
Roadmaps • Dies installed using spring loaded die retention pins — no
need for tools
• Crimp head rotates 360° — provides versatility for use in
restricted spaces

Equipment
& Rack
Grounding
Kits
Std.
Pkg.
Part Number Part Description Qty.
CT-2931 Terminates PANDUIT ® PAN-LUG ™ Compression Connectors: 1

• Copper compression lugs and splices for #8 AWG – 750 kcmil code conductor
Common • Copper compression lugs and splices for #8 AWG – 600 kcmil flex conductor
Bonding • Copper compression CTAPF taps for #10 AWG – 3/0 AWG code conductor
Network • Copper compression CTAP taps for #8 AWG – 4/0 AWG code conductor
(CBN) • Copper compression HTCT taps for #14 AWG – 250 kcmil code conductor, #14 AWG – 4/0 AWG flex conductor
Components • Aluminum compression lugs and splices for #6 AWG – 600 kcmil code conductor
• Aluminum compression HTAPS for #14 AWG – 500 kcmil code conductor
• PANDUIT ® PAN-TERM ® Tubular Terminals for #8 AWG – 250 kcmil code conductor

Warranty: 3 years

CT-2931 includes:
• Tool
• Two 12 VDC, rechargeable NiMH batteries
Crimping • One battery charger
Tools • Steel tool case with storage for batteries, charger and crimp dies

For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.
CG-920 crimp force measurement gauge available, sold separately, see the Termination Solutions Catalog SA-TMCB02.
*Makita is a registered trademark of Makita Corporation.

Technical
Information

Index

26
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

CD-920 Crimping Dies


• Crimping dies and connectors are color coded for • Part number permanently marked on crimping die for
easy matching easy identification Introduction
• Embosses die index number on connector barrels for post • Provides circumferential crimp results in terminations with
crimp inspection premium electrical and mechanical performance
• Used in PANDUIT crimping tools; see the CT-930 crimping
Die tool on page 25, the CT-2931 crimping tool on page 26
Color and the complete line of PANDUIT crimping tools in the
Termination Solutions Catalog SA-TMCB02

Grounding
Roadmaps

Die Number

Used to Install PANDUIT Compression Lug & Splice Sizes Std. Equipment
Pkg. & Rack
Part Number Copper Code Conductor Size and Die Color & Die No. Qty. Grounding
Kits
CD-920-8 #8 AWG, Red P21 1
CD-920-6 #6 AWG, Blue P24 1
CD-920-4 #4 AWG, Gray P29 1
CD-920-2 #2 AWG, Brown P33 1
CD-920-1 #1 AWG, Green P37 1
CD-920
CD-920-1/0 1/0 AWG, Pink P42 1
Common
CD-920-2/0 2/0 AWG, Black P45 1 Bonding
CD-920-3/0 3/0 AWG, Orange P50 1 Network
(CBN)
CD-920-4/0 4/0 AWG, Purple P54 1 Components
CD-920-250 250 kcmil, Yellow P62 1

Used to Install PANDUIT HTAP Part Numbers Std.


Pkg.
Part Number Copper HTAP and Die Color & Die No. Qty.
CD-920H-6 HTCT6-6-1, Orange PH6 1
CD-920H-2 HTCT2-2-1, Brown PH2 1 Crimping
Tools
CD-930H-250 HTCT250-2-1, 1
HTCT250-250-1, Purple PH25
For the complete line of PANDUIT crimping tools and dies, see the Termination Solutions Catalog SA-TMCB02.

Technical
Information

Index

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 27
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

PANDUIT ® STRUCTUREDGROUND ™ System for Data Center Grounding


Application Standards
Introduction
Alliance for Telecommunications Industry J-STD-607-A-2002, Commercial Building Grounding
Solutions ATIS (Earthing) and Bonding Requirements for
Telecommunications is jointly developed by TIA/EIA and ATIS’
ATIS is a technical planning and standards development technical committee T1E1. This document is available on the
organization that is committed to rapidly developing and promoting ATIS Document Center at www.atis.org.
technical and operations standards for the communications and
related information technologies industry worldwide using a Adhering to the grounding principles outlined in J-STD-607-A helps
pragmatic, flexible and open approach. Over 1,200 participants from ensure that telecommunications equipment and systems
more than 400 communications companies are active in ATIS’ 22 operate reliably. As stated in J-STD-607-A, the preferred means of
industry committees, and its Incubator Solutions Program. connecting conductors to busbars is by using two-hole
Grounding
Roadmaps www.atis.org irreversible compression lugs listed by a nationally recognized
testing laboratory (NRTL) such as UL. PANDUIT ® PAN-LUG ™ Copper
Compression Connectors meet these requirements, in all of the
barrel sizes specified by the 607 standard.
Telecommunications Industry Association TIA ANSI/TIA-942 Draft 5.0a – Telecommunications
Infrastructure Standard for Data Centers

