Está en la página 1de 34

TATA PROJECTS LIMITED

TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 1


CIVIL STRUCTURE

ITC LIMITED: INTEGRATED FOODS FACTORY AT PANCHLA, HOWRAH

COOLING TOWER : DESIGN DOCUMENT FOR CIVIL STRUCTURE


Document No: TPL-3430-X9690-EC-DC-6042

Owner: - ITC LIMITED

BOP Contractor: - M/s. TATA PROJECTS LIMITED


HYDERABAD

REV.NO. R0 ISSUE

INITIALS SIGN. INITIALS SIGN. INITIALS SIGN. INITIALS SIGN.

PPD.BY GA Sd/-

CHD.BY RS Sd/- R0

APD.BY AS Sd/-

DATE 24.02.2016
TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 2
CIVIL STRUCTURE

SEC. NO DESCRIPTION

1.0 GENERAL

2.0 SCOPE

3.0 REFERENCES

4.0 DESCRIPTION OF STRUCTURE

5.0 MATERIALS

5.1 Cement
5.2 Concrete
5.3 Reinforcement steel

6.0 LOADS AND LOAD COMBINATIONS

6.1 Dead Load


6.2 Live Load
6.3 Seismic/Wind Load

7.0 STRUCTURAL ANALYSIS AND DESIGN

7.1 Design summary of beam and column


7.2 Design summary of slab

8.0 DESIGN CALCULATIONS

ANNEXURE A :

STAAD FILE

DESIGN CALCULATION FOR SLAB


TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 3
CIVIL STRUCTURE

1.0 GENERAL
This document covers the analysis and design of foundations for COOLING TOWER of integrated
foods factory of ITC Limited at Panchla, Howrah (WB)

2.0 SCOPE
The document covers the design of super structure and sub structure.

3.0 REFERENCES
The following codes and standards with the latest revisions and drawings have been referred
for the structural analysis and design

3.1 Codes and Standards


IS : 456 - Code or practice for Plain and Reinforced Concrete
IS : 875 - Code of practice for Design Loads (other than Earthquake) for Buildings and
Structures
Part 1 – Dead Loads
Part 2 – Live Loads
Part 3 – Wind Loads
Part 5 – Load combinations
IS: 1893 - Code of practice for Earthquake Resistant Design
SP 16 - Design aids for Reinforced Concrete to IS: 456
IS 3370 -2009
(Part I & II) - Concrete structure for storage of liquids - Code of practice

3.2 Drawings / Documents


TPL-3430-X5000-EM-LA-1000 Plot Plan

4.0 DESCRIPTION OF STRUCTURE


COOLING TOWER platform is of size 17.4 m X 6.4 m. The average NGL at the location is 8.364 m
and the FGL is 10.00 m. Boreholes BH 4, 5, 8 are in the vicinity of the area.
TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 4
CIVIL STRUCTURE

4.1. Soil Data


2
The net SBC at 1.2 m below NGL (2.8 m below FGL) for 1.5 m wide footing is 88 KN/m

5.0 MATERIALS
5.1 Cement
Ordinary Portland Cement (OPC) of grade 43 confirming to IS: 8113 / IS: 12269 shall be used for
weigh bridge foundation

5.2 Concrete
Reinforced concreted of grade M25 with 20mm nominal size aggregate confirming to IS: 456 is used.

Following properties are used in the design


2
Elastic modulus, E = 25000 N/mm

Poisson’s ratio, µ = 0.2


3
Density = 25 kN/m

The minimum ultimate compressive strength of concrete shall be as follows,

25 N/mm² - Base slab & walls

7.5 N/mm² – Fill and lean concrete

5.3 Reinforcement Steel


High Yield Strength Deformed steel bars of grade Fe 500 bars confirming to IS: 1786 is used (Yield
strength = 500 MPa)
TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 5
CIVIL STRUCTURE

6.0 Dead load


Dead load for self weight of slab, columns, roof beam , pedestal, plinth beam, back fill soil and etc are
consider in the STAAD model.
6.1 Live load / Collateral Load
The LL considered is 5 KN/m2 for 6 T cooling tower

6.2 Earthquake Load/Wind load


Earthquake Load on tank is calculated as per is 1893 and wind load is calculated as per IS 875 : Part
3.

7.0. Design of beam and column:

The RCC beam and column are designed as per limit state method conforming to IS: 456: 2000

The calculations are enclosed in Annexure A

Design of Dyke wall:

The RCC slab are designed as per limit state method conforming to IS: 456: 2000

The calculations are enclosed in Annexure A


TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 6
CIVIL STRUCTURE

Annexure A
TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 7
CIVIL STRUCTURE

Staad file
STAAD SPACE
START JOB INFORMATION
ENGINEER DATE 09-Feb-16
END JOB INFORMATION
INPUT WIDTH 79
UNIT METER KN
JOINT COORDINATES
1 0 0 0; 2 4.2875 0 0; 3 8.575 0 0; 4 12.8625 0 0; 5 17.15 0 0; 6 0 0 3.08;
7 4.2875 0 3.08; 8 8.575 0 3.08; 9 12.8625 0 3.08; 10 17.15 0 3.08;
11 0 0 6.16; 12 4.2875 0 6.16; 13 8.575 0 6.16; 14 12.8625 0 6.16;
15 17.15 0 6.16; 16 0 4 0; 17 4.2875 4 0; 18 8.575 4 0; 19 12.8625 4 0;
20 17.15 4 0; 21 0 4 3.08; 22 4.2875 4 3.08; 23 8.575 4 3.08;
24 12.8625 4 3.08; 25 17.15 4 3.08; 26 0 4 6.16; 27 4.2875 4 6.16;
28 8.575 4 6.16; 29 12.8625 4 6.16; 30 17.15 4 6.16; 31 0 -2.85 0;
32 4.2875 -2.85 0; 33 8.575 -2.85 0; 34 12.8625 -2.85 0; 35 17.15 -2.85 0;
36 0 -2.85 3.08; 37 4.2875 -2.85 3.08; 38 8.575 -2.85 3.08;
39 12.8625 -2.85 3.08; 40 17.15 -2.85 3.08; 41 0 -2.85 6.16;
42 4.2875 -2.85 6.16; 43 8.575 -2.85 6.16; 44 12.8625 -2.85 6.16;
45 17.15 -2.85 6.16;
MEMBER INCIDENCES
1 1 2; 2 2 3; 3 3 4; 4 4 5; 5 1 6; 6 2 7; 7 3 8; 8 4 9; 9 5 10; 10 6 7; 11 7 8;
12 8 9; 13 9 10; 14 6 11; 15 7 12; 16 8 13; 17 9 14; 18 10 15; 19 11 12;
20 12 13; 21 13 14; 22 14 15; 23 1 16; 24 2 17; 25 3 18; 26 4 19; 27 5 20;
28 6 21; 29 7 22; 30 8 23; 31 9 24; 32 10 25; 33 11 26; 34 12 27; 35 13 28;
36 14 29; 37 15 30; 38 16 17; 39 17 18; 40 18 19; 41 19 20; 42 16 21; 43 17 22;
44 18 23; 45 19 24; 46 20 25; 47 21 22; 48 22 23; 49 23 24; 50 24 25; 51 21 26;
52 22 27; 53 23 28; 54 24 29; 55 25 30; 56 26 27; 57 27 28; 58 28 29; 59 29 30;
60 1 31; 61 2 32; 62 3 33; 63 4 34; 64 5 35; 65 6 36; 66 7 37; 67 8 38;
68 9 39; 69 10 40; 70 11 41; 71 12 42; 72 13 43; 73 14 44; 74 15 45;
START GROUP DEFINITION
MEMBER
_BEAM 1 TO 22 38 TO 59
_COLUMN 23 TO 37 60 TO 74
END GROUP DEFINITION
DEFINE MATERIAL START
ISOTROPIC CONCRETE
TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 8
CIVIL STRUCTURE

