TABLERO CEG CC206S

No. DE Carga Watts SISTEMA A UTILIZAR Corriente Corriente X Corriente Ic

F.T. F.A.
Voltaje ITM

1.25 0.91 0.8


CTO. 162 W 162 W FASES HILOS Inom

1 4 2 972 1 2 127 8.50 10.63 0.91 0.80 14.60 1P - 15


2 5 810 1 2 127 7.09 8.86 0.91 0.80 12.17 1P - 15
TOTAL 9 2 1782 2 3 220 9.00 11.25 0.91 0.80 15.45 2P - 15
CONDUCTOR CONDUCTOR DE Longitud Caida de

WATTS

PUESTA A TIERRA

EN mm EN AWG. EN mm EN AWG. Tension A B

3.31 12 2.08 1-14d 30 2.43 972


3.31 12 2.08 1-14d 25 1.69 810

3.31 12 2.08 1-14d 0.00 972 810

FASE MAYOR 972


FASE MENOR 810
DESBALANCE 16.67%
TABLERO CNG CC412PQO
No. DE Carga Watts SISTEMA A UTILIZAR Corriente Corriente X

TAB CNPB TAB CN1 TAB CN2 TAB CN3 F.T.


Voltaje

1.25 0.91
CTO. 162 W 3888 W 3078 W 2430 W 4536 W FASES HILOS Inom

1-3 1 4536 2 3 220 22.909091 28.636364 0.91


2
4-6 1 2430 2 3 220 12.272727 15.340909 0.91
5-7 1 3078 2 3 220 15.545455 19.431818 0.91
8
9-11 1 3888 2 3 220 19.636364 24.545455 0.91
10
12 6 972 1 2 127 8.50 10.63 0.91

TOTAL 6 1 1 1 1 14904 3 4 220 43.46 54.32 0.91


Corriente Ic CONDUCTOR CONDUCTOR DE Longitud Caida de

F.A. WATTS
ITM
PUESTA A TIERRA

0.8
EN mm EN AWG. EN mm EN AWG. Tension A B C

0.8 39.335664 2P - 30 8.37 8 5.26 1-10d 0 0 2430 2106

0.8 21.072677 2P - 20 3.31 12 3.31 1-12d 0 0 1458 972


0.8 26.692058 2P - 20 5.26 10 3.31 1-12d 0 0 1458 1620

0.8 33.716284 2P - 30 8.37 8 5.26 1-10d 0 0 1620 2268

0.80 14.60 1P - 15 3.31 12 2.08 1-14d 11 0.89 972


0.80 74.62 3P - 60 33.62 2 5.26 1-10d 0.00 4860 5184 4860

FASE MAYOR 5184


FASE MENOR 4860
DESBALANCE 6.25%
TABLERO CNPB CC104EN
No. DE Carga Watts SISTEMA A UTILIZAR Corriente Corriente X Corriente Ic

F.T. F.A.
Voltaje ITM

1.25 0.91 0.8


CTO. 162 W 162 W FASES HILOS Inom

1 7 3 1620 1 2 127 14.17 17.72 0.91 0.80 24.34 1P - 20


2 3 3 972 1 2 127 8.50 10.63 0.91 0.80 14.60 1P - 15
3 5 3 1296 1 2 127 11.34 14.17 0.91 0.80 19.47 1P - 20
TOTAL 15 9 3888 2 3 220 19.64 24.55 0.91 0.80 33.72 2P - 30
CONDUCTOR CONDUCTOR DE Longitud Caida de

WATTS

PUESTA A TIERRA

EN mm EN AWG. EN mm EN AWG. Tension B C

3.31 12 3.31 1-12d 18 2.43 1620


3.31 12 2.08 1-14d 16 1.29 972
3.31 12 3.31 1-12d 13 1.40 1296

8.37 8 5.26 1-10d 0.00 1620 2268

FASE MAYOR 2268


FASE MENOR 1620
DESBALANCE 28.57%
TABLERO CN1 CC104EN
No. DE Carga Watts SISTEMA A UTILIZAR Corriente Corriente X Corriente Ic

F.T. F.A.
Voltaje ITM

1.25 0.91 0.8


CTO. 162 W 162 W FASES HILOS Inom

1 8 1 1458 1 2 127 12.76 15.94 0.91 0.80 21.90 1P - 20


2 7 3 1620 1 2 127 14.17 17.72 0.91 0.80 24.34 1P - 20
TOTAL 15 4 3078 2 3 220 15.55 19.43 0.91 0.80 26.69 2P - 20
CONDUCTOR CONDUCTOR DE Longitud Caida de

WATTS

PUESTA A TIERRA

EN mm EN AWG. EN mm EN AWG. Tension A C

3.31 12 3.31 1-12d 19 2.31 1458


3.31 12 3.31 1-12d 16 2.16 1620

5.26 10 3.31 1-12d 0.00 1458 1620

FASE MAYOR 1620


FASE MENOR 1458
DESBALANCE 10.00%
TABLERO CN2 CC104EN
No. DE Carga Watts SISTEMA A UTILIZAR Corriente Corriente X Corriente Ic

F.T. F.A.
Voltaje ITM

1.25 0.91 0.8


CTO. 162 W 162 W FASES HILOS Inom

1 4 5 1458 1 2 127 12.76 15.94 0.91 0.80 21.90 1P - 20


2 4 2 972 1 2 127 8.50 10.63 0.91 0.80 14.60 1P - 15
TOTAL 8 7 2430 2 3 220 12.27 15.34 0.91 0.80 21.07 2P - 20
CONDUCTOR CONDUCTOR DE Longitud Caida de

WATTS

PUESTA A TIERRA

EN mm EN AWG. EN mm EN AWG. Tension B C

3.31 12 3.31 1-12d 19 2.31 1458


3.31 12 2.08 1-14d 16 1.29 972

3.31 12 3.31 1-12d 0.00 1458 972

FASE MAYOR 1458


FASE MENOR 972
DESBALANCE 33.33%
TABLERO CN3 CC206S
No. DE Carga Watts SISTEMA A UTILIZAR Corriente Corriente X Corriente Ic

F.T. F.A.
Voltaje ITM

1.25 0.91 0.8


CTO. 162 W 162 W FASES HILOS Inom

1 5 3 1296 1 2 127 11.34 14.17 0.91 0.80 19.47 1P - 20


2 2 3 810 1 2 127 7.09 8.86 0.91 0.80 12.17 1P - 15
3 4 3 1134 1 2 127 9.92 12.40 0.91 0.80 17.04 1P - 15
4 7 1 1296 1 2 127 11.34 14.17 0.91 0.80 19.47 1P - 20
TOTAL 18 10 4536 2 3 220 22.91 28.64 0.91 0.80 39.34 2P - 30
CONDUCTOR CONDUCTOR DE Longitud Caida de

WATTS

PUESTA A TIERRA

EN mm EN AWG. EN mm EN AWG. Tension A B

3.31 12 3.31 1-12d 21 2.27 1296


3.31 12 2.08 1-14d 18 1.21 810
3.31 12 2.08 1-14d 10 0.94 1134
3.31 12 3.31 1-12d 13 1.40 1296

8.37 8 5.26 1-10d 0.00 2430 2106

FASE MAYOR 2430


FASE MENOR 2106
DESBALANCE 13.33%