The Telecommunications Industry Association is a leading U.S. TIA-942 states that electrical continuity is required throughout the
non-profit trade association serving the communications and rack materials. Adhering to these principles protects network
Equipment information technology industry. TIA represents providers of equipment and maintains system performance. PANDUIT ®
& Rack communications and information technology products and services STRUCTUREDGROUND ™ System for Data Center Grounding meets
Grounding for the global marketplace through its core competencies in TIA-942 requirements by incorporating an all-copper grounding path.
Kits standards development. Paint piercing grounding washers ensure metal to metal contact of
rack members and two-hole compression lugs for a permanent and
reliable connection.

The Institute of Electrical and Electronics IEEE Std 1100-1999 (IEEE Emerald Book) – IEEE
Engineers, Inc. (IEEE) Recommended Practice for Powering and Grounding
Electronic Equipment
Common The IEEE promotes the engineering process of creating,
Bonding developing, integrating, sharing, and applying knowledge about The main objective of the Emerald Book is to provide a consensus of
Network electro and information technologies and sciences for the benefit recommended practices to address electronic equipment
(CBN) of humanity and the profession. performance issues while maintaining a safe installation, as
Components specified in the National Electrical Code ® (NEC ®) (NFPA 70-1999)
and recognized testing laboratories' standards.

NEBS Level 3 Approval as Tested by Telcordia Technologies NEBS Level 3 Criteria is the minimum level of
environmental compatibility needed to provide maximum
Telcordia Technologies, formerly known as Bellcore, serves as the assurance of equipment operability within the network
testing agency for the Regional Bell Operating Companies. Network facility environment.
Equipment-Building Systems (NEBS) was developed by Bellcore
Crimping and is currently maintained by Telcordia Technologies. NEBS was The Level 3 Criteria is the highest assurance of product operability.
Tools developed to standardize requirements for Central Office Equipment Products that meet NEBS Level 3 Criteria are suited for equipment
and to develop criteria for personal safety, protection of property and applications which demand minimal service interruptions over the life
operational continuity. span of the equipment. PANDUIT is the first in the industry to have a
system of copper compression lugs and splices (#8 AWG – 1,000
kcmil) and crimping tools physically and rigorously tested by
Telcordia Technologies to meet NEBS Level 3 compliance.

Underwriters Laboratories, Inc. • UL 467 Grounding and Bonding Equipment


• UL 486A Wire Connectors and Soldering Lugs for Use with
Technical Underwriters Laboratories, Inc. is an independent, not-for-profit Copper Conductors – Covers pressure wire connectors and
Information safety testing and certification organization based in the soldering lugs for use with copper conductors according to the
United States. National Electrical Code NFPA 70
• UL VW-1 Flammability Rating

Underwriters Laboratories, Inc. Standards applicable to specified


PANDUIT ® STRUCTUREDGROUND™ System for Data Center Grounding
and PAN-LUG ™ Power and Grounding Connectors.

Canadian Standards Association • C22.2 NO. 41-M1987 (R2004) Grounding and


Bonding Equipment
Index
Canadian Standards Association is a not-for-profit membership • C22.2 NO. 65-03 Wire Connectors
based association serving business, industry, government, and
consumers in Canada and the global marketplace. C.S.A. works in Canadian Standards Association standards that are applicable to
Canada and around the world to develop standards that enhance specified PANDUIT ® STRUCTUREDGROUND™ System for Data Center
public safety and health. Grounding and PAN-LUG ™ Power and Grounding Connectors.