E 2.17185e+007
POISSON 0.17
DENSITY 23.5616
ALPHA 1e-005
DAMP 0.05
TYPE CONCRETE
STRENGTH FCU 27579
END DEFINE MATERIAL
MEMBER PROPERTY AMERICAN
23 TO 37 60 TO 74 PRIS YD 0.25 ZD 0.25
1 TO 22 38 TO 59 PRIS YD 0.3 ZD 0.25
CONSTANTS
MATERIAL CONCRETE ALL
SUPPORTS
31 TO 45 FIXED
DEFINE 1893 LOAD
ZONE 0.16 RF 3 I 1.0 SS 3 ST 2 DM 0.02 DT 2.8
JOINT WEIGHT
1 WEIGHT 0.62
2 WEIGHT 0.115
3 WEIGHT 0.731
4 WEIGHT 0.115
5 WEIGHT 0.62
6 WEIGHT 0.081
7 WEIGHT 1.599
8 WEIGHT 0.447
9 WEIGHT 1.599
10 WEIGHT 0.081
11 WEIGHT 0.62
12 WEIGHT 0.115
13 WEIGHT 0.731
14 WEIGHT 0.115
15 WEIGHT 0.62
16 WEIGHT 19.141
17 WEIGHT 47.732
18 WEIGHT 42.723
19 WEIGHT 47.732
20 WEIGHT 19.141
TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 9
CIVIL STRUCTURE

21 WEIGHT 47.216
22 WEIGHT 108.715
23 WEIGHT 101.119
24 WEIGHT 108.715
25 WEIGHT 47.216
26 WEIGHT 19.141
27 WEIGHT 47.732
28 WEIGHT 42.723
29 WEIGHT 47.732
30 WEIGHT 19.141
31 WEIGHT 0
32 WEIGHT 0
33 WEIGHT 0
34 WEIGHT 0
35 WEIGHT 0
36 WEIGHT 0
37 WEIGHT 0
38 WEIGHT 0
39 WEIGHT 0
40 WEIGHT 0
41 WEIGHT 0
42 WEIGHT 0
43 WEIGHT 0
44 WEIGHT 0
45 WEIGHT 0

LOAD 1 LOADTYPE None TITLE SLX


1893 LOAD X 1
LOAD 2 LOADTYPE None TITLE SLZ
1893 LOAD Z 1
LOAD 3 LOADTYPE None TITLE SL-X
1893 LOAD X -1
LOAD 4 LOADTYPE None TITLE SL-Z
1893 LOAD Z -1
LOAD 5 LOADTYPE None TITLE DL
SELFWEIGHT Y -1
FLOOR LOAD
YRANGE 4 4 FLOAD -4.75 GY
TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 10
CIVIL STRUCTURE

LOAD 6 LOADTYPE None TITLE LL


FLOOR LOAD
YRANGE 4 4 FLOAD -5 GY
LOAD COMB 15 COMBINATION LOAD CASE 15
5 1.0 6 1.0
****dl,ll,eq comb****serviceability***
LOAD COMB 16 COMBINATION LOAD CASE 16
5 1.0 6 1.0 1 1.0
LOAD COMB 17 COMBINATION LOAD CASE 17
5 1.0 6 1.0 2 1.0
LOAD COMB 18 COMBINATION LOAD CASE 18
5 1.0 6 1.0 3 1.0
LOAD COMB 19 COMBINATION LOAD CASE 19
5 1.0 6 1.0 4 1.0
LOAD COMB 20 COMBINATION LOAD CASE 20
5 1.0 1 1.0
LOAD COMB 21 COMBINATION LOAD CASE 21
5 1.0 2 1.0
LOAD COMB 22 COMBINATION LOAD CASE 22
5 1.0 3 1.0
LOAD COMB 23 COMBINATION LOAD CASE 23
5 1.0 4 1.0
****dl,eq comb****
*****failure comb******
LOAD COMB 40 COMBINATION LOAD CASE 40
5 1.5 6 1.5
LOAD COMB 41 COMBINATION LOAD CASE 41
5 1.2 6 1.2 1 1.2
LOAD COMB 42 COMBINATION LOAD CASE 42
5 1.2 6 1.2 2 1.2
LOAD COMB 43 COMBINATION LOAD CASE 43
5 1.2 6 1.2 3 1.2
LOAD COMB 44 COMBINATION LOAD CASE 44
5 1.2 6 1.2 4 1.2
LOAD COMB 46 COMBINATION LOAD CASE 46
5 1.5 1 1.5
LOAD COMB 47 COMBINATION LOAD CASE 47
5 1.5 2 1.5
TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 11
CIVIL STRUCTURE

LOAD COMB 48 COMBINATION LOAD CASE 48


5 1.5 3 1.5
LOAD COMB 49 COMBINATION LOAD CASE 49
5 1.5 4 1.5
PERFORM ANALYSIS
START CONCRETE DESIGN
CODE INDIAN
**beam design *****
FC 25000 MEMB _BEAM
FYMAIN 500000 MEMB _BEAM
FYSEC 415000 MEMB _BEAM
MAXMAIN 32 MEMB _BEAM
MINMAIN 12 MEMB _BEAM
MINSEC 8 MEMB _BEAM
DESIGN BEAM _BEAM
********column design *******
FC 25000 MEMB _COLUMN
FYMAIN 500000 MEMB _COLUMN
FYSEC 415000 MEMB _COLUMN
MAXMAIN 32 MEMB _COLUMN
MINMAIN 12 MEMB _COLUMN
MINSEC 8 MEMB _COLUMN
DESIGN COLUMN _COLUMN
END CONCRETE DESIGN
FINISH
TATA PROJECTS LIMITED
TPL-3430-X9690-EC-DC-6042 COOLING TOWER : DESIGN DOCUMENT FOR Page 12
CIVIL STRUCTURE
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: SR Owner : ITC LIMITED SUBJECT: cooling tower

DATE: 24-02-2016 JOB NO.: TPL 3430 REV. NO.: 0

Design of of Isolated Footing B1(NODE 1)


(for member forces ref staad out put / super structure design document)

FOUNDATION DESIGN NODE 1 F1 F2 F3 F4 F5 F6 F7 F8 F9 F10

Description Units Symbol Formulae 31 32 33 34 35 41 42 43 44 45


INPUT DATA L/C from STAAD 15 15 15 15 15 15 15 15 15 15
Max
UNFACTORED LOAD from
P/A+Mz/Zz+M Max vertical force (Fy) Max Moment (Mz)
STAAD file
x/Zx
Vertical load kN P input 49.27 96.15 90.05 96.15 49.27 49.27 96.15 90.05 96.15 49.27
Moment about x-x kN-m Mx input 0.06 0.01 0.02 0.01 0.06 0.06 0.01 0.02 0.01 0.06
Moment about y-y kN-m My input 0.27 0.24 0.00 0.24 0.27 0.27 0.24 0.00 0.24 0.27
Horizontal load along x-x kN Hx input 0.32 0.25 0.00 0.25 0.32 0.32 0.25 0.00 0.25 0.32
Horizontal load along y-y kN Hz input 0.00 0.00 0.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00
Application of Horizontal load
above FGL. If the
m h input 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
superstructure is on RCC,
then input this as "0"
Load factor lf input 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50
Net SBC kN/m2 S input 86 86 86 86 86 86 86 86 86 86
Grade of concrete (M20, M25 &
N/m2 fck input 25 25 25 25 25 25 25 25 25 25
M30)
Grade of steel (Fe 415 & Fe
N/mm2 fy input 500 500 500 500 500 500 500 500 500 500
500)
2
Density of soil kN/m gd input 18 18 18 18 18 18 18 18 18 18
Load case considered (DL or
- LC input 0 0 0 0 0 0 0 0 0 0
WL/EL) DL= 0 & WL/EL = 1
Coefficient friction 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33
FOOTING DATA
Width of Footing m W input 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50
Length of Footing m L input 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50
Thickness of Footing m T input 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30
Founding level below FGL m H input 2.84 2.84 2.84 2.84 2.84 2.84 2.84 2.84 2.84 2.84
COL DATA
Width of col m w input 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
Length of col m l input 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: SR Owner : ITC LIMITED SUBJECT: cooling tower

