Program PowerSuite

HISTORY

Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03

The PowerSuite Team


This document is a record or history database that describes what's new in the latest
Contents
and previous versions of this program.
• Installation
• Compatibility
• New in This Version PowerSuite is a software application designed for programming Compack-, Smartpack-,
• In Previous Versions
• Reported Problems
Smartpack2- and Smartpack S-based DC Power Supply Systems from a personal
computer.
Installation
Computer’s Requirements
— Minimum:
PC with 1GHz CPU, 512MB RAM memory, 850MB free hard disc space, a 1024x768
display, MS Windows XP Home Edition as the operating system, MS Internet
Explorer 6.0 and Windows Installer 3.1 or later.
— Recommended:
PC with 1GHz CPU, 512MB RAM memory, 2GB free hard disc space, a 1024x768
16 bit color display and MS Windows 7 as the operating system.
— Communication with the Controller:
The PC running PowerSuite may be connected to the controller either locally via an
USB port or remotely via an Ethernet LAN (UDP tunneling protocol)
Notice:
— Do not connect the USB cable
to the PC before installing the application and drivers, if USB port connection is used
— Automatic Upgrade
The PowerSuite installation software will upgrade and overwrite your previously
installed version of PowerSuite.
— Upgrade of USB Driver 6.3
The installation software will prompt you to upgrade the Eltek USB to UART driver to
version 6.3 (required for MS Windows 7 and 64 bit operating systems).
If you are using the USB port connection and are unsure whether you have such a
driver installed, or which version, we advise you to click on the “Install” button to
install or upgrade the driver.
Installation Procedure:
You can install PowerSuite directly from the CD-ROM, from the FTP server or from the
Eltek intranet. Follow the instructions on the screen.
In short, to install PowerSuite carry out following steps:
1. Run the setup.exe file,
and the “PowerSuite Install Wizard” will guide you through the installation
— Let the wizard install the Eltek USB driver 6.1, if unsure
— Skip steps 2 and 3, if connecting to the Eltek controller via Ethernet LAN
2. Switch the Eltek controller ON and connect the USB cable
3. Wait for Windows to detect the Eltek controller (“Found New Hardware” balloon
tip)
In the “Found New Hardware Wizard”, select:
— “No, not this time” (not to connect to Windows Update),
— “Install the software automatically (Recommended)” and
— “Continue Anyway”
— After the installation, you must let Windows restart the computer
4. Start the PowerSuite program

More info in Online Help: installing when connecting via USB or via Ethernet
^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 1(19)

www.eltek.com
.
Compatibility  Eltek Controllers, CAN Nodes versus PowerSuite
For a complete overview of compatibility between PowerSuite, controllers, rectifiers and communication
protocols, e-mail your contact person at Eltek.

Controller Firmware PowerSuite Version No.


Part No. & Version No. 3.4
3.4.1 3.5
1.0 2.0 2.2 2.3 2.4 3.0 3.1 3.2 3.3 3.4.2 3.6
(SP) 402070.003, v 01.01 X
(SP) 402070.003, v 01.02 X X X X X X X X X X
(SP) 402070.003, v 01.03 X X X X X X X X X X

(SP) 402073.003, v 01.00 X X X X

(SP) 402073.009, v 02.00 X X X X X X X X X


(SP) 402073.009, v 02.02 X X X X X X X X
(SP) 402073.009, v 02.03 X X X X X X X X
(SP) 402073.009, v 02.04 X X X X X X X
(SP) 402073.009, v 03.03 X X X X X X
(SP) 402073.009, v 03.04 X X X X X
(SP) 402073.009, v 03.05 X X X
(SP) 402073.009, v 03.07 X X X
(SP) 402073.009, v 03.08 X X
(SP) 402073.009, v 03.09 X X

(SP2) 405006.009, v 1.0 X X X


(SP2) 405006.009, v 1.1 X X X
(SP2) 405006.009, v 1.2 X X X
(SP2) 405006.009, v 2.0 X X X
(SP2) 405006.009, v 2.1 X X
(SP2) 405006.009, v 2.1.1 X X
(SP2) 405006.009, v 2.2 X
(SP2) 405006.009, v 2.2.1 X

