Dept. Electrical Equipment ID MOTOR-3A Shift C
Name of Fault / Breakdown (Please state the parts damaged , Location if any )
ID fan motor -3A tripped on Percentage Differential Over Current fault protection. ID fan motor stator winding insulation failure.
Action Taken
ROOT CAUSE: INSULATION FAILURE DUE TO AGEING & WEDGE LOOSENESS.
1. After taking PTW (Permit no:4002916535) measured the insulation resistance and winding resistance of Motor from panel end.
IR: RYB-E= 0.0 Mohms with 5KV applied voltage & winding resistance: RY=0.32 ohms YB=0.32 ohms BR=0.31 ohms
2. From the above results it is predicted stator winding's insulation
punctured.
3. For further inspection dis connected the motor power cable and measured the winding insulation resistance. Meggar values: R-E:4.5 Gohms
Y-E:0.0 Gohm B-E: 2.24 Gohm.
4. Replaced the motor with new indian make CG motor.
1.It is strictly recommended to replace the Chinese ID fan motor with indian make Motor due to insulation failures observed in all ID motors.
2.Strictly Maintain the voltage 11.5 KV for ID fan motor opertation.
3.During Overhauling, Wedge & Rotor Bar Inspection & Strenghten the Winding.