Reinforcement Details
Bottom steel
mm2 Required 360 360 360 360 360 360 360 360 360 360
About x-x mm2 Provided 566 566 566 566 566 566 566 566 566 566
Diameter mm d1 input 12 12 12 12 12 12 12 12 12 12
Spacing mm s1 input 200 200 200 200 200 200 200 200 200 200
mm2 Required 360 360 360 360 360 360 360 360 360 360
About y-y mm2 Provided 566 566 566 566 566 566 566 566 566 566
Diameter mm d2 input 12 12 12 12 12 12 12 12 12 12
Spacing mm s2 input 200 200 200 200 200 200 200 200 200 200
Top steel
mm2 Required 180 180 180 180 180 180 180 180 180 180
About x-x mm2 Provided 344 344 344 344 344 344 344 344 344 344
Diameter mm d3 input 8 8 8 8 8 8 8 8 8 8
Spacing mm s3 input 200 200 200 200 200 200 200 200 200 200
mm2 Required 180 180 180 180 180 180 180 180 180 180
About y-y mm2 Provided 344 344 344 344 344 344 344 344 344 344
Diameter mm d4 input 8 8 8 8 8 8 8 8 8 8
Spacing mm s4 input 200 200 200 200 200 200 200 200 200 200
RUN
Design Results
For bearing bressure SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
For shear in x-x direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
For moment in x-x direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
For shear in y-y direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
For moment in y-y direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
For punching shear SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
top steel in x-x direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
top steel in y-y direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
FOS- Sliding SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
FOS- Overturning SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
% Loss of contact area during
SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
Tension
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: SR Owner : ITC LIMITED SUBJECT: cooling tower

CALCULATIONS
Footing area m2 A W*L 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25
Weight of Footing kN WF A*T*25 16.88 16.88 16.88 16.88 16.88 16.88 16.88 16.88 16.88 16.88
Weight of soil above Footing kN WS (A-(w*l))*(H-T)*gd 99.86 99.86 99.86 99.86 99.86 99.86 99.86 99.86 99.86 99.86
Col weight kN WC (w*l)*(H-T)*25 3.96 3.96 3.96 3.96 3.96 3.96 3.96 3.96 3.96 3.96
Total load kN WT W F+W S+W C+P 169.96 216.84 210.74 216.84 169.96 169.96 216.84 210.74 216.84 169.96
Eccentricity along y-y m EY Mo-x / W T 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Eccentricity along x-x m EX Mo-y / W T 0.01 0.00 0.00 0.00 0.01 0.01 0.00 0.00 0.00 0.01
P/A kN/m2 PV WT / A 75.54 96.37 93.66 96.37 75.54 75.54 96.37 93.66 96.37 75.54
Z about x-x m3 ZXX (1/6)*(W*L*L) 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56
Z about y-y m3 ZYY (1/6)*(W*W*L) 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56
Total mx kN-m Mo-x Mx+{Hy(H+h)} 0.06 0.01 0.02 0.01 0.06 0.06 0.01 0.02 0.01 0.06
Total my kN-m Mo-y My+{Hx(H+h)} 1.19 0.94 0.00 0.94 1.19 1.19 0.94 0.00 0.94 1.19
Mx/Zx kN/m2 PX Mx/Zx 0.11 0.01 0.04 0.01 0.11 0.11 0.01 0.04 0.01 0.11
My/Zy kN/m2 PY My/Zy 2.11 1.67 0.00 1.67 2.11 2.11 1.67 0.00 1.67 2.11
SBC with overburden soil kN/m2 GS S+(H*gd) 107.60 107.60 107.60 107.60 107.60 107.60 107.60 107.60 107.60 107.60
Base pressure
Pmax (Pa) kN/m2 PA PV+PX+PY 77.77 98.06 93.70 98.06 77.77 77.77 98.06 93.70 98.06 77.77
Pmin (Pb) kN/m2 PB PV-PX-PY 73.31 94.69 93.62 94.69 73.31 73.31 94.69 93.62 94.69 73.31
(Pc) kN/m2 PC PV+PX-PY 73.54 94.72 93.70 94.72 73.54 73.54 94.72 93.70 94.72 73.54
(Pd) kN/m2 PD PV-PX+PY 77.54 98.03 93.62 98.03 77.54 77.54 98.03 93.62 98.03 77.54

Base pressure check kN/m2 Predi no tension no tension no tension no tension no tension no tension no tension no tension no tension no tension

Redistr. Pressure kN/m2 NA NA NA NA NA NA NA NA NA NA


% Loss of contact % 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: SR Owner : ITC LIMITED SUBJECT: cooling tower

Design of footing-about x-x


Avg max base pressure (gross) kN/m2 PE (PA+PC)/2 75.65 96.39 93.70 96.39 75.65 75.65 96.39 93.70 96.39 75.65
Avg min base pressure (gross) kN/m2 PF (PB+PD)/2 75.43 96.36 93.62 96.36 75.43 75.43 96.36 93.62 96.36 75.43
Max base pr. At col face 75.56 96.38 93.67 96.38 75.56 75.56 96.38 93.67 96.38 75.56
Avg pr.(net) kN/m2 PAVG (PE+PG)/2-Over burden pr. 22.46 43.23 40.54 43.23 22.46 22.46 43.23 40.54 43.23 22.46
Cantilever length m LY L/2 - l/2 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63
((PE-PG)*0.5*L*2L/3)+((PG-
Moment at face of col kN-m MY 4.39 8.44 7.92 8.44 4.39 4.39 8.44 7.92 8.44 4.39
W dead)*L*L/2)

Over burden load from top kN/m2 wdead T*25+(H-T)*gd 53.15 53.15 53.15 53.15 53.15 53.15 53.15 53.15 53.15 53.15
Factored moment kN-m MUY MY*lf 6.58 12.67 11.88 12.67 6.58 6.58 12.67 11.88 12.67 6.58
Mu limit factor as per table-D of SP-16 3.33 3.33 3.33 3.33 3.33 3.33 3.33 3.33 3.33 3.33
Depth required mm dreqd sqrt(MUY*10^6/Mu limit*1000) 44.47 61.67 59.72 61.67 44.47 44.47 61.67 59.72 61.67 44.47
Depth provided mm dprod T*1000-(50)-(d1/2) 219.00 219.00 219.00 219.00 219.00 219.00 219.00 219.00 219.00 219.00
pt required (min of 0.12%) - ptreqd 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12
Area of steel reqd mm2 Ast-r (ptreqd*dprod)*10 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00
Area of steel provided mm2 Ast-p 1000/s*(area of one bar) 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56
pt Bottom (provided) - ptprod (Ast-p / dprod)*10 0.26 0.26 0.26 0.26 0.26 0.26 0.26 0.26 0.26 0.26
Cantilever dist for shear mm ls (LY*1000)-dprod 406.00 406.00 406.00 406.00 406.00 406.00 406.00 406.00 406.00 406.00
((PE-PG)/L)*((L/2)+
pressure ordinate at "d" away kN/m2 psh
(l/2)+d)+PF
75.59 96.38 93.68 96.38 75.59 75.59 96.38 93.68 96.38 75.59