(SP2B) 405007.009, v 1.03 X

(SP2BI) 405019.009, v 2.3.1 X

(CP) 405002.009, v 01.00 X X X X X


(CP) 405002.009, v 01.01 X X X X X
(CP) 405002.009, v 01.02 X X X X
(CP) 405002.009, v 01.03 X X X X
(CP) 405002.009, v 01.04 X X X X
(CP) 405002.009, v 01.05 X X X X
(CP) 405002.009, v 2.1.2 X X

(SP S) 405021.009, v 2.1 X X


(SP S) 405021.009, v 2.2.1 X

(SmNde) 402077.009, v 4.1 X


(BMon) 402086.009, v 1.04 X
(LMon) 402087.009, v 2.01 X
(IOMon) 402088.009, v 4.12 X
(FxMon) 405028.009, v 1.00 X

Controllers:
SP= Smartpack; SP2= Smartpack2; SP2B= Smartpack2 Basic; SP2BI= Smartpack2 Basic Industrial and
SP S= Smartpack S
Control Units & CAN nodes:
SmNde= SmartNode; BMon= Battery Monitor; LMon= Load Monitor; IOMon= I/O Monitor; FxMon=
FlexiMonitor

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 2(19)

www.eltek.com
Version &
New in This Version
Date
Art. 402207.009

3.6 New functionality (3.6)


2014-10-03  Improved program installation
— Using Wix instead of InstallShield
— Secure the removal of all PowerSuite traces from Windows registry after uninstall
— Added terms and conditions in PowerSuite installation
 Implemented support for 380V system voltages
 Included command button <Set Default Cfg with XML Files>
to load XML default files from internal disc (Flash) and external disc (SD card)
 Improved the Energy Log user interface
adding columns Time, Day, Week, Month, as in the controller’s web-based interface
 Implemented Energy Log for up to 6 solar chargers
 Implemented Drop-Diode setting on Load Voltage input
 Implemented Destination setting in PComm messages
 Included a new Generator Stop criteria, when solar or wind chargers supply the load
 Implemented to display only the Value and Description fields in Power monitors
 Implemented the display of rectifiers as converters, when they are DC fed
 Included the FlexiMonitor top level status in the Control System dialog box
 Implemented the “Suppress Mains Alarm when the generator is not running” setting
 Included the setting “Allow Rectifier Remote ON/OFF” check box,
at Factory Access level
 Expanded the configuration of relay outputs with Nag-Timer settings (“Normally
Activated Resettable” and “Normally Deactivated Resettable”)
 Implemented Power Animation support for systems with DC feed
 Implemented the display of critical and warning texts in the Event Log
 Included new Time Delay values on temperature alarm monitors, to match new
default values
 Implemented that System Polarity setting does not affect Programmable Inputs
configured as “Voltage”
 Support for Elevation setting with negative values
 Improved FlexiMonitor presentation in the user interface

Most Important Fixes in PowerSuite (3.6):

ID Symptom Status
8996 Programmable inputs configured as “Voltage” are not presented Fixed in version 3.6
correctly in the Data Log

9485 The tunnelling protocol communication does not work correctly via Fixed in version 3.6
modems

8785 The calibration of voltages above 327V does not function Fixed in version 3.6
satisfactorily

9154 Resetting of the Master password is not working correctly Fixed in version 3.6

8895 Loading of binary configuration files created by the controller’s web- Fixed in version 3.6
based interface does not function satisfactorily

8836 The Power Animation does not update the displayed status correctly Fixed in version 3.6

7795 Internal symmetry reports an alarm, if internal symmetry Fixed in version 3.6
measurement is disabled

^Top

 Also, read the description of reported problems or bugs, at the end of this file

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 3(19)

www.eltek.com
Version &
In Previous Versions
Date

3.5 New functionality (3.5)


2013-08-15
 Implemented grouping functionality for AC Mains (Mains Groups)
 Implemented grouping functionality for battery banks (Battery Groups)
 Added support for new I/O Monitor units (Flexi Monitor)
 Increased the number of available Alarm Output Groups to 49 groups
 Modified the Power Animation pane to resemble the Web-based interface

