Documentos de Académico
Documentos de Profesional
Documentos de Cultura
PIP PCCEL001
Instrumentation Electrical Requirements
PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES
In an effort to minimize the cost of process industry facilities, this Practice has
been prepared from the technical requirements in the existing standards of major
industrial users, contractors, or standards organizations. By harmonizing these technical
requirements into a single set of Practices, administrative, application, and engineering
costs to both the purchaser and the manufacturer should be reduced. While this Practice
is expected to incorporate the majority of requirements of most users, individual
applications may involve requirements that will be appended to and take precedence over
this Practice. Determinations concerning fitness for purpose and particular matters or
application of the Practice to particular project or engineering situations should not be
made solely on information contained in these materials. The use of trade names from
time to time should not be viewed as an expression of preference but rather recognized as
normal usage in the trade. Other brands having the same specifications are equally
correct and may be substituted for those named. All Practices or guidelines are intended
to be consistent with applicable laws and regulations including OSHA requirements. To
the extent these Practices or guidelines should conflict with OSHA or other applicable
laws or regulations, such laws or regulations must be followed. Consult an appropriate
professional before applying or acting on any material contained in or suggested by the
Practice.
PIP PCCEL001
Instrumentation Electrical Requirements
Table of Contents
1. Introduction ..................................2 8. Terminations .............................. 15
1.1 Purpose ............................................2 8.1 General .......................................... 15
1.2 Scope ...............................................2 8.2 Milliamp Signals - Typically 4 to
20 mA ............................................ 15
2. References....................................2 8.3 Voltage Signals - 100 mV or
2.1 Process Industry Practices ................2 Greater........................................... 15
2.2 Industry Codes and Standards ..........2 8.4 Voltage Signals - Less than
2.3 Government Regulations ..................4 100 mV........................................... 16
8.5 Thermocouple Signals.................... 16
3. Definitions.....................................4
9. Instrument Power Systems ....... 16
4. General..........................................5 9.1 General .......................................... 16
5. Environmental ..............................6 9.2 Branch Circuits Design ................... 17
1. Introduction
1.1 Purpose
The purpose of this Practice is to provide electrical requirements for process
measurement and control systems.
1.2 Scope
This Practice provides the requirements for the equipment selection, system design,
and installation of electrical supply and wiring to support process measurement and
control systems.
2. References
Applicable requirements in the latest edition (or the edition indicated) of the following industry
codes, standards, and references shall be considered an integral part of this Practice. Short
titles will be used herein when appropriate.
3. Definitions
AC Safety Ground: The grounding system required by NEC Article 250 to provide protection
for personnel and electrical equipment. The Instrument Ground Bus is connected to the Safety
Ground per the NEC requirements.
Control Room: The location where direct operation of the unit or plant is performed and where
operations personnel are in constant attendance
Field Instrument Enclosure: The term used in the generic sense to indicate a cabinet or
building that houses instruments and/or wiring termination external to Instrument Rooms or
Control Buildings
Field-Powered Devices: Instruments located in the field that are powered from sources other
than the Basic Process Control System (BPCS) and/or Safety Instrumented System (SIS).
These are sometimes referred to as 4-wire devices.
Instrument Rooms: The term used in the generic sense for a walk-in type structure, including
rack rooms, remote instrument enclosures, or any completely enclosed structure that houses
control equipment
Instrument Ground Bus (IGB): Grounding system connected to a high-quality earth ground,
independent from the AC Safety Ground, for all instrumentation signals. The IGB is tied to the
AC Safety Ground at only one point, near a high-quality earth ground, per NEC and Figure 1
of this Practice. The IGB is isolated from all other grounds.
Junction Box (JB): A protective enclosure around connections between electric wires or cables
(ISA Comprehensive Dictionary). The junction box may be a Field Junction Box, usually
referred to as JB, or it may be within a control building or instrument enclosure, where it is
referred to as an Interface Box (IB). The IB is sometimes called a Marshalling Cabinet or
Termination Cabinet.
Uninterruptible Power Supply (UPS): A power supply system that provides uninterrupted
power to the connected equipment for a specified period of time, even during failure of the
primary power source. The UPS is typically a rectifier with batteries and an inverter system to
provide alternating current (AC). A UPS is often used to provide reliable power to the
instrumentation power distribution system. (Refer to NEC Article 645-11.)
4. General
4.1 All process measurement and control equipment shall be suitable for the electrical area
classification in which they are installed.
4.2 All techniques used to comply with area classification requirements shall comply with
NEC Chapter 5 or the authority having jurisdiction.
