Documentos de Académico
Documentos de Profesional
Documentos de Cultura
Table of Contents
Section 1 History of Personal Protective Grounding
Purpose and Scope
Definitions
Historical Aspects of Protective Grounding
Section 2 Effects of Current on the Human Body
How Determined
Body Resistance Values
Current Level vs. Bodily Damage
Section 3 Requirements
of Utilities
by Regulating Agencies
Section 4 Standards
ASTM, IEEE, IEC
Section 5 Electrical Principles
Ohm's Law
Series Circuits
Parallel Circuits
Combination Series / Parallel Circuits
Section 6 Hazards
Accidental Re-energization
Induced Currents and Voltages
Step Potential
Touch Potential
Section 7 Theory of Personal Protective Grounding
Creating Equipotential Zones
Use of Neutrals and Static Wires
Earth as a Return Path
Effect of Multiple Grounded Locations
Section 8 Personal Protective Equipment
Clamps
Cable
Ferrules
Assemblies
Section 9 Basic Protection Methods
Double Point
Single Jumper
Single Point
Section 10 General Installation Procedures
Applications and Considerations
Equipotential at the Worksite
Remote Worksite, Limited Distance
Bracket at Worksite
Ground Support Workers
Around Trucks or Equipment
Underground
Substations
Section 12 Relevant Instruments and Meters from Catalog Section 2450
Section 13 Grounding Equipment Catalog Section 3000
AnnanAiv A nih,i~,.r.lnh.,
History of Personal Protective Grounding
Section 1
History of Personal Protective Grounding
Worker protection has always been an im- istration (OSHA) were published in January
portant activity. Worker safety has become a 1994. CFR29 1910.269Subpart R171regulates
more important issue than ever before and has a broad scope of utility activities. It puts
received increased attention in recent years. forth requirements relating to operation and
As the country has grown so have the electri- maintenance of generation, transformation,
cal needs of the pop;lation: More people, more transmission and distribution of lines and
businesses and factories, all usingmore power. equipment and of tree trimming activities.
Electric power lines have been upgraded and Other rulings by OSHA address other util-
new ones constructed to supply the increas- ity related topics. Very little is being left to
ing demand for electric power. Today we are chance. These rules carry the weight of law
seeing higher voltage lines, with higher levels and violators may face severe penalties and
of both rated and fault current. monetary fines. Some states have adopted
their own version of the OSHA regulations.
This growth has increased the difficulty in This is allowed if the state version is at least
providing a safe worksite. In many cases a s stringent as the federal regulations.
the "old" methods are not only inappropriate
but are also unsafe. One of the "old timers" Worker protection is the focus
at a mid-west rural utility related that they of the decade.
used to cut a "fat green weed" to ground the
line. Thankfully, the days of grounding with
"fat green weeds" and grounding chains are
This publication intends to assist utility per-
sonnel at many levels to understand and apply
iI
long gone. Back then, the probability that a techniques for workers to use during mainte-
worker happened to be in contact at the very nance after a line has been de-energized and I
instant that the line accidentally became re-
energized was very small. In most cases the
taken out of service. Each section has been
written with a particular reader in mind. The
i
absence of injuries was more the result of the
worker lacking contact at that moment than
sections are arranged in a sequential manner,
and each stands alone on the information it 1
the protection scheme in use at the time.
Separate JumpersTo Separate Earth Connections Separate JumpersTo Common Earth Connection 1E
I
j
I
Another modification used shortened jump- wire is present and the worker is near or touch-
ers between phases and a single jumper to a ing it, the separate current path remains. If
single Earth connection [I3], as diagramed in there is no pole down wire, the pole may have
Figures 1-3a and 1-3b. This was another at- a resistance high enough to keep the body
tempt to improve worker protection that did current flow to a low level but not necessar-
not change the basic circuitry. The worker ily to a safe level. Each pole is different. Pole
remains a separate current return path. resistance depends upon the amount of mois-
ture sealed in the wood during the pressure
All of these schemes protected the system by treating, the surface contaminants, and the
indicating a fault, but left the worker in a situ- amount of water present on the surface and
ation that could prove fatal. As can be seen in the type of wood.
the diagrams and the associated schematics,
substantial voltage can be developed across the Some companies had adopted a policy of plat-
worker. This was not a satisfactory solution. ing a full set of grounds on the pole at the
worksite and also on each pole on both sides
What if the structure is wood? If a pole down of the worksite. This offered protection but
By monitoring the voltage applied, the re- Using this formula, it can be determined that
sulting current flow, and the reaction of the on average a 110 lb. lineworker should with-
volunteers, a great deal of information was stand 67 milliamps for 3 seconds before going
developed. Calculations were made to develop into heart fibrillation and a 155 lb. worker
a value of resistance for the "average" human would withstand 91 milliamps. Or the same
body. Voltages duringsome ofthe experiments workers would be susceptible to heart fibril-
were measured a t 21 volts hand to hand and lation after a 670 Amp. and 906 Amp. shock
10 volts from one hand to the feet. Calcula- respectively after only 0.03 seconds, or about
tions of resistance using the measured values 2 cycles of 60 Hz. current flow through the
yielded 2,330 ohms hand-to-hand and 1,130 chest cavity. Values presented in tables are
ohms hand-to-feet. This early low voltage commonly rounded to even values of current
research established an average safe let-go for ease of presentation and remembering.
current for an "average" man as 16 milliam-
peres. Itwas also determined that the human Dalziel's research also formed the basis of the
body responds to current in an exponential that is used throughout the indus-
manner. That is, the body responds to an try today. The chart presents several levels of
increasing current as the time shortens in a current and the average body's response. The
similar manner as it responds to a decreasing table for 60 Hz. is presented in Table 2-1.
current and lengthening duration. This time
current relationship is shown in Figure 2-1.
Perception Level (the least amount of current detectable by the ungloved hand) = 1 .I milliampere*
*Theseare average levels for men, empirically developed from Charles Dalziel'~['~.'~l
research.
Training
Equipment
Requirements
Section 3
Utility Requirements
Developing a safe worksite by maintaining Many utilities have prepared internal publi-
the current through the body a t a safe level cations to outline work rules and practices,
now becomes the task of all involved. First approved for use by their utility. Others may
and foremost, utility management and the not have a formal set of rules in place, rely-
Safety Department must determine what ing rather on experienced linemen and the
they consider to be the maximum safe level tailgate conference, now required by OSHA
of current flow allowable through the worker. 29 CFR 1910.269(c)17' before beginning work
Or, stated another way, the maximum allow- each day.
able voltage that can be considered safe that
can be developed across the worker must be According to OSHA regulations, a worker's
specified. At the time of this writing, there training must be reviewed annually 17' and
was no standard or widely acceptedmaximum be documented. Additional training must be
allowable body current. A value of 50 V is provided if the review finds it to be needed.
commonly used, but is not arequirement.This Additional information on the topic oftraining
upper limit of exposure is a key consideration can be found in the next section on regulat-
in selecting the size of protective equipment. ing agencies.
Each worksite and each situation may be dif-
ferent, with each utility accepting a different Worker safety is now everybody's job. With
margin of safety. OSHA regulations now in place, penalties
for accidents can be severe and may affect
To develop a safe worksite requires the cooper- a broad range of personnel throughout the
ation of several departments within the utility.
A utility if a lack of training is determined to
The EngineeringDepartment must supply an be the cause.
a~oroximate
A A
level offault current expected at
an individual worksite or within an assigned Equipment: The utility must provideadequate
working region. Engineering must also pro- equipment for the worker to perform the task
vide the maximum time that a fault current in a safe, yet efficient manner. Depending
mav" flow at the identified sites. The Opera- upon its size, a utility typically has a person
tions Department must develop appropriate or department makingequipment-purchasing
A -
work and eauipment maintenance methods. decisions. Many utilities rely on national
The Purchasing Department, in cooperation consensus standards to define equipment
with the Standards Group, must acquire ap- requirements. Some utilities have safety de-
propriate safety equipment for issue and use partments working in conjunction with those
by the workers. The Safety Department must responsible for purchasing. They may have
coordinate all of these activities. Methods of their own set of performance specifications
evaluating and accomplishing a safe worksite drawn from several standards to meet their
are discussed later in this document. individual needs.
Training: Utilities must use workers who Adequate equipment to perform safe de-
possess the necessary skills to safely perform energized line maintenance includes voltage
theirjobs. Linemen have different skill levels. detectors, personal protective grounding as-
Typically, an electrical worker's employer or semblies made up with clamps, ferrules and
the union formally defines each skill level. cable with strengths and ratings to meet the
The levels typically consist of apprentice safety needs of the worker. Choices and ex-
t,hmnvh innmevmnn. Formal nlns nn-the-inh ,.--I-- -C -..;t-hl- --..:----+ --- ------&-A
Requirements Placed upon Utilities
by Regulating Agencies
Training: OSHAL7'has placedtheresponsibility current that could flow (authors underline for
for training directly on each utility employer. emphasis) a t the point of grounding for the
29 CFR 1910.269 (a)(l)establishes require- time necessary to clear the fault". Further,
ments for the operation and maintenance of 29 CFR 1910.269 (n)(4)(ii)states "Protective
electric power generation, control, transfor- grounds shall have an impedance low enough
mation, transmission and distribution lines to cause immediate operation of protective
and equipment and tree trimming operations. devices in case of accidental energizing of the
OSHA does not establish individual work lines or equipment."
rules but rather a basic set of requirements
the individual utility must meet when using A n equipment maintenance program is not
its own work procedures. specificallymentioned, but it is implied based
on the requirement for supplying suitable
29 CFR 1910.269 (a)(2) sets forth the train- equipment for use on the job. See 29 CFR
ing requirements that relate to meeting the 1910.269 (n)(4).A lack of maintenance may
above requirements. It states that "Employ- result in unsuitable equipment which would
ees shall be trained in and familiar with the then not meet the requirement. Broken con-
safety-related work practices, safety proce- ductor strands, high resistance connections
dures, and other safety requirements in this between the clamp parts or between the clamp
section that pertain to their respective job and ferrule or cable end connection may lead
assignments." to a loss of protection during the time a line
becomes accidentally re-energized. A loss of
29 CFR 1910.269(a)(2)(vi)establishes employ- protection is clearly in violation of the OSHA
ee proficiency in work practices. It specifies ruling which requires the supply of suitable
that additional training requirements must equipment for use on a job.
be given before a worker can be considered
a "qualified employee" including the use of For Liability: With the adoption of 29 CFR
personal protective equipment and insulated 1910.269, the utility's liability appears to
tools forworking on or near exposed energized have been increased significantly because the
parts. utility employer has been specifically named
as being responsible for training or certify-
29 CFR 1910.269(a)(2)(vii)requires that: "The ing the training of the employee in proper
employer shall certify that each employee has and safe procedures and to provide suitable
received the training-required."