28
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

Specification Layout for Data Center Grounding per BICSI TDM Manual,
10th Edition
Introduction

Roof
Red
iron

Backbone pathway
Suspended ceiling area
TR TR Grounding
GE GE Roadmaps

Building steel
Building steel

TGB TGB

Red Equipment
iron & Rack
Grounding
Exterior building wall

Backbone pathway Kits


Suspended ceiling area

Exterior building wall


TR TR

(TBB)
TBB Common
Bonding
TGB TGB Network
(CBN)
Components

Sleeve Red
iron

Backbone pathway
Suspended ceiling area

EF TBB within conduit ER


(TBB)

ACEG Crimping
Panel Tools
Primary
(TBB)

board
cable
protection

TMGB TGB
Electrical
EF
GEC
BCT Source: BICSI TDM Manual, 10th Edition Technical
Grounding ACEG = Alternating current equipment ground Information
electrode BC = Bonding conductor
system BCT = Bonding conductor for telecommunications
EF = Entrance facility
ER = Equipment room
GE = Grounding equalizer
GEC = Grounding electrode conductor
TBB = Telecommunications bonding backbone
TGB = Telecommunications grounding busbar
TMGB = Telecommunications main grounding busbar
TR = Telecommunications room Index

For more technical grounding information, please see the Data Center Grounding White Paper at www.panduit.com/dcgrounding.

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 29
S TRUCTURED G ROUND ™ SYSTEM FOR DATA CENTER GROUNDING

Recommended Sizing of the Telecommunications Bonding Backbone (TBB)


and Grounding Equalizer (GE) per J-STD-607-A
Introduction

The TBB shall be a copper conductor. The minimum conductor size shall be a No. 6 AWG. The TBB
shall be sized at 2 kcmil per linear foot of conductor length up to a maximum size of a 3/0 AWG. The
TBB may be insulated. The Bonding conductor for Telecommunications (BCT) shall be, as a minimum,
the same size as the TBB.(1)

Sizing of the TBB


Grounding
Roadmaps
TBB Length
linear M (ft) TBB Size (AWG)
less than 4 (13) 6
4 – 6 (14 – 20) 4
6 – 8 (21 – 26) 3
8 – 10 (27 – 33) 2
Equipment 10 – 13 (34 – 41) 1
& Rack
Grounding 13 – 16 (42 – 52) 1/0
Kits 16 – 20 (53 – 66) 2/0
greater than 20 (66) 3/0*
*3/0 may not always be available. 4/0 is a more common size that may be substituted.

Common
Bonding Recommended Cable Sizes for Grounding Applications
Network
(CBN) Use the
Components Following
Purpose Code Cables
Other connections to the TGB and TMGB, #6 AWG, green insulated
including building steel, main water pipe, etc.
Underfloor CBN #2 AWG, bare
Connections to Underfloor CBN from pipes, #6 AWG, bare
ventilation ducts, etc.
Connection from Underfloor CBN to TGB 2/0 AWG, bare
Crimping
Tools

Key Terminology
Ground A conducting connection, whether intentional or
accidental, by which an electric circuit or equipment is
connected to the earth, or to some conducting body of
Technical relatively large extent that serves in place of the earth.
Information

Bonding The permanent joining of metallic parts to form an


electrically conductive path that will assure electrical
continuity and the capacity to conduct safely any
current likely to be imposed.

Common Bonding Network (CBN) The principal means for affecting bonding and earthing
Index
inside a building.

1. Telecommunications Industry Association, Commercial Building Grounding (Earthing) and Bonding Requirements For Telecommunications, J-STD-607-A,
October 2002.

30
S TRUCTURED G ROUND ™GSystem
S TRUCTURED ROUND ™ for DataFOR
SYSTEM Center
DATA Grounding
CENTER GROUNDING
Introduction

Part Number Index


Introduction
Part Number Page Part Number Page Part Number Page
Number Number Number