4.3 Equipment and enclosures that require purging to comply with area class requirements
shall be purged in accordance with NFPA 496. Use of purging to reduce area
classification shall require Owner’s approval. For environmental purges, see Section
5.4.
4.4 Instruments shall not be installed in Zone 0, Zone 1, or Division 1 areas unless
approved by Owner.
4.5 Instrument electrical equipment shall be rated for continuous energized duty.
4.6 Instrument cabinets or panels that contain more than one power source shall have a
caution sign identifying the separate power sources.
4.7 Redundant instruments shall be supplied from separate circuits and from separate
branches where practical for each instrument. Separate I/O cards should be
considered.
4.8 Indicator lights (non-annunciator lights used to visually communicate messages) on
control panels shall be uniformly color-coded within each operating unit and,
preferably, across each site. A recommended color code for panel indicating lights is:
4.8.1 Green - Normal state, operating, usually energized
4.8.2 Red - Abnormal state, out of service, usually de-energized, or potentially
dangerous
Comment: This convention is opposite to electrical power indicating light
convention and is not allowed on UL- (Underwriters Laboratories,
Inc.) labeled devices.
4.9 Each device of 50 V (AC or DC) or greater shall have its own individual lockable
disconnect switch with appropriate labeling. Either local or remote lockout is
permissible.
4.10 All electrical equipment including instrumentation shall be designed and installed in
accordance with NEC and OSHA 1910 Subpart S.
4.11 Any box, including junction boxes, containing voltages higher than 50 V (AC or DC)
shall have a caution sign on the outside of the box.
4.12 Voltages over 120 VAC in instrument enclosures require Owner’s approval.
4.13 Field instruments directly connected to flammable or explosive process fluids shall be
designed with multiple barriers to prevent entry of vapors into the cable/conduit
system. If the additional seal is required, a drain, vent, or other device is required so
that the failure of the primary seal is obvious. Refer to NEC Article 501-5(f)(3).
Comment: The use of a sealing fitting with a drain, provided that the drain is on
the instrument side, will satisfy the above-mentioned NEC requirement.
4.14 Minimum Design Capacity Allowance shall be provided as follows:
4.14.1 Design capacity allowance is the capacity available at the completion of
design.
4.14.2 Control building cabinets and consoles shall be designed to accommodate a
minimum of 20% additional equipment.
4.14.3 Field junction boxes and field cables shall be designed and installed to
accommodate a minimum of 20% additional field devices.
4.14.4 Field wire raceways, exclusive of conduits, shall be designed for a minimum
of 20% future additions.
4.14.5 Cable tray from the process area into the control room and instrument
buildings shall be sized for a minimum of 40% future additions.
4.14.6 Power panels shall have at least 20% spare circuit breakers or fuses installed
at design completion (refer to Section 9.2.5).
4.15 Input and output circuits of controllers that are not current limited shall be protected
by fuses.
5. Environmental Considerations
6.1 All analog transmitted instrumentation signals shall be a current signal having a range
7.1 General
The installation of all wiring and cables, including low-voltage instrument cables, shall
comply with NEC requirements for the type of cable or wiring being used and the
location in which it is being installed.
7.1.1 The routing for cables from field areas to the control room and instrument
room in new plant areas is in overhead cable trays. Cable trays should not be
routed in fire hazardous areas (e.g., over pumps, under process air fans, etc.).
7.1.2 For fire protection of instrument cables, refer to PIP PCCGN002 or to
Owner-supplied procedure.
7.1.3 Cables that are laid directly under raised floors shall be specifically approved
for this method of installation by NEC Article 354. AC power wiring (120
VAC and higher) routed in the raised floor space shall utilize conduit, metal-
enclosed raceway, metal clad cable, or cable tray, with adequate separation
from the signal wiring.
7.1.4 The use of the area under a raised floor for an HVAC plenum shall require
Owner’s approval. The wiring shall be installed in accordance with NEC
Article 300-222. Any wiring in the HVAC plenum shall be “Plenum Rated”
and non-toxic, unless installed in an enclosed conduit system.
7.1.5 For Safety Instrumented Systems (SIS) wiring, refer to ISA S84.01 and
PIP PCESS001.
7.1.6 If the room is classified as an information technology equipment room, it shall
meet all the requirements of NEC Article 645.
Comment: Process control electronic equipment alone does not require the
room to be classified as a computer/data-processing room.
7.5.2.1 Field instruments shall be wired from the field junction box to the
field instrument by a dedicated, individual cable. Single pair cables
in conduit or trays shall be the preferred wiring method.