. Certification equipment. The implication ofthis is that the
is complete after the employee demonstrates employer can now be held accountable by the
proficiency in the workpractices. The training regulating agencies and the legal system in
records are to be kept and maintained for the the case of employee accidents that can be
duration of the employee's employment. attributed to lack of training or equipment
failures. The final results of these require-
Equipment: 29 CFR 1910.269 (n)(4)(i)states ments are not known because they have not
that it is the utilities responsibility to provide yet been fully tested in the courts.
"protective grounding equipment" that "shall
be c a ~ a b l eof conduct in^ the maximnm fanlt.
Standards
Section 4
industry Standards
Standards are used widely in the utility in- While other countries also may have their
dustry. They cover a wide range oftopics. For own national standards, the International
instance, performance specifications for prod- Electrotechnical Commission (IEC) is the
ucts or components used'"', line construction primary source of internationally accepted
methods and overhead line maintenan~e[~'.standards. IEC standards are also consen-
Other documents are presented as guides or sus standards, developed by knowledgeable
general methods of equipment use without representatives from each member country
specifying a particular work method, but al- including the U.S. During recent years, the
low the utility the freedom to adapt them to influence of IEC standards has increased,
individual situations. Consensus standards even in the U.S., as a result of treaties such
developed by agreement among an array of as NAFTA.
users, manufacturers, utility representatives
and experienced consultants are widely ac- All consensus standards developed are pub-
cepted and used. Some utilities have devel- lished andwidelv distributed. Thev " are avail-
oped standards for their own use, patterned able for a fee from the sponsoringorganization.
after consensus standards, but modified to Thev " are continuallv
" reviewed and uadated
meet their own particular needs. as industry needs and technology change.
In the United States, compliance with stan- OSHA and National Electric Code standards
dards is voluntary in most instances, other are not voluntary. However, even these take
thangovernmental regulations such as OSHA input from consensus standards groups spon-
requirements. The manufacturer of personal sored by various standards organizations
protective grounding equipment may choose because of the broad range of experience and
which standardits products meet and accord- knowledge ofthe representatives who develop
ingly market them. However, the manufac- them. Official governmental regulations nor-
turer may be required to meet all that applies mally are open to public comment prior to the
due to thevariations and requirements within issuing of rulings which are then printed in
its customer base. the Federal Register.
The main authoring groups of voluntary The Reference section of this publication
standards in the United statesaddressing contains a partial list of standards that con-
utility needs are: trol the manufacture, selection and use of
I = V / R o r I =V/2Rnow,whichis
110 VAC 1242 Ohms
I = 0.454 Amp.
R
Parallel Circuit
Fig. 5-6
R
9% , P)
Jfl+\F\/\-' /, \j
For example: Volts
"0"S
Volts
I
Fig. 5-7
Combination SeriesIParallel Circuits
The real world is filled with circuits. Few are An exact determination is beyond the scope
as simple as the pure series or parallel ones of this presentation. Assumptions about the
described above. Most are combinations of worker (typically 1,000 Ohms) and earth re-
series and parallel connections. The typical sistances and source and return paths can be
worksite is an example . of this. Consider a made. Each parallel portion can be reduced
de-energized single-phase source connected t o an equivalent resistance using Equations
to the conductor feeding- the worksite (series). 5 or 6. Total circuit resistance can be found
A worker is standing on a pole above a clus- by adding all the series resistances plus the
ter bar in contact with the conductor with a parallel equivalents. If the source voltage is
jumper bypassing him (parallel).The cluster known, it allows calculation of the fault cur-
bar is connected both to the Earth and to the rent available a t a worksite. While this is a
return neutral (parallel). Perhaps, also, it valid technique, it is included primarily to
is connected to an overhead static line (ad- illustrate the process used. The engineering
ditional parallel). department of the utility should be consulted
for a more accurate value.
As complicated as this appears, it can be re-
duced to a simple equivalent circuit for ease of It then becomes necessary to analyze only
analysis. To do so requires the determination the connections at the worksite. As an aid to
of the resistances of the conductor, neutral, analysis, Table 5-1''" presents the DC resis-
safetyjumpers and the possible static wire. A tance of several common conductors in Ohms
realistic estimation can be used, because the per 1,000ft.Ifit becomes necessary to include
normal loads on the line will not be discon- a return path through the Earth, a value of
nected and they will affect the final value. resistance must be assigned to that path.
1/ RwN-EciuIv = I / R , + I / ( R , + R J
= 1/ 2.223 + 1/ (25 + .002) =1/0.490
and RRTN-eQUrV= l/ 0.490 = 2.041 Ohms
----------- - - - - - - -- -
Figure 5-8 illustrates this scenario. As an The current from the source:
example of the calculations involved, all the
mentioned components have been included. ISOURCE= V / R = 12,000 / 4.265
Assume the source may achieve 12 kV, even = 2,813 Amp
momentarily.
The current through each of the circuit parts
V = Source voltage = 12,000 volts can now be determined.
R, = 5 miles of 210 Cu 19 strand
conductor = 2.223 Ohm The current through the man:
R, = 25 ft. of 210 Cujumper, cluster -
bar to Earth = 0.002 Ohm I m - 'SOURCE x (R, / (R, + R,) = 2,813 x
R , = Assumed man resistance = [0.001/(1000 + 0.OOl)J
1,000 Ohm
R, = 5 miles of 210 19 strand Cu = ,003 Amp = 3 milliamp
neutral = 2.223 Ohm
R, = Personal Protective Jumper; The current through the jumper:
10 ft. of 210 Cu = 0.0008 Ohm
RE = Earth Return resistance = Ij = IsouRcEx (R, / (R, + RJ) = 2,813 x
25 Ohm [I000 / (1000 + 0.001)1
= 2,812.998 Amp
First determine the total current drawn from or I, = 2813 - ,003 = 2,812.997 Amp
the source. Find the equivalent resistances
of each of the parallel portions. Then add all The current returning through the neutral:
or the resistances in series together. Now
knowing both the source voltage and the IN= 'SOURCE x [(R, + RE )/ (R, + RE+ RN)l
circuit resistances, Equation 2 can be used
to determine the source current. So: +
= 2,813 x [(0.0023 25) / (0.0023 + 25
+ 2.223)l = 2,583 Amp
The madjumper equivalent resistance is:
URM-EQUIV = URM + l/R J and that through the earth:
= 1/1000 + l/0.0008
= ,001 + 1250 Ie = ISOURCE
x (R, (R, + Re + R,)
= 1250.001
As can be seen from this example, much
less current flows through the Earth when a
neutral return is included in the protective
circuit because it represents a much lower
resistance path.
Fig. 6-2
A step potential hazard is defined as the
voltage across a ground support worker who
steps across or otherwise bridges an ener- This is a hazard for ground personnel. It
gized path of Earth. The transfer of the rise is a real danger for workers leaving a truck
in line voltage during a fault to Earth is by that may have become energized through
way of a jumper or other direct connection. accidental contact with an energized conduc-
This raises the Earth's point of contact to tor and maintenance workers around under-
approximately the same voltage as the line ground distribution equipment. Protection
itself during the fault. methods include insulation, isolation or
development o f an equipotential zone.
The Earth itselfhas resistance[20'.Remember,
current flowing through a resistive element Touch Potential[i~4~121
creates a voltage drop. As with any voltage
drop, it is spread over the resistance itself. The worker has still another hazard to contend
Consider the Earth as a string of resistors all with: Touch Potential. This is the voltage
connectedin series. Eachresistor in the series resulting from touching a conductive ele-
will develop a voltage because of the current ment that is connected to a remote energized
flowing through it. This is the voltage drop component. The voltage is called transferred
bridged by the worker who steps across it. potential and it rises to the same value as the
contact that becomes energized. It could be
As the distance from the point of contact in- thought of as standing on aremote Earth spot
creases, voltage at that remote Earth point while holding a long wire that becomes ener-
decreases. Tests indicate that the voltage gized on its far end. Touch voltage between
drops to approximately half of the point of the remote site and the voltage where stand-
contact voltage in the first 3 feet, at least at ing can be quite different. Refer to Fig. 6.2.
distribution voltages levels. It drops to half The voltage is developed across the ground
of that voltage again in the next 3 feet until worker's body. Methods of protection remain
it can (for all practical purposes) be consid- the same: Isolate, insulate or develop an
ered zero. equipotential zone.
Theory of Personal Protective Grounding
Section 7
Theory of Personal Protective mounding
C6002102
G42291SJ
All Angle
Transformer or Switch
C6000785
Cutout Ground Clamp
C6000619
Mounted Substation Clamp
ASTMr6Iratings of clamps, ferrules and assemblies are shown in Table 8-1
Cable
Figure 8-9
bution system components.
While not specified, these two statements It may not be practical to make micro-ohm
imply a responsibility to ensure equipment resistance measurements on aluminum
is maintained for use in a safe and usable clamps using a low voltage source. A coating
state. In the past, little attention was paid to of aluminum oxide covers bare aluminum
the condition of personal protective jumpers. surfaces. The coatingis describedin thickness
They often were coiled loosely and thrown of molecules, rather than inches. Aluminum
into the back of a line truck by the workers oxide is an insulator for very low voltages,
whose very lives depended upon them. This but it takes only a few volts to break down
type of oversight must be corrected. this layer and allow current to flow. The
breakdown voltage can be as low as 5 to 10
Maintenance involves manual and visual Volts. Levels below 1Volt may give an incor-
inspection and electrical testing. Electrical rect resistance reading.
tests are used to determine the condition of
the clamp, ferrule and cable-to-ferrule in- Chance offers a microprocessor-controlled
terface. convenient electrical tests have not tester for personal protective grounding sets,
been fully developed that will identify broken the Chance C4033220 Tester for Protective
strands in the cable away from the crimp Grounding Sets. It allows the user to input
ferrules, unless a very large number of the the selected level of body voltage considered
strands are broken and not in contact with safe and the cable size. The measurement
each other. Most electrical tests make resis- made is the resistance from clampjaw surface
tance measurements using various levels of to clamp jaw surface. The maximum allowed
test current for short periods of time. If some withstand current a s specified in ASTM
strands are broken but still in contact with F855 for the input cable size is represented
each other, held together by the outer jacket to pass through the cable and is used in the
in the cable position, test current can still calculation of the maximum voltage across
flow through both the broken and unbroken the entire length of the jumper. In addition
strands. The change in total resistance over to the microvolt reading, a green or red (pass/
t h n lnsrrth -f t h n --hlfi A n n Cn o m n l l otvonrl fn:l\ *-no1 1;rrht . ~ ~ ; lhl o ; l l n m ; n o t o r l t n -oa;ot
be used when testing the ground set that To ensure proper test procedures andmethods
will be connected directly in parallel with are applied when testing temporary ground-
t h e worker. ingjumpers, refer to ASTM F2249-03 and t h e
manufacturer's instructions for proper use of
T h e Chance Ground Set Tester C4033220 t h e ground set tester.
