Está en la página 1de 32

User Guide

Tracer™ TD7 with UC 800


for RTHD chillers

RLC-SVU006A-E4
Original instructions
Copyright
All rights reserved
This document and the information in it are the property of Trane and may not be
used or reproduced in whole or in part, without the written permission of Trane.
Trane reserves the right to revise this publication at any time and to make changes
to its content without obligation to notify any person of such revision or change.

Trademarks
TD7, RTHD Trane, the Trane logo, and Tracer are trademarks of Trane. All trademarks
referenced in this document are the trademarks of their respective owners.

2 © 2014 Trane RLC-SVU006A-E4


Table of Contents
General Recommendations ................................................................................................... 4
Units with Nitrogen Charge Option ...................................................................................... 5
Installer-Supplied Components............................................................................................. 5
Power Supply Wiring .............................................................................................................. 5
Control Power Supply ............................................................................................................ 5
Motor Cable .................................................................................................................................................. 6
Motor Rotation Check .................................................................................................................................. 6
AC Mains Connection .................................................................................................................................. 6

Interconnecting Wiring ........................................................................................................... 7


Chilled Water Pump Control ........................................................................................................................ 7

Programmable Relays ............................................................................................................ 7


Relay Assignments Using Tracer™ TU .................................................................................. 9
Low Voltage Wiring ................................................................................................................. 9
Emergency Stop ........................................................................................................................................... 9
External Auto/Stop ....................................................................................................................................... 9

Ice Building Option ............................................................................................................... 10


External Chilled Water Setpoint (ECWS) Option................................................................ 10
External Demand Limit Setpoint (EDLS) Option ............................................................... 10
EDLS and ECWS Analog Input Signal Wiring Details: ........................................................11
Chilled Water Reset (CWR) ....................................................................................................11
Communications Interface .................................................................................................. 12
LonTalk™ Interface (LCI-C) ........................................................................................................................ 12
BACnet Protocol ........................................................................................................................................ 12
BACnet Testing Laboratory (BTL) Certification......................................................................................... 12
Modbus RTU Protocol................................................................................................................................ 12

Overview ............................................................................................................................... 13
UC800 Specifications ........................................................................................................... 13
Wiring and Port Descriptions .................................................................................................................... 13
Communication Interfaces ........................................................................................................................ 13
Rotary Switches.......................................................................................................................................... 13
LED Description and Operation ................................................................................................................ 13

Tracer TD7 Operator Interface .............................................................................................. 14


Tracer™ TU ............................................................................................................................ 14
Starter Diagnostics ............................................................................................................... 17
Main Processor Diagnostics ................................................................................................ 20
Communication Diagnostics ............................................................................................... 26
Operator Display Diagnostics and Messages .................................................................... 29

RLC-SVU006A-E4 3
Installation Electrical
General Recommendations WARNING
Hazardous Voltage - Pressurized Burning Fluid!
As you review this manual, keep in mind that:
Before removing compressor terminal box cover for
• All field-installed wiring must conform to European servicing, or servicing power side of control panel,
guidelines and any applicable local codes. Be sure to CLOSE COMPRESSOR DISCHARGE SERVICE VALVE
satisfy proper equipment grounding requirements per and disconnect all electric power including remote
European guidelines. disconnects. Discharge all motor start/run capacitors.
• Compressor motor and unit electrical data (including Follow lockout/tagout procedures to ensure the
motor kW, voltage utilization range, rated load amps) power cannot be inadvertently energized. Verify with
is listed on the chiller nameplate. an appropriate voltmeter that all capacitors have
• All field-installed wiring must be checked for proper discharged.
terminations, and for possible shorts or grounds. The compressor contains hot, pressurized refrigerant.
Note:: Always refer to wiring diagrams shipped with Motor terminals act as a seal against this refrigerant.
chiller or unit submittal for specific electrical Care should be taken when servicing NOT to damage or
schematic and connection information. loosen motor terminals.
Do not operate compressor without terminal box cover
WARNING in place.
Proper Field Wiring and Grounding Required! Failure to follow all electrical safety precautions could
result in death or serious injury.
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field For additional information regarding the safe discharge
wiring poses FIRE and ELECTROCUTION hazards. To of capacitors, see “Adaptive Frequency™ Drive (AFD3)
avoid these hazards, you MUST follow requirements for Capacitor Discharge,” p. 28 and PROD-SVB06A-EN.
field wiring installation and grounding as described in
local electrical codes. Failure to follow code could result NOTICE:
in death or serious injury. Use Copper Conductors Only!
Unit terminals are not designed to accept other types
WARNING of conductors. Failure to use copper conductors could
Hazardous Voltage w/Capacitors! result in equipment damage.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run and AFD Important:: To prevent control malfunctions, do not run
(Adaptive Frequency™ Drive) capacitors before servicing. low voltage wiring (<30 V) in conduit with
Follow proper lockout/tagout procedures to ensure the conductors carrying more than 30 volts.
power cannot be inadvertently energized.
• For variable frequency drives or other energy storing
components provided by Trane or others, refer to the
appropriate manufacturer’s literature for allowable
waiting periods for discharge of capacitors. Verify
with an appropriate voltmeter that all capacitors have
discharged.
• DC bus capacitors retain hazardous voltages after
input power has been disconnected. Follow proper
lockout/tagout procedures to ensure the power cannot
be inadvertently energized. After disconnecting input
power, wait five (5) minutes for the DC capacitors to
discharge, then check the voltage with a voltmeter.
Make sure DC bus capacitors are discharged (0 VDC)
before touching any internal components.
Failure to follow these instructions could result in death
or serious injury.
For additional information regarding the safe discharge
of capacitors, see “Adaptive Frequency™ Drive (AFD3)
Capacitor Discharge,” p. 28 and PROD-SVB06A-EN.

4 RLC-SVU006A-E4
Installation Electrical
In case of drive servicing only Power Supply Wiring
WARNING
DISCHARGE TIME! WARNING
Frequency converters contain DC-link capacitors that Proper Field Wiring and Grounding Required!
can remain charged even when the frequency converter All field wiring MUST be performed by qualified
is not powered. To avoid electrical hazards, disconnect personnel. Improperly installed and grounded field
AC mains, any permanent magnet type motors, and wiring poses FIRE and ELECTROCUTION hazards. To
any remote DClink power supplies, including battery avoid these hazards, you MUST follow requirements for
backups, UPS and DC-link connections to other field wiring installation and grounding as described in
frequency converters. Wait for the capacitors to fully your local electrical codes. Failure to follow code could
discharge before performing any service or repair work. result in death or serious injury.
The amount of wait time is listed in the Discharge Time
All power supply wiring must be sized and selected
table. Failure to wait the specified time after power has
accordingly by the project engineer in accordance
been removed before doing service or repair could result
with EN 60204.
in death or serious injury.
All wiring must comply with local codes. The installing
(or electrical) contractor must provide and install the
Table 1. Capacitor Discharge Times system interconnecting wiring, as well as the power
Minimum waiting supply wiring. It must be properly sized and equipped
Voltage Power
time [min] with the appropriate fused disconnect switches.
380-500 V 90-250 kW 20 The type and installation location(s) of the fused
disconnects must comply with all applicable codes.
315-800 kW 40

NOTICE:
Use Copper Conductors Only!
Units with Nitrogen Charge Option
Unit terminals are not designed to accept other types
For units with nitrogen charge option (model number of conductors. Failure to use copper conductors could
digit 15 = 2), the unit must NOT have shore power, or result in equipment damage.
unit power applied until the unit has been charged.
Applying power will drive EXV valves closed, and will
inhibit sufficient vac for unit charging. Cut holes into the sides of the control panel for the
appropriately-sized power wiring conduits. The wiring
is passed through these conduits and connected to the
Installer-Supplied Components terminal blocks, optional unit-mounted disconnects, or
Customer wiring interface connections are shown in HACR type breakers.
the electrical schematics and connection diagrams that The high voltage field-provided connections are made
are shipped with the unit. The installer must provide the through patch plate on the right side of the panel. The
following components if not ordered with the unit: low voltage connections are made through knockouts
• Power supply wiring (in conduit) for all field-wired provided on the left side of the panel. Additional grounds
connections. may be required for each 115 volt power supply to the
unit. Green lugs are provided for 115V customer wiring.
• All control (interconnecting) wiring (in conduit) for
field supplied devices.
• Fused-disconnect switches or circuit breakers. Control Power Supply
The unit is equipped with a control power transformer.
It is not necessary to provide additional control power
voltage to the unit. No other loads should be connected
to the control power transformer.
All units are factory-connected for appropriate labeled
voltages.

RLC-SVU006A-E4 5
Installation Electrical
Motor Cable Figure 1. Connecting to AC Mains
The motor must be connected to terminals U/T1/96, V/
T2/97, W/T3/98. Earth (ground) to terminal 99. All types of
three-phase asynchronous standard motors can be used
with a frequency converter unit. The factory setting is for
clockwise rotation with the frequency converter output
connected as follows:

Table 2.

Terminal no. Function

Mains U/T1, V/T2, W/T3


96, 97, 98, 99
Earth (ground)

Motor Rotation Check


The direction of rotation can be changed by switching
two phases in the motor cable or by changing the setting
of 4-10 Motor Speed Direction.
Table 3.
• Terminal U/T1/96
connected to U-phase
• Terminal V/T2/97
connected to V-phase
• Terminal W/T3/98
connected to W-phase

Table 4.