C L P
CD-920-1 . . . . . . . . . . . . . . . . . . . . .27 LCC1-14AW-E . . . . . . . . . . . . . . . . . .17 PV10-10RX-L . . . . . . . . . . . . . . . . . .16
CD-920-1/0 . . . . . . . . . . . . . . . . . . . .27 LCC1-38DW-E . . . . . . . . . . . . . . . . .17 PV10-14RX-L . . . . . . . . . . . . . . . . . .16
CD-920-2 . . . . . . . . . . . . . . . . . . . . .27 LCC1/0-14AW-X . . . . . . . . . . . . . . . .17 PV10-6RX-L . . . . . . . . . . . . . . . . . . .16
CD-920-2/0 . . . . . . . . . . . . . . . . . . . .27 LCC1/0-38DW-X . . . . . . . . . . . . . . . .17 PV10-8RX-L . . . . . . . . . . . . . . . . . . .16
CD-920-250 . . . . . . . . . . . . . . . . . . .27 LCC10-14BW-L . . . . . . . . . . . . . . . . .17 PV14-10RX-C . . . . . . . . . . . . . . . . . .16 Grounding
CD-920-3/0 . . . . . . . . . . . . . . . . . . . .27 LCC10-14JAW-L . . . . . . . . . . . . . . .17 PV14-14RX-C . . . . . . . . . . . . . . . . . .16 Roadmaps
CD-920-4 . . . . . . . . . . . . . . . . . . . . .27 LCC10-14JAWF-L . . . . . . . . . . . . . . .17 PV14-6RX-C . . . . . . . . . . . . . . . . . . .16
CD-920-4/0 . . . . . . . . . . . . . . . . . . . .27 LCC10-14JAWH-L . . . . . . . . . . . . . . .17 PV14-8RX-C . . . . . . . . . . . . . . . . . . .16
CD-920-6 . . . . . . . . . . . . . . . . . . . . .27 LCC2-14AW-Q . . . . . . . . . . . . . . . . .17
CD-920-8 . . . . . . . . . . . . . . . . . . . . .27 LCC2-38DW-Q . . . . . . . . . . . . . . . . .17
CD-920H-2 . . . . . . . . . . . . . . . . . . . .27 LCC2/0-14AW-X . . . . . . . . . . . . . . . .17 R
CD-920H-6 . . . . . . . . . . . . . . . . . . . .27 LCC2/0-38DW-X . . . . . . . . . . . . . . . .17 RGCBNJ660P . . . . . . . . . . . . . . . . . .11
CD-930H-250 . . . . . . . . . . . . . . . . . .27 LCC250-12DW-X . . . . . . . . . . . . . . . .17 RGEJ1024PF . . . . . . . . . . . . . . . . . .12
CLRCVR1-1 . . . . . . . . . . . . . . . . . . .21 LCC250-38DW-X . . . . . . . . . . . . . . . .17 RGEJ1024PH . . . . . . . . . . . . . . . . . .12 Equipment
CLRCVR2-1 . . . . . . . . . . . . . . . . . . .21 LCC3/0-12W-X . . . . . . . . . . . . . . . . .17 RGEJ1036PF . . . . . . . . . . . . . . . . . .12 & Rack
Grounding
CLRCVR3-1 . . . . . . . . . . . . . . . . . . .21 LCC3/0-38DW-X . . . . . . . . . . . . . . . .17 RGEJ1057PF . . . . . . . . . . . . . . . . . .12 Kits
CT-100 . . . . . . . . . . . . . . . . . . . . . . .24 LCC4-14ADW-L . . . . . . . . . . . . . . . . .17 RGEJ624PF . . . . . . . . . . . . . . . . . . .12
CT-1550 . . . . . . . . . . . . . . . . . . . . . .24 LCC4-38DW-L . . . . . . . . . . . . . . . . . .17 RGEJ624PH . . . . . . . . . . . . . . . . . . .12
CT-1570 . . . . . . . . . . . . . . . . . . . . . .24 LCC4/0-14AW-X . . . . . . . . . . . . . . . .17 RGEJ636PF . . . . . . . . . . . . . . . . . . .12
CT-1700 . . . . . . . . . . . . . . . . . . . . . .24 LCC4/0-38DW-X . . . . . . . . . . . . . . . .17 RGEJ657PF . . . . . . . . . . . . . . . . . . .12
CT-2931 . . . . . . . . . . . . . . . . . . . . . .26 LCC6-10ABW-L . . . . . . . . . . . . . . . . .17 RGESD-1 . . . . . . . . . . . . . . . . . . . . .13
CT-930 . . . . . . . . . . . . . . . . . . . . . . .25 LCC6-14BDW-L . . . . . . . . . . . . . . . . .17 RGRB19 . . . . . . . . . . . . . . . . . . . . . .14
LCC6-14EW-L . . . . . . . . . . . . . . . . . .17 RGREJ1096 . . . . . . . . . . . . . . . . . . .14