provides a 10V DC test voltage. This DC
voltage level can easily break down any alu- Ground sets that will not be connected in
minum oxide on aluminum ferrules to give parallel with the body are not t h e subjects of
a reliable reading on all personal protective body voltage measurement. For example, the
ground sets. requirement of a ground assembly that con-
nects the cluster bar installed below workers
There are other ground set testers on t h e mar- feet to t h e Earthis only that it not melt or fuse
k e t today that use a n AC source for testing. into two parts. Its added length will have an
These test sets m a y not apply a test voltage increasedresistance that m a y reach avoltage
to the jumper high enough to break down in excess of t h e selected level of body safety
any aluminum oxide on ferrules, which could during the passage of a high fault current.
potentially give a n incorrect reading. Possible However, this voltage is not across the worker.
errors are also noted in ASTM F2249-03, sec- T h e micro-ohm measurement of such a cable
tion 7.5.4 Note 3 and Note 4: can be compared to t h e expected resistance
based upon standard resistance tables for a
Note 3 - AC testing measurements of ground- cable of the same size and length, but does
ingjumperassemblies are susceptible to errors not affect worker voltage.
and inconsistent results due to induction in
the cable if the cable is not laid out per tlze
test inetlzod instructions.
Note 4 -ACtestingmeasurementsofgrounding
jumper assemblies are susceptible to errors if
metal is laid across the cable or tlze cable is
laid across a metal object, even i f the metal
object is buried, such as a reinforcing bar
embedded in a concrete floor.
. ,
I be near 0 1
Figure 9-3
Here, good judgment by the worker must be
exercised to evaluate the site, the variables Bracket Grounding, Same Structure
and conditions present. Because so many situ- Figure 9-4
ations possible in Bracket Grounding would
require a judgment decision by the worker Storm damage often requires Bracket Ground-
at each site, it is recommended to develop ing. It is used if a conductor has broken and
a suitable work method to avoid such field is on the ground. Then it becomes necessary
judgments. to ground at the structures on either side of
the break. But if the line becomes energized
Now consider the situation where two per-
and the worker is standing on the Earth, he
sonal protectiveground sets are bothinstalled
is also a return path. In this case, it would
on the same structure, one on each side of the
be necessary to bond a conductive mat to the
worker. This form is an adaptation of both
two conductor ends for him to stand on while
the Bracket Method mentioned above and the
makingrepairs, to maintain the samevoltage
Equipotential Method. In Figure 9-4, conduc-
from the hands to the feet.
-
tors have been connected together and to a
cluster bar beneath the worker's feet. Protec-
tion results from the low resistance ground There are other maintenance situations that
do not lend themselves to Single-Point (or
sets directly in parallel with the worker, not
equipotential worksite) grounding. In most
because there is a set on either side. There
of those situations Bracket Grounding can be
is a benefit to using this technique. If very
large fault currents are available, the jumper a usable method if thought is given to worker
cables themselves can be of a smaller size as protection in combination to the bracketing
(see the combination of Single-Point and
the current is now divided between the two
"o+" Th4" -"Tr-"lrn ;-"+-ll-L:-- ---:-.-
---J
Bracket Grounding in the next section).
Single Bypass Ground Set Minimum - equipment fails to recognize that a fault has
occurred, leaving the line energized for an
Requirement for Worker Protection
extended time.
In this configuration, only a single jumper This is an incomplete solution because the
used with a cluster bar would be used. It system protective equipment may not see
would connect from the one conductor be- that a fault exists, or because the estimates
ing maintained to the cluster bar below the may be completely wrong. Therefore, this is
worker's feet. The jumper maintains the re- not a recommended method. By expanding
quiredlow resistance pathin parallel with the upon this method, a usable method can be
obtained.
body. As in all parallel situations, all current
available divides between the jumper and the An acceptable form of this method is the use of
worker if the worker is in contact a t the time a Single bypass ground set AND the Bracket
of current flow. Method. The bracket grounds provide the
system fault information to the protection
Whether sufficient current bypasses the body equipment. The single bypass ground set,
to maintain a safe environment is a function called a personal ground set, connects be-
of the equipment and body resistances pres- tween the cluster bar and the conductor to
be contacted. It provides the low resistance
ent. To use this method, some information or
parallel path without requiring the installa-
estimates must initially be acquired. Needed tion of a full set of ground sets a t the worksite
are the worksite available fault current, the on all phases, neutrals, etc. This combination
assumed value of worker resistance and re- method provides a means of worker safety
quired jumper length and the resistance of when the worksite moves from pole to pole,
the remaining path to Earth (pole or tower), within the area between the two ground sets
because that would be the return path. With that make up the bracket grounds.
these data, calculations can be made for sizing
the protective jumper. Equation 7 is a repeat It is important that the worker not touch
of Equation 5a and can be used to make this any conductor except the one connected to
calculation. the single bypass ground set. For example, if
contact is made to phase B while the ground
- IAvmABLE ('JUMPER) ~ q 7. set is connected to phase A, the current shunt
I,,, - path is now phase B conductor length from
(M
' A, + 'JuM,E, ) the worksite to the bracket set and back to
Again using parallel circuit theory, the maxi- the worksite on phase A, then to the cluster
mum ground set resistance can be determined bar. The added resistance of the added con-
which would maintain the body current level ductor lengths may be fatal, depending upon
below the selected value. Even if there is only the resistance of the conductors.
avery small current due to high pole and earth
resistance in the overall circuit, the percent-
age division between the paths remains the
same as the calculated ratios. Obviously, the
higher the current, the lower the protective
ground set resistance must be to keep the
body current below the safe level.
If the worker is on a wood pole with only
one protective ground set in place, the pole
resistance and return Earth path become the
current-limiting resistances. The ground set
Worksite or Single-Point or Earth connection would be bonded together
a t the worksite. The low resistance ground
Equipotential Grounding
set in parallel with the worker provides the
worker protection. The bondingof the phases
The key to a successful equipotential pro-
to the neutral and Earth ensure the maxi-
tection method is to place the worker in a
mum speed in fault clearance. This meets the
parallel path with a conductor of sufficiently
two requirements of a safe worksite, a low
low resistance to shunt the dangerous lev-
resistance parallel path to the worker and
els of current around the body and limiting
the shortest time energized as possible. The
the maximum voltage across the worker to
multiple connection of neutral and Earth
an acceptable level. Remember that some
represent a dual return path to ensure a fast
current will flow in every possible path, but
clearance. This could be a critical feature if an
it divides in inverse proportion to the path's
undersized neutral is present and has insuf-
resistance. The use of a low resistance
ficient current-carrying capability to avoid
jumper is the major factor. The second key
fusing during the fault current flow. The
factor is to have the line protective equip-
worksite potential rise remains a function
ment provide fast fault removal.
of the Earth return resistance and conduc-
This method is commonly referred to as tor and neutral resistances. In many cases,
"Single-Point", "worksite" or "Equipotential the maximum level achieved will be around
Grounding." The OSHA 29 CFR 1910.269 50% of the line voltage a t the time the line
document requires grounding wherever it becomes accidentally re-energized.
can be used. It uses multiple jumpers a t The actual connections recommended for a
the worksite to offer both worker protection wooden structure are:
and fast operation by the system protective
equipment. A ground set from an Earth connection
The term "Equipotential" technically means point to a cluster bar mounted below
equal potential, or objects that are a t the the worker's feet
same voltage (or equal potential). Potential A ground set from the cluster bar to
is another name for voltage. As used in per- the neutral
sonal protective grounding, it refers to the A ground set from the cluster bar to
voltage developed across a worker during the the nearest phase conductor
time of fault current flow. The voltage can- A ground set from the nearest phase
not be exactly the same because current flow conductor to the next phase conduc-
through anything with resistance creates a
tor
voltage drop (refer to Equation 2 in Section
1).The drop can be very small compared to Finally, a ground set to the last phase
the typical utility line voltage. The voltage conductor
across the worker will be the same a s that of
the jumper because it forms a parallel circuit A ground set may be used to connect to a
with the worker. The maximum voltage on staticwire overhead. The staticwire normally
the worker then becomes a function of the should not be used as the only return path. It
fault current through the personal protective often is steel wire, which has a higher resis-
jumper. This is an application
- .. of one form of tance. It does not always provide a continu-
Equation 2 (Vw = R,",,
- I,
X1 ,,,,, 1. I,,,
for all practical purposes because of
ous return path to the source because it may
be intentionally broken at periodic lengths.
the extremely low jumper resistance. This But, it may provide a connection to multiple
voltage must be limited to the maximum Earth return paths to help divide any fault
selected safe value. current present.
value because this is the jumper provid- Rearranging this equation to solve for
ing protection to the worker. Its resistance R m ~ ~ ~ ~ :
must be based upon the utility's selected
maximum body current andlor voltage. This
can be achieved by selecting an appropriate
conductor size and length, keeping in mind R 1,000~Ohms
m= ~ ~ x [o.o9lamp /
that resistance increases with length and de- (12,000 amp - 0.091 amp)]
creases as the cross sectional area increases. = 0.0076 ohm or 7.6 milliohm
The remaining ground sets must be sized to Therefore:
ensure they do not fuse duringthe flow offault
current. These ground sets are to maximize Vw = ImlPERx R ,, = (12,000 amp
the fault current so the system protective - ,091 amp) x .0076 ohm
devices operate as quickly as possible. = 91.2 volts
Which meets the requirement.
An example will be used to illustrate the
procedure for calculating this maximum This will meet the two specifiedrequirements.
resistance value. The values used in the Now it is necessary to select the components
example were selected only for the example. for each jumper assembly.
First, we request the available fault current
and maximum breaker operation time a t the Note that this is the maximum resistance per-
site from the engineering department. Next, mitted for the complete assembled jumper(s)
the company safety department provides the in parallel with the worker. As the worker
maximum allowed voltage across the worker, reaches from one phase to another, the num-
the current through the worker, or both. ber of jumpers in parallel with the body may
Assume: Maximum worksite available fault change, dependingupon the installation. The
current = 12,000 amp. maximum number that can be in parallel
The maximum breaker interrupt must be considered. On a 3-phase system, the
time is 20 cycles (0.333 sec.) worker may place his body in parallel with
The accepted level of safety: up to three seriesjumpers without thoughtful
Voltage across the worker, placement, see Figures 9-6 and 9-7.