1 Mains connection
A motor rotation check can be performed using1-28
Motor Rotation Check and following the steps shown in 2 Motor connection
the display.
• Earth (ground) the cable in accordance with the
AC Mains Connection instructions provided
• Size wiring is based upon the input current of the • All frequency converters may be used with an isolated
frequency converter input source as well as with earth (ground) reference
• Comply with local and national electrical codes for power lines. When supplied from an isolated mains
cable sizes source (IT mains or floating delta) or TT/TN-S mains
with a grounded leg (grounded delta), set 14-50 RFI
• Connect 3-phase AC input power wiring to terminals
Filter to OFF.
L1, L2, and L3 (see Figure 1)
When off, the internal RFI filter capacitors between
the chassis and the intermediate circuit are isolated to
avoid damage to the intermediate circuit and to reduce
earth (ground) capacity currents in accordance with
IEC 61800-3.

6 RLC-SVU006A-E4
Installation Electrical
Interconnecting Wiring If evaporator water flow is lost once it had been
established, the EWP relay remains energized and a
Chilled Water Pump Control non-latching diagnostic is generated. If flow returns, the
diagnostic is cleared and the chiller returns to normal
operation.
NOTICE:
In general, when there is either a non-latching or latching
Equipment Damage!
diagnostic, the EWP relay is turned off as though there
If the microprocessor calls for a pump to start and was a zero time delay. Exceptions whereby the relay
water does not flow, the evaporator may be damaged continues to be energized occur with:
catastrophically. It is the responsibility of the installing
• Low Chilled Water Temp. diagnostic (non-latching)
contractor and/or the customer to ensure that a pump
(unless also accompanied by an Evap Leaving Water
will always be running when called upon by the chiller
Temperature Sensor Diagnostic)
controls.
or
• Loss of Evaporator Water Flow diagnostic (non-
An evaporator water pump output relay closes when
latching) and the unit is in the AUTO mode, after
the chiller is given a signal to go into the Auto mode
initially having proven evaporator water flow.
of operation from any source. The contact is opened to
turn off the pump in the event of most machine level
diagnostics to prevent the build up of pump heat. Programmable Relays
The relay output is required to operate the Evaporator A programmable relay concept provides for enunciation
Water Pump (EWP) contactor. Contacts should be of certain events or states of the chiller, selected from a
compatible with 115/240 VAC control circuit. Normally, list of likely needs, while only using four physical output
the EWP relay follows the AUTO mode of the chiller. relays, as shown in the field wiring diagram. The four
Whenever the chiller has no diagnostics and is in the relays are provided (generally with a Quad Relay Output
AUTO mode, regardless of where the auto command LLID) as part of the Programmable Relay Option. The
is coming from, the normally open relay is energized. relay’s contacts are isolated Form C (SPDT), suitable
When the chiller exits the AUTO mode, the relay is timed for use with 120 VAC circuits drawing up to 2.8 amps
to open in an adjustable (using TU) 0 to 30 minutes. inductive, 7.2 amps resistive, or 1/3 HP and for 240 VAC
The non-AUTO modes in which the pump is stopped, circuits drawing up to 0.5 amp resistive.
include Reset, Stop, External Stop, Remote Display Stop,
The list of events/states that can be assigned to the
Stopped by Tracer, Start Inhibited by Low Ambient Temp,
programmable relays can be found in Table 6. The relay
and Ice Building complete.
will be energized when the event/state occurs.

Table 5. Pump Relay Operation

Chiller Mode Relay Operation

Auto Instant close

Ice Building Instant close

Tracer Override Close

Stop Timed Open

Ice Complete Instant Open

Diagnostics Instant Open

When going from Stop to Auto, the EWP relay is


energized immediately. If evaporator water flow is not
established in 20 minutes (for normal transition) or 4
minutes, 15 seconds (for pump commanded ON due to
an override safety), the UC800 de-energizes the EWP
relay and generates a non-latching diagnostic. If flow
returns (e.g. someone else is controlling the pump),
the diagnostic is cleared, the EWP is re-energized, and
normal control resumed.

RLC-SVU006A-E4 7
Installation Electrical
Table 6. Chiller events/status descriptions

Event/State Description

Alarm - Latching This output is true whenever there is any active diagnostic that requires a manual
reset to clear, that effects the Chiller, the Circuit, or any of the Compressors on a
circuit. This classification does not include informational diagnostics.

Alarm - Auto Reset This output is true whenever there is any active diagnostic that could automatically
clear, that effects the Chiller, the Circuit, or any of the Compressors on a circuit.
This classification does not include informational diagnostics. If all of the auto
resetting diagnostics were to clear, this output would return to a false condition.

Alarm This output is true whenever there is any diagnostic effecting any component,
whether latching or automatically clearing. This classification does not include
informational diagnostics.

Warning This output is true whenever there is any informational diagnostic effecting any
component, whether latching or automatically clearing.

Chiller Limit Mode This output is true whenever the chiller has been running in one of the Unloading
types of limit modes (Condenser, Evaporator, Current Limit or Phase Imbalance
Limit) continuously for the last 20 minutes. A given limit or overlapping of different
limits must be in effect continuously for 20 minutes prior to the output becoming
true. It will become false, if no Unload limits are present for 1 minute. The filter
prevents short duration or transient repetitive limits from indicating. The chiller
is considered to be in a limit mode for the purposes of front panel display and
annunciation, only if it is fully inhibiting loading by virtue of being in either the
“hold” or “forced unload” regions of the limit control, excluding the “limited
loading region”. (In previous designs, the “limit load” region of the limit control
was included in the criteria for the limit mode call out on the front panel and
annunciation outputs)

Compressor Running The output is true whenever any compressors are started or running on the
chiller and false when no compressors are either starting or running on the chiller.
This status may or may not reflect the true status of the compressor in Service
Pumpdown if such a mode exists for a particular chiller.

Chiller Head Pressure Relief This relay output is energized anytime the chiller is running in one of the following
Request Relay modes; Ice Making Mode or Condenser Pressure Limit Control Mode continuously
for the duration specified by the Chiller Head Relief Relay Filter Time. The Chiller
Head Relief Relay Filter Time is a service setpoint. The relay output is de-energized
anytime the chiller exits all above modes continuously for the duration specified by
the same Chiller Head Relief Relay Filter Time.

8 RLC-SVU006A-E4
Installation Electrical
Relay Assignments Using Low Voltage Wiring
Tracer™ TU The remote devices described below require low voltage
wiring. All wiring to and from these remote input devices
Tracer™ TU Service Tool is used to install the
to the Control Panel must be made with shielded, twisted
Programmable Relay Option package and assign any
pair conductors. Be sure to ground the shielding only at
of the above list of events or status to each of the four
the panel.
relays provided with the option. (See “Tracer™ TU,”
for more information on the Tracer TU service tool.) Important:: To prevent control malfunctions, do not run
The relays to be programmed are referred to by the low voltage wiring (<30 V) in conduit with
relay’s terminal numbers on the LLID board 1A10. conductors carrying more than 30 volts.
The default assignments for the four available relays of Emergency Stop
the Programmable Relay option are: UC800 provides auxiliary control for a customer
Table 7. Default assignments specified/installed latching trip out. When this customer-
furnished remote contact 5K22 is provided, the chiller
Relay will run normally when the contact is closed. When the
contact opens, the unit will trip on a manually resettable
Relay 0Terminals J2-1,2,3: Head press. diagnostic. This condition requires manual reset at the
chiller switch on the front of the control panel.
Relay 1Terminals J2-4,5,6: Limit mode
Connect low voltage leads to terminal strip locations
Relay 2Terminals J2 - 7,8,9: Alarm 1A12. Refer to the field diagrams that are shipped with
the unit.
Relay 3Terminals J2 -10,11,12: CMP Running Relay
Silver or gold-plated contacts are recommended. These
customer-furnished contacts must be compatible with 24
If any of the Alarm/Status relays are used, provide VDC, 12 mA resistive load.
electrical power, 115 VAC with fused-disconnect to the
panel and wire through the appropriate relays (terminals External Auto/Stop
on 1A10). Provide wiring (switched hot, neutral, and If the unit requires the external Auto/Stop function, the
ground connections) to the remote annunciation devices. installer must provide leads from the remote contacts
Do not use power from the chiller’s control panel 5K21 to the proper terminals of the LLID 1A12 on the
transformer to power these remote devices. Refer to the control panel.
field diagrams which are shipped with the unit. The chiller will run normally when the contacts are
closed. When either contact opens, the compressor(s), if
operating, will go to the RUN:UNLOAD operating mode
and cycle off. Unit operation will be inhibited. Closure
of the contacts will permit the unit to return to normal
operation.
Field-supplied contacts for all low voltage connections
must be compatible with dry circuit 24 VDC for a 12
mA resistive load. Refer to the field diagrams that are
shipped with the unit.