7.5.2.2 Termination of conduit with flex conduit in Division 2 or approved
flex for Division 1 area shall be used to provide isolation of the
conduit system from vibration to protect against thermal expansion
and for maintenance. The length shall be limited to 24 inches unless
otherwise approved by Owner.
7.5.2.3 Conduit wiring capacity shall be sized in accordance with NEC.
Comment: When performing this sizing calculation, care must
be taken to allow for the reduced area of the
conduit fitting.
7.5.2.4 In highly corrosive environments, aluminum, PVC, or PVC-coated
conduit may be used where approved by Owner. When PVC is
used, the use of a grounding wire and additional supports are
required in accordance with NEC Article 347.
7.5.2.5 Fiber and data highways shall meet equipment and cable vendor’s
installation requirements and NEC Article 770.
7.5.2.6 Redundant data highways shall have separate routings with
maximum practical physical separation to minimize the possibility
of a single event causing the simultaneous loss of both wiring
systems. Redundant data highway routings shall be approved by
Owner.
Table 1
Wire and Cable Requirements for Instrument Circuits
(For control panel wiring, see PIP PCSCP001. For 300 volt instrument tray cable, see PIP ELSWC02.
For 600 volt power and control cable, see PIP ELSWC03.)
A. NEC Class 1 Circuits (Notes 1 and 3)
Instrument Class Circuit Example Conduit Wiring Tray Cable
A. 120 VAC or Less Switches, Solenoids, Relays 600 V THWN, Insulated, 600 V TC, Insulated
14 AWG Minimum
B. NEC Article 727 Circuits, Conduits, and Cable Tray Installations (Notes 1 and 11)
B1. Instrument Circuit Example Single Pairs or Triads Multiple Pair or Triad Cable
Circuit Class and
Type
B2. 24 VDC or Less 4 - 20 mA DC RTDs, Weigh 300 V Shielded Twisted Pairs or 300 V ITC PVC Insulated
(Notes 4 and 8) Cells, Solenoids, Alarms, Triads Twisted Pairs or Triads, Overall
Switches, Relays, CABLE TYPES: Shield
Secondary Motor Control, SPISCO, STISCO CABLE TYPES:
Digital Process Transmitter MPISCO, MTISCO
(Notes 2, 3, 5, 9, and 10)
(Notes 2, 3, 4, 9, and 10)
B3. Frequency or Speed, Vibration, Turbine 300 V Shielded Twisted Pairs or Individually Shielded Pairs Tray
Pulse Train Digital Meter Triads Cable or Triads
Communication CABLE TYPES: CABLE TYPES:
(Note 6) SPISCO, STISCO MPISCO, MTISCO
(Notes 2, 3, 9, and 10) (Notes 2, 3, 5, 9, and 10)
B4. Thermocouple Thermocouples 300 V ITC, 16 AWG, Individually 300 V ITC, 20 AWG, Individually
Measurement Shielded Twisted Pair Shielded Twisted Pairs, Overall
(Note 8) CABLE TYPES: Shield
SPTECO CABLE TYPES:
(Notes 2, 3, 9, and 10) MPTECO
(Notes 2, 3, 9, and 10)
C. Data Highways and Other High-Speed Circuits
Data Highways EIA-422A Data Highways/ Follow Cable and System Follow Cable and System
(Notes 7 and 10) High-Speed Communication Manufacturer’s Manufacturer’s
Recommendation Recommendation
Notes:
1. Type A circuits shall be separated from all other types of instrument circuits by either conduit tray dividers or separate trays.
2. 20 AWG minimum wire size for multi-pair cable; 16 AWG minimum wire size for single pair cable. A larger wire size shall be used if
required by the calculations.
3. Wire sizes listed in the table and notes are minimum requirements. Actual wire size shall be based on load current and voltage drop
requirements. The use of parallel wires to meet the current requirements is not allowed.
4. Higher DC levels require Owner’s approval.
5. Type ITC cable shall not be installed on either non-power-limited circuits or powered-limited circuits operating at more than 150 volts
or more than 5 amperes.
6. Vibration signals shall be run in galvanized steel conduit, flexible conduit, or armored cables from the probe to the local transducer.
7. Maximum separation between redundant highways shall be obtained within the operating plant. The use of a single cable tray for
primary and redundant highways is not acceptable.
8. Type B1 and B3 circuits may be routed in the same conduits and trays.
9. For a description of the six-letter designators, see Section 6.2.1.7 and refer to the listings in
PIP ELSWC05 and PIP ELSWC05D.