Net shear force kN /m Vu ((PE+Psh)/2-Wdead)*ls*lf 13.69 26.33 24.69 26.33 13.69 13.69 26.33 24.69 26.33 13.69
Actual shear stress N/mm2 tv Vu*10000/1000*dprod 0.06 0.12 0.11 0.12 0.06 0.06 0.12 0.11 0.12 0.06
Allowable shear stress N/mm2 tc as per IS456 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37
x-x direction Top reinforcement
Percentage of top steel provided % ptprod 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11
Bending moment at face of
kN-m 22.15 28.24 27.45 28.24 22.15 22.15 28.24 27.45 28.24 22.15
column (due to base pressure)
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: SR Owner : ITC LIMITED SUBJECT: cooling tower

Bending moment at face of


column(due to soil & dead wt. of kN-m 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38
mat)
pt (top) redquired (min of 0.12%) - ptreqd 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06
design of footing-about y-y
Avg max base pressure (gross) kN/m2 PE (PA+PD)/2 77.65 98.04 93.66 98.04 77.65 77.65 98.04 93.66 98.04 77.65
Avg min base pressure (gross) kN/m2 PF (PB+PC)/2 73.43 94.70 93.66 94.70 73.43 73.43 94.70 93.66 94.70 73.43

Max base pr. At col face (gross) kN/m2 PG ((Pe-Pf)/W*(W/2+w/2))+Pf 75.89 96.65 93.66 96.65 75.89 75.89 96.65 93.66 96.65 75.89

Avg pr. kN/m2 PAVG (PE+PG)/2 23.62 44.20 40.51 44.20 23.62 23.62 44.20 40.51 44.20 23.62
Base pr. At col face kN/m2 PE ((Pe-Pf)/W*(W/2+w/2))+Pf 75.89 96.65 93.66 96.65 75.89 75.89 96.65 93.66 96.65 75.89
Cantilever length m LX W/2 - w/2 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63
Moment at face of col kN-m MX 4.67 8.68 7.91 8.68 4.67 4.67 8.68 7.91 8.68 4.67
Factored moment kN-m MUX MX*lf 7.01 13.02 11.87 13.02 7.01 7.01 13.02 11.87 13.02 7.01
Depth reqd mm dredq sqrt(MUX*10^6/Mu limit*1000) 45.87 62.52 59.70 62.52 45.87 45.87 62.52 59.70 62.52 45.87
Depth provided mm dprod T*1000-(50)-(d1)-(d2/2) 207.00 207.00 207.00 207.00 207.00 207.00 207.00 207.00 207.00 207.00
pt required (min of 0.12%) - 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12
Area of steel reqd mm2 Ast-r (ptreqd*dprod)*10 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00
Area of steel provided mm2 Ast-p 1000/s*(area of one bar) 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56
pt Bottom (provided) - pt (Ast-p / dprod)*10 0.273 0.273 0.273 0.273 0.273 0.273 0.273 0.273 0.273 0.273
Cantilever dist for shear mm ls (LX*1000)-dprod 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00
Check for cantilever dist for
mm - 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00
shear
pressure ordinate at "d" away kN/m2 - 76.51 97.14 93.66 97.14 76.51 76.51 97.14 93.66 97.14 76.51
Net shear force kN /m Vu (PAVG)*Lx*ls 15.01 27.87 25.40 27.87 15.01 15.01 27.87 25.40 27.87 15.01
Actual shear stress N/mm2 tv Vu*lf*10000/1000*dprod 0.07 0.13 0.12 0.13 0.07 0.07 0.13 0.12 0.13 0.07
Allowable shear stress N/mm2 tc as per IS456 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: SR Owner : ITC LIMITED SUBJECT: cooling tower

Y-Y direction Top reinforcement


Percentage of top steel provided % ptprod 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11
Bending moment at face of
22.58 28.59 27.44 28.59 22.58 22.58 28.59 27.44 28.59 22.58
column (due to base pressure)
Bending moment at face of
column(due to soil & dead wt. of kN-m 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38
mat)
pt top required (min of 0.12%) - ptreqd 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06
Punching shear [ @ d/2 ]
max pr. Ordinate at + d/2 kN/m2 ps1 75.57 96.38 93.68 96.38 75.57 75.57 96.38 93.68 96.38 75.57
min pr. Ordinate at - d/2 kN/m2 ps2 75.50 96.37 93.65 96.37 75.50 75.50 96.37 93.65 96.37 75.50
Avg pr. Ordinate kN/m2 ps3 75.54 96.37 93.66 96.37 75.54 75.54 96.37 93.66 96.37 75.54
Punching shear-length mm 469 469 469 469 469 469 469 469 469 469
Punching shear-width mm 469 469 469 469 469 469 469 469 469 469
Area for punching shear mm2 219961 219961 219961 219961 219961 219961 219961 219961 219961 219961
Punching shear force N 60673 124115 115861 124115 60673 60673 124115 115861 124115 60673
Punching shear stress N/mm2 0.16 0.32 0.30 0.32 0.16 0.16 0.32 0.30 0.32 0.16
Allowable shear stress N/mm2 as per cl.31.6.3 of IS 456 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25
Beeta-c 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Ks 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50
Ks 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
tc 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

CHECK FOR OVER TURNING


About x-x 1991.76 23232.91 6872.01 23232.91 1991.76 1991.76 23232.91 6872.01 23232.91 1991.76
about y-y 107.21 173.23 0.00 173.23 107.21 107.21 173.23 0.00 173.23 107.21
CHECK FOR SLIDING 0.00 0.00 0.00 2.39 1.87 1.87 2.39 2.32 2.39 1.87
BY: GA
TATA PROJECTS LIMITED
DATE: 24-02-2016 CLIENT: ITC LIMITED

CHD.: NP Owner : ITC LIMITED

DATE: 24-02-2016 JOB NO.: TPL 3430

Design of of Isolated Footing


(for member forces ref staad out put / super structure design document)

FOUNDATION 2 F1 F2 F3 F4 F5

Description Units Symbol Formulae 36 37 38 39 40


INPUT DATA L/C from STAAD 15 15 15 15 15
Max
UNFACTORED LOAD from
P/A+Mz/Zz+M Max vertical force (Fy)
STAAD file
x/Zx
Vertical load kN P input 91.79 178.32 170.04 178.32 91.79
Moment about x-x kN-m Mx input 0.00 0.00 0.00 0.00 0.00
Moment about y-y kN-m My input 0.57 0.38 0.00 0.38 0.57
Horizontal load along x-x kN Hx input 0.66 0.38 0.00 0.38 0.66
Horizontal load along y-y kN Hz input 0.00 0.00 0.00 30.00 30.00
Application of Horizontal load
above FGL. If the
m h input 0.00 0.00 0.00 0.00 0.00
superstructure is on RCC,
then input this as "0"
Load factor lf input 1.50 1.50 1.50 1.50 1.50
2
Net SBC kN/m S input 84 84 84 84 84
Grade of concrete (M20, M25 &
N/m2 fck input 25 25 25 25 25
M30)
Grade of steel (Fe 415 & Fe
N/mm2 fy input 500 500 500 500 500
500)
Density of soil kN/m2 gd input 18 18 18 18 18
Load case considered (DL or
- LC input 0 0 0 0 0
WL/EL) DL= 0 & WL/EL = 1
Coefficient friction 0.33 0.33 0.33 0.33 0.33
FOOTING DATA
BY: GA
TATA PROJECTS LIMITED
DATE: 24-02-2016 CLIENT: ITC LIMITED

CHD.: NP Owner : ITC LIMITED

Width of Footing m W input 2.00 2.00 2.00 2.00 2.00


Length of Footing m L input 2.00 2.00 2.00 2.00 2.00
Thickness of Footing m T input 0.30 0.30 0.30 0.30 0.30
Founding level below FGL m H input 2.84 2.84 2.84 2.84 2.84
COL DATA
Width of col m w input 0.25 0.25 0.25 0.25 0.25
Length of col m l input 0.25 0.25 0.25 0.25 0.25
BY: GA
TATA PROJECTS LIMITED
DATE: 24-02-2016 CLIENT: ITC LIMITED

