Está en la página 1de 9

7C Switch Rack Assemblies Cl. I, Div.

1 & 2, Groups B, C, D Explosionproof


Cl. II, Div. 1, Groups E, F, G Dust-Ignitionproof
Cl. II, Div. 2, Groups F, G Raintight
Cl. III Wet Locations
NEMA 3, 4X, 7BCD, 9EFG, 12 Watertight

Applications:
Free-standing switch rack assemblies are
used:
• To provide a complete motor control
center in one integrated package
• Outdoors and indoors
• In damp, wet or corrosive locations such
as sewage treatment plants, lumber
mills, marine installations, and food
preparation areas
• In areas made hazardous due to the
presence of flammable vapors or gases,
such as petroleum refineries, chemical
and petrochemical plants, gas gathering
plants, pipeline compressor stations,
and drilling rigs, both onshore and
7C

offshore
• In areas where hazardous dusts are
present, such as coal handling facilities, Certifications and Standard Finishes:
grain processing and handling plants, Compliances: • Rack frame – hot dip galvanized steel
and certain food process industries or natural aluminum
• NEC:
Class I, Divisions 1 & 2, Groups C, D • Components – see sections A & C for
Features: (Group B optional) finishes
• Complete factory assembled and wired Class II, Division 1, Groups E, F, G
switch racks Class II, Division 2, Groups F, G Options:
• Pre-drilled bus boxes allow for quick Class III • Rack frame finish – corrosion resistant
and easy changing or adding of • NEMA: 3, 4X (optional), 7B (optional) CD, primer with air dry epoxy
components 9EFG, 12 • Options listed for individual components
• Complete assembly covered under one can be incorporated in complete switch
order, eliminates engineering costs, racks
additional costs of placing separate Standard Materials:
orders with several vendors for various • Rack frames – structural steel or
components, and assembly and aluminum channel members, bolted and
scheduling problems at job site welded
• Wiring is simple. After switch rack is in • Components – see sections A & C for
place, feeders are connected to the material
main bus and connections made from
starters motors. No other field wiring is
necessary
• Maintenance time and costs are
reduced by having controls grouped.
Work is performed in one location
instead of moving from one control to
another in various locations
• Major components are standard EBM,
EPC, NMC, NMG, NCB, FLB, D2PB,
EXD, D2D, EPL, and D2L enclosures
featuring ready access to starters and
breakers for inspection and maintenance
• Custom built racks to meet your exact
requirements are an Eaton's Crouse-
Hinds specialty. Complete quotations
will be supplied for any job, large or
small (38' length max)

614 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
Switch Rack Assemblies Cl. I, Div. 1 & 2, Groups B, C, D Explosionproof 7C
Cl. II, Div. 1, Groups E, F, G Dust-Ignitionproof
Cl. II, Div. 2, Groups F, G Raintight
Cl. III Wet Locations
NEMA 3, 4X, 7BCD, 9EFG, 12 Watertight

Construction: Rack Frame Design: Main Bus Equipment:


General: Structure: Class I, Division 1:
• All construction to be in accordance with • Switch rack, either single or double face • Main bus material shall be copper only
current National Electrical Code® (NEC), as required, shall be rigid, free-standing and capable of withstanding up to 65K
National Electrical Manufacturers' structures. Racks shall be factory- amps fault current. Cable bus will be
Association (NEMA), state and local welded, assembled and fabricated from wired to terminal blocks enclosed in
standards as designated by the standard rolled structural steel or cast, copper-free aluminum,
purchaser. aluminum shapes. explosionproof junction boxes, Eaton's
• All hazardous area enclosures for motor • Vertical risers will be 6" I-beam and Crouse-Hinds type EJB. Such junction
starters, combination motor starters, horizontal members shall be 6-inch boxes for incoming power and
circuit breakers, motor circuit protectors, channel. distribution wiring shall be provided at
instrument enclosures, panelboards, • Mounting feet shall be 6-inch channel. either the top or bottom of the rack.
main bus, fittings, receptacles, and Width of such feet for single-sided racks Enclosures shall be connected by rigid
lighting fixtures shall be made and shall be 41 inches. conduit with conduit seals installed in
supplied by the manufacturer. accordance with the NEC. Load conduit
• End mounting feet will be braced or cable will leave rack either below or
• All explosionproof threaded enclosures (welded) to the upright with 6" T