10. Differences in the manufacturer-recommended cable and these requirements shall be resolved with the Owner.
11. Physical barriers are also required to separate intrinsically safe wiring from other wiring.
Table 2
Segregation and Minimum Spacing Requirements for Parallel Runs
(For wiring level definitions, see Note 1. For units of measurement in inches, see Note 3.)
Steel-Conduit-to-Steel-Conduit Spacing
Wiring Levels 1 2 3 4 5
1 0 1 3 12 12
2 1 0 3 9 12
3 3 3 0 0 0
4 12 9 0 0 0
5 12 12 0 0 0
Tray-to-Tray Spacing or Tray-to-Conduit Spacing
Wiring Levels 1 2 3 4 5
1 0 1 6 26 26
2 1 0 6 18 26
3 6 6 0 6 12
4 26 18 6 0 0
5 26 26 12 0 0
Notes:
1. Wiring Levels:
Level 1 - High Noise Susceptibility Application
1. 4 - 20 mA, 24 VDC instrument signals, other analog < 50 VDC and digital process transmitters
2. Discrete, 24 VDC instrument signals
3. +/- 50 VDC and common buses feeding analog instrument signals
4. +/- 24 VDC and common buses feeding digital instrument signals
5. Thermocouple and RTD circuits
6. Telephone circuits
Level 2 - Medium Noise Susceptibility Application
1. Light and switching circuits 24 VDC or less
2. Analog signals > 50 VDC < 28 VAC ripple
Level 3 - Low Noise Susceptibility Application
1. 120/240 VAC feeders < 20 amps
2. Light and switching circuits 24 VDC or greater
3. 120/240 VDC relay, contactor and circuit breaker coils < 20 amps
4. Analog signals > 50 VDC < 28 VAC ripple
Level 4 - Medium Power Application
1. Primaries and secondary of transformers > 5 KVA
2. AC and DC buses 0 - 800 volts with currents > 20 amps
Level 5 - High Power Application
1. AC and DC buses > 1 kW or currents > 800 amps, or both
2. This table is based on IEEE 518.
3. This table does not apply to the use of non-metallic conduit.
4. Cable tray spacing is defined as the minimum distance (in inches) between the top of one tray and the bottom of the tray above or
between the sides of adjacent trays. This spacing also applies to the distance between trays and power equipment less than 100
KVA.
Conduit spacing is defined as the minimum distance (in inches) between the outside surfaces of conduits. This spacing also
applies to the distance between conduits and power equipment less than 100 KVA.
5. When unlike signal levels must cross, in trays they shall cross at 90-degree angles. Where it is not possible to maintain spacing,
a grounded metal barrier should be placed between unlike levels at the crossover point.
6. Levels 3 and 4 may be run in a common tray if separated by a barrier.
7. When separate trays are impractical, Levels 1 and 2 may be combined in a common tray, provided a grounded metal barrier
separates the levels.
8. Trays for all levels were based on metal, solidly grounded, with good ground continuity.
9. Only cables having the same voltage class (Table 1) may be run together.
10. Trays and conduits containing Levels 1 and 2 shall not be routed parallel to high-power equipment enclosures of 100 KVA and
larger at a spacing of less than 5 feet for trays and 2-1/2 feet for conduit.
11. Where the spacing listed in Table 2 is difficult to maintain, parallel runs should be minimized and in no case be run parallel to
each other for a distance greater than 5 feet.
8. Terminations
8.1 General
8.1.1 All field instruments wiring shall be landed on terminal strips in field junction
boxes. See NEC Article 110-14. Devices with attached pigtails may be spliced
in conduit fittings with Owner’s approval. See
NEC Article 370-16.
8.1.2 Individual circuit wires shall not be spliced.
8.1.3 Connections to terminal strips shall be limited to two wires per screw. If the
wires are solid or ferruled, then only one wire shall be connected per screw.
8.1.4 When terminating lugs are used on stranded wire, they shall be of the locking
type and limited to their design capability (i.e., two wires maximum per lug).
8.1.5 Terminal shall be tightened to the torque required by manufacturer.
8.1.6 All wires (including spares and shield drain wires) of each cable shall be
landed on both ends in continuous order on terminals, dressed out neatly, and
labeled.
8.1.7 Overall cable shield drain wires and individual pair shields shall be grounded
to the IGB in the instrument building in which the cables terminate. Grounded
thermocouples shall be installed per
Section 8.5 with shield wire grounded in thermocouple head.