V,oR,R,MAX= 100 volts OR
Current through the worker, The cable is chosen from Table 8-1. The avail-
able 12,000 amp for 20 cycles exceeds the
,,
IWORrnR, -
- 113 the heart
fibrillation level AWG#2 rating soAWG 110is selected. Wiring
The average workers weight = 155 tables for copper AWG 110 grounding cables
lb. show it has 0.098 milliohm/ft. Assume each
Average man resistance = 1,000 cable/ferrule/clamp combination resistance
ohms is 0.5 milliohm. Ths provides three 10 ft.
-I=k/& jumpers equal to 1.98 milliohm each or 5.94
ImBmLmTIoN - milliohm total.
where k = 157 for 155 lbs.
and t = ,333 seconds By careful placement ofjumpers at the work-
site, we ensure the worker never has more
- 272 milliampere
ImBmLLmo, - than two series ground sets in parallel with
his body. This will meet the safety specifica-
-
I W O R I=~3' R ,I,IB~RILmT,oN - tions.
1/3 x 272 = 91 milliampere
path to exceed the selected safe level of body be fully rated for the total available fault
current selected by the workers utility. current. In some instances, it may be neces-
sary to parallel grounds to adequately carry
Ifitis necessarytouse longerjumpers, alarger the available fault current. This is also used
cable size should be considered as a means of as a convenience for the workers when the
maintaining the needed low resistance. size of the equipment becomes so large or
heavy that it is difficult to install. To obtain
equal current flow through each paralleled
set, the sets should be identical to ensure
the resistance of each path is equal. The
clamps should be installed as close together
as possible. Because higher fault currents
are expected, cables should be tied to the
structure to minimize whipping or mechani-
cal damage to the clamps. When using this
method and tying the cables together, each
paralleled ground set must have its current
carrying capability de-rated by 10%. Do not
Parallel with up to Three Series Jumpers wind the cables around the structure as this
Figure 9-6 increases the coupling between the cables
and the structure and increases any induced
current or voltage in the structure.
For example:
Equipotential or Single-Point
Grounding at the Worksite
consisting of a cluster bar and single ground- %,I = Worker Resistance = 1,000 ohm
ing jumper. Note that this method requires
the installation of both the full set described Personal protective jumpers between the
as Equipotential (or single-point protection) worksite and Source A:
plus the personal ground set.
I, = ISOURCEx (RJl + R,+ % + Ra + RN)l the cluster bar to the conductor, as here con-
= 10,000 x [(0.001/(0.001+0.024 tact is expected, in parallel with the worker
+ 1,000 + 0.001+ 0.024)] to provide protection to the worker aloft.
= 10 milliampere Again, the distance from the fully installed
or 10 volts impressed across the worker. set must be considered. In this case, there
Personal protective jumpers opposite from always will be a full set of protective ground
the worksite and Source B: This is a situa- sets present and a low resistance ground set
t i o n t o avoid. in parallel with the worker, assuring lower
current through the worker and rapid removal
of the line voltage.
Additional distance away from the full set is
achieved by addingthe jumper to the personal
jumper described earlier. Placing the ground
sets from the cluster bar to the neutral and
from the cluster barto the phase beingworked
ensures the worker always will be in parallel
with a low resistance ground set.
Assume the worksite is now five spans from
X (R, + R,, + RN)1 (R, + R,,
IM = ISOURCE the installed personal protective ground set
+ R,+R,+R,,) on the side away from the source. R, and RN
are now (5 X 0.024) = 0.120 Ohms each.
(0.024 + 0.001+ 0.024+ 1,000 + ,001)
= 490 milliampere
-
Now calculate the current through the
worker using Equation 5.
I, 10,000 X (R,, / (R,,
milliampere
Or a body voltage of 10 Volts
-t R,)) = 10
toucl~esany metal part essentially is touching would then be developed across the person. If
the line voltage.
- Remember: For ~rotection. the outriggers are placed on dry wood blocks,
A
a worker must be insulated, isolated or in there may not be a good Earth contact and
parallel with a low resistance path. any contact with the vehicle could be fatal.
Tests have indicated that the voltage across This is an excellent but deadly example of
the body of a person standing immediately the "touch potential" hazard, illustrated in
. ., . . . . .- F~VIII-O 11-Q
Grounding the truck body does not change additional hazard to be aware ofis flash burns
anything. It only protects the system. Ground- from a high current arc that may occur during
ing to a driven rod helps ensure the system a fault current flow.
will recognize a fault current and the break- Maintenance on theabove~groun~equipment
ers or fuses will operate, but does not offer typically requires the cables coming up from
any protection the person in with below grade to be This usually
the truck while standing on the Earth. The means placing both end elbows of the same
truckalready has multiple contact points with cable on agroundedparkingstand, afeed-thru
the Earth formed the tires and bushingwith a fault-current-rated grounding
Each of those contacts transfers the elbow, or other equivalent method as allowed
from the truck body to the Earth at that point. by the utility work rules, This bonds the
Adding another contact point provides center conductors, concentric neutrals and
a redistribution of the available current into the Earth together at those points. Similar I
the available paths. Tests have verified these requirements apply to work in vaults. 1
!
scenarios. See Table 11-1. i
I
Table 11-1 !
barricades should be established so the truck rubber glove or hot stick work difficult, if not
cannot be touched during the work. After this, impossible. Because ofthis difficulty,workers 1f
i
the boom can be elevated and work begun. may resist this method. Insulation is not a j
The barricade shouldnot be removeduntil the
boom has been lowered again into a definite
practical method to use for working on buried
cables between connection points. Rubber
11
position of non-contact with a phase. gloves make cable stripping and splice as-
I!
sembly nearly impossible.
Portable ground mats could be placed and j
connected around the truck. This develops Isolation is the method of keeping the worker t,
an equipotential zone for the worker. How- away from any situation that would allow
ever, he must remain on the nlat during the contact with any possible source voltage. The Ij
1
entire time the boom is elevated and until it alternative is to totally isolate equipment from
is lowered before it is safe to step off. any power source. This may not be practical for
maintenance of existing installed equipment
.,
Underaround because every connection must be removed Ii
and isolated: This method also is plagued
Protection for workers on underground sys-
with the difficulty of work problems similar
tems is much more difficult because of the
to that of insulation,
.
comaactness of the eaui~ment.the location
of the work and the difficulty defining safe The Equipotential Method is better suited
work procedures in this environment. How- for use a t connection points, switches, trans-
ever, the same methods of protection apply: formers, etc. Because a worker is standing
" 1 1 - . + + I - - nn tho E'qrth ",,A honrll;r," no*+, thnt mn.i
bonding a conductive mat to the normally concentric neutral and the center conductor.
energized part to be contacted (after it is If the conductor is energized, an arc is es-
de-energized). Note: The elbow is parked on tablished to the neutral. This is a crude but
a grounded parking stand. This connection effective means of ensuring the correct line
and the mat under the worker establish the has been de-energized.
zone. As long as the worker remains on the
After this determination, work can begin.
mat, the voltage developed across the body is
Extra care must be exercised during the
limited to the drop across this parallel connec-
actual cutting to ensure the cable remains
tion. This is illustrated in Figure 11-10. The
de-energized as there is no protection until
size of the mat can be extended to include a
the conductor is exposed and bonded. Remote-
second worker or tool placement by bonding
operated hydraulic cutters often are used
additional mats to the first. The mats must
for this task. A temporary connection should
remain bonded together during the work and
be made between the concentric neutrals of
the hand-to-foot resistance of the total path
the two open ends to maintain continuity
in parallel with the contacting worker must
as it functions as part of a system neutral.
remain low.
A conductive ground mat to work from can
then be bonded to the concentric neutral. The
two center conductors cannot be included in
the bonding until they are exposed. During
the stripping, a hazard will exist if the line
becomes accidentally energized. When the
connections are complete, see Figure 11-11A,
themat develops an equipotential zone for the
worker if the cable is accidentally re-energized
by a fault from either direction.
attached line but they may form an induced example, transformers have the capability
current loop. They are widely used in large to step low voltages up to lethal levels. Even
substations. test equipment connected to the low voltage
windings can raise the output to a high volt-
Because of the size, length and weight of the age. Capacitor banks must be discharged
protective equipment, assistance with the before handling. The terminals must remain
installation is sometimes required. A tool shorted to prevent charge from migrating
that isvery helpfulinlifting alarge bus clamp from the dielectric material to the terminals
with one or two AWG 410 cables attached is and re-establishing a hazard. Large power
the Chance Lift Hook Assembly (Shepherd's cables and their terminations can retain a
Hook). This is a long, insulated handle with charge. They should be grounded and remain
a large hook on one end. Near the hook is a grounded before handling or cutting.
rope pulley. The hook is placed over the bus
and the rope is connected to the clamp to be Personal protective jumpering methods in
landed on the bus. A second worker guides substations are similar to the methods used
and tightens the clamp using a n equally at remote work sites. The underlying prin-
long Gripall Clamp Stick (commonly called a ciple of maintaining a low-resistance path
"shotgun" stick). The rope must be clean and closely in parallel with the worker remains
dry to be considered insulating. the same. One difference is that a grounding
jumper some distance away from the actual
Other specialty items available for use in worksite can be added to the protection in a
substation personal protective jumpering substation that has a buried grid. While the
are various lugs, stirrups and studs. These multiple connections aid in increasing the
devices are all designed to provide permanent overall current carrying capability, it poses
connectionpoints for the protective equipment other problems. The greater the separation,
necessary for working safely. Figure 11-14 the larger the loop formed by the jumpers, the
illustrates some of these devices. worker and the grid. As this loop increases,
the voltage across the worker will increase. A
hazard if applying or removing the personal
jumper by hand.
" www.hubbellpowersystems.com
E-mail: hpsliterature@hps.hubbell.com
Phasing Testers
-
2452
POWERSYSTEMS, IWC.
for +DistributionCircuits
ChancePhasingTesterseasilydeterminephaserelatio~lships
and approximate voltage, line-to-line or line-to-pound.
Each tester consists oftwo fiberglass poles with end fittings
threaded for interchangeable probes. The probe fittings
couple with a high-impedance component encased in each
pole. To complete the test circuit, a 22-foot length of insu-
lated flexible cable stores on the reel affixed to one pole and
connects to the voltmeter on the other pole.