7C
for combination starters, circuit breakers, above. Manufacturer shall provide
member. conduit layouts.
motor circuit protectors, and starters • Mounting feet shall be anchored at the
shall be UL classified. Class I, Division 2:
job site with 1-inch diameter bolts.
• All other standard hazardous area Anchor bolts and mounting pads will be • Main bus material shall be copper only
enclosures shall be UL listed or UL the responsibility of the user. and capable of withstanding up to 65K
classified. amps fault current. Cable bus will be
• Maximum horizontal spacing between wired to terminal blocks enclosed in
• Manufacturer shall retain permanent mounting legs shall not exceed 6 feet.
records of all motor control racks and cast, copper-free aluminum
(Specific dimensions to be determined weathertight junction boxes, Eaton's
shall have the capability of duplicating, by the manufacturer.)
or replacing, any fully-assembled rack or Crouse-Hinds type WJB. Such junction
• Racks longer than 20 feet will be boxes for incoming power and
rack component. supplied as bolt-together sections. distribution wiring shall be provided at
• Manufacturer to assume responsibility (Specific section dimensions to be either the top or bottom of the rack.
for construction, purchase/manufacturer determined by the manufacturer.) Enclosures shall be connected by rigid
of components, complete circuit
continuity testing, and testing of Grounding: conduit with conduit seals installed as
required by the NEC. Load conduit or
mechanical functions of components. • A pressure-type grounding lug with cable will leave rack either below or
appropriate wire capacity will be above. Manufacturer shall provide
provided at each end of frame. conduit layouts.
Finish:
• Rack frame shall be hot-dip galvanized
after fabrication or natural aluminum.
Bus Duct in Lieu of
Junction Boxes (Optional):
• Cable bus will be wired to a
weathertight bus duct provided at the
top or bottom of the rack.

Canopy (Optional):
• Single- or double-pitched canopy shall
have minimum 15-degree pitch with a
minimum 7'6" ground clearance, and 2-
foot overhang. Roofing material shall be
corrugated aluminum. Canopy roof
trusses, cross channels, roof material,
and mounting hardware shall be
shipped unassembled for quick
assembly at the job site. All holes in
structure shall be provided except for
roof mounting holes which will be drilled
in the field. Manufacturer will supply
drawings and material for complete field
assembly of canopy.

Eaton's Crouse-Hinds switch rack installed in a fuel storage area.

www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business 615
7C Switch Rack Assemblies

Motor Control • All enclosures shall be fitted, as • Motor starter overload reset operating
standard, with adjustable, extended, mechanisms shall be field adjustable.
Components: corrosion-resistant, copper-free • Threaded construction enclosures shall
Explosionproof Quick Opening aluminum hinges that shall allow the be Eaton's Crouse-Hinds type EPC,
Enclosures: cover to swing away from the body Underwriters Laboratories, Inc. classified
• All circuit breakers, motor circuit when opened and shall permit for use in Class I, Groups C, D, Divisions
protectors and combination or across- unobstructed working space for 1 and 2, Class II, Groups E, F, G
the-line motor starters shall be enclosed maintenance, adjustment or replacement Divisions 1 and 2 and Class III
in quick-opening enclosures (Eaton's of the internal apparatus. Additionally hazardous locations and shall also be
Crouse-Hinds types EBM or EPC). these hinges shall allow minimum suitable for Type 3, 3R and/or Type 4
enclosure-to-enclosure spacing with (NEMA 3, 3R and 4) areas.
Types: little interference between an open cover
• Ground joint bolted cover enclosure • All enclosures shall be cast of a
and an adjacent enclosure. Enclosures corrosion-resistant copper-free
shall be Eaton's Crouse-Hinds type with hinges fabricated from steel or
EBM, Underwriters Laboratories Inc. aluminum alloy (less than 0.4% copper)
aluminum stampings shall not be and shall be of a three section design.
classified for use in Class I, Groups C, permitted.
D, Divisions 1 and 2, Class II, Groups E, Multiple-start straight buttress threads
• All enclosures shall be provided with between the covers and the body shall
7C