RLC-SVU006A-E4 9
Installation Electrical
These customer-supplied contact closures must Connect leads from 5K12 to the proper terminals of
be compatible with 24 VDC, 12 mA resistive load. 1A15. Refer to the field diagrams which are shipped with
Silver or gold plated contacts are recommended. the unit.
Silver or gold-plated contacts are recommended. These
Ice Building Option customer furnished contacts must be compatible with
24 VDC, 12 mA resistive load.
UC800 provides auxiliary control for a customer
specified/installed correct with contact closure 5K20 for
ice building if so configured and enabled. This output External Chilled Water Setpoint
is known as the Ice Building Status Relay. The normally (ECWS) Option
open contact will be closed when ice building is in
progress and open when ice building has been normally The UC800 provides inputs that accept either 4-20 mA or
terminated either through Ice Termination setpoint being 2-10 VDC signals to set the external chilled water setpoint
reached or removal of the Ice Building command. This (ECWS). This is not a reset function. The input defines the
output is for use with the ice storage system equipment setpoint. This input is primarily used with generic BAS
or controls (provided by others) to signal the system (building automation systems). The chilled water setpoint
changes required as the chiller mode changes from set via the Tracer TD7 or through digital communication
“ice building” to “ice complete”. When contact 5K12 is with Tracer (Comm4). The arbitration of the various
provided, the chiller will run normally when the contact chilled water setpoint sources is described in the flow
is open. charts at the end of the section.
UC800 will accept either an isolated contact closure The chilled water setpoint may be changed from a
(External Ice Building command) or a Remote remote location by sending either a 2-10 VDC or 4-20 mA
Communicated input (Tracer) to initiate and command signal to the 1A14, terminals 5 and 6 LLID. 2-10 VDC and
the Ice Building mode. 4-20 mA each correspond to a 10 to 65°F (-12 to 18°C)
external chilled water setpoint.
UC800 also provides a “Front Panel Ice Termination
Setpoint”, settable through Tracer™ TU, and adjustable The following equations apply:
from 20 to 31°F (-6.7 to -0.5°C) in at least 1°F (1°C) Voltage Signal
increments. As generated from external source VDC=0.1455*(ECWS) + 0.5454
Note:: When in the Ice Building mode, and the As processed by UC800 ECWS=6.875*(VDC) - 3.75
evaporator entering water temperature drops Current Signal
below the ice termination setpoint, the chiller As generated from external source mA=0.2909(ECWS) + 1.0909
terminates the Ice Building mode and changes As processed by UC800 ECWS=3.4375(mA) - 3.75
to the Ice Building Complete Mode.

If the ECWS input develops an open or short, the LLID


NOTICE: will report either a very high or very low value back to
Equipment Damage! the main processor. This will generate an informational
Freeze inhibitor must be adequate for the leaving water diagnostic and the unit will default to using the Front
temperature. Failure to do so will result in damage to Panel (TD7) Chilled Water Setpoint.
system components. Tracer TU Service Tool is used to set the input signal type
from the factory default of 2-10 VDC to that of 4-20 mA.
Tracer TU is also used to install or remove the External
Tracer™ TU must also be used to enable or disable Ice
Chilled Water Setpoint option as well as a means to
Machine Control. This setting does not prevent the Tracer
enable and disable ECWS.
from commanding Ice Building mode.
Upon contact closure, the UC800 will initiate an ice
building mode, in which the unit runs fully loaded at all
External Demand Limit Setpoint
times. Ice building shall be terminated either by opening (EDLS) Option
the contact or based on the entering evaporator water
temperature. UC800 will not permit the ice building Similar to the above, the UC800 also provides for an
mode to be reentered until the unit has been switched optional External Demand Limit Setpoint that will accept
out of ice building mode (open 5K12 contacts) and either a 2-10 VDC (default) or a 4-20 mA signal. The
then switched back into ice building mode (close 5K12 Demand Limit Setting can also be set via the Tracer TD7
contacts.) or through digital communication with Tracer (Comm4).
The arbitration of the various sources of demand limit is
In ice building, all limits (freeze avoidance, evaporator, described in the flow charts at the end of this section. The
condenser, current) will be ignored. All safeties will be External Demand Limit Setpoint may be changed from a
enforced. remote location by hooking up the analog input signal to
If, while in ice building mode, the unit gets down to the the 1A14 LLID terminals 2 and 3. Refer to the following
freeze stat setting (water or refrigerant), the unit will paragraph on Analog Input Signal Wiring Details.
shut down on a manually resettable diagnostic, just as in
normal operation.

10 RLC-SVU006A-E4
Installation Electrical
The following equations apply for EDLS: Chilled Water Reset (CWR)
Voltage Signal Current Signal
UC800 resets the chilled water temperature set point
As generated from VDC+0.133*(%)-6.0 mA=0.266*(%)-12.0 based on either return water temperature, or outdoor air
external source
temperature. Return Reset is standard, Outdoor Reset is
As processed by %=7.5*(VDC)+45.0 %=3.75*(mA)+45.0 optional.
UCM
The following shall be selectable:
• One of three Reset Types: None, Return Water
If the EDLS input develops an open or short, the LLID Temperature Reset, Outdoor Air Temperature Reset, or
will report either a very high or very low value back to Constant Return Water Temperature Reset.
the man processor. This will generate an informational
diagnostic and the unit will default to using the Front • Reset Ratio Set Points.
Panel (Tracer TD7) Current Limit Setpoint. For outdoor air temperature reset there shall be both
positive and negative reset ratio’s.
The Tracer™ TU Service Tool must be used to set the
input signal type from the factory default of 2-10 VDC to • Start Reset Set Points.
that of 4-20 mA current. Tracer TU must be also be used • Maximum Reset Set Points.
to install or remove the External Demand Limit Setpoint The equations for each type of reset are as follows:
Option for field installation, or can be used to enable or Return
disable the feature (if installed).
CWS’ = CWS + RATIO (START RESET - (TWE - TWL))

EDLS and ECWS Analog Input and CWS’ > or = CWS


and CWS’ - CWS < or = Maximum Reset
Signal Wiring Details: Outdoor
Both the ECWS and EDLS can be connected and setup CWS’ = CWS + RATIO * (START RESET - TOD)
as either a 2-10 VDC (factory default), 4-20 mA, or
and CWS’ > or = CWS
resistance input (also a form of 4-2OmA) as indicated
below. Depending on the type to be used, the Tracer TU and CWS’ - CWS < or = Maximum Reset
Service Tool must be used to configure the LLID and the where
MP for the proper input type that is being used. This is CWS’ is the new chilled water set point or the “reset
accomplished by a setting change on the Custom Tab of CWS”
the Configuration View within Tracer TU.
CWS is the active chilled water set point before any reset
Important:: For proper unit operation, BOTH the EDLS has occurred, e.g. normally Front Panel, Tracer, or ECWS
and ECWS settings MUST be the same
(2-10 VDC or 4-20mA), even if only one RESET RATIO is a user adjustable gain
input is to be used. START RESET is a user adjustable reference
The J2-3 and J2-6 terminal is chassis grounded and TOD is the outdoor temperature
terminal J2- 1 and J2-4 can be used to source 12 VDC. TWE is entering evap. water temperature
The ECLS uses terminals J2-2 and J2-3. ECWS uses TWL is leaving evap. water temperature
terminals J2-5 and J2-6. Both inputs are only compatible
with high-side current sources. MAXIMUM RESET is a user adjustable limit providing
the maximum amount of reset. For all types of reset,
CWS’ - CWS < or = Maximum Reset.
Figure 2. Wiring examples for EDLS and ECWS
Range Increment

Reset Reset Start Max Factory


J2-1 & 4 Dual IP Units SI Units
J2-2 & 5 Analog Type Ratio Reset Reset Default
2-10 VDC, 4-20mA J2-3 & 6 I/O LLID
10 to
Return 4 to 30 F 0 to 20 F 1% 1% 50%
120%

(2.2 to (0.0 to
Resister J2-1 & 4 Dual
16.7 C) 11.1 C)
J2-2 & 5 Analog
I J2-3 & 6 I/O LLID
80 to 50 to
Outdoor 0 to 20 F 1% 1% 10%
I = 20/(R + 200) -80% 130 F

(10 to (0.0 to
54.4 C) 11.1 C)
J2-1 & 4 Dual
J2-2 & 5 Analog
J2-3 & 6 I/O LLID

RLC-SVU006A-E4 11
Installation Electrical
In addition to Return and Outdoor Reset, the MP BACnet Protocol
provides a menu item for the operator to select a The Building Automation and Control Network (BACnet
Constant Return Reset. Constant Return Reset will reset and ANSI/ASHRAE Standard 135-2004) protocol is a
the leaving water temperature set point so as to provide standard that allows building automation systems or
a constant entering water temperature. The Constant components from different manufacturers to share
Return Reset equation is the same as the Return Reset information and control functions. BACnet provides
equation except on selection of Constant Return Reset, building owners the capability to connect various
the MP will automatically set Ratio, Start Reset, and types of building control systems or subsystems
Maximum Reset to the following. together for a variety of reasons. In addition, multiple
RATIO = 100% vendors can use this protocol to share information for
START RESET = Design Delta Temp. monitoring and supervisory control between systems
and devices in a multi-vendor interconnected system.
MAXIMUM RESET = Design Delta Temp.
The BACnet protocol identifies standard objects (data
The equation for Constant Return is then as follows: points) called BACnet objects. Each object has a defined
CWS’ = CWS + 100% (Design Delta Temp. - (TWE - TWL)) list of properties that provide information about that
and CWS’ > or = CWS object. BACnet also defines a number of standard
and CWS’ - CWS < or = Maximum Reset application services that are used to access data and
manipulate these objects and provides a client/server
When any type of CWR is enabled, the MP will step communication between devices.
the Active CWS toward the desired CWS’ (based on
the above equations and setup parameters) at a rate BACnet Testing Laboratory (BTL)
of 1 degree F every 5 minutes until the Active CWS Certification
equals the desired CWS’. This applies when the chiller All Tracer™ UC800 controllers are designed to
is running. support BACnet communication protocol. In
When the chiller is not running, CWS is reset addition,someparticular revisions of the UC800 firmware
immediately (within one minute) for Return Reset and at have been tested and have achieved BTL certification by
a rate of 1 degree F every 5 minutes for Outdoor Reset. an official BACnet testing laboratory. For more details,
The chiller will start at the Differential to Start value refer to the BTL website at www.bacnetassociation.org.
above a fully reset CWS or CWS’ for both Return and
Outdoor Reset.
Modbus RTU Protocol
Modicon Communication Bus (Modbus) is an application
layer-messaging protocol that, like BACnet, provides
Communications Interface client/server communication between devices over
a variety of networks. During communications on a
LonTalk™ Interface (LCI-C) Modbus RTU network, the protocol determines how
UC800 provides an optional LonTalk™ Communication each controller will know its device address, recognize
Interface (LCI-C) between the chiller and a Building a message addressed to its device, determine what
Automation System (BAS). An LCI-C LLID shall be used action to take, and extract any data or other information
to provide “gateway” functionality between a LonTalk contained in the message. Controllers communicate
compatible device and the Chiller. The inputs/outputs using a master/slave technique, whereby, only one
include both mandatory and optional network variables device (master) can initiate transactions (queries). Other
as established by the LonMark Functional Chiller Profile devices (slaves) respond by supplying the requested
8040. data to the master or by taking the action requested in
Note:: For more information see ACC-SVN100*-EN. the query.
The master can address individual slaves or it can
initiate a broadcast message to all slaves. In turn, the
slaves respond to queries that are addressed to them
individually or broadcasted. The Modbus RTU protocol
establishes the format for the master’s query by placing
into it the device address, a function code defining the
requested action, any data to be sent, and an error-
checking field.