S1rn111c:to operate, the tester polc;; first attach t,, I\VO 6-foot
Epoxixl;t.;: insulat~tlruniversal h;inclles inclu~le!cli n each
Gt forproper working clearances). Then the probes can be
brought into contact with the conductors appropriate for the
meter to read phase-to-phase or phase-to-sound voltage.
Distribution Phasing Testers
Single-Range Units
Catalog No. I Description Weight
HI876 1 '16 kV Tester K i t / 27% lb.112.4 kg.
HI8761 / '16 kV Tester Hook Probes,
Case and Manual
1 -
23 lb.ll0.4 kc.
Accessories
14 I HI7601 I Universal Pale 1Y.C x 6' / 1%lb.10.7 kg. /
-%a Needed
P6436 Bag for Two Poles 1 lb.10.45 kg.
A d a p t e r s ( p a g e 2458) a n d
HI8763 Case only for Tester 2 lh.10.9 kg.
A d a p t e r s f o r E l b o w s and
R..cL:..-.- *ACV\ I H18766P Pigtail Hook Probe % lb.10.1 kg.
Distribution
Phasing Tester Kit
for overhead
and Underground Systems
Dual Range: 5kV & 16kV Scales
C4031762
To check instrument
before and after use, Phasing
Phasing Voltmeter Voltmeter
Tester lead plugs into Tester (with
test-point jack by ,, HI7601 Hotstick
meter. Other lead in Kit P6436 Bag
clips onto each probe.
Switch on Voltmeter
Tester reverses
polarity for thorough,
easy field-checking
procedure. Complete
instructions included.
Ordering Information
Catalog No.1 Description
T4032557 1 Phasing Tester Kit
Weight
13l1I2lb.114.2 kg.
For convenience on different systems, toggle on meter hous-
ing can- switch
-. calibration
. .
between the .
. . ...
two. scales.on .the II
2454
POWER SYSTEMS, IWC.
Digital Phasing Testers
* 16kV and 40kV models, plus 80kV extensions
For Overhead & Underground
,
2455
Digital Phasing Testers pOmsysRMs~E
Two HI7601
6-ft. x lt/,"-dia. 6-ft. x l'/,"-dia. Tester
EpoxiglasO
universal poles
in P6436 Bag
Extension Resistors for 16kV Digital Phasing Tester Extension Resistors for 40kV Digital PhasingTester
HI8762 Pair of Extension Resistors 6 lb.12.7 kg. C4033371 1 Pair of Extension Resistors 1
4 lb.11.8 kq.
.
for up to 80 kV (32" long) I for up to 80 kV (21" long)
HI8764 Pair of Extension Resistors 4 ib.11.8 kg. P6242 I Bag for C403-3371 80 kV Resistors 11 lb.10.45 kg.
for up to 48 kV (21" long) NOTICE: Use ONLY the Extension Resistors SDecified for each
P6242 Bag for 48 kV Resistors 1 lb.10.45 ikg. Digital Phasing Tester as listed on this page.
P6244 Bag for H1876-2 80 kV Resistors ?'A lb.10.56 kg. Extension Resistors are NOT interchangeable between
16kV and 40kV Dioital Phasino Testers.
2456
@z2&n
POWER SYSTEMS,IHC.
PSE4033473
Phasing Voltmeter Tester
for Digital Transmission
Phasing Testers -
40 240 kV
Digital PhasingTester
The tester uses each instrument's own meter to disnlav its
operating condition. The tester plugs into the jaclcon the
instrument and meter readings are noted when the tester's C4030459
clip is contacted to each of the instrument's two terminals 96" Epoxiglas@
and the tester's polarity switch is in both of its positions. If Handles
all four readings are within two units, the instrument is in
proper worlring order. Pulling the plug from the jack auto-
matically disconnects the tester's battery. The 9-volt battery,
furnished, usually lasts one year and is easily replaced. The
tester's durable and compact fiberglass housingwillwithstand
the abuse of field applications.
1 Catalog NO. 1 Description / Weight I
POWER SYSTEMS, INC.
2457
Analog PhasingTesters
Three kits for Transmission Circuits
To easily determine phase relationships, these Chance
Phasing Testers read approximate voltage (line-to-line or
line-to-ground) on transmission circuits. The testers consist
.,
of two high-imnedance comnonents encased i n fiberglass
1101t!s,t:;lch with an elltl fitt~nfi thro;~dedibr intcrcliangc:~bll:
l1110k 1~r011(:s.1\22-i0~t-Io~~lr insulatt.tl Hex:blc cable fro111tlit.
voltmeter stores on a reel-on the other pole
Three comnlete kits offer achoice ofvolta~eranaesfors~ecific
..
system a p p l i c n t ~ ~ Each
i ~ s . kit includeha p i i i r ~ f l :'-tlii~n~etcr
'
inst~l:~ted hnndlcs for orol,er \vorkinr:clea~~anccs. Individunl
items listed in each tit's bill of materials may be ordered
separately by reference numbers given.
Orderina Information
Weight
39 lb.117.7 kg.
(1) Instruction Manual
(1)I34030498 'Ibster (62"long) 22%lb.
(2) C4030459 Handles (96") 10 lb.
1 111 -~
. . P6218 Bar for Handles 1108"l
(1)C4030460 Bag for Tester
~
3% lb.
3 lb.
C4030458 169-161kV Phasing .Tester Kit: 44 lb.120 kg.
(1)Instruction Manual
(1)I34030499 Tester (75"long)
(2) C4030459 Handles (96")
(1)P6218 Bag for Handles (108")
[ ( I )~ 4 0 3 0 4 6 4 for
~ a'Ibster
~
T4032781 69-240 kV Phasing Tester Kit:
(1)Instruction Manual
27Yi lb.
10 lb.
3% ib.
3 lb.
60 1b.127.2 kg.
1 H -
96" Epoxiglasm
11 Analog
Transmission
Phasing Tester
1
(1) E4032780 Tester (98" long1 43%lb.
(2) C4030459 Handles (96") 10 lb.
(1)P6218 Bag for Handles (108") 3% Ib.
(1)C4030464 Bag for Tester 3 lb.
Ordering Information
Catalog No. Description Weight
PSC4033465 10 - 120 kV PhasingTester Kit: 39 lb.117.7 kg.
(1) lnstruction Manual
(1) PSE4033454 Phasing Tester 22% Ib.
(64"long)
(2) C4030459 Handles (96") 10 lb. Large direct display with
(1) P6218 Bag for Handles (108") 3% Ib. backlight and hold features
(1) C4030460 Bag for Tester 3 lb.
PSC4033466 40 - 240 kV Phasing Tester Kit: 60 lb.127.2 kg.
(1) Instruction Manual
(1) PSE4033455 Phasing Tester 43% Ib.
(102"long)
(2)C4030459 Handles (96") 10 lb.
(1)P6218 Bag for Handles (108") 3% Ib.
(1)C4030464 Bag for Tester 3 ib.
D.C. Hi-Pot the larger end threads onto the meter probe of the
phasingtool. Fortesting andsubsequent discharg-
ing, a brass female fitting a t the smaller end accepts
URD Test Adapters either ChanceElbowAdaptersorBushingAdapters
for 15 through 35 kV (page 2455).
For quick, reliable fault detection on underground cables,
two units are available for phase-to-phase system voltages Illustrated instruction booklet is included. Units
up to 16 k~ or 35 k ~B~ . c o n v e r t i n g ~source
~ voltage to a contain high-voltage rectifiers encapsulated in
rectified half-wave, these adapters permit testing of cables Orange l'" and l"' diameter Epoxiglasm
with a potential level equal to peak source voltage. This housings.
field-effective method proves especially beneficial for: Hi-Pot Adapters measure only 13" i n length for 35
Testing new cable before initial energizing. kV unit, and 10" for 16 1cV unit, far right.
* Testing repaired cable before re-energizing. Catalog No. Description Weight, each
* Testing suspect cable spans for faults.
C4031762 '';I6 kV Hi-Pot Adapter 1lb.10.45 kg.
Formetered readout, theHi-PotAdapters workwith Chance c~~~~~~~ +35 k~ ~ ~~d~~~~~ - p l ~b , ~~ kg,
~ . ~ ~
Phasing Tool HI876 (page 2452). Abrass male fitting inside
"'Maximum phase-t
eter Stick of Phasing Tester
Disconnect
Buried
Primar
Cable
Auto-Ranging ee
POWER SYSTEMS, INC.
2460
Voltage Indicator (ARVI)
Complies with OSHA 1910.269 to Test for Absence of Nominal Voltage
a 6 0 0 to
~ 69kV For Overhead & Underground
Bright display lights indicate voltage class
This smart new-generation instrument makes hot-line volt-
age testing easier than ever. Its state-of-the-art electronics
eliminate the needfora selector switch. Its automatic-ranging
functionquickly displays the approximate line-to-linevoltage
class. It provides a n easy, yet reliable means for the operator
to determine if a line is:
a ) De-energized, or
b) Carrying less than normal system voltage from any
source or induced charged from an adjacent live circuit,
or
C) Energized a t full system voltage.
Simpletooperate, thetesterattachestoan Epoxiglas"insu1at-
inguniversal handle of appropriatelength to maintain proper
OSHAworlung clearances. Asingle pushbutton activates the
instrument, then a single light indicates either Power On
(by glowing solid) or Low Battery (by blinking). With a good
battery condition, the instrument performs a confirmingself-
test by illuminating each of the six indicator lights in series
while emitting an alternating audible signal.
Then the probe can be brought into contact with the conduc-
-
tor. I t automaticallv. bezins detectine a t anwroximatelv 480
Volts and holds t h e display of one $ thesevoltage e1;sses:
600V, 4kV, 15kV, 25kV, 351cV or 69kV phase-to-phase. The
audible signal begins as a slow beeping that becomes faster
a s the final reading is displayed.
When not i n use, the unit's energy-saving Sleep mode auto-
matically conserves the battery.
ARVI
Auto-Ranging
Votage lndicator
ARVI Kit
for Overhead and Underground
Catalog No.T4033418 (16Y4lb.n.37 kg.)
Includes the tester unit, shepherd hook probe, elbow
adapter, bushing adapter, voltage indicator tester,
instruction manual and hard shell padded case.
Basic ARVI
for Overhead A ~ ~ l i c a t i o n s
PQWER SYSTEMS. INC.
Ordering Information
URD Voltage-Presence
Test on elbows with
Test Points can be
performed with Straight
Probe when selector is
Includes:
Straight probe for URD elbows with test points
H o o k robe for overhead uses
POW SYSTEMS, IIIC.