Common
LCC6-14JAW-L . . . . . . . . . . . . . . . . .17 RGREJ696 . . . . . . . . . . . . . . . . . . . .14 Bonding
G LCC6-14JAWF-L . . . . . . . . . . . . . . . .17 RGRKCBNJ . . . . . . . . . . . . . . . . . . .14 Network
GB2B0304TPI-1 . . . . . . . . . . . . . . . .15 LCC6-14JAWH-L . . . . . . . . . . . . . . . .17 RGRKCBNJEJ . . . . . . . . . . . . . . . . .14 (CBN)
GB2B0306TPI-1 . . . . . . . . . . . . . . . .15 LCC6-38BDW-L . . . . . . . . . . . . . . . . .17 RGS134-1 . . . . . . . . . . . . . . . . . . . . .11 Components
GB2B0312TPI-1 . . . . . . . . . . . . . . . .15 LCC6-56BW-L . . . . . . . . . . . . . . . . . .17 RGS134-10-1 . . . . . . . . . . . . . . . . . .11
GB4B0612TPI-1 . . . . . . . . . . . . . . . .15 LCC8-10ABW-L . . . . . . . . . . . . . . . . .17 RGTBS-C . . . . . . . . . . . . . . . . . . . . .14
GB4B0624TPI-1 . . . . . . . . . . . . . . . .15 LCC8-14ABW-L . . . . . . . . . . . . . . . . .17 RGTBSM6-C . . . . . . . . . . . . . . . . . . .14
GPL-14-X . . . . . . . . . . . . . . . . . . . . .22 LCC8-14DW-L . . . . . . . . . . . . . . . . . .17 RGTS-C . . . . . . . . . . . . . . . . . . . . . .14
GPL-15-X . . . . . . . . . . . . . . . . . . . . .22 LCC8-38DW-L . . . . . . . . . . . . . . . . . .17 RGTSM6-C . . . . . . . . . . . . . . . . . . . .14
GPL-8-Q . . . . . . . . . . . . . . . . . . . . . .22 LCCX1-14A-X . . . . . . . . . . . . . . . . . .18 RGW-100-1 . . . . . . . . . . . . . . . . . . . .13
LCCX1-38D-X . . . . . . . . . . . . . . . . . .18 RGW-12-1 . . . . . . . . . . . . . . . . . . . . .13
Crimping
LCCX1/0-14A-X . . . . . . . . . . . . . . . .18 RGW-32-1 . . . . . . . . . . . . . . . . . . . . .13 Tools
H LCCX1/0-38D-X . . . . . . . . . . . . . . . .18
HTCT2-2-1 . . . . . . . . . . . . . . . . . . . .20 LCCX2-38D-E . . . . . . . . . . . . . . . . . .18
HTCT250-2-1 . . . . . . . . . . . . . . . . . .20 LCCX2/0-14A-X . . . . . . . . . . . . . . . .18 W
HTCT250-250-1 . . . . . . . . . . . . . . . .20 LCCX2/0-38D-X . . . . . . . . . . . . . . . .18 WB12-L . . . . . . . . . . . . . . . . . . . . . . .23
HTCT6-6-1 . . . . . . . . . . . . . . . . . . . .20 LCCX250-38D-X . . . . . . . . . . . . . . . .18 WB34-X . . . . . . . . . . . . . . . . . . . . . .23
HTWC2-2-1 . . . . . . . . . . . . . . . . . . . .19 LCCX3/0-38D-X . . . . . . . . . . . . . . . .18 WB58-Q . . . . . . . . . . . . . . . . . . . . . .23
HTWC250-2-1 . . . . . . . . . . . . . . . . . .19 LCCX4-14AB-L . . . . . . . . . . . . . . . . .18
HTWC250-250-1 . . . . . . . . . . . . . . . .19 LCCX4-38BD-L . . . . . . . . . . . . . . . . .18
HTWC6-6-1 . . . . . . . . . . . . . . . . . . . .19 LCCX4/0-38D-X . . . . . . . . . . . . . . . .18 Technical
LCCX6-10B-L . . . . . . . . . . . . . . . . . .18 Information
LCCX6-14AB-L . . . . . . . . . . . . . . . . .18
K LCCX6-14D-L . . . . . . . . . . . . . . . . . .18
KP1-C . . . . . . . . . . . . . . . . . . . . . . .23 LCCX6-38AC-L . . . . . . . . . . . . . . . . .18
KP2-L . . . . . . . . . . . . . . . . . . . . . . . .23 LCCX6-38D-L . . . . . . . . . . . . . . . . . .18
LCCX8-10AB-L . . . . . . . . . . . . . . . . .18
LCCX8-14AB-L . . . . . . . . . . . . . . . . .18
LCCX8-14D-L . . . . . . . . . . . . . . . . . .18
LCCX8-38D-L . . . . . . . . . . . . . . . . . .18
LTYK . . . . . . . . . . . . . . . . . . . . . . . . .15
Index