12 RLC-SVU006A-E4
Controls
Overview Figure 3. Wiring locations and connection ports

RTHD units utilize the following control/interface


components:
• Tracer™ UC800 Controller
• Tracer TD7 Operator Interface

UC800 Specifications
This section covers information pertaining to the UC800
controller hardware.
Wiring and Port Descriptions
Figure 3 illustrates the UC800 controller ports, LEDs,
rotary switches, and wiring terminals. The numbered list
following Figure 3 corresponds to the numbered callouts
in the illustration.

Figure 3. Wiring locations and connection ports Bottom View

1. Rotary Switches for setting BACnet® MAC address or MODBUS ID.


2. LINK for BACnet MS/TP, or MODBUS Slave (two terminals, ±). Field
wired if used.
3. LINK for BACnet MS/TP, or MODBUS Slave (two terminals, ±). Field
wired if used.
4. Machine bus for existing machine LLIDs (IPC3 Tracer bus 19.200 baud).
IPC3 Bus: used for Comm4 using TCI or LonTalk® using LCI-C.
5. Power (210 mA at 24 Vdc) and ground terminations (same bus as
item 4). Factory wired.
6. Not used.
7. Marquee LED power and UC800 Status indicator.
8. Status LEDs for the BAS link, MBus link, and IMC link.
9. USB device type B connection for the service tool (Tracer TU).
10. The Ethernet connection can only be used with the Tracer AdaptiView
display.
11. USB Host (not used).

Communication Interfaces
There are four connections on the UC800 that support
the communication interfaces listed. Refer to Figure 3,
p. 13 for the locations of each of these ports.
• BACnet MS/TP
• MODBUS Slave
• LonTalk using LCI-C (from the IPC3 bus)
Front View • Comm 4 using TCI (from the IPC3 bus)
Rotary Switches
There are three rotary switches on the front of the UC800
controller. Use these switches to define a three-digit
address when the UC800 is installed in a BACnet or
MODBUS system (e.g., 107, 127, etc.).
Note:: Valid addresses are 001 to 127 for BACnet and 001
to 247 for MODBUS.
LED Description and Operation
There are 10 LEDs on the front of the UC800. Figure 4
shows the locations of each LED and Table 8, p. 14
describes their behavior in specific instances.

RLC-SVU006A-E4 13
Controls
Figure 4. LED locations Tracer TD7 Operator Interface
Information is tailored to operators, service technicians,
and owners.
When operating a chiller, there is specific information
you need on a day-to-day basis—setpoints, limits,
diagnostic information, and reports.
Day-to-day operational information is presented at the
display. Logically organized groups of information—
chiller modes of operation, active diagnostics, settings
and reports put information conveniently at your
fingertips.

Tracer™ TU
The RTHD operator interface allows for daily operational
tasks and setpoint changes. However, to adequately
service chillers Tracer™ TU service tool is required.
(Non-Trane personnel, contact your local Trane office
for software purchase information.) Tracer TU adds a
level of sophistication that improves service technician
effectiveness and minimizes chiller downtime. This
portable PC-based service-tool software supports service
and maintenance tasks, and is required for software
upgrades, configuration changes and major service
Table 8. LED behavior tasks.
Tracer TU serves as a common interface to all Trane®
LED UC800 Status
chillers, and will customize itself based on the properties
of the chiller with which it is communicating. Thus, the
Powered. If the Marquee LED is green solid,
the UC800 is powered and no problems exist. service technician learns only one service interface.
The panel bus is easy to troubleshoot using LED sensor
Low power or malfunction. If the Marquee
Marquee verification. Only the defective device is replaced. Tracer
LED is red solid, the UC800 is powered, but
LED TU can communicate with individual devices or groups
there are problems present.
of devices.
Alarm. The Marquee LED blinks Red when an All chiller status, machine configuration settings,
alarm exists. customizable limits, and up to 100 active or historic
The TX LED blinks green at the data transfer diagnostics are displayed through the service-tool
rate when the UC800 transfers data to other software interface.
LINK, devices on the link. LEDs and their respective Tracer TU indicators visually
MBUS, IMC The Rx LED blinks yellow at the data transfer confirm the availability of each connected sensor, relay,
rate when the UC800 receives data from and actuator.
other devices on the link.
Tracer TU is designed to run on a customer’s laptop,
The LINK LED is solid green if the Ethernet connected to the Tracer control panel with a USB cable.
link is connected and communicating. Your laptop must meet the following hardware and
Ethernet
Link The ACT LED blinks yellow at the data software requirements:
transfer rate when data flow is active on the • 1 GB RAM (minimum)
link.
• 1024 x 768 screen resolution
The Service LED is solid green when pressed. • CD-ROM drive
Service For qualified service technicians only. Do not
use. • Ethernet 10/100 LAN card
• An available USB 2.0 port
NOTICE: • Microsoft® Windows® XP Professional operation
system with Service Pack 3 (SP3) or Windows 7
Electrical Noise!
Enterprise or Professional operating system (32-bit or
Maintain at least 6 inches between low-voltage (<30V) 64-bit)
and high voltage circuits. Failure to do so could result in
• Microsoft .NET Framework 4.0 or later
electrical noise that could distort the signals carried by
the low-voltage wiring, including IPC.

14 RLC-SVU006A-E4
Controls
Note:: Tracer TU is designed and validated for this
minimum laptop configuration. Any variation
from this configuration may have different results.
Therefore, support for Tracer TU is limited to only
those laptops with the configuration previously
specified.
Note:: For more information, see TTU-SVN01A-EN
Tracer TU Getting Started Guide

Figure 5. Tracer TU

RLC-SVU006A-E4 15
Diagnostics
Diagnostic Name and Source: Name of Diagnostic and Persistence: Defines whether or not the diagnostic and
its source. Note that this is the exact text used in the its effects are to be manually reset (Latched), or can be
User Interface and/or Service Tool displays. either manually or automatically reset when and if the
Affects Target: Defines the “target” or what is affected condition returns to normal (Nonlatched).
by the diagnostic. Usually either the entire Chiller, Active Modes [Inactive Modes]: States the modes or
or a particular Circuit or Compressor is affected by periods of operation that the diagnostic is active in
the diagnostic (the same one as the source), but in and, as necessary, those modes or periods that it is
special cases functions are modified or disabled by the specifically “not active” in as an exception to the active
diagnostic. None implies that there is no direct affect to modes. The inactive modes are enclosed in brackets, [ ].
the chiller, sub components or functional operation. Note that the modes used in this column are internal and
Design Note: Tracer™ TU does not support the display not generally annunciated to any of the formal mode
of certain targets on its Diagnostics pages although displays.
the functionality implied by this table is supported. Criteria: Quantitatively defines the criteria used in
Targets such as Evap Pump, Ice Mode, Chilled Water generating the diagnostic and, if nonlatching, the criteria
Reset, External Setpoints etc. – are displayed as simply for auto reset. If more explanation is necessary a hot link
“Chiller” even though they do not imply a chiller to the Functional Specification is used.
shutdown – only a compromise of the specific feature. Reset Level: Defines the lowest level of manual
Severity: Defines the severity of the above effect. diagnostic reset command which can clear the
Immediate means immediate shutdown of the affected diagnostic. The manual diagnostic reset levels in order of
portion, Normal means normal or friendly shutdown priority are: Local or Remote. For example, a diagnostic
of the affected portion, Special Action means a special that has a reset level of Remote, can be reset by either
action or mode of operation (limp along) is invoked, but a remote diagnostic reset command or by a local
without shutdown, and Info means an Informational diagnostic reset command.
Note or Warning is generated. Design Note: Tracer TU Help Text: Provides for a brief description of what kind
does not support display of “Special Action”, on its of problems might cause this diagnostic to occur. Both
Diagnostics pages, so that if a diagnostic has a special control system component related problems as well as
action defined in the table below, it will be displayed chiller application related problems are addressed (as
only as “Informational Warning” as long as no circuit can possibly be anticipated). These help messages will
or chiller shutdown results. If there is a shutdown and be updated with accumulated field experience with the
special action defined in the table, then the Tracer TU chillers.
Diagnostics Page display will indicate the shutdown
type only.