CHD.: NP Owner : ITC LIMITED

Reinforcement Details
Bottom steel
mm2 Required 360 380 362 380 360
About x-x mm2 Provided 566 566 566 566 566
Diameter mm d1 input 12 12 12 12 12
Spacing mm s1 input 200 200 200 200 200
mm2 Required 360 434 407 434 360
About y-y mm2 Provided 566 566 566 566 566
Diameter mm d2 input 12 12 12 12 12
Spacing mm s2 input 200 200 200 200 200
Top steel
mm2 Required 180 180 180 180 180
About x-x mm2 Provided 344 344 344 344 344
Diameter mm d3 input 8 8 8 8 8
Spacing mm s3 input 200 200 200 200 200
mm2 Required 180 180 180 180 180
About y-y mm2 Provided 344 344 344 344 344
Diameter mm d4 input 8 8 8 8 8
Spacing mm s4 input 200 200 200 200 200
RUN
Design Results
For bearing bressure SAFE SAFE SAFE SAFE SAFE
For shear in x-x direction SAFE SAFE SAFE SAFE SAFE
For moment in x-x direction SAFE SAFE SAFE SAFE SAFE
For shear in y-y direction SAFE SAFE SAFE SAFE SAFE
For moment in y-y direction SAFE SAFE SAFE SAFE SAFE
For punching shear SAFE SAFE SAFE SAFE SAFE
top steel in x-x direction SAFE SAFE SAFE SAFE SAFE
top steel in y-y direction SAFE SAFE SAFE SAFE SAFE
FOS- Sliding SAFE SAFE SAFE SAFE SAFE
BY: GA
TATA PROJECTS LIMITED
DATE: 24-02-2016 CLIENT: ITC LIMITED

CHD.: NP Owner : ITC LIMITED

FOS- Overturning SAFE SAFE SAFE SAFE SAFE


% Loss of contact area during
SAFE SAFE SAFE SAFE SAFE
Tension
BY: GA
TATA PROJECTS LIMITED
DATE: 24-02-2016 CLIENT: ITC LIMITED

CHD.: NP Owner : ITC LIMITED

CALCULATIONS
Footing area m2 A W*L 4.00 4.00 4.00 4.00 4.00
Weight of Footing kN WF A*T*25 30.00 30.00 30.00 30.00 30.00
Weight of soil above Footing kN WS (A-(w*l))*(H-T)*gd 179.74 179.74 179.74 179.74 179.74
Col weight kN WC (w*l)*(H-T)*25 3.96 3.96 3.96 3.96 3.96
Total load kN WT W F+W S+W C+P 305.49 392.02 383.74 392.02 305.49
Eccentricity along y-y m EY Mo-x / W T 0.00 0.00 0.00 0.00 0.00
Eccentricity along x-x m EX Mo-y / W T 0.01 0.00 0.00 0.00 0.01
2
P/A kN/m PV WT / A 76.37 98.01 95.93 98.01 76.37
Z about x-x m3 ZXX (1/6)*(W*L*L) 1.33 1.33 1.33 1.33 1.33
Z about y-y m3 ZYY (1/6)*(W*W*L) 1.33 1.33 1.33 1.33 1.33
Total mx kN-m Mo-x Mx+{Hy(H+h)} 0.00 0.00 0.00 0.00 0.00
Total my kN-m Mo-y My+{Hx(H+h)} 2.43 1.45 0.00 1.45 2.43
2
Mx/Zx kN/m PX Mx/Zx 0.00 0.00 0.00 0.00 0.00
My/Zy kN/m2 PY My/Zy 1.82 1.09 0.00 1.09 1.82
SBC with overburden soil kN/m2 GS S+(H*gd) 105.60 105.60 105.60 105.60 105.60
Base pressure
Pmax (Pa) kN/m2 PA PV+PX+PY 78.19 99.09 95.93 99.09 78.19
Pmin (Pb) kN/m2 PB PV-PX-PY 74.55 96.92 95.93 96.92 74.55
(Pc) kN/m2 PC PV+PX-PY 74.55 96.92 95.93 96.92 74.55
(Pd) kN/m2 PD PV-PX+PY 78.19 99.09 95.93 99.09 78.19

Base pressure check kN/m2 Predi no tension no tension no tension no tension no tension

Redistr. Pressure kN/m2 NA NA NA NA NA


% Loss of contact % 0.00 0.00 0.00 0.00 0.00
BY: GA
TATA PROJECTS LIMITED
DATE: 24-02-2016 CLIENT: ITC LIMITED

CHD.: NP Owner : ITC LIMITED

Design of footing-about x-x


Avg max base pressure (gross) kN/m2 PE (PA+PC)/2 76.37 98.01 95.93 98.01 76.37
Avg min base pressure (gross) kN/m2 PF (PB+PD)/2 76.37 98.01 95.93 98.01 76.37
Max base pr. At col face 76.37 98.01 95.93 98.01 76.37
Avg pr.(net) kN/m2 PAVG (PE+PG)/2-Over burden pr. 23.22 44.86 42.79 44.86 23.22
Cantilever length m LY L/2 - l/2 0.88 0.88 0.88 0.88 0.88
((PE-PG)*0.5*L*2L/3)+((PG-
Moment at face of col kN-m MY 8.89 17.17 16.38 17.17 8.89
W dead)*L*L/2)

Over burden load from top kN/m2 wdead T*25+(H-T)*gd 53.15 53.15 53.15 53.15 53.15
Factored moment kN-m MUY MY*lf 13.34 25.76 24.57 25.76 13.34
Mu limit factor as per table-D of SP-16 3.33 3.33 3.33 3.33 3.33
Depth required mm dreqd sqrt(MUY*10^6/Mu limit*1000) 63.28 87.95 85.90 87.95 63.28
Depth provided mm dprod T*1000-(50)-(d1/2) 219.00 219.00 219.00 219.00 219.00
pt required (min of 0.12%) - ptreqd 0.12 0.13 0.12 0.13 0.12
2 (ptreqd*dprod)*10
Area of steel reqd mm Ast-r 360.00 380.07 362.07 380.07 360.00
Area of steel provided mm2 Ast-p 1000/s*(area of one bar) 565.56 565.56 565.56 565.56 565.56
pt Bottom (provided) - ptprod (Ast-p / dprod)*10 0.26 0.26 0.26 0.26 0.26
Cantilever dist for shear mm ls (LY*1000)-dprod 656.00 656.00 656.00 656.00 656.00
((PE-PG)/L)*((L/2)+
pressure ordinate at "d" away kN/m2 psh
(l/2)+d)+PF
76.37 98.01 95.93 98.01 76.37

Net shear force kN /m Vu ((PE+Psh)/2-Wdead)*ls*lf 22.85 44.14 42.10 44.14 22.85


2 Vu*10000/1000*dprod
Actual shear stress N/mm tv 0.10 0.20 0.19 0.20 0.10
2
Allowable shear stress N/mm tc as per IS456 0.37 0.37 0.37 0.37 0.37
x-x direction Top reinforcement
Percentage of top steel provided % ptprod 0.11 0.11 0.11 0.11 0.11
Bending moment at face of
kN-m 43.85 56.28 55.09 56.28 43.85
column (due to base pressure)
BY: GA
TATA PROJECTS LIMITED
DATE: 24-02-2016 CLIENT: ITC LIMITED

CHD.: NP Owner : ITC LIMITED

Bending moment at face of


column(due to soil & dead wt. of kN-m 20.35 20.35 20.35 20.35 20.35
mat)
pt (top) redquired (min of 0.12%) - ptreqd 0.06 0.06 0.06 0.06 0.06
design of footing-about y-y
Avg max base pressure (gross) kN/m2 PE (PA+PD)/2 78.19 99.09 95.93 99.09 78.19
2
Avg min base pressure (gross) kN/m PF (PB+PC)/2 74.55 96.92 95.93 96.92 74.55