 Added following new Alarm Monitors:


— “Rect Groups in minor alarm”
— “Bad Test Results”
— Voltage alarm monitors in the Load dialog boxes
(configured as Voltage or Drop Diode)

 Included following new configuration settings:


— “Exclude Redundant Rectifier”
— Under current limitation, added Rectifier Capacity Limit
— An alternative Battery Interval Test schedule
— Configuration of Max. Fan Speed
— A ticker or clock for the Outdoor Test mode

 Added Partial Shutdown in the Event list


 Implemented the presentation of voltage values up to 655V

Most Important Fixes in PowerSuite (3.5):

ID Symptom Status
7540 In the “Output Test” dialog box, the contactor Fixed in version 3.5
graphics on the test buttons are now displayed
correctly

7767 Remove /hide Rectifier disconnect Fixed in version 3.5

8477 Setting Load Fuse Configuration from file does not Fixed in version 3.5
work

8478 Setting LVBD Disconnect / Reconnect voltage from Fixed in version 3.5
file — after setting NiCad batteries (battery cell
voltage below 1.72V) from file — does not work

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 4(19)

www.eltek.com
Version &
In Previous Versions
Date

3.4.2 New functionality (3.4.2)


2013-04-04
 No new functionality has been added

Most Important Fixes in PowerSuite (3.4.2):

ID Symptom Status
8006 In the file IO Monitor Configuration.xml, the data Fixed in version 3.4.2
type for the Fan Control Temp High data and the
Fan Control Temp Low data was corrected

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

3.4.1 New functionality (3.4.1)


2012-09-27
 No new functionality has been added

Most Important Fixes in PowerSuite (3.4.1):

ID Symptom Status
7190 Configuring the Smartpack rectifiers’ default voltage Fixed in version 3.4.1
works properly, even if the voltage is not displayed
correctly in PowerSuite, (byte swapping from the
rectifier).
The default voltage is now displayed correctly in
PowerSuite.

7199 The Scaling tab in the scalable input’s dialog box is Fixed in version 3.4.1
now displayed correctly

7218 The error message caused when right-clicking on Fixed in version 3.4.1
the “Fan Control” — in the Outdoor dialog box to
Configure or Calibrate the input — is now corrected

7229 Refreshing data (F5) — in the Config tab of the Fixed in version 3.4.1
alarm monitors’ dialog boxes — is now working
correctly

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 5(19)

www.eltek.com
Version &
In Previous Versions
Date

3.4 New functionality (3.4)


2012-08-27
 Implemented upgrade for USB to UART driver version 6.3
 Added support for Wind charger and fuel cell units
 Added support for Smartpack S and Smartpack2 Basic Industrial controllers
 Added rectifier bay functionality (max. 96 rectifiers per bay; max. 10 bays)
 Added current monitor functionality (configuration and status update)
 Added field to enter rectifier default voltage
 Added “Silence rectifier alarm” setting
 New events: Critical, warning, silence buzzer and equalize, earth fault inhibit
 New monitors:
o Battery: Ah charge counter, Ah discharge counter
o Load: load currents, load drop diode
o Control unit: Earth fault
 Added PS language; Japanese, Portuguese, Korean
 Added control unit language; Korean, Greek, Japanese and US English
 DCDC48 has been renamed to DCDC
 DC voltage allows values up to 630V
 New outdoor functionality: Delta-temp monitor and temp source selection
 New setting in output configuration dialog: off delay, used to delay alarm output reset
 Added new tab in battery dialog: equalize (configuration and status update)
 Added button in energy page to reset min/max values
 Added reading of physical input settings for monitors
 Added new start/stop criteria for generator control
 Removed temp calibration for Compack, SP2 and SP S controllers.
SP1 has temp calibration on factory level
 Added password in command line
 Data log setup moved from factory level to service level
 Added power/voltage characteristics in Wind monitor dialog
 Current monitors for load group, mutually exclusion against battery currents
 Data log: increased max number of logs to 20. Added blank monitor
 Communication speed changeable
 Default XML files: modified data type to correspond to JSON data types
 Added virtual input for some programmable inputs
 Added boost/equalize temp compensation enable/disable