16 RLC-SVU006A-E4
Diagnostics
Starter Diagnostics
Hex Diagnostic Name Effects Active Modes Reset
Severity Persistence Criteria
Code and Source Target [Inactive Modes] Level

Compressor A phase reversal was detected on the


energized incoming current. On a compressor startup
E5 Phase Reversal Chiller Immediate Latch to transition the phase reversal logic must detect and Local
command [All trip in a maximum of 0.3 second from
Other Times] compressor start.

While in the Starter Dry Run Mode either


Starter Dry Run 50% Line Voltage was sensed at the Potential
188 Starter Dry Run Test Chiller Immediate Latch Local
Mode Transformers or 10 % RLA Current was
sensed at the Current Transformers.

a) No current was sensed on one or two


of the current transformer inputs while
running or starting (See Nonlatching Power
Loss Diagnostic for all three phases lost
while running). Must hold = 20% RLA.
Must trip = 5% RLA. Time to trip shall be
longer than guaranteed reset on Starter
Start Sequence
E4 Phase Loss Chiller Immediate Latch Module at a minimum, 3 seconds maximum. Local
and Run modes
Actual design trippoint is 10%. The actual
design trip time is 2.64 seconds. b) If Phase
reversal protection is enabled and current
is not sensed on one or more current
xformer inputs. Logic will detect and trip in
a maximum of 0.3 second from compressor
start.

Momentary Power Loss option disabled: No


All compressor effect.
running and Momentary Power Loss option enabled: A
Momentary Power stopping modes loss of power on three line cycles or more
E2 Chiller Immediate Nonlatch Remote
Loss [all compressor was detected. Diagnostic is reset in 30
starting and non- seconds.
running modes] See Momentary Power Loss Protection
specification for additional information.

The compressor had previously established


currents while running and then all three
phases of current were lost. Design: Less
than 10% RLA, trip in 2.64 seconds. This
diagnostic will preclude the Phase Loss
Diagnostic and the Transition Complete Input
Opened Diagnostic from being called out.
To prevent this diagnostic from occurring
with the intended disconnect of main
power, the minimum time to trip must be
greater than the guaranteed reset time of
the Starter module. Note: This diagnostic
All compressor
prevents nuisance latching diagnostics due
running modes
to a momentary power loss – It does not
1A0 Power Loss Chiller Immediate NonLatch [all compressor Remote
protect motor/compressor from uncontrolled
starting and non-
power reapplication. See Momentary Power
running modes]
Loss Diagnostic for this protection. This
diagnostic will auto reset in 10 seconds from
its occurrence, and is not active during the
start mode before the transition complete
input is proven. This prevents the chiller from
cycling due to some internal starter problem,
as the starter would latch out on either a
“Starter Fault Type 3” or a “Starter Did Not
Transition” latching diagnostic. However true
power loss occurring during a start would
result in a misdiagnosis and the chiller would
not automatically recover.

A 30% current imbalance has been detected


Severe Current
E3 Chiller Normal Latch All Running Modes on one phase relative to the average of all Local
Imbalance
3 phases for 90 continuous seconds.

RLC-SVU006A-E4 17
Diagnostics
Hex Diagnostic Name Effects Active Modes Reset
Severity Persistence Criteria
Code and Source Target [Inactive Modes] Level

This is a specific starter test where 1M(1K1)


is closed first and a check is made to ensure
Starting - Y Delta that there are no currents detected by the
1E9 Starter Fault Type I Chiller Immediate Latch Local
Starters Only CT's. If currents are detected when only 1M
is closed first at start, then one of the other
contactors is shorted.

a. This is a specific starter test where the


Shorting Contactor (1K3) is individually
energized and a check is made to ensure that
there are no currents detected by the CT's. If
Starting All types
1ED Starter Fault Type II Chiller Immediate Latch current is detected when only S is energized Local
of starters
at Start, then 1M is shorted. b. This test in a.
above applies to all forms of starters (Note:
It is understood that many starters do not
connect to the Shorting Contactor.).

As part of the normal start sequence to


apply power to the compressor, the Shorting
Starting Contactor (1K3) and then the Main Contactor
[Adaptive (1K1) were energized. 1.6 seconds later
1F1 Starter Fault Type III Chiller Immediate Latch Local
Frequency Starter there were no currents detected by the
Type] CT's for the last 1.2 seconds on all three
phases. The test above applies to all forms
of starters.

Solid State Starter


189 Chiller Immediate Latch All The Solid State Starter Fault Relay is open Local
Fault

701 AFD Drive Fault Chiller Immediate Latch All The AFD Drive Fault Relay is open Local

The Starter Module did not receive a


transition complete signal in the designated
time from its command to transition. The
must hold time from the Starter Module
Starter Did Not On the first check transition command is 1 second. The Must
F0 Chiller Immediate Latch Local
Transition after transition. trip time from the transition command is
6 seconds. Actual design is 2.5 seconds. This
diagnostic is active only for Y-Delta, Auto-
Transformer, Primary Reactor, and X-Line
Starters.

The starter module did not receive an “Up


to Speed” or “End of Ramp” signal from the
Compressor Did Not SSS within 2.5 seconds after commanding a
1F5 Chiller Immediate Latch Start Mode Local
Accelerate Fully bypass, or after the maximum acceleration
time had expired, whichever is longer. This
diagnostic only applies to SSS/AFD.

The compressor did not come up to speed


(get to <85%RLA) in the allotted time
defined by the Maximum Acceleration Timer
and a transition was forced (motor put across
Compressor Did Not the line) at that time. This applies to all
1FA Chiller Info Latch Start Mode Remote
Accel: Transition starter types. Note: Since RTHD SSS has no
forced transition capability, this info warning
can be followed with a “Compressor did not
accelerate fully” diagnostic above and an
aborted start.

The compressor did not come up to speed


(get to <85%RLA) in the allotted time
Compressor Did Not
EE Chiller Immediate Latch Start Mode defined by the Maximum Acceleration Timer Remote
Accelerate: Shutdown
and and the start was aborted per the starter
configuration selected.

The Transition Complete input is shorted


Transition Complete
3D5 Chiller Immediate Latch Pre-Start before the compressor was started. This is Local
Input Shorted
active for all electromechanical starters.

The “At Speed” input is shorted before the


At Speed Input
3D6 Chiller Immediate Latch Pre-Start compressor was started. This is active for Local
Shorted
solid state starters and AFD.

18 RLC-SVU006A-E4
Diagnostics
Hex Diagnostic Name Effects Active Modes Reset
Severity Persistence Criteria
Code and Source Target [Inactive Modes] Level

The Transition Complete input is open


All Running Modes
Transition Complete with the compressor motor running after a
3D7 Chiller Immediate Latch after transition Local
Input Opened successful completion of transition. This is
completed
active only for all electromechanical starters

The “At Speed” input was found to be


All Running Modes opened with the compressor motor running
At Speed Input
3D8 Chiller Immediate Latch after At Speed after successfully obtaining an at speed and Local
Opened
proven bypassed condition. This is active for solid
state starters and AFD

Compressor current exceeded overload time


Motor Current vs. trip characteristic. For A/C products Must
EC Chiller Immediate Latch Chiller Energized Local
Overload trip = 140% RLA, Must hold=125%, nominal
trip 132.5% in 30 seconds

Detected compressor currents greater than


10% RLA on any or all phases when the
compressor was commanded off. Detection
time shall be 5 seconds minimum and
10 seconds maximum. On detection and until
Starter Contactor
Immediate the controller is manually reset: generate
Starter Contactor not Energized
CA Chiller and Special Latch diagnostic, energize the appropriate alarm Local
Interrupt Failure [Starter Contactor
Action relay, continue to energize the Evap and
Energized]
Cond Pump Outputs, continue to command
the affected compressor off, fully unload the
effected compressor. For as long as current
continues, perform liquid level and oil return
gas pump control

a. Average of all monitored Line voltages


above + 10% of nominal. [Must hold =
+ 10% of nominal. Must trip = + 15% of
nominal. Reset differential = min. of 2%
D7 Over Voltage Chiller Normal NonLatch All and max. of 4%. Time to trip = minimum Remote
of 1 min. and maximum of 5 min.)
Design: Nom. trip: 60 seconds at greater
than 112.5%, + or - 2.5%, Auto Reset at
109% or less.

a. Average of all monitored Line voltages


below - 10% of nominal or the Under/
Overvoltage transformer(s) are not
connected. [Must hold = - 10% of nominal.
Must trip = - 15% of nominal. Reset
D8 Under Voltage Chiller Normal NonLatch All differential = min. of 2% and max. of 4%. Remote
Time to trip = min. of 1 min. and max. of
5 min.) Design: Nom. trip: 60 seconds at
less than 87.5%, + or - 2.8% at 200V or
+ or - 1.8% at 575V, Auto Reset at 90%
or greater.

RLC-SVU006A-E4 19
Diagnostics
Main Processor Diagnostics
Hex Effects Active Modes Reset
Diagnostic Name Severity Persistence Criteria
Code Target [Inactive Modes] Level

The main processor has successfully come


out of a reset and built its application.
A reset may have been due to a power up,
MP: Reset Has
D9 Chiller Info NonLatch All installing new software or configuration. This Remote
Occurred
diagnostic is immediately and automatically
cleared and thus can only be seen in the
Historic Diagnostic List in TechView

All Cprsr Running The Starter module status reported back that
modes, Starting, it is stopped when it should be running and
Unexpected Starter
6B5 Chiller Normal Nonlatch Running and no Starter diagnostic exists. This diagnostic NA
Shutdown
Preparing to will be logged in the active buffer and then
Shutdown cleared.

a. The inferred Saturated Evap Refrigerant


Temperature (calculated from suction
pressure transducer(s)) dropped below the
Low Refrigerant Temperature Cutout Setpoint
for 450°F-sec (10°F-sec max rate) while the
circuit was running after the ignore period
had expired. The integral is held at zero for
the 1 minute ignore time following the circuit
startup and the integral will be limited to
Low Evaporator
All Ckt Running never trip in less than 45 seconds, i.e. the
FB Refrigerant Chiller Immediate Latch Remote
Modes error term shall be clamped to 10°F. The
Temperature
minimum LRTC setpoint is -5°F (18.7 Psia)
the point at which oil separates from the
refrigerant. b. During the timeout of the
trip integral, the unload solenoid(s) of the
running compressors on the circuit, shall be
energized continuously and the load solenoid
shall be off. Normal load/unload operation
will be resumed if the trip integral is reset by
return to temps above the cutout setpoint.