URD Voltage-Presence
Test on Elbows with
Test Points can be
performed only by
Model C4030979*set Ordering Information
at TP and fitted with
its Straight Probe. Distribution and Transmission
Multi-Range Voltage Detectors
Catalog No. Scales Weight
C4030979"; 1- 40 1cV 5% lb.12.5 kg.
- C4031029 - 16 - -
161 1cV 5% lb.12.5 kg.
C4031140 69 - 600 1cV 5% lb.12.5 kg.
;!:For testin- TJRT? dhows with teal: noints n n l v mnrlol
POWER SYSTEMS,BC.
I
Multi-Range Voltage D(
for Overhead & URD ~ .
v s t e m sto 40 kV
This Multi-Range Voltage Detector (MRVD)tests both over-
head andunderprounddistributionsvstemsinvoltace classes
from 5 through$kv. ~hismode1~ro;ides aneasy, yltreliable
means for the operator to determine if a line is:
a ) De-enerzized.
- . or
b) Carrying less than normal system voltage from any
source or induced charged kom a n adjacent live circuit,
or
c) Energized a t full system voltage.
For this basic function, this model adapts to both overhead
lines as well as URD circuits with 200 and 600 Amp load-
break elbows, including those with and without capacitance
test-points. Interchangeable probes and adaptersjust thread
into the MRVD end fitting and the selector switchdials to the
voltage range or test point (T.P.) setting appropriate to each T4032271
application. Furnished owner's manual illustrates operating
details for all models. for Overhead and for URD Loadbreak Elbows
with
Straight
Probe
on
Elbows
with
Test
Points
and
your feed-thru device*
C4031369
for0-lOkV
Elbow Bushing
Adapter Adapter
Instruction Booklet
POWBl SYSTEMS, IHC.
Protective-Grounding-Set Tester
* U.S. Patent 5,811,979 Meets ASTM Standard F 2249
* Microprocessor technology for easy, accurate diagnostics
Protective-Grounding-SetTester
U.S. Patent 5,811,979 Microprocessor technology for easy, accurate diagnostics
Meets ASTM Standard F 2249
I I
Optional Straight Stud Terminal T4033159 for testing Optional Elbow Adapter C4033449 for testing temporary
grounded-parking-stand temporary grounding sets. grounding sets fitted with a grounding elbow.
Ordering Information
Included with each Protective-Grounding-Set Tester:
* Self-contained carry case * Instruction manual
* 2 Ball-stud terminals 0 2 Troubleshooting probes
Complete
Protective
Optional Adapters: Ground-Set
Tester
T4033159 Straight Stud Terminal ?4113.10.225 kg. Catalog No.
for 15 and 25 k V C4033220.
C4033449 / Elbow Adapter I 1lb.10.45 kg.
I
section
e>
I mmrornL
3000
I Grounding
~quiprnent
Section 13
3002 Chance grounding clamps, ferrules a n d cable meet ASTM F855,
POWER SYSTEMS, IWC.
To indicate energized conditions on overhead lines, (from leR) Chance Auto Ranging Voltage Indicator, Digital Volt-
age Detector and Multi-Range Voltage Detector. At far right, Energized Cable S e n s o r performs the same function
on URD cable with an exposed concentric neutral and elbows without test points.
See Catalog Section 2450, "Instruments and Meters," for details and ordering information.
General Practices
On de-energized distribution lines, Chance recommends Double-Point grounding ( a t b o t h s t r u c t u r e s a d j a c e n t t o w o r k
site: jumpering all three phases together and grounding) p l u s a personal ground a t the worksite (from any one phase
to a grounded cluster bar well below the worlcer's feet). On a system without a neutral, Chance recommends connecting
down leads to screw ground rods installed a t least 20 feet from all structures and barricaded. Only for maintenance tasks
during which grounds need n o t be replaced does Chance find acceptable the Single-Point grounding method ( a t only t h e
worksite: jumpering all phases together and grounding plus personal ground, as above).
Where adequate phase-to-phase clearances permit, Chance accepts the practice of grounding only the phase being worked
(in the same manner as personal ground, above).
5. ShrinkTubing , , I i'
I
' ,
eThis translucent
..
option .recommended
.. " .
for stress relief
. and .. . >. I .
I
3004 -* Chance grounding clamps, ferrules and cable meet ASTM F 855.
PDWER SISTEldS,INC.
C-Type Grounding
-
Jumper Range Min.
Chance grounding clamps, ferrules and cable meet ASTM F 855. 3005
POWER SYSTEMS, IHC.
C-Type Grounding Clamps
T6003203 T6000658
*Mounted Clamp Aluminum body, Aluminum body,
Aluminum body, Smooth jaws, Smooth jaws,
Serrated jaws, Bronze eyescrew Bronze eyescrew
Bronze eyescrew with Acme threads, with Acme threads,
with Acme threads, Tapped for 5/w11 UNC Drilled for 5/a-11 UNC
Bronze pressure-type terminal threaded ferrule threaded ferrule
Recommended Torque (m -Ib 250 250 250 250 250 250 250
I I I I I I I
Main Line Range -Max. 2' O.D. Bus 2" O.D. Bus 2" O.D. Bus 2" O.D. Bus 2' OD. Bus 2" O.D. Bus 2" O.D. Bus
" - iviin.
Main Line Renco / Pfi Sol. Cii.
-~ I tffi.Snl
. ... Cn
.. . I !.J.(i.S- .
n.l. C.
n.. / Pfi.Sol Cn
..~~I it6 Sol. Cu. 1 #6 Sol. Cu. I #6 Sol. Cu.
/ 1 1 / 1 1 1
~ ~~~
G3369 C6000337
Aluminum body, Aluminum body,
Smooth jaws, Smooth jaws,
Bronze eyescrew Bronze eyescrew
with Acme threads, with Acme threads,
Bronze pressure-type terminal Bronze pressure-type terminal
GI8102
Aluminum body, G36221
Bronze upper jaw, Aluminum body,
Smooth jaws, Smooth jaws,
Bronze eyescrew Bronze eyescrew
with fine threads, with fine threads,
Bronze pressure-type terminal Bronze pressure-type terminal
HG37061
'Mounted Clamp T6000806
Aluminum body, Aluminum body,
Smooth jaws, Serrated jaws,
Bronze eyescrew Bronze eyescrew
with fine threads, with fine threads,
Bronze pressure-type terminal Bronze pressure-type terminal
C6000198
Aluminum body, 'Mounted Clamp
Aluminum body,
Bronze eyescrew Serrated jaws,
with fine threads, Bronze eyescrew
Tapped for Sh-llUNC threaded ferrule with Acme threads,
Tapped for 5/s-ll UNC threaded ferrul
C6000197
Aluminum body, C6000434
Aluminum body,
Bronze evescrew Serrated jaws,
with ~ c m threads,
e Bronze eyescrew
Tapped for =h-11 UNC threaded ferrule with fine threads,
Bronze pressure-type terminal
3-Cluster Set
Smooth jaws, Bronze eyescrews with Acme threads, Smooth jaws, Bronze eyescrews with fine threads,
and &phase Aluminum cluster bar and 3-phase Aluminum cluster bar
with Bronze Pressure-type terminals with Bronze Pressure-type terminals
Important Note:
Cluster Sets are furnished as shown above. The center clamp is bolted to the cluster bar.
Typical fourth ground clamp
(not included in 3-Cluster Set
must be ordered as separate ite
I I
Jumpet.Rnnge - Mor. 410 Grd. Cable 210 Grd. Cable 210 Grd. Cable 410 Grd. Cable 210 Grrl. Cable 210 Grd. Cable
$",Threaded Stud wlPlain Plug w,Threuded Stud \/Threaded Stud wmlain Plug w,Tl>reudcd Stud
3010 Chance grounding clamps, ferrules and cable meet ASTM F855.
POWER SYSTEMS.IHC.
Jumper Range - Max. 410 Grd. Cable 210 Grd. Cable 210 Grd. Cable 410 Grd. Cablo 210 Grd. Cable 210 Grd. Cable
wffhreaded Stud wPlain Plug ~vmhreadedStud wvmhreaded Stud \"Plain Plug w/Phresded Stud
-
Jumper Range Ivlin. #2 Grd. Cable 112 Grd. Cable 112 Grd. Cable #2 Grd. Cable #2 Grd. Cable #2 Grd. Cable
wR.hreadcd Stud w/PI.lin P l m stirri
~ P r h ~ ~ ~ r i~ ~
vm~ hi r ~ a rSl ~
t ~dl d ivlPlilin Plmn t u m h r o a r i ~ rS
i tl~ri
Chance grounding clamps, ferrules and cable meet ASTM F 855. 3011
POWER SYSTEMS,IHC.
G33631 C6000085
Bronze body, Aluminum body and retainer,
Serrated jaws, Bronze scrubber-type contact pads,
Bronze eyescrew BronzeT-handle
with fine threads, with fine threads,
Bronze pressure-type terminal Bronze pressure-type terminal
G33632 C6001783
Bronze body, Bronze body,
Serrated jaws, Serrated jaws and retainers,
BronzeT-handle Tapped for 5/r11 UNC threaded ferrule
with fine threads,
Bronze pressure-type terminal
W"i"hi Ti,rh
w/Plvin Plug
01,. ,L 83 . 7.-
wlPluin Plug
"1, ,L .
,, ,...
iviFlain Plug
":a, ,L 3. ., ~ - wn'hreaded Stud
7 ,, ," "- >
3012 Chance grounding clamps, ferrules and cable meet ASTM F855.
POWER SYSTEMS,IHG.
All-Angle Grounding Clamps
Aluminum Bodies with Serrated Jaws
-:*,
.,
G42291SJ C6001732
'PressureTerminal *Bronze PressureTerminal Tapped for 5h-11 UNC threaded ferrule
(Clamp same as G42291SJ)
'' For adapter to convert t o threaded terminal, see Page 3019.
1 Catalog Number I G42291SJ I 'HG42296SJ I C6001732
For installation ease, jaws pivot ELECTRICALRATINGS
75" left or right.
Continuous Current (AMPS) 1 400 I 400 I 400
Fault Current - 15 Cycles (AMPS1 1 43,000 43,000 43,000
Fault Current - 30 Cycles (AMPS1 / 30,000 30,000 30,000
MECHANICAL RATINGS
' . --
16001693
G422810SJ tHG422816SJ Tapped for $/s-ll UNC threaded ferrule
+Bronze PressureTerminal 'Bronze PressureTerminal (Two single serrated jaws,
(Clamp same as G4228-10SJ) for pothead and bus applications)
ASTM Designation of Type I, Class A, Grade 5 for any of Ball Stud C6002102
these clamps is met if associated grounding-cable sets are 5," dia. shank
fitted with 5/s" copper ferrules as on page 3019.