Most Important Fixes in PowerSuite (3.4):

ID Symptom Status
4737 Corrected the longitude limitation error Fixed in version 3.4

5085 Corrected error in result group column in logical Fixed in version 3.4
groups window

4032 Improved the data displayed in battery table dialog Fixed in version 3.4
box (deleted rows were shown with confusing
values)

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 6(19)

www.eltek.com
Version &
In Previous Versions
Date

3.3 New functionality (3.3)


2010-11-10  Compatibility with MS Windows 7 and 64 bit operating systems
 Implemented upgrade for USB to UART driver version 6.1
 Increased Import/Export tool, by only recording configuration changes to an XML-file
(Factory Access)
 Improved Import/Export tool, to also support binary configuration files
 Added new “Location” tab with Map Coordinates fields for entering the exact Power
System global position
 PowerSuite language improvements:
New PowerSuite language: Japanese
Implemented support to select Portuguese as controller language
 Added support for Smartpack2 Master and Smartpack2 Basic controllers
 Added support for I/O Monitor2 units (T2)
 Added support for Mains Monitor units
 Implemented “Mains Outage Log” functionality
 Improved display of the tree in Explorer pane: Battery node is hidden when battery
banks and battery monitors are set to 0
 Renamed the “Load Bank X” term with “Load Group X” in the tree in Explorer pane
 The “Efficiency” tab is displayed in the “Rectifiers” dialog box for all rectifier types
 Implemented functionality for “Tank Configuration” in the “Generator” dialog box
 Implemented a “Run Hours Log” in the “Generator” dialog box
 Implemented a “Fuel Consumption Log” in the “Generator” dialog box
 Implemented a battery “Discharge Cycles Log” in the “Battery” dialog box
 Implemented “Voltage Setup” as start criteria in the “Generator” dialog box

Most Important Fixes in PowerSuite (3.3):

ID Symptom Status
3798 Activating the “Restore Settings” in large systems, Fixed in version 3.3
does not always restore settings in all units (Slower reconnection to ensure correct
restoring of settings in all units)

3717 When system polarity is set to Negative, some Fixed in version 3.3
voltages may be stored incorrectly

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 7(19)

www.eltek.com
Version &
In Previous Versions
Date

3.2 New functionality (3.2)


2009-09-18  Only improvements are implemented in this version

Most Important Fixes in PowerSuite (3.2):

ID Symptom Status
3747 The configuration file for I/O units does not include Fixed in version 3.2
events for Outdoor Temperature monitors

3771 The XML file includes all events for battery fuse Fixed in version 3.2
monitor

3772 In some cases, for Programmable Inputs, the Fixed in version 3.2
configuration list includes Clock and Voltage for
battery fuse monitor

3746 Site Manager dialog box uses old password for Fixed in version 3.2
verification, after changing the password from the
Access menu (from v2.3-v3.1)

3799 The Shuffle Time in Rectifier Efficiency Manager is Fixed in version 3.2
too low in the Smartpack default configuration file

3721 Reallocating rectifiers, in Rectifier Overview, does Fixed in version 3.2


not function

3728 Alarms overview dialog box displays incorrect Fixed in version 3.2
number of outputs

3715 All minor alarms for I/O units are displayed as Fixed in version 3.2
Control Unit Error in the Alarms Overview Summary

3684 The Alarms Overview - Review filters is very slow Fixed in version 3.2
due to too many monitors are read

3701 Event Log files have no file extension Fixed in version 3.2

3777 Modem connections do not function Fixed in version 3.2


. (Slow response on 9600 baud
connections. Reconnect, if
. communication is aborted)