The oil pressure was out of the acceptable


pressure range for 15 seconds, while the
Delta Pressure was greater than 15 Psid.:
Chiller Energized
Acceptable range is 0.50 or 0.60 > (PC-Po) /
198 Low Oil Flow Chiller Immediate Latch and Delta P above Local
(PC-PE) for the first 2.5 minutes of operation,
15 Psid
and 0.40 or 0.50 > (PC-Po) / (PC-PE)
thereafter. The higher ratios used if the
system DP is less than 23 psid

In running modes , Oil Loss Level Sensor


Loss of Oil at
Starter Contactor detects lack of oil in the oil tank feeding the
59C Compressor Chiller Immediate Latch Local
Energized compressor (distinguishing a liquid flow from
(Running)
a vapor flow)

Oil Loss Level Sensor detects a lack of oil in


Loss of Oil at Immediate Compressor Pre- the oil tank feeding the compressor for 90
59D Compressor Chiller and Special Latch start [all other seconds after EXV preposition is completed. Local
(Stopped) Action modes] Note: Compressor start is delayed while
waiting for oil to be detected.

The system differential pressure was either


below 15 Psid for more than 164 Psid-sec,
or below 23.0 Psid for 3000 Psid-sec. The
latter integral’s value is not cleared for any
reason including diagnostic trip, manual
Low Differential reset, or power up reset (ie. Integral is saved
1AE Chiller Immediate Latch Chiller Energized Remote
Refrigerant Pressure nonvolatily on power down). The integral will
decay while circuit is running at a max rate
of –10 PSID, and while stopped at a rate of
–0.4 PSID. This same integral is associated
with the operating mode “Compressor Cool
Down”. Also see diagnostic below

The system differential pressure was below


7.7 Psid. The occurrence of this diagnostic
No Differential
297 Chiller Immediate Latch Chiller Energized will saturate the above “Low Diff Rfgt Press” Remote
Refrigerant Pressure
Integral and invoke the same “Compressor
Cool Down” op mode.

20 RLC-SVU006A-E4
Diagnostics
Hex Effects Active Modes Reset
Diagnostic Name Severity Persistence Criteria
Code Target [Inactive Modes] Level

a. The system differential pressure was


above 160 Psid- trip immediately (normal
High Differential shutdown)
1C6 Chiller Normal Latch Chiller Energized Remote
Refrigerant Pressure
B The diff pressure was above 152 Psid - trip
in 1 hour

The system pressure ratio exceeded 5.61 for


1 contiguous minute. This pressure ratio is
High Refrigerant Service Pumpdown
1C6 Chiller Immediate Latch a fundamental limitation of the compressor. Remote
Pressure Ratio Only
The pressure ratio is defined as Pcond (abs)/
Pevap(abs).

The compressor discharge temperature


exceeded 190°F. This diagnostic will be
suppressed if it occurs during the compressor
run-unload period or after the compressor
All [compressor
High Cprsr has stopped, but a run unload will be
not running or
1C2 Rfgt Discharge Chiller Immediate Latch terminated early as a result. Note: As part Remote
during compressor
Temperature of the Compressor High Temperature Limit
run unload]
Mode (aka Minimum Capacity Limit), the
compressor shall be forced loaded as the
filtered discharge temperature nears this
trip-point.

While Running Normally, the Discharge


Superheat was less than 12 degrees F +- 1F
Low Discharge
18E Chiller Normal Latch Any Running Mode for more than 6500 degree F seconds. Remote
Superheat
At startup the UCM shall ignore the Discharge
Superheat for 5 minutes.

Compressor
284 Discharge Chiller Immediate Latch All Bad Sensor or LLID Remote
Temperature Sensor

Evaporator Liquid
27D Chiller Normal Latch All Bad Sensor or LLID Remote
Level Sensor

The BAS was setup as “installed” and the


BAS did not communicate with the MP within
15 minutes after power-up. Refer to Section
BAS Failed
on Setpoint Arbitration to determine how
390 to Establish Chiller Special At power-up Remote
setpoints and operating modes may be
Communication
effected. Note: The original requirement for
this was 2 minutes, but was implemented at
15 minutes for RTAC.

The BAS was setup as “installed” at the MP


and the Comm 3 llid lost communications
with the BAS for 15 contiguous minutes
after it had been established. Refer to
Section on Setpoint Arbitration to determine
BAS Communication
398 Chiller Special All how setpoints and operating modes may Remote
Lost
be effected by the comm loss. The chiller
follows the value of the Tracer Default Run
Command which can be previously written
by Tracer and stored nonvolatilely by the MP
(either use local or shutdown).

The liquid level sensor is seen to be


at or near its low end of range for 80
Starter Contactor
Low Evaporator Liquid contiguous minutes while the compressor
583 Chiller Info NonLatch Energized Remote
Level is running. Design: 20% or less of bit count
[all Stop modes]
corresponding to –21.2 mm or less liquid
level for 80 minutes)

The liquid level sensor is seen to be at or


near its high end of range for 80 contiguous
Starter Contactor minutes while the compressor is running.
High Evaporator
584 Chiller Normal Latch Energized (The diagnostic timer will hold, but not clear Remote
Liquid Level
[all Stop modes] when the circuit is off). Design: 80% or more
of bit count corresponding to +21.2 mm or
more liquid level for 80 minutes)

RLC-SVU006A-E4 21
Diagnostics
Hex Effects Active Modes Reset
Diagnostic Name Severity Persistence Criteria
Code Target [Inactive Modes] Level

a. Function Not “Enabled”: no diagnostics. b.


“Enabled”: Out-Of-Range Low or Hi or bad
External Chilled/Hot LLID, set diagnostic, default CWS to next
87 Chiller Info NonLatch All Remote
Water Setpoint level of priority (e.g. Front Panel SetPoint).
This Info diagnostic will automatically reset if
the input returns to the normal range.

a. Not “Enabled”: no diagnostics. b.


“Enabled”: Out-Of-Range Low or Hi or bad
External Current Limit LLID, set diagnostic, default CLS to next level
89 Chiller Info NonLatch All Remote
Setpoint of priority (e.g. Front Panel SetPoint. This
Info diagnostic will automatically reset if the
input returns to the normal range.

Out-Of-Range Low or Hi or bad LLID,


AFD output power set diagnostic, This Info diagnostic will
702 Chiller Info NonLatch All
input automatically reset if the input returns to the
normal range.

a. Not “Enabled”: no diagnostics. b.


“Enabled”: Out-Of-Range Low or Hi or bad
Info and
External Base Loading LLID, set diagnostic, default BLS to next level
4C4 Chiller Special NonLatch All Remote
Setpoint of priority (e.g. Front Panel SetPoint. This
Action
Info diagnostic will automatically reset if the
input returns to the normal range.

The entering evaporator water temp fell


below the leaving evaporator water temp.
Any Ckt(s) by more than 2°F for 100°F-sec. For falling
Evap Water Flow
Energized film evaporators this diagnostic cannot
8A (Entering Water Chiller Info NonLatch Remote
[No Ckt(s) reliably indicate loss of flow, but can warn
Temp)
Energized] of improper flow direction through the
evaporator, misbound temperature sensors,
or other system problems

Bad Sensor or LLID Normal operation unless


CHW Reset is enabled. If CHW Reset is
Info and
Evaporator Entering enabled and either Return or Constant Return
8E Chiller Special Latch Remote
Water Temp Sensor Chilled Water Reset is selected, its effect will
Action
be removed but slew rates on the change will
be limited per the Chilled Water Reset spec.

Evaporator Leaving
AB Chiller Normal Latch All Bad Sensor or LLID Remote
Water Temp Sensor

Info and Bad Sensor or LLID. If chiller running, and


Condenser Entering
9A Chiller Special Latch All condenser water regulating valve option Remote
Water Temp Sensor
Action installed, force valve to 100% flow.

Condenser Leaving
9B Chiller Info Latch All Bad Sensor or LLID Remote
Water Temp Sensor

Condenser Rfgt
5B8 Chiller Normal Latch All Bad Sensor or LLID Remote
Pressure Transducer

Evaporator Rfgt
5BA Chiller Normal Latch All Bad Sensor or LLID Remote
Pressure Transducer

Oil Pressure
5BE Chiller Normal Latch All Bad Sensor or LLID Remote
Transducer

The Oil Pressure Transducer for this Chiller


Starter Contactor is reading a pressure either above its
Oil Flow Protection
1E1 Chiller Immediate Latch Energized [all Stop Condenser Pressure by 15 Psia or more, or Local
Fault
modes] below its Evaporator Pressure 10 Psia or
more for 30 seconds continuously.

The Evaporator Refrigerant Pressure dropped


below 10 psia just prior to compressor
Low Evaporator Chiller Prestart and start. The pressure fell below 10 psia while
B5 Chiller Immediate Latch Local
Refrigerant Pressure Chiller Energized running but before the 3 minute ignore time
had expired or fell below 16 Psia after the
3 minute ignore time had expired.