Max base pr. At col face (gross) kN/m2 PG ((Pe-Pf)/W*(W/2+w/2))+Pf 76.60 98.14 95.93 98.14 76.60
2
Avg pr. kN/m PAVG (PE+PG)/2 24.25 45.47 42.79 45.47 24.25
2
Base pr. At col face kN/m PE ((Pe-Pf)/W*(W/2+w/2))+Pf 76.60 98.14 95.93 98.14 76.60
Cantilever length m LX W/2 - w/2 0.88 0.88 0.88 0.88 0.88
Moment at face of col kN-m MX 9.38 17.47 16.38 17.47 9.38
Factored moment kN-m MUX MX*lf 14.08 26.20 24.57 26.20 14.08
Depth reqd mm dredq sqrt(MUX*10^6/Mu limit*1000) 65.02 88.70 85.90 88.70 65.02
Depth provided mm dprod T*1000-(50)-(d1)-(d2/2) 207.00 207.00 207.00 207.00 207.00
pt required (min of 0.12%) - 0.12 0.14 0.14 0.14 0.12
2 (ptreqd*dprod)*10
Area of steel reqd mm Ast-r 360.00 434.33 406.51 434.33 360.00
Area of steel provided mm2 Ast-p 1000/s*(area of one bar) 565.56 565.56 565.56 565.56 565.56
pt Bottom (provided) - pt (Ast-p / dprod)*10 0.273 0.273 0.273 0.273 0.273
Cantilever dist for shear mm ls (LX*1000)-dprod 668.00 668.00 668.00 668.00 668.00
Check for cantilever dist for
mm - 668.00 668.00 668.00 668.00 668.00
shear
pressure ordinate at "d" away kN/m2 - 77.00 98.38 95.93 98.38 77.00
Net shear force kN /m Vu (PAVG)*Lx*ls 24.50 45.68 42.87 45.68 24.50
2 Vu*lf*10000/1000*dprod
Actual shear stress N/mm tv 0.12 0.22 0.21 0.22 0.12
2
Allowable shear stress N/mm tc as per IS456 0.38 0.38 0.38 0.38 0.38
BY: GA
TATA PROJECTS LIMITED
DATE: 24-02-2016 CLIENT: ITC LIMITED

CHD.: NP Owner : ITC LIMITED

Y-Y direction Top reinforcement


Percentage of top steel provided % ptprod 0.11 0.11 0.11 0.11 0.11
Bending moment at face of
44.60 56.72 55.09 56.72 44.60
column (due to base pressure)
Bending moment at face of
column(due to soil & dead wt. of kN-m 20.35 20.35 20.35 20.35 20.35
mat)
pt top required (min of 0.12%) - ptreqd 0.06 0.06 0.06 0.06 0.06
Punching shear [ @ d/2 ]
max pr. Ordinate at + d/2 kN/m2 ps1 76.37 98.01 95.93 98.01 76.37
min pr. Ordinate at - d/2 kN/m2 ps2 76.37 98.01 95.93 98.01 76.37
Avg pr. Ordinate kN/m2 ps3 76.37 98.01 95.93 98.01 76.37
Punching shear-length mm 469 469 469 469 469
Punching shear-width mm 469 469 469 469 469
Area for punching shear mm2 219961 219961 219961 219961 219961
Punching shear force N 124173 246837 235095 246837 124173
Punching shear stress N/mm2 0.32 0.64 0.61 0.64 0.32
Allowable shear stress N/mm2 as per cl.31.6.3 of IS 456 1.25 1.25 1.25 1.25 1.25
Beeta-c 1.00 1.00 1.00 1.00 1.00
Ks 1.50 1.50 1.50 1.50 1.50
Ks 1.00 1.00 1.00 1.00 1.00
tc 1.25 1.25 1.25 1.25 1.25
CHECK FOR OVER TURNING
About x-x 0.00 0.00 0.00 0.00 0.00
about y-y 125.80 270.55 0.00 270.55 125.80
CHECK FOR SLIDING 0.00 0.00 0.00 4.31 3.36
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: NP Owner : ITC LIMITED SUBJECT: COOLING TOWER

DATE: 24-02-2016 JOB NO.: TPL 3430 REV. NO.: 0

Design of of Isolated Footing


(for member forces ref staad out put / super structure design document)

FOUNDATION 1 FOR WL F1 F2 F3 F4 F5 F6 F7 F8 F9 F10

Description Units Symbol Formulae 31 32 33 34 35 41 42 43 44 45


INPUT DATA L/C from STAAD 19 19 19 19 19 19 19 19 19 19
Max
UNFACTORED LOAD from
P/A+Mz/Zz+M Max vertical force (Fy) Max Moment (Mz)
STAAD file
x/Zx
Vertical load kN P input 59.21 108.43 103.03 108.43 59.21 39.33 83.86 77.07 83.86 39.33
Moment about x-x kN-m Mx input 6.56 7.68 8.14 7.68 6.56 6.43 7.69 8.18 7.69 6.43
Moment about y-y kN-m My input 0.26 0.25 0.00 0.25 0.26 0.28 0.24 0.00 0.24 0.28
Horizontal load along x-x kN Hx input 0.32 0.25 0.00 0.25 0.32 0.33 0.24 0.00 0.24 0.33
Horizontal load along y-y kN Hz input 0.00 0.00 0.00 30.00 30.00 30.00 30.00 30.00 30.00 30.00
Application of Horizontal load
above FGL. If the
m h input 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
superstructure is on RCC,
then input this as "0"
Load factor lf input 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50
Net SBC kN/m2 S input 88 88 88 88 88 88 88 88 88 88
Grade of concrete (M20, M25 &
N/m2 fck input 25 25 25 25 25 25 25 25 25 25
M30)
Grade of steel (Fe 415 & Fe
N/mm2 fy input 500 500 500 500 500 500 500 500 500 500
500)
2
Density of soil kN/m gd input 18 18 18 18 18 18 18 18 18 18
Load case considered (DL or
- LC input 1 1 1 1 1 1 1 1 1 1
WL/EL) DL= 0 & WL/EL = 1
Coefficient friction 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33 0.33
FOOTING DATA
Width of Footing m W input 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50
Length of Footing m L input 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50
Thickness of Footing m T input 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30 0.30
Founding level below FGL m H input 2.84 2.84 2.84 2.84 2.84 2.84 2.84 2.84 2.84 2.84
COL DATA
Width of col m w input 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
Length of col m l input 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: NP Owner : ITC LIMITED SUBJECT: COOLING TOWER

Reinforcement Details
Bottom steel
mm2 Required 360 360 360 360 360 360 360 360 360 360
About x-x mm2 Provided 566 566 566 566 566 566 566 566 566 566
Diameter mm d1 input 12 12 12 12 12 12 12 12 12 12
Spacing mm s1 input 200 200 200 200 200 200 200 200 200 200
mm2 Required 360 360 360 360 360 360 360 360 360 360
About y-y mm2 Provided 566 566 566 566 566 566 566 566 566 566
Diameter mm d2 input 12 12 12 12 12 12 12 12 12 12
Spacing mm s2 input 200 200 200 200 200 200 200 200 200 200
Top steel
mm2 Required 180 180 180 180 180 180 180 180 180 180
About x-x mm2 Provided 344 344 344 344 344 344 344 344 344 344
Diameter mm d3 input 8 8 8 8 8 8 8 8 8 8
Spacing mm s3 input 200 200 200 200 200 200 200 200 200 200
mm2 Required 180 180 180 180 180 180 180 180 180 180
About y-y mm2 Provided 344 344 344 344 344 344 344 344 344 344
Diameter mm d4 input 8 8 8 8 8 8 8 8 8 8
Spacing mm s4 input 200 200 200 200 200 200 200 200 200 200
RUN
Design Results
For bearing bressure SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
For shear in x-x direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
For moment in x-x direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
For shear in y-y direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
For moment in y-y direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
For punching shear SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
top steel in x-x direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
top steel in y-y direction SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
FOS- Sliding SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
FOS- Overturning SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
% Loss of contact area during
SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE SAFE
Tension
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: NP Owner : ITC LIMITED SUBJECT: COOLING TOWER