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 8(19)

www.eltek.com
Version &
In Previous Versions
Date

3.1 New functionality (3.1)


2009-06-05  Support for Compack controllers
 Support for Solar Charger Units
 Implemented configuration of logged alarm monitors in Data Log
 Implemented logging of Energy and Power
 New selection: enable/disable Efficiency Manager functionality (HE)
 New Temperature Handler tab (alarm monitors) in control unit’s dialog boxes
 Increased the Event Log’s maximum number of events
 Improved Import/Export Configuration (“clone tool”) to also read from customized files,
in addition to the default Configuration Files (xml)
 Added new functionality to I/O Monitor units: Humidity Reduction Scheme, Pressure
Test, selective temp probe setting on temperature monitors
 Implemented new alarm monitor in I/O Monitor units: Speed Deviation
 Added new digital inputs’ configuration settings: Voltage and Clock
 Added new control for digital inputs used with setting: Clock
 Implemented more PLC functionality, for “AND (&)” of alarm groups
 Added Standard Generator setup
 Improved 60V systems settings command: Set Default
 PowerSuite language improvements. New language: Greek
 Added selection check boxes for Load Events, in Alarms Overview dialog box
 Improved current measurement functionality: display in deci-ampere
 Implemented Master Password functionality
 Added new events: Battery Test Inhibit and System Shut Down (Use rectifier ON/OFF
function)
 Implemented upgrade for USB to UART driver version 5.4

Most Important Fixes in PowerSuite (3.1):

ID Symptom Status
3190 Programmable Inputs are displayed as “Configured Fixed in version 3.1
As: Normally Closed”, when I/O card is not installed

2383 PowerSuite program hangs when suddenly Fixed in version 3.1


disconnecting the cable between the PC and the
Smartpack controller.

3489 In the Data Log dialog box, the Cancel button does Fixed in version 3.1
not stop loading the log.

3301 Error message “Object reference not set to an Fixed in version 3.1
instance of an object”.

3420 Error message when no connection. In case of Fixed in version 3.1


unstable communication the user will be notified,
with the possibility to disconnect or to continue
communication.

3655 The "Find COM-Port #" button in the Site Manager Fixed in version 3.2
dialog box doesn’t work properly.

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 9(19)

www.eltek.com
Version &
In Previous Versions
Date

3.0 New functionality (3.0)


2008-06-26  New Alarms Overview dialog box
 Implemented C#-comm driver
 New Profiles functionality implemented
 Improved Import/Export dialog box (clone tool functionality)
 Improved Battery Table dialog box
 New dialog box – AC Generator functionality
 Support for new control unit - Mains Monitor
 Added password protection on I/O Monitor control unit
 Ability to rename Battery Monitor and Mains Monitor
 Data Log functionality is moved to control unit level
 Added system capacity scale, battery boost current threshold and voltage threshold
 Improved control on battery symmetry vs. digital inputs
 PowerSuite language improvements. New language: Russian
 Improved Site Manager dialog box
 Added attribute (versions header) in XML file
 Updated XML files
 Improved Modem Callback dialog box
 Improved OVS reference voltage; 4 decimals for better accuracy
 Implemented delete Data Log functionality
 Nominal voltage setting based on cell voltage and number of cells

Most Important Fixes in PowerSuite (3.0):

ID Symptom Status
2402 Site Manager’s difficulties resulting in wrong port Fixed in version 3.0
connections

2665 Import/Export (cloning tool) possibility to read other Fixed in version 3.0
files than default Smartpack

2152 Output Test dialog box should only display existing Fixed in version 3.0
outputs

2605 Fan Configuration reading functionality Fixed in version 3.0

2417 Rectifiers Reallocation problems with high IDs Fixed in version 3.0

2448 Slow navigation when activating tabs in Rectifiers Fixed in version 3.0
dialog box

2736 Battery Capacity (Ah) not saved in Smartpack (from Fixed in version 3.0
battery table file)

2677 MainsFail monitor deactivation – info about Fixed in version 3.0


consequences

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 10(19)

www.eltek.com
Version &
In Previous Versions
Date

2.4 New functionality (2.4)


2007-11-05  MS Windows Vista compatibility
 Battery-Capacity used alarm monitor
 I/O Alarm Interface Functionality on CAN bus connected units
 Rectifier Shut Down alarm monitor (only in Chinese versions)
 PowerSuite language improvements
 Eltek branding code implemented (logo, colours, etc)
 Import & Export configuration uses a new Wizard; clone tool improved
 Calibration, Scale and Configuration of Alarm Monitor functionality; improvement
 Battery Test Guard Time remaining time indication on Status bar; improvement
 Site Manager adjustments; improvement
 PowerSuite appearance options or themes ; improvement

Most Important Fixes in PowerSuite (2.4):

ID Symptom Status
1594 At times the dots in the Power Animation are not Fixed in version 2.4
displayed. Part of another window is displayed
instead.