22 RLC-SVU006A-E4
Diagnostics
Hex Effects Active Modes Reset
Diagnostic Name Severity Persistence Criteria
Code Target [Inactive Modes] Level

The leaving Evaporator water temp. fell


below the leaving water temp cutout setting
Unit in Stop Mode, for 30 degree F seconds while the Chiller is
or in Auto Mode in the Stop mode, or in Auto mode with no
Info and
Low Evaporator Water and No Ckt(s) compressors running. Energize Evap Water
C5 Chiller Special NonLatch Remote
Temp (Unit Off) Energized pump Relay until diagnostic auto resets,
Action
[Any Ckt then return to normal evap pump control.
Energized] Automatic reset occurs when the temp rises
2°F (1.1°C) above the cutout setting for
30 minutes.

The evap sat temp fell below the water temp


cutout setting while the respective evap
liquid level was greater than –21.2 mm for
30 (or 150 begining with rev 08) degree F
Unit in Stop Mode,
seconds while Chiller is in the Stop mode, or
Info and or in Auto Mode
Low Evaporator in Auto mode with no compressors running.
6B3 Chiller Special NonLatch and No Ckt's Remote
Temp: Unit Off Energize Evap Water pump Relay until
Action Energizd
diagnostic auto resets, then return to normal
[Any Ckt Energizd]
evap pump control. Automatic reset occurs
when either the evap temp rises 2°F (1.1°C)
above the cutout setting or the liquid level
falls below –21.2mm for 30 minutes

The Evaporator water temp. fell below the


cutout setpoint for 30 degree F Seconds
Any Ckt[s]
Immediate while the compressor was running. Automatic
Low Evaporator Water Energized
C6 Chiller and Special NonLatch reset occurs when the temperature rises Remote
Temp (Unit On) [No Ckt(s)
Action 2°F (1.1°C) above the cutout setting for
Energizd]
2 minutes. This diagnostic shall not de-
energize the Evaporator Water Pump Output.

Evaporator water flow was not proven within


20 minutes of the Evaporator water pump
Estab. Evap. Water relay being energized. The Evap pump
Evaporator Water
384 Chiller Normal NonLatch Flow on going from command status will not be effected. This Remote
Flow Overdue
STOP to AUTO. diagnostic will auto-clear on proof of flow
(6-10 seconds of continuous flow), or if
chiller is returned to Stop mode.

The Evaporator water flow proof input was


open for more than 6-10 contiguous seconds
after flow had been proven. The pump
Evap pump command status will not be effected. Even
Evaporator Water commanded “on” though the pump may be commanded to run
ED Chiller Immediate NonLatch Remote
Flow Lost except for in the STOP modes (pump off delay time),
[All Stop modes] this diagnostic shall not be called out in the
STOP modes. This diagnostic will auto-clear
on proof of flow (6-10 seconds of continuous
flow), or if chiller is returned to Stop mode.

Condenser water flow was not proven within


20 minutes of the condenser pump relay
Condenser Water Estab Cond Water being energized. The Cond Pump shall be
DC Chiller Normal NonLatch Remote
Flow Overdue Flow commanded off. Diagnostic is reset with
return of flow (although only possible with
external control of pump)

The condenser water flow proof input was


open for more than 6 contiguous seconds
after flow had been proven. This diagnostic
Condenser Water Start and All Run
F7 Chiller Immediate NonLatch is automatically cleared once the compressor Remote
Flow Lost Modes
is stopped by a fixed time out of 7 sec. The
Cond Pump shall be commanded off but the
Evap pump command will not be effected.

The evaporator refrigerant pressure has


risen above 190 psig (future use – add “for
continuous15 seconds”). The evaporator
water pump relay will be de-energized to
Immediate
High Evaporator stop the pump regardless of why the pump
6B8 Chiller and Special NonLatch All Local
Refrigerant Pressure is running. The diagnostic will auto reset
Action
and the pump will return to normal control
when the evaporator pressures falls below
185 psig. This diagnostic must shutdown the
chiller if it is running.

RLC-SVU006A-E4 23
Diagnostics
Hex Effects Active Modes Reset
Diagnostic Name Severity Persistence Criteria
Code Target [Inactive Modes] Level

The leaving water temperature exceeded


the high evap water temp limit (TV service
menu settable –default 105F) for 15
continuous seconds. The evaporator water
pump relay will be de-energized to stop the
Only effective if pump but only if it is running due one of the
either diagnostics listed on the right. The diagnostic
will auto reset and the pump will return to
1)Evap Wtr Flow
normal control when the temperature falls
Info and Overdue,
High Evaporator 5°F below the trip setting. The primary
6B6 Chiller Special NonLatch 2)Evap Wtr Flow purpose is to stop the evaporator water Local
Water Temperature
Action Loss, or 3)Low pump and its associated pump heat from
Evap Rfgt Temp,- causing excessive waterside temperatures
Unit Off, diagnostic and waterside pressures when the chiller is
is active. not running but the evap pump is on due to
either Evap Water Flow Overdue, Evaporator
Water Flow Loss , or Low Evap Temp – Unit
Off Diagnostics. This diagnostic will not
auto clear solely due to the clearing of the
enabling diagnostic.

A high pressure cutout was detected; C.O. on


rise @ 180 psig, reset @ 135 psig (+/-5 psi
on switching tolerance) Note: Pressure relief
valve is 200 Psig +- 2% trip at 315 ± 5 psi.
F5 High Pressure Cutout Chiller Immediate Latch All Note: Other diagnostics that may occur as an Local
expected consequence of the HPC trip will be
suppressed from annunciation. These include
Phase Loss, Power Loss, and Transition
Complete Input Open.

a. EMERGENCY STOP input is open. An


external interlock has tripped. Time to trip
FD Emergency Stop Chiller Immediate Latch All Local
from input opening to unit stop shall be 0.1
to 1.0 seconds.

Bad Sensor or LLID. This diagnostic will only


Info and
Outdoor Air occur if OA sensor is configured.OA Chilled
A1 Chiller Special Latch All Remote
Temperature Sensor water reset will be suspended if selected and
Action
Tracer OA unavailable.

Refrigerant Monitor Open or Shorted input and the Rfgt Monitor


2F2 Chiller Info NonLatch All –if installed Remote
Input is setup as installed

Checksum on RAM copy of the Starter LLID


Starter Module
5C5 Chiller Info Latch All configuration failed. Configuration recalled Local
Memory Error Type 1
from EEPROM.

Starter Module Checksum on EEPROM copy of the Starter


5C9 Memory Error Chiller Immediate Latch All LLID configuration failed. Factor default Local
Type 2 - values used.

MP: Invalid MP has an invalid configuration based on the


5FF None Immediate Latch All Remote
Configuration current software installed

The real time clock had detected loss of its


oscillator at some time in the past. Check /
replace battery? This diagnostic can be
2E6 Check Clock Chiller Info Latch All effectively cleared only by writing a new Remote
value to the chiller’s time clock using the
TechView or DynaView’s “set chiller time”
functions.

Starter Failed to Arm/ Starter failed to arm or start within the


6A3 Chiller Info Latch All Remote
Start allotted time (2 minutes).

The Restart Inhibit was invoked on a


28C Restart Inhibit Chiller Info NonLatch All compressor. This indicates excessive chiller Remote
cycling which should be corrected.

The neuron software in the LCI-C module


does not match the chiller type. Download
LCI-C Software
the proper software into the LCI-C neuron.
Mismatch: Use BAS Chiller info NonLatch All Remote
To do this, use the Rover service tool, or
Tool
a LonTalk® tool capable of downloading
software to a Neuron 3150®.

24 RLC-SVU006A-E4
Diagnostics
Hex Effects Active Modes Reset
Diagnostic Name Severity Persistence Criteria
Code Target [Inactive Modes] Level

A high level software watchdog has


detected a condition in which there was a
continuous 5 minute period of compressor
operation, with neither chilled water flow
Software Error All Latch – nor a” contactor interrupt failure” diagnostic
705 Number: 1001 Call func- Immediate power down all active. The occurrence of this software error local
Trane Service tions reset is reqd message suggests an internal software state
chart misalignment has occurred. The events
that led up to this failure, if known, should be
recorded and transmitted to Trane Controls
Engineering – (SW rev 6 and higher)

RLC-SVU006A-E4 25
Diagnostics
Communication Diagnostics
Hex Active Modes Reset
Diagnostic Name Effects Severity Persistence Criteria
Code [Inactive Modes] Level

Continual loss of communication between the


Comm Loss: Slide
5D1 Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Valve Unload
30 second period.

Continual loss of communication between the


Comm Loss: Slide
5D2 Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Valve Load
30 second period.

Continual loss of communication between the


Comm Loss: External
5DD Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Auto/Stop
30 second period.

Continual loss of communication between the


Comm Loss:
5DE Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Emergency Stop
30 second period.

Continual loss of communication between


Comm Loss: Ice the MP and the Functional ID has occurred
5E1 External Ice Building Build- Normal Latch All for a 30 second period. Chiller shall revert to Remote
Command ing normal (non-ice building) mode regardless of
last state.

Continual loss of communication between


Ice the MP and the Functional ID has occurred
Comm Loss: Ice
5FA Build- Normal Latch All for a 30 second period. Chiller shall revert to Remote
Building Status Relay
ing normal (non-ice building) mode regardless of
last state.