For service and technical support, call 800-777-3300 (outside the U.S. and Canada, see back cover). 31
PANDUIT is a global leader in cabling and communication products,
delivering end-to-end solutions in support of
demanding electrical and networking requirements.

PANDUIT Catalogs

Cable Ties Termination Solutions


SA-CTCB03 SA-TMCB02

!PAN-TY ® Cable Ties !CONTOUR-TY ® Cable Ties !PAN-TERM ® Terminals !Crimping Tools and Dies
!PAN-TY Clamp Ties
®
!DURA-TY Cable Ties

!PAN-TERM ® Disconnects !PAN-LUG ™ Mechanical Connectors
!PAN-TY Push Mount Ties
®
!BELT-TY In-Line Cable Ties

!PAN-TERM Splices
®
!PAN-LUG ™ Grounding Connectors
!PAN-TY Marker Ties
®
!TAK-TY Hook & Loop Cable Ties
®
!PAN-TERM Ferrules
®
!Support Products
!DOME-TOP ® Barb Ty Cable Ties !STA-STRAP ® Cable Ties !PAN-LUG ™ Compression
!DOME-TOP ® Barb Ty Clamp Ties !Cable Tie Installation Tools Connectors
!DOME-TOP Barb Ty Marker Ties
®
!Custom Hot Stamping

Wiring Accessories/Abrasion Protection Stainless Steel Products


SA-CTCB03 SA-SSCB06

!Adhesive Backed Cable Tie !Grommet Edging !PAN-STEEL ® Stainless Steel !PAN-STEEL® System Accessories
Mounts !Braided Expandable Sleeving Cable Ties !PAN-STEEL® System
!Screw Applied Cable Tie Mounts !Corrugated Loom Tubing !PAN-STEEL ® Stainless Steel Permanent Identification
!Flat Cable Mounts and Fittings Strapping
!Fixed Diameter Clamps !Heat Shrink Tubing !Installation Tools
!Harness Board Accessories !Non-Shrink PVC Tubing
!Spiral Wrap !PAN-WRAP ™ Split Harness Wrap

Identification Products Surface Raceway


SA-IDCB16 SA-SRCB02

!Hand-Held Printers !Lockout/Tagout Products !Office Furniture Raceway !Faceplates, Surface Mount Outlet
!Desktop Printers !Voltage Markers !Cove Raceway Boxes & Labeling Administration
!Labeling Software !Warning Labels !PAN-WAY TG-70 Surface Raceway
® !PAN-WAY ® LD Profile Surface
Raceway
!Computer Printable Labels !Safety Signs and Tags !PAN-WAY ® T-70 & Twin-70
Surface Raceway !PAN-WAY ® T130 Surface Raceway
!Wire Markers !Letters and Numbers
!PAN-WAY ® T-45 Surface Raceway !PAN-POLE ™ Outlet Poles
!ULTIMATE ID ® Network
Labeling System

Wiring Duct Network Connectivity


SA-WDCB05 SA-NCCB04

!PANDUCT ® Slotted Wall !PANDUCT ® Hinged Slotted Wall !Modules !Racks & Cable Management
Wiring Duct Wiring Duct !ULTIMATE ID ® System !Grounding and Bonding
!PANDUCT ® Solid Wall Raceway !PANDUCT ® Flexible Wiring Duct !Work Area !Fiber Routing
!PANDUCT ® Halogen Free Slotted !PANDUCT ® Low Smoke Slotted !Zone Cabling !Surface Raceway
Wall Wiring Duct Wall Wiring Duct
!Patch Panels, Copper Patch !Labeling & Administration
!PANDUCT ® Flush Cover Round !Wiring Duct Accessories and Cords & Punchdowns !Cable Ties & Accessories
Hole Wiring Duct Installation Tools
!Fiber Connectors, Enclosures &
Patch Cords

32