1596 Missing monitor text link, after opening the Power Fixed in version 2.4
Summary pane and clicking on the Apply or OK
buttons. Also, after editing values, before clicking
on these buttons.

2178 The Clone tool write to file "Save button" does not Fixed in version 2.4
save file.

2415 The Reconnect message dialog box does not Fixed in version 2.4
disappear after clicking on the dialog box Cancel
button

2410 The Battery Bank Current alarm monitors do not Fixed in version 2.4
display the shunt size, before you edit the size
value manually

2416 The alarm monitor’s alarm group list is not updated, Fixed in version 2.4
when an alarm group is edited (outputs enabled) on
other control units than Smartpack

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 11(19)

www.eltek.com
Version &
In Previous Versions
Date

2.3 New functionality (2.3)


2007-07-dd  Rectifier ID reassignment directly from PowerSuite
 Connection to an Smartpack Connection File
 Modem Call-Back Functionality
 Battery String Monitor Functionality on CAN bus connected units
 All Smartpack connection and login tasks collected in the same dialog box
 Site Manager connection data (phonebook) preserved after upgrades
 Calibrate, Configure and Scale functionality on applicable Alarm Monitors
 Import & Export configuration data supports several units; improvement
 PowerSuite version displayed in title bar; improvement
 White unused nodes in Power Explorer pane; improvement
 More PowerSuite languages, added

Most Important Fixes in PowerSuite (2.3):

ID Symptom Status
1982 Rectifier Status and Details export Fixed in version 2.3

2079 Battery test log does not show correct info Fixed in version 2.3

1977 More information in the battery test log file Fixed in version 2.3

1995 Added explanation in discontinuance tab Fixed in version 2.3

1881 The OK button will not save data Fixed in version 2.3

2076 String view is not correct Fixed in version 2.3

906 In negative system polarity, most of the dc-voltages Fixed in version 2.3
will be shown as negative

2080 Status field - When system is in critical state, show Fixed in version 2.3
“Critical” in the status field

1849 Increased the number of maximum Control Units Fixed in version 2.3
from 10 to 100

1845 Control System \ Summary: Hide the OK and Apply Fixed in version 2.3
buttons

2062 Added "Reset Manual Alarm" in the "Tools" menu Fixed in version 2.3

2065 Options dialog - bug when closing dialog fixed Fixed in version 2.3

2125 Tree View - Only nodes that are "In view" are Fixed in version 2.3
updated for status. Should be all nodes where the
parent node is expanded

1120 The battery table Export to File function only Fixed in version 2.3
exports the actual displayed table values. Other
relevant battery test data will not be exported.

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 12(19)

www.eltek.com
Version &
In Previous Versions
Date

2.2 New functionality (2.2)


2007-03-16  No new functionality has been added

Most Important Fixes in PowerSuite (2.2):

ID Symptom Status

NNN When manually configuring Battery Symmetry Fixed in version 2.2


settings with Power Suite, v 2.1, other battery
configuration settings might be inadvertently
changed too.

 Also, read the description of reported problems or bugs at the moment, at the end of
this file.