8.1.8 All wire pairs, triads, and cables (including spares) used to connect instrument
components and systems shall have uniform identification labels on each wire
and cable at each point of termination.
9.1 General
9.1.1 Control system instrument power requirements generally shall be 120 VAC
and/or 24 VDC. Use of other voltages requires Owner’s approval.
9.1.2 AC power for instrument systems and supervisory control computers shall be
supplied from UPS. The UPS shall be supplied from both a primary and a
secondary power source.
9.1.3 For a typical power distribution system for the BPCS and SIS that requires a
UPS, see Figure 1.
9.1.4 Alarms shall be installed in the control room to indicate:
a. The loss of the secondary source
b. A transfer to the secondary source
c. UPS trouble
d. UPS on batteries
e. Low-battery alarm
9.1.5 A dedicated isolation instrument power transformer shall be provided for UPS
bypass power.
9.1.6 The instrument power system shall be separate and distinct from non-critical
circuits such as heating and lighting.
9.1.7 Operating time capability (power from batteries of UPS) required after the
total outage of AC supply power shall be set by the Owner considering unit
response time and needs of units served.
Comment: A minimum of 30 minutes is a typical time for instrument
systems power backup. Where additional time is required,
consideration should be given to a backup generator as a
secondary source for UPS.
9.1.8 Provisions for testing the UPS with process running shall be provided.
9.2.5 Design and installation of the neutral wire shall satisfy the following
requirements:
Grounding: The main bonding jumper at the derived source or the first panel
downstream of the derived source establishes the AC neutral
ground point. All circuit neutral wiring shall be insulated.
Color Coding: Neutral wires shall be white except when there is more than
one, in which case, each shall be color coded to satisfy
NEC Article 210.5.
Splicing: Splicing of the neutral wire is prohibited except when necessary
at a field device.
Connection: The neutral wire connected to a device shall always be the one
assigned to the source that serves that device, never one from
some other circuit source.
10. Grounding
10.1 Grounding electronic systems (e.g., BPCS, SIS, and Programmable Logic Controller
(PLC)) shall follow the criteria below and the manufacturer’s recommendations. Any
deviation shall be reviewed by the manufacturer’s technical representative and
approved by Owner. See Figure 1 (INSTGND001).
10.2 Two grounding systems shall be required in the control room or instrument building:
a. AC Safety Grounding for personnel safety
b. IGB for signal reference
The IGB and AC Safety Grounds shall join electrically at a single point near a high-
quality earth ground (IEEE 1100, API RP 552, and Figure 1).
10.3 All electrical equipment shall be grounded to the AC Safety Ground for personnel
protection to satisfy NEC Article 250.
10.4 The IGB wiring shall be installed to provide a stable voltage reference. The grounding
system(s) should provide ground resistance level(s) consistent with supplier
recommendations and should meet the NEC requirements.
10.5 Ground systems shall be installed to provide a ground system that meets vendor
requirements. Since various suppliers have different grounding requirements, care
must be taken to develop a scheme that meets those requirements, meets the NEC
requirements, has testing capabilities, and has supplier approval. (See IEEE 1100.)
Comment: A removable link may be provided between the AC Safety Ground and
the IGB to allow testing of the IGB.
10.6 All IGB bars, plates, and wire shall be isolated from building AC Safety Ground path
except at the one point specified in Section 10.2 above.
10.7 The following signal and equipment connections shall be made to the IGB:
a. Instrument power supplies (negative leads)
b. BPCS, PLC, SIS, and other control modules (signal common, logic ground,
network ground, etc.)
c. Instrument (individual and overall cable) shields
10.8 Signals originating from instruments powered by sources external to the control
building (e.g., a chromatograph in an analyzer building) often are electrically
referenced to another ground potential. These instruments shall have isolated outputs,
or the output signals shall be electrically isolated when brought into the BPCS, PLC,
SIS, and other control modules.
10.9 Ground loops shall be avoided.
Comment: Ground loops exist when extraneous, unwanted currents flow in a wire
causing an offset in the instrument reading. Care must be taken to
avoid multiple grounds.
Comment: When instrumentation wiring is of the shielded type, shields should be
grounded at only one place.
12.2 All non-incendive wiring shall be installed in accordance with NEC Article 500-4(f)
and ISA RP 12.12.
All control panels, consoles, and equipment cabinets shall be wired in accordance with
PIP PCSCP001.
14. Installation
Primary and backup data highway cables shall follow different routing and preferentially
enters buildings and/or enclosures from opposite sides.