Continual loss of communication between the


MP and the Functional ID has occurred for a
Info and 30 second period. Note that if this diagnostic
Comm Loss: Outdoor
5E2 Chiller Special Latch All occurs, Chiller shall remove any OA Chilled Remote
Air Temperature
Action Water Reset, if it was in effect and if Tracer
OA was unavailable. Apply slew rates per
Chilled Water Reset spec

Continual loss of communication between the


Comm Loss: Evap
5E3 Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Leaving Water Temp
30 second period.

Continual loss of communication between


the MP and the Functional ID has occurred
Info and
Comm Loss: Evap for a 30 second period. Chiller shall remove
5E4 Chiller Special Latch All Remote
Entering Water Temp any Return or Constant Return Chilled Water
Action
Reset, if it was in effect. Apply slew rates per
Chilled Water Reset spec.

Comm Loss: Continual loss of communication between the


6B6 Condenser Leaving Chiller Info Latch All MP and the Functional ID has occurred for a Remote
Water Temp 30 second period.

Continual loss of communication between


Comm Loss: Info and the MP and the Functional ID has occurred
6B6 Condenser Entering Chiller Special Latch All for a 30 second period. If chiller running, Remote
Water Temp Action and condenser water regulating valve option
installed, force valve to 100% flow.

Continual loss of communication between the


Comm Loss: Cprsr
6B6 Chiller Immediate Latch All MP and the Functional ID has occurred for a Remote
Discharge Rfgt Temp
30 second period.

Continual loss of communication between the


MP and the Functional ID has occurred for a
Comm Loss: Ext Info and
30 second period. Chiller shall discontinue
5E9 Chilled/Hot Water Chiller Special Latch All Remote
use of the External Chilled Water Setpoint
Setpoint Action
source and revert to the next higher priority
for setpoint arbitration

Continual loss of communication between the


MP and the Functional ID has occurred for a
Info and
Comm Loss: Ext 30 second period. Chiller shall discontinue
5EA Chiller Special Latch All Remote
Current Limit Setpoint use of the External Current limit setpoint and
Action
revert to the next higher priority for Current
Limit setpoint arbitration

26 RLC-SVU006A-E4
Diagnostics
Hex Active Modes Reset
Diagnostic Name Effects Severity Persistence Criteria
Code [Inactive Modes] Level

Comm Loss: High Continual loss of communication between the


5EB Pressure Cutout Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Switch 30 second period.

Comm Loss: Continual loss of communication between the


5EF Evaporator Water Chiller Immediate Latch All MP and the Functional ID has occurred for a Remote
Flow Switch 30 second period.

Comm Loss: Continual loss of communication between the


6B6 Condenser Water Chiller Immediate Latch All MP and the Functional ID has occurred for a Remote
Flow Switch 30 second period.

Comm Loss: Continual loss of communication between the


5F0 Evaporator Rfgt Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Pressure 30 second period.

Comm Loss: Continual loss of communication between the


5F2 Condenser Rfgt Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Pressure 30 second period.

Continual loss of communication between the


Comm Loss: Oil
5F4 Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Pressure
30 second period.

Continual loss of communication between the


Comm Loss: Oil
6B6 Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Return Gas Pump Fill
30 second period.

Comm Loss: Oil Continual loss of communication between the


6B6 Return Gas Pump Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Drain 30 second period.

Continual loss of communication between the


Comm Loss: Oil Loss
6B6 Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Level sensor Input
30 second period.

Continual loss of communication between the


Comm Loss: Master
6B6 Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Oil Line SV
30 second period.

Comm Loss: Continual loss of communication between the


5F8 Evaporator Water Chiller Info Latch All MP and the Functional ID has occurred for a Remote
Pump Relay 30 second period.

Comm Loss: Continual loss of communication between the


6B6 Condenser Water Chiller Info Latch All MP and the Functional ID has occurred for a Remote
Pump Relay 30 second period.

Continual loss of communication between the


Comm Loss: SSS/AFD
6B6 Chiller Info Latch All MP and the Functional ID has occurred for a Remote
Fault
30 second period.

Comm Loss: Continual loss of communication between the


6B6 Refrigerant Monitor Chiller Info Latch All MP and the Functional ID has occurred for a Remote
Input 30 second period.

Continual loss of communication between


the MP and the Functional ID has occurred
Info and
Comm Loss: Ext Base for a 30 second period. The external
6B6 Chiller Special Latch All Remote
Loading Setpoint base load setpoint input is removed from
Action
the arbitration to establish the Base
LoadingSetpoint.

Continual loss of communication between


Info and the MP and the Functional ID has occurred
Comm Loss: Ext Base
6B6 Chiller Special Latch All for a 30 second period. The external base Remote
Loading Command
Action load input is removed from the arbitration to
enable Base Loading.

Comm Loss: Continual loss of communication between the


688 Evaporator Rfgt Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Liquid Level 30 second period.

Continual loss of communication between the


690 Comm Loss: Starter Chiller Immediate Latch All MP and the Functional ID has occurred for a Local
30 second period.

RLC-SVU006A-E4 27
Diagnostics
Hex Active Modes Reset
Diagnostic Name Effects Severity Persistence Criteria
Code [Inactive Modes] Level

Comm Loss: Continual loss of communication between the


694 Electronic Expansion Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Valve 1 30 second period.

Comm Loss: Continual loss of communication between the


695 Electronic Expansion Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Valve 2 30 second period.

Starter Comm Loss: Starter has had a loss of communication with


5CD Chiller Immediate Latch All Local
Main Processor the MP for a 15 second period.

Continual loss of communication between the


Info and
Comm Loss: Local MP and the Functional ID has occurred for a
69D Chiller Special Latch All Remote
BAS Interface 30 second period. Use the last values sent
Action
from BAS

Comm Loss: Op Continual loss of communication between the


6A0 Status Programmable Chiller Info Latch All MP and the Functional ID has occurred for a Remote
Relays 30 second period.

Comm Loss: Continual loss of communication between the


6B6 Compressor % RLA Chiller Info Latch All MP and the Functional ID has occurred for a Remote
Output 30 second period.

Continual loss of communication between the


Comm Loss: Cond
6B6 Chiller Normal Latch All MP and the Functional ID has occurred for a Remote
Rfgt Pressure Output
30 second period.

Comm Loss: Cond Continual loss of communication between the


6B6 Head Press Cntrl Chiller Immediate Latch All MP and the Functional ID has occurred for a Remote
Output 30 second period.

Continual loss of communication between the


Comm Loss: AFD
703 Chiller Immediate Latch All MP and the Functional ID has occurred for a Remote
speed signal output
30 second period.

Continual loss of communication between the


Comm Loss: AFD
704 Chiller Immediate Latch All MP and the Functional ID has occurred for a Remote
output power input
30 second period.

Continual loss of communication between the


Comm Loss: External Warning
687 Chiller Info All MP and the Functional ID has occurred for a Remote
Hot Water Command Reset
30 second period.

28 RLC-SVU006A-E4
Diagnostics
Operator Display Diagnostics and Messages

Table 9. Operator display diagnostics and messages


Description
Operator Display Message
//Troubleshooting

• A valid configuration is present in the MP’s nonvolatile memory. The configuration


is a set of variables and settings that define the physical makeup of this
A Valid Configuration is Present particular chiller. These include: number/airflow,/and type of fans, number/and
size of compressors, special features, characteristics, and control options.
• //Temporary display of this screen is part of the normal power up sequence.

• Ethernet cable not connected between display and UC800.


• UC800 not powered.
Communication Lost with UC800 • UC800 has an invalid configuration – Download a valid configuration
• UC800 is in Binding View. When exit Binding View, select ‘Restart’ on this
message.

• Ethernet cable not connected between display and UC800.


• UC800 not powered.
Display Failed to Establish
Communication • UC800 just has the backup application running as received from the vendor.
Download CTV application software.
• UC800 has an invalid configuration – Download a valid configuration

• The display is low on memory, and needs to re-start. Select Yes to restart.
Display is about to Restart Selecting Yes will not affect the UC800 operation.. Only the Operator Display is
reset.

• This error message is displayed when the MP code finds itself in an illegal
location. These assertion points are placed in code locations to aid the software
team in identifying why the MP locked up as a result of vectoring to an invalid
location.
Error Resulted From Invalid • When this message occurs, copy down the file name and line number and have
Configuration – Record Condition and this ready to give Trane service.
Call Trane Service • This message remains on the screen for two minutes. After two minutes, the
Assertion: ‘File Name’ ‘Line Number’ watchdog times out and a ‘Watchdog Error’ message is displayed The watchdog
then resets the MP. The MP heads into a boot and configuration mode the same
as it does on a power up.
• These error messages are on the AdaptiView screen and do not appear in Tracer
TU nor in the diagnostic logs.

File Not Found • Update UC800 software with Tracer TU

Screen partially populated. Auto and


• Valid configuration is not present. Download a configuration.
Stop button graphics display, no text.

Screen Unresponsive • Tracer TU is downloading software. Wait till download is complete.

• Most likely this UC800 has only the backup application. Download the latest UC
800 software build.
• This could also mean that the UC800 does not have a valid configuration.
The Page Cannot be found Download a configuration to it.
• Cycle power to the OD and UC800.
• UC could be in binding view. If so, get it out of binding view by navigating to
another screen in Tracer TU.

UC800 Configuration is Invalid • Update the UC800 configuration with Tracer TU.

RLC-SVU006A-E4 29
Notes

30 RLC-SVU006A-E4
Notes

RLC-SVU006A-E4 31
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader
in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio
of advanced controls and HVAC systems, comprehensive building services and parts. For more information visit
www.Trane.com

© 2014 Trane All rights reserved We are committed to using environmentally


conscious print practices that reduce waste.
RLC-SVU006A-E4 April 2014
New

También podría gustarte