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 13(19)

www.eltek.com
Version &
In Previous Versions
Date

2.1 New functionality (2.1)


2006-12-21  Site Manager, PowerSuite site connection overview
 Storage of the 5 last site connections
 Modem Dial-up functionality
 Efficiency Management functionality
 Distributed functionality and configuration, improved
 PowerSuite languages, added
 Smartpack language configuration
 Default setting for 48V and 24V systems
 Smartpack Data Log overview
 PowerSuite Data Log overview
 Symmetry Configuration, improved
 Battery String overview, improved
 Discontinuance Battery Test
 Inhibit Battery Test option
 Battery Test Log view, improved
 DeltaStringCurr – monitor, added
 RectCapacity – monitor, added
 RectCurrShareEr – monitor, added
 “Max. Discharge (Ah)” configuration in Simplified Battery Test, added

Most Important Fixes in PowerSuite (2.1):

ID Symptom Status

904 The PowerSuite program window hides behind Fixed in version 2.1
other program windows

1098 LVD monitors may display negative values, when Fixed in version 2.1
entering data outside the min/max limits

1118 The Get Data button, in the Battery table data, may Fixed in version 2.1
be disabled (grey), when it should be active.

1198 The String Cell monitor text may not be displayed Fixed in version 2.1
correctly, the first time you open the window.

1605 The Control Unit dialog box may sometimes hide Fixed in version 2.1
behind the Animation View pane.

Xxxx We have also corrected several other fixes, among Fixed in version 2.1
them fixes with following ID numbers: 1046, 1506,
1520, 1573, 1589, 1649, 1650, 1685, 1785, 1805,
1832.
For detailed information about these and other
fixes, e-mail your contact person at Eltek .

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 14(19)

www.eltek.com
Version &
In Previous Versions
Date

2.0 New functionality (2.0)


2006-07-17
 Distributed functionality
Support for larger power systems with several Smartpack controllers.
 Multilanguage support
 Automatic data refresh for dialog boxes
 Dialog boxes design improvement
OK and Cancel buttons located on the bottom of dialog boxes
 PowerSuite Help implemented
 Improved Event-log functionality
 More configurable LVD alarm groups
 Shunt scaling implemented
 Expanded calibration functionality
 Control unit Error monitor implemented
 Smartpack’s front panel option disabled
 Rectifier Fail suppressed, when Mains Fail option is active
 Rectifier Walk-in time configuration implemented
 Rectifier Communication Error monitor implemented
 Rectifier Capacity monitor implemented
 Battery Test/Boost event configuration implemented
 Manual Reset Configuration monitor extended
 Hysteresis Configuration monitor implemented
 Time Delay Configuration monitor implemented
 Fuse Input Configuration (NO/NC/Diode Matrix) implemented

Most Important Fixes in PowerSuite (2.0):

ID Symptom Status

611 If Time/Date is adjusted during a Battery Test or Fixed in version 2.0


boost it will affect the test time.

832 Test Mode could have sub levels: Boost, Float Fixed in version 2.0
Man., Auto, Interval and Charge/Discharge.

834 If you try to start a Battery Test and it is not Fixed in version 2.0
possible, a warning should be displayed informing
the reason.

867 Refreshing the Power Explorer pane expands all Fixed in version 2.0
the tree options.

881 Cancel functionality. Automatic refresh. Fixed in version 2.0

918 As the Event Log list is displayed in a ring-buffer- Fixed in version 2.0
manner, all messages will re-appear after last
message.

923 Alarm group names longer than 16 characters may Fixed in version 2.0
be entered in PowerSuite. But, characters above 16
are lost when refreshing (Smartpack’s max. string
length)

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 15(19)

www.eltek.com
Version &
In Previous Versions
Date
930 It is possible to set the rectifier’s Standby Voltage to Fixed in version 2.0
be higher than the battery test End Voltage. This
may cause the battery test to enter an endless loop.

972 Changing temperature scale (Celsius, Fahrenheit) Fixed in version 2.0


does not update battery monitor’s denominations.

974 Information, controls, etc. may not refresh properly Fixed in version 2.0
in certain dialogue windows.

1009 When Time / Clock is selected in read only mode, Fixed in version 2.0
you are not allowed to log in to adjust the time.

1027 Certain buttons and controls seem to be Fixed in version 2.0


deactivated at times.

1059 Warnings for incorrect system voltages entries do Fixed in version 2.0
not refresh properly (hang)

1073 The Battery Test results table and the graph Fixed in version 2.0
columns at the bottom are not displayed in the
same order, when more than 10 test results are
displayed. The result parameters are displayed
correctly.