CALCULATIONS
Footing area m2 A W*L 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25
Weight of Footing kN WF A*T*25 16.88 16.88 16.88 16.88 16.88 16.88 16.88 16.88 16.88 16.88
Weight of soil above Footing kN WS (A-(w*l))*(H-T)*gd 99.86 99.86 99.86 99.86 99.86 99.86 99.86 99.86 99.86 99.86
Col weight kN WC (w*l)*(H-T)*25 3.96 3.96 3.96 3.96 3.96 3.96 3.96 3.96 3.96 3.96
Total load kN WT W F+W S+W C+P 179.90 229.13 223.72 229.13 179.90 160.02 204.55 197.76 204.55 160.02
Eccentricity along y-y m EY Mo-x / W T 0.04 0.03 0.04 0.03 0.04 0.04 0.04 0.04 0.04 0.04
Eccentricity along x-x m EX Mo-y / W T 0.01 0.00 0.00 0.00 0.01 0.01 0.00 0.00 0.00 0.01
P/A kN/m2 PV WT / A 79.96 101.83 99.43 101.83 79.96 71.12 90.91 87.90 90.91 71.12
Z about x-x m3 ZXX (1/6)*(W*L*L) 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56
Z about y-y m3 ZYY (1/6)*(W*W*L) 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56 0.56
Total mx kN-m Mo-x Mx+{Hy(H+h)} 6.56 7.68 8.14 7.68 6.56 6.43 7.69 8.18 7.69 6.43
Total my kN-m Mo-y My+{Hx(H+h)} 1.16 0.97 0.00 0.97 1.16 1.22 0.91 0.00 0.91 1.22
Mx/Zx kN/m2 PX Mx/Zx 11.66 13.65 14.46 13.65 11.66 11.43 13.67 14.54 13.67 11.43
My/Zy kN/m2 PY My/Zy 2.07 1.72 0.00 1.72 2.07 2.17 1.62 0.00 1.62 2.17
SBC with overburden soil kN/m2 GS S+(H*gd) 131.60 131.60 131.60 131.60 131.60 131.60 131.60 131.60 131.60 131.60
Base pressure
Pmax (Pa) kN/m2 PA PV+PX+PY 93.69 117.20 113.89 117.20 93.69 84.72 106.21 102.44 106.21 84.72
Pmin (Pb) kN/m2 PB PV-PX-PY 66.23 86.47 84.97 86.47 66.23 57.52 75.62 73.35 75.62 57.52
(Pc) kN/m2 PC PV+PX-PY 89.55 113.76 113.89 113.76 89.55 80.39 102.96 102.44 102.96 80.39
(Pd) kN/m2 PD PV-PX+PY 70.36 89.91 84.97 89.91 70.36 61.86 78.86 73.35 78.86 61.86

Base pressure check kN/m2 Predi no tension no tension no tension no tension no tension no tension no tension no tension no tension no tension

Redistr. Pressure kN/m2 NA NA NA NA NA NA NA NA NA NA


% Loss of contact % 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: NP Owner : ITC LIMITED SUBJECT: COOLING TOWER

Design of footing-about x-x


Avg max base pressure (gross) kN/m2 PE (PA+PC)/2 91.62 115.48 113.89 115.48 91.62 82.55 104.59 102.44 104.59 82.55
Avg min base pressure (gross) kN/m2 PF (PB+PD)/2 68.30 88.19 84.97 88.19 68.30 59.69 77.24 73.35 77.24 59.69
Max base pr. At col face 81.90 104.11 101.84 104.11 81.90 73.03 93.19 90.32 93.19 73.03
Avg pr.(net) kN/m2 PAVG (PE+PG)/2-Over burden pr. 33.61 56.65 54.72 56.65 33.61 24.64 45.74 43.23 45.74 24.64
Cantilever length m LY L/2 - l/2 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63
((PE-PG)*0.5*L*2L/3)+((PG-
Moment at face of col kN-m MY 6.88 11.43 11.08 11.43 6.88 5.12 9.30 8.84 9.30 5.12
W dead)*L*L/2)

Over burden load from top kN/m2 wdead T*25+(H-T)*gd 53.15 53.15 53.15 53.15 53.15 53.15 53.15 53.15 53.15 53.15
Factored moment kN-m MUY MY*lf 10.32 17.15 16.62 17.15 10.32 7.68 13.96 13.26 13.96 7.68
Mu limit factor as per table-D of SP-16 3.33 3.33 3.33 3.33 3.33 3.33 3.33 3.33 3.33 3.33
Depth required mm dreqd sqrt(MUY*10^6/Mu limit*1000) 55.67 71.77 70.65 71.77 55.67 48.04 64.74 63.10 64.74 48.04
Depth provided mm dprod T*1000-(50)-(d1/2) 219.00 219.00 219.00 219.00 219.00 219.00 219.00 219.00 219.00 219.00
pt required (min of 0.12%) - ptreqd 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12
Area of steel reqd mm2 Ast-r (ptreqd*dprod)*10 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00
Area of steel provided mm2 Ast-p 1000/s*(area of one bar) 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56
pt Bottom (provided) - ptprod (Ast-p / dprod)*10 0.26 0.26 0.26 0.26 0.26 0.26 0.26 0.26 0.26 0.26
Cantilever dist for shear mm ls (LY*1000)-dprod 406.00 406.00 406.00 406.00 406.00 406.00 406.00 406.00 406.00 406.00
((PE-PG)/L)*((L/2)+
pressure ordinate at "d" away kN/m2 psh
(l/2)+d)+PF
85.31 108.09 106.07 108.09 85.31 76.36 97.18 94.57 97.18 76.36

Net shear force kN /m Vu ((PE+Psh)/2-Wdead)*ls*lf 21.51 35.71 34.61 35.71 21.51 16.02 29.07 27.62 29.07 16.02
Actual shear stress N/mm2 tv Vu*10000/1000*dprod 0.10 0.16 0.16 0.16 0.10 0.07 0.13 0.13 0.13 0.07
Allowable shear stress N/mm2 tc as per IS456 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37 0.37
x-x direction Top reinforcement
Percentage of top steel provided % ptprod 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11
Bending moment at face of
kN-m 25.89 32.72 32.19 32.72 25.89 23.26 29.53 28.83 29.53 23.26
column (due to base pressure)
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: NP Owner : ITC LIMITED SUBJECT: COOLING TOWER

Bending moment at face of


column(due to soil & dead wt. of kN-m 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38
mat)
pt (top) redquired (min of 0.12%) - ptreqd 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06
design of footing-about y-y
Avg max base pressure (gross) kN/m2 PE (PA+PD)/2 82.02 103.55 99.43 103.55 82.02 73.29 92.54 87.90 92.54 73.29
Avg min base pressure (gross) kN/m2 PF (PB+PC)/2 77.89 100.11 99.43 100.11 77.89 68.95 89.29 87.90 89.29 68.95

Max base pr. At col face (gross) kN/m2 PG ((Pe-Pf)/W*(W/2+w/2))+Pf 80.30 102.12 99.43 102.12 80.30 71.48 91.18 87.90 91.18 71.48