Weight, each:
Ib. 10.23 ka.
Fault Current Ratings 43,000Amps - 1 5 cycles
-
30,000 Amps 30 cycles
Grounding Stud Cover -fits onto 1" ball-studs of Apparatus Grounding Clamps above
This flexible cover fits only C6002102 or T6002364 ball- Snap-fit keeps cover i n
studs. Ofthe same material a s Chance line hose. nonconduc- place. The 5h"-I.D. loop
rive covr.r n1:1y hclp prcvcnt H:i~hoveron btill stucls init:llled a t top permits hot-line
in cllrlosed swlrchgml., ;;witchy>r~l.;or subsr;irions. tools to "pop" i t on and
An tn\,ironlnent:il protrrrurto rc-ducr corrwslon n1ld(ontnm1- off. Chance silicone
n:ition on rhe h;lll-stu~l\ellen enrrpizc(l cover IS 1101 intcntlrd lubricant C4002320
for personnel protection and should not be considered as t,r C-1170287 lnlny case
i n s d a t i v e cover-up equipment. Resilient ozoneicorona- instnllarion :md re-
resistant thermo-plastic elastomer does not absorb water. moval
Special formulation resists aginglchecking and retains high-
visibility orange color.
3014 Chalnce grounding clamps, ferrules and cable meet ASTM F855.
POWEB SYSTEMS, INC.
Catalog ~ 0 . ~ 6 0 0 3 0 9consists
4 of:
I A ISerrated iaw. " C clam^ / 10 / For Plain Plug for- 1
Cat. No. C600227G rules
B Glaund Cluster Support 1 Cat. No. TG001549
110 Copper Ground Cable 60 R. 3 Cables G R. long
C Cut. No. S7568 1Cable 12 ft. long
1 Cable 30 ft. long
D U0 Plain Plug Ferrules 10 Cat. No. CG002627
E Clamp Support Stud 3 Cat. No. G3626
F Scrow Ground Rod 1 Cat. No. G3370
Chance grounding clamps, ferrules and cable meet ASTM F 855. 3017 i
POWER SYSZEMS. IHC. 1
Cutout Grounding Clamps
Bronze clamp is used to ground the bottom hinge contact on
cutouts used on distributionriser poles orwheregrounding is
required. I t fits these cutouts: ChanceF2, F3, and C Cutouts;
Westinghouse LDX, Southern States B-80; Southern States
Series 63; Joslyn; S&C Type SX; McGraw-Edison LMO, and
GE Durahute.
Clamp can be installed with or without grounding cable to
aid as a warning and possibly avoid accidental closing of
cutout.
CIamp'.;(lr~lledtel.rnil~;iiacccprs riireadcd-stud citblr ferl.ule.;.
Ii :~iso: ~ c c c ~tlircnded
ts I.-Stud ;]nil 'l'Stlld 'Il:rni~nals 'V:
diameter bronze) for use with conventional ground-clamp
cable sets.
Fault Current rating: 20,000 amps for 30 cycles
-I
Catalog NO./
- ..... . .
Description Weight, each
Chance grounding clamps, ferrules and cable meet ASTM F 855.
POWER SYSTEMS, iNC.
Extension Pole
I
Electro-Static Precipitator T6000891
Grounding Tool Set
Simple Safety Procedures
By design, this tool set provides a reliable means of drain-
ing off static charges that remain on collector plates after
electrostatic-precipitator pollution-control equipment is de-
energized for servicing. Pre-assembled for Ready Use
With the electrical system of the precipitator de-energized, Epoxiglas"11andle (42"x1%")meets OSHAelectrical require-
first secure the tool's grounding clamp to a known ground. ments, gives operator sufficient added reach needed to make
Then use insulated handle to bring the Copper hook in contacts. Contact hook of 98%-conductive Copper is double-
contact with the precipitator collector plates. The Contact bolted to handle. T-handle Aluminum grounding clamp with
hook hangs from the collector plates (with the grounding semated flat-face jaw assures proper bonding. Jaws open to
clamp still attached to groundl while selvice is performed 1W for attachment to grounded structural angles, flats or
on the precipitator. rods. Extra-flexible (1638 strands) Copper grounding cable,
7 ft., with clear jacket fitted with Copper
. terminal a t each
Who" rnn;n*anonrai. mmnlotorl .rrn+h,:""..l^+"A I.--d1- r.. . . ...
Chance grounding clamps, ferrules and cable meet ASTM F855. 3019
- Ferrules
Grounding
Selection criteria
ROWER SYSTEMS,IWC.
See ordering tables for crimping-die sizes applicable.
S h r o u d e d f e r r u l e s overlap onto thegrounding cablejacket
for stress relief to the terminal. Two crimps secure the fer- 1 Unshrouded ferrules
rule against the bare strands and one crimp applies on the
, . I , I,.,:,. ,#,,
jacket. !~III~~I!I,;,!,
U n s h r o u d e d f e r r u l e s are available with shrink tubing
that overlaps the bare cable conductor and jacket for stress Cable
relief.
Available e i t h e r factory-installed i n p a i r s o n a n y cable
l e n g t h specified o r as s e p a r a t e iildividualunits, thefer-
rules install simply with a hydraulic crimping tool. Complete
illustrated installation instructions come with the ferrules
and include a table for the crimping die sizes to use. Cable
Copper ferrules
Plain-plug type for pressure-type grounding-clamp terminals
Shrouded plain copper ferrules Unshrouded plain copper ferrules
1 1 1 1 unit each, I I Cable I
I not installed I
Burndy Die No.$ I Size, I
Catalog No. or equivalent
C6002614
C6002615 U165
C6002616 U165 210
C6002617 U166 410 I
Copper Groundina Cable Either aluminum or copper ferrules may be used with copper
cao c .
Cst,lo s.,. II,.,,,,,.,,, :\I,,,!, x 0 1) :\1,1,r,, It',
I . \ \ s . I,,rl,r, 11.r.o~. Ib11.000 ft
Yellow-Jacket Copper Cable
56116 2 665 0.320 0.55 280
Conper Grounding Cable is available i n black. vellow and 56117 110 1045 0.410 0.66 425
cl&, is extra-flexke for handling ease yet strong and tough 56118 210 1330 0.470 0.73 520
for long wear. Jacketingis smooth, abrasion, weather and oil 56119 410 2109 0.590 0.87 760
resistant in accordance with applicableASTM Specifications, Clear-Jacket Copper Cable
marked with AWG size approximately every 4 feet. 56449 2 665 0.344 0.53 289
57568 U0 1050 0.445 0.63 520
Yellow and black jackets are T-prene rubber compound with 56450 210 1323 0.487 0.70 546
-20°F recommended low temperature. Clear jackets (which 56451 410 2107 0.616 0.84 841
allow visual inspection of strand conditions) are ultravio- Black-Jacket Copper Cable
1-4. :"L:h:'."A 3,,.1..x,; ,...I nh,",.:,l" ,DX,", D ----.-*--1-2 I"... C1711 I 1 I En& 1 "29" 1 n G6 I "t2n
3020 @S
& Chance grounding clamps, ferrules and cable meet ASTM F855.
POWER SYSPEMS, IHC.
Aluminum ferrules
Plain-plug type for pressure-type grounding-clamp terminals
Shrouded plain aluminum ferrules
-
Shrink tubina for lain ferrules
Clearheat-shrinktubes providecorrosion-inhibitor by exclud-
Unshrouded plain aluminum ferrules
ing moisture and stress-relief for cable jacket and ferrule-to-
1 unit each, Cable
stranding connection.
not installed Burndv, Die No.'
~~~~-~ Size.
----,
Catalog No. or equivalent AWG Part No. Lengths
C6002610 U165 #2
P6001593P
C6002611 U165 110 P6001982P
C6002612 U165 210 Pfi002069P
C6002613 11249 410
'Anderson die-less VERSA-CRIMP compression tools require no dies and are capable of making these crimped connections.
if using another crimp tool brand, contact that manufacturer for Burndy die equivalents.
Conversion Terminals
Threaded-terminal adapters for pressure-type grounding-clamp terminals
1
I
Simply retrofit these bolt-on adapters to convert clamps
with pressure-type terminals to accept %-11 UNC threaded
ferrules.
Typical Application
Storage Bag
for Temporary Grounding Clamps-and-Cable Sets
Cable Splice
for cables with plain-plug ferrules
arerequired.
Useforsplicinggroundingcablewhenextensio~~s
Thumb screw makes attachment easy.
Cluster Bars
for wood, steel and concrete poles and
tower angles
Compact 5" aluminum-alloy bar(?@ diameter) accepts C-type
or duckbill clamps for phase-to-phase grounding technique.
Adjustable wheel binder and 3 6 chain for pole applications.
Hook style for attachment to tower angles. for poles only
CatalogNo. 1 Description I Weight
T6001549 / Pole-Mount Grounding Cluster Bur 1 71% lb.14.09 kg.
T6001737 1 Towel;Mount Grounding Cluster Bar / 9 lb.14.09 kg.
. i
Chance grounding clamps, ferrules and cable meet ASTM F 855, 3023
POWER SYSTEMS,IHC.
Temporary Ground Rod The Ch.incc Screw Ground Rot1 pro\,itles n te~~~porrlr~.grou~icI
woere a system ground is not ~ ~ \ ~ : i i l :\\'lien
~ b l ~ ~instnllccl.
. the
6' spiralea g r o u a rod develops less resistance than straight
ground rods. However, actual effectiveness depends upon
soil properties. The reusable Ground Rod is copper clad. The
helix (spiral) and handle are bronze. For truclr-grounding
applications, see kit below.
. . .. - .
112 Copper Grounding Cable 50 ft.
4 " - . .. -""""".".
Cat. No. S6116, see page 3018
""."
3024 Chance grounding clamps, ferrules and cable meet ASTM F 855.
POWEA SVSTMIS, INC.
Operation
To quickly test any proposed configuration, just depress the
transformer foot switch to energize a fault on the system.
Durable and accurate If the light glows and the hell sounds on the "worl~er,"this
Built to last, the poles are aluminum pipe material. Cros- indicates the grounding system i n place fails to provide pro-
sarms are wood. tection. Or, if no such signals occur, the scheme of grounding
connectionsdoescreate aprotective zoneofequalizedpotential
Electrically correct, the aluminum poles effect the conduc- a t the worksite.
tivity which should be assumed for actual poles. Leads from
the poles and the neutral connect to the ground side on the To answer a multitude of "what-if' questions from the vari-
source (transformer). ous personnel concerned with grounding practices, the kit
transformer rapidly recycles while you rig the grounding
leads for the next test. A "ready" light comes on a s soon as
the transformer is reset.