1097 Slow update of animations Fixed in version 2.0

1107 When pressing the + or – button in the Explorer Fixed in version 2.0
pane -- or when double-clicking the Expand /
Retract Hierarchy Tree icon -- a window is opened
from the Explorer pane.

1108 Power System Install date and Service date have Fixed in version 2.0
no Min/Max check in PowerSuite.

1125 The Disconnect / Connect animation may display Fixed in version 2.0
red dots missing.

1128 Calibration in system configuration may not refresh Fixed in version 2.0
the displayed data. Neither the Refresh button nor
closing and reopening the window will refresh the
data.

1130 When you open a LVLD monitor, blank fields (no Fixed in version 2.0
values) may be displayed.

1132 PowerSuite allows displaying LVLD and LVBD data Fixed in version 2.0
in several windows.

1134 Incorrect temperature scale is displayed in the Fixed in version 2.0


Rectifier detailed data. E.g.: displaying degree
Celsius when Fahrenheit are selected.

1587 System Configuration dialog box crashes if not Fixed in version 2.0
loaded completely.

1598 Active alarm groups prevent status on slave alarm Fixed in version 2.0
groups to be presented correctly.

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 16(19)

www.eltek.com
Version &
In Previous Versions
Date
1602 Error message in Event Log. Fixed in version 2.0

1606 Buttons disappear when downsizing the Event Log Fixed in version 2.0
dialog box.

1607 Alarm group Configuration may report an error Fixed in version 2.0
message, forcing to quit the application.

xxxx PowerSuite allows displaying Battery Test Result Fixed in version 2.0
data in several windows.

^Top

1.0 New functionality (1.0)


2005-11-04
 Finally we release the official version!
This program is made for you, hopefully making your Flatpack2 configuration tasks
easier.
 The beta testing is now completed.
The R&D Department thanks Asbjørn, Steffen, Hanne and Bjarne-- special beta test
group -- for good accomplished testing job. They have used PowerSuite extensively
during many months.

Most Important Fixes in PowerSuite (1.0):

 Hopefully we have been able to removed most of the initial problems in the
application. But should you find any bugs, please let us know about them
 Future software versions will describe the new functionality and fixes in each version.
Also, this history file will describe the reported problems or bugs at the moment.

Beta Our beta test group tested and used PowerSuite during many months, and the R&D
2005-mm- Department has revised and improved the software extensively.
dd

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 17(19)

www.eltek.com
Reported Problems ~ 2014-10-03
ID Symptom Status Workaround
5419 If a programmable input is set to Eltek has confirmed that this Set the input to "Voltage", then select one of the other
"Clock", other options like "Normally might be annoying, and is options
Open", "Normally Closed" and "Diode working to correct the issue.
Matrix" might not be selectable in the
control unit

7090 & In Compack-based 12V power Eltek has confirmed that this To configure the correct calibration values, regardless of
7136 systems, the controller’s might be bothersome, and is what the programmable inputs or “LoadFuse nn” alarm
programmable inputs and the working to correct the issue. monitor are configured as, do following in PowerSuite:
“LoadFuse nn” alarm monitor do not 1- Open in turn all “ProgInput n.n” and the “LoadFuse nn”
get correct calibration values by alarm monitor dialog boxes
default. 2- In the Configuration tab, select an option different than
the correct one, e.g. “Diode Matrix”, and click “Apply”
button
3- Then select the correct option, and the “OK” button

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 18(19)

www.eltek.com
The PowerSuite Team
Many in Eltek have contributed to create the PowerSuite application, among others:

Programmers & Architects: Tonny Mastad


Hanne Cathrine Enger
Sherry Zhang
Tonny Mastad Testers: Asbjørn Skjereng
Hanne Cathrine Enger
Bjørn Marthinsen

Product Manager: Bjarne Stavnes

Help and Installation: Manuel Fernández

Contributors Ole Morten Lunden


Håkon Andersen

Thanks to all for a great job!

^Top

PowerSuite Program History


Doc 402207.063, Issue 3.6, 2014-October, Pub. 2014-10-03 19(19)