Avg pr. kN/m2 PAVG (PE+PG)/2 28.01 49.69 46.28 49.69 28.01 19.24 38.71 34.75 38.71 19.24
Base pr. At col face kN/m2 PE ((Pe-Pf)/W*(W/2+w/2))+Pf 80.30 102.12 99.43 102.12 80.30 71.48 91.18 87.90 91.18 71.48
Cantilever length m LX W/2 - w/2 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63 0.63
Moment at face of col kN-m MX 5.53 9.75 9.04 9.75 5.53 3.82 7.60 6.79 7.60 3.82
Factored moment kN-m MUX MX*lf 8.29 14.63 13.56 14.63 8.29 5.72 11.41 10.18 11.41 5.72
Depth reqd mm dredq sqrt(MUX*10^6/Mu limit*1000) 49.90 66.28 63.81 66.28 49.90 41.46 58.53 55.29 58.53 41.46
Depth provided mm dprod T*1000-(50)-(d1)-(d2/2) 207.00 207.00 207.00 207.00 207.00 207.00 207.00 207.00 207.00 207.00
pt required (min of 0.12%) - 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12 0.12
Area of steel reqd mm2 Ast-r (ptreqd*dprod)*10 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00 360.00
Area of steel provided mm2 Ast-p 1000/s*(area of one bar) 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56 565.56
pt Bottom (provided) - pt (Ast-p / dprod)*10 0.273 0.273 0.273 0.273 0.273 0.273 0.273 0.273 0.273 0.273
Cantilever dist for shear mm ls (LX*1000)-dprod 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00
Check for cantilever dist for
mm - 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00 418.00
shear
pressure ordinate at "d" away kN/m2 - 80.91 102.62 99.43 102.62 80.91 72.12 91.66 87.90 91.66 72.12
Net shear force kN /m Vu (PAVG)*Lx*ls 17.75 31.31 29.02 31.31 17.75 12.26 24.42 21.79 24.42 12.26
Actual shear stress N/mm2 tv Vu*lf*10000/1000*dprod 0.09 0.15 0.14 0.15 0.09 0.06 0.12 0.11 0.12 0.06
Allowable shear stress N/mm2 tc as per IS456 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38 0.38
ITC LIMITED: INTEGRATED
BY: GA
TATA PROJECTS LIMITED PROJECT:
FOODS FACTORY AT PANCHLA,
HOWRAH
DATE: 24-02-2016 CLIENT: ITC LIMITED DOC. NO.:

CHD.: NP Owner : ITC LIMITED SUBJECT: COOLING TOWER

Y-Y direction Top reinforcement


Percentage of top steel provided % ptprod 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11 0.11
Bending moment at face of
23.86 30.20 29.13 30.20 23.86 21.30 26.98 25.75 26.98 21.30
column (due to base pressure)
Bending moment at face of
column(due to soil & dead wt. of kN-m 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38 10.38
mat)
pt top required (min of 0.12%) - ptreqd 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06
Punching shear [ @ d/2 ]
max pr. Ordinate at + d/2 kN/m2 ps1 83.60 106.10 103.95 106.10 83.60 74.70 95.19 92.44 95.19 74.70
min pr. Ordinate at - d/2 kN/m2 ps2 76.31 97.57 94.91 97.57 76.31 67.55 86.64 83.35 86.64 67.55
Avg pr. Ordinate kN/m2 ps3 79.96 101.83 99.43 101.83 79.96 71.12 90.91 87.90 90.91 71.12
Punching shear-length mm 469 469 469 469 469 469 469 469 469 469
Punching shear-width mm 469 469 469 469 469 469 469 469 469 469
Area for punching shear mm2 219961 219961 219961 219961 219961 219961 219961 219961 219961 219961
Punching shear force N 74127 140742 133425 140742 74127 47220 107486 98298 107486 47220
Punching shear stress N/mm2 0.19 0.36 0.34 0.36 0.19 0.12 0.28 0.25 0.28 0.12
Allowable shear stress N/mm2 as per cl.31.6.3 of IS 456 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25
Beeta-c 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Ks 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50 1.50
Ks 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
tc 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.25

CHECK FOR OVER TURNING


About x-x 20.57 22.38 20.62 22.38 20.57 18.66 19.95 18.13 19.95 18.66
about y-y 116.12 177.59 0.00 177.59 116.12 98.38 168.07 0.00 168.07 98.38
CHECK FOR SLIDING 0.00 0.00 0.00 2.52 1.98 1.76 2.25 2.18 2.25 1.76
DESIGN OF TWO WAY FLOOR SLAB

Data:
Concrete M25 fck = 25 N/mm²
Steel Fe 500 fy = 500 N/mm²

Shorter Span Lx = 3.08 m


Longer Span Ly = 4.29 m
Assuming Depth of Slab D = 150 mm
Assuming Dia of reinf. = 8 mm
Clear Cover = 25 mm
Eff. Depth of Slab d = 121 mm
Eff.Shorter Span lx = 3.20 m
Eff. Longer Span ly = 4.41 m

Load Calculations:
Self weight of slab including floor finish = 4.71 kN/m²
Live load = 5.00 kN/m²

Total load = 9.71 kN/m²


Load Factor = 1.50
Factored Load = 14.57 kN/m²

Span Ratio ly/lx = 4.41 / 3.20


= 1.38

Bending Moment Calculation:


Support Condition 4 Two Adjacent edges Discontinuous
From IS 456-2000 Table 26 aNx = 0.070
aPx = 0.052
4 aNy = 0.047
aPy = 0.035
Shorter Span:
Negative Moment (Support) MNx = aNx x wu x lx²
= 0.070 x 14.57 x 3.20²
= 10.392 kN.m
Positive Moment (Mid span) MPx = aPx x wu x lx²
= 0.052 x 14.57 x 3.20²
= 7.774 kN.m
Longer Span :
Negative Moment (Support) MNy = aNy x wu x lx²
= 0.047 x 14.57 x 3.20²
= 7.014 kN.m
Positive Moment (Mid span) MPy = aPy x wu x lx²
= 5.223 kN.m
Reinforcement:
Required in Shorter Span Reinf Required Reinf Provided
Support 8Ø @ 245mm c/c - 8 dia @ 225 mm c/c
Mid span 8Ø @ 330mm c/c - 8 dia @ 225 mm c/c
Required in Longer Span
Support 8Ø @ 345mm c/c - 8 dia @ 225 mm c/c
Mid span 8Ø @ 345mm c/c - 8 dia @ 225 mm c/c
CHECK FOR SHEAR
Maximum factored shear force = 26.91612 kN
Shear stress, Tv = 0.222447273 Mpa
k = 1.3
Tc = 0.422 Mpa
kTc = 0.5486
SAFE
CHECK FOR DEFLECTION
Allowable span / depth Ratio l/d = 26
Shorter span
reinforcement Mid Span Ast req Ast Pro pt req.span Pt pro.span
2 2
Dia Spacing mm mm % %
8 330 152.32 223.4 0.13 0.18

Required Compression pt
reinforcement Support Ast req Ast Pro req.Support Pt pro.Support
2 2
Dia Spacing mm mm % %
8 245 205.17 223.4 0.17 0.18

Modification factor for tension reinforcement


Service stress in steel fs 0.58 x fy x ( Area of cross xn of steel required ) /( Area of cross xn of steel
= Provided)
Modification 0.58 x fy Ast Required (Tension) Ast Provided (Tension) fs F1
factor for
tension 290 152.32 223.4 197.73 2.00
Modification factor for (Compression)
%Ast Provided (Compression) = 0.18
Modification factor for Comp. reinf. F2 = 1.05 (From Fig 5 in IS 456 - 2000)
Modification factor for Tension reinf. F1 = 2.00
Modification factor for Comp. reinf. F2 = 1.05
Modified span/depth ratio = l/d x F1 x F2
= 26 x 2.00 x 1.05
= 54.60

Actual span/depth ratio = 3201 / 121


= 36.43

Actual span/depth ratio < Modified span/depth ratio 36.43 < 54.60 SAFE

También podría gustarte