Ordering Information
Chance grounding clamps, ferrules and cable meet ASTM F 855. 3025
POWER SYSTEMS, IHC.
Ordering- Information
Basic EQUI-MAT@ Personal Protective Ground Grid
Each Basic Unit includes a Long Ball Stud and illustrated
instructions.
Catalog No. I Size I Weight
Single '/4" Perimeter Braid
C6002850 58" x 58" 5 lb. I 11kg.
C6002851 58" x 120" 10 lb. I 2 2 kg.
C6002852 120" x 120" 20 lb. 1 4 4 kg.
Pre-Packaged Kits
Each Pre-Packaged Kit includes Ground Grid (size below
with Long Ball Stud and illustrated instructions) plus
Ground Set T6002841 and Storage Bag C4170147.
Kit EOIJI-MA+ Personal Protective Ground Grid Weight
Catalog No. Size per Kit
C6002989 58" x 58" 11lb. / 24.2 kg.
C6002990 58" x 120" 17 lb. 137.4 kg.
C6002991 120" x 1 2 0 29 lb. / 63.8 kg.
Accessory Items
Long Ball StudT6002364
included with each Basic E Q I J I - M A
Personal
~
Protective Ground Grid (Catalog page 3013)
Simple to join multiples for larger areas one. Whenever a larger area i s needed, simply place lug
Cascading (or joining together) two or more mats is easy connector tabs of two adjacent nlats on the supplied bolt
with the connecting tab and hardware furninshed with each or threaded shank of a hall stud and secure with supplied
mat. So connected i n series, the conductive grids become washer and nut.
II
L 1.
(Left)To join mats, conduc-
live grids simply connect at -- -,
. .
a,-:,
- -
I tabs with bolt, washer and
$ nut included with each mat.
Tabs have shrink tube for
., stress relief. (Right) Ball stud
-; can join mats and connect to
---&
\r '
=,* 7 I -A
f
.....- . ....--
. .. . . . - ground set clamps. - 3 . . .
tc' $
.*&
Long ball stud acceptsvariousgrounding ctampsas shown
below and at right: Ball/Socket. CType and Duckbill. .i .'
- 6. . "
. . . ......
--
.-
'*%.
+!
",*")
BULLETIN 3026.1
Slip-Resistant (Black) EQUI-MAT@
Personal Protective Ground Grid
Complies with OSHA 1910.269 for equipotential requirements
near vehicles, underground gear, overhead switches and in substations
U.S. Patent No. 6,477,027
Portable, lightweight, high performance
The EQUI-MAPPersonal Protective Ground Grid provides
a n easy way to help establish an equipotential zone for a
lineworker to stand on during various energized and de-
energized work practices. Properly applied, it accomplishes
compliance with Occupational Safety andHealthAclministra-
tion (OSHA) 1910,269:
"Equipotential Zone. Temporary protective grounds
SHALL be placed a t such locations and arranged in such
amanner as toprevent each employee from being exposed
to hazardous differences in electrical potential."
The EQUI-MAP Personal Protective Ground Grid easily can
be taken anywhere needed, is simple to use, maintain and Slip-Resistant material
store. It consistsofahigh-ampacitytinned-copper-braidcahle For rain, snow and ice conditions, the napped surface of the
sewn in a grid pattern onto a vinyYpolyester fabric. Cable S l i p - R e s i s t a n t ( ~ l a c k ) E ~ u ~ - ~ ~ P e r s o n a P rGround
otecve
ternlinals permit connecting the grid in series with Grid offers superior footing. For dry conditions, consider the
a n electrical ground and the suhject system component or Standard (Orange) EQUI-MAPPersonal Protective Ground
vehicle. Simply rinsing with water comprises all the care the Grid, available in the same sizes and kits.
mat requires. The mat may be folded and stored in a tool bag
to help keep it clean and protected. Complete instructions . . . continued on the next page. . .
are included with each unit.
Slip-Resistant EQUI-MA+Personal Protective Ground Grid
Each Unit includes Ground Grid, Long Ball Stud and
illustrated instructions.
Catalog No. 1 Size 1 Weight
Single 54'' Perimeter Braid
PSC6003345 58" x 58" 5 lb. I l l kg.
PSC6003346 58" x 1 2 0 10 lb. 122 kg.
PSCGOO3347 120" x 120" 20 lb. 1 44 kg.
r- s ',.
-c
--
'Y
, . - . -. . -
-
Appendix A Bibliography
[ I ] ANSlllEEE 80-1 986; IEEE Guide For Safety In AC Substation Grounding
[2] IEEE 516-2003; IEEE Guide for Maintenance Methods on Energized Power Lines
[3] IEEE 524 - 2003; IEEE Guide to the Installation of Overhead Transmission Line Conductors
[4] IEEE 1048 - 2003; IEEE Guide for Protective Grounding of Power Lines
[5] IEEE 1246 - 2004; IEEE Guide for Temporary Protective Grounding Systems Used in Substations
[6] ASTM F855 - 2004; Standard Specifications for Temporary Protective Grounds to Be Used on
De-energized Electric Power Lines and Equipment
[7] Electric Power Generation, Transmission, and Distribution; Electrical Protective Equipment; Final
Rule; Department of Labor, Occupational Safety and Health Administration 29 CFR Part 1910
[8] EPRl EL-5258, Fusing Research on Personal Grounding Cables, Final Report, July 1987
[9] Protective Jumpering, OSHA Speaks; by Clayton C. King; Tips of the Trade; Tips & News, June
1995; Bulletin 09-9502
[ l o ] Ground Clamps, critical safety components; by Clayton C. King; A. B. Chance Co. 1995; Bulletin
09-9501
[ I l l Grounding; Chance Tips of the Trade; by Clayton C. King; Chance Tips Vol. 51 No. 3, December
1990: bulletin 09-9001
[I21 Why Proper Grounding Is Vital For Worker Safety; by Clayton C. King; Electrical World; November
1990 (available from Hubbell Power Systems as Bulletin 9-9002GE)
[I31 Technical Considerations in Protective Grounding and Jumpering by Clayton C. King; A. B. Chance
Co.; Bulletin 09-8001
[I41 Grounding and Jumpering; by Franklin D. Myers; A. B. Chance Co. Bulletin No. 9-8002
[I 51 Personnel Protective Grounding in Substations; Made Easy by Chance Tips, December 1990
. . -.
11 61 Thermoolastic Insulated Wire and Cable for the Transmission and Distribution of Electrical Enerav.
NEMA standards Publication No. WC 5 and ICEA Publication S-61-402
~1
[I71 Placement of Protective Grounds for Safety of Linemen, E.J. Harrington and T.M.C. Martin, AIEE
Safety committee Paper 54-206, AIEE Transactions Vol. 73, Aug. 1954 p. 950-955
[I81 Electric Shock Hazard, Charles Dalziel, IEEE Spectrum Feb. 1972 p. 41-50
[I91 The Effects of Electric Shock on Man, Safety and Fire Protection Bulletin, United States Atomic
- ~
Energy Commission, Office of Health &safety, Washington D.C. (Reprinted from IRE Transaction
on Medical Electronics May 1956)
1201 A Modern Approach to Grounding Systems, ITT Blackburn - Data Folder 7302
Appendix B - Asymmetrical Current
An asymmetrical current is one that is not contribute to the X,.As the line distance from
initially symmetrical about the zero axis. the sub-station increases the X,decreases, in
From a de-energized circuit the initial current comparison to resistance and the problem of
peaks may be significantly greater than those asymmetry decreases.
of the anticipated RMS steady state peak
values. The offset of this current reduces to The mathematical equation for asymmetry is:
a symmetrical current in a few cycles. The I= IVmIZI (sine(ot+O-u)- e(-R'"-) sine(u-0))
problem caused by theincreased offset ofthese = IS1 (sine(wt+O-u)- e@""X) sine(u-8))
peaks may result in mechanical breaking of where:
the grounding assembly clamps because the peak voltage available, v
mechanical force increases as the square ofthe circuit impedance, Q
current. That is, if the current peak doubles peak current available, A
the mechanical force is momentarily four circuit resistance, Q
times as great. An additional problem is the time from current initiation,
increased heating due to the cumulative offset 2nf (radiansls)
of the current flowing. This further reduces frequency, Hz
the melting time of the connecting cable. In voltage angle at cutxent initiation,
earlier editions of the ASTM F855 standard radians
the maximum asymmetry specified was 20%, circuit phase angle, radians
determined to be a maximumX,/R of 1.8, and circuit inductance, Xlw, Q
failure was based upon the melting of the in- inductive reactance, X,
terconnecting cable. Now asymmetry values
of 30% to 40% are being addressed with ac- The equation is divided into two components.
companying highX,/Rratios. If aline current The sine function calculates the symmetrical
recorder were connected to a line with high RMS current of the circuit. The exponential
asymmetry the recorded waveshape would function calculates the d.c. offset curve. The
appear as shown in Fig. 11-15. It is during combination of sine and exponential values
this reduction of asymmetry that mecl~anical forms the asymmetrical curve. Notice also
breakage may occur. that as the value of XL/R and closing angle
(a) the resulting wave changes. To achieve
Current asymmetryhas been known for many the maximum first cycle peak the combina-
years. In the past many substation current tion of time (t) and closing angle ( a ) must
levels were low enough that mechanical break- equal zero (0). Notice that the asymmetrical
age was not seen. As demands for electricity wave is symmetrical about the decaying d.c.
grew substations were enlarged and asym- component.
metry problems began to appear.
continued
Asymmetry is caused by the relationship
of circuit inductive reactance (X,) to circuit
resistance (R). The problem caused by asym-
metryismosttroublinginsubstations because
that is where the currents are the largest and
where the greatestx, to R ratio is found. The
X, is a major property of coils. Substations
Figure B-1 is an example of a high asymmetry Utilities must evaluate their sites and provide I
waveform. It takes approximately 15 cycles protective grounding assemblies that have 1
to return to near symmetrical current. If
mechanical breakage is going to occur it will
been tested and rated for use under these
conditions, if deemed necessary. The current i
probably be within the first 1to 5 cycles. ASTM F855 standard addresses this and pro-
vides testing procedures and required values.
Some substations remain sufficiently low in
current that mechanical breakage may not Ii
be a problem. This is not something easily
(
determined in the field. It must be considered r
prior to entering a substation site for main- $.
tenance. *t,
1600001
Time
Asymmetrical Current (30 kA, WR=30)
Figure B-1
Time
Asymmetrical Current (30 kA, X/R=1.8)
Figure B-2