F, G, Divisions 1 and 2 and Class III


drilled, tapped and plugged conduit ensure quick access to the interior in
hazardous locations and shall also be
entrances suitably sized for the electrical less than two full turns of the covers. A
suitable for Type 3, 3R and/or Type 4
application. Power conduit entrances system of stops shall prevent
(NEMA 3, 3R and 4) areas.
shall be located 1 (or 2) each on (or overtightening and thread seizing. A
• All enclosures shall be cast of a equally spaced from) the enclosure system of locks shall prevent covers
corrosion-resistant copper-free vertical centerline at top and bottom. A from loosening due to external vibration.
aluminum alloy (less than 0.4% copper) single, plugged 1" entrance for a control
and shall be of a semi clamshell design • Female threads on the top cover with
conduit shall be provided at the bottom male threads on the bottom cover shall
with external flange to promote ease of of the enclosure. (Some enclosures can
apparatus installation, adjustment and ensure inherent water and rain shedding.
also be provided with a plugged 1"
maintenance. Most importantly, entrance for control conduit at the top.) • All exposed screws, bolts and hardware
enclosure inside dimensions shall shall be stainless steel.
• All conduit entrances shall be furnished
conform to the wire bending space • The external circuit breaker operating
with removable copper-free aluminum
requirements of the National Electrical handle affixed to a stainless steel shaft,
reducers, each with integral wire pulling
code NFPA70 paragraph 373-6. shall be padlockable in either the "ON"
bushing. All conduit entrances shall be
Enclosures with flat covers, internal or "OFF" position with up to three
located the same distance from the
flanges or those not conforming to padlocks. Circuit breaker mechanisms
enclosure mounting surface to facilitate
NFPA70 paragraph 373-6 are not shall be trip-free of the circuit breaker
conduit run layout and/or stub up
permitted. itself to allow the circuit breaker to open
construction.
• Covers shall be hinged on the left side under overload conditions even if it is
• All enclosures shall have rugged, cast locked in the "ON" position.
and, when closed, shall be affixed top
copper-free aluminum circuit breaker
the body by multiple lead thread bolts to • The mounting bracket shall provide a
and motor starter overload reset
promote quick opening and closing of three-point suspension system for quick
operating handles located on the right
the enclosure. installation and adjustment.
side of the enclosure. These handles
• Cover bolts shall be hex head stainless shall operate the internal mechanisms • Conduit entrances shall have integral
steel without screwdriver slots, to via stainless steel, gasketed shafts and wire pulling bushings and conduit stops.
promote the use of a socket or wrench bearings through the side wall of the These openings shall be arranged two at
for proper tightening. They shall be body. Correct circuit breaker and the top and two at the bottom and shall
captive to the cover and stainless steel overload reset operation shall be visually be sized for power and control
spring loaded to indicate the fully confirmed with the cover open. requirements.
unthreaded position. Spring loading shall
• Circuit breaker handles shall be
give visual indication that the bolts are
free of the body when the cover is being
padlockable in either the "OFF" or "ON" General:
position, and shall be trip-free of the • All enclosures shall be bolted to the
opened. The cover flange ground joint
circuit breaker itself. An attached horizontal frame members on either the
shall have an integeral gasket to prevent
indicating plate shall give clear, visual front or back or both front and back.
the entry of windblown dust, rain or
confirmation of the circuit breaker Enclosures shall be connected to the
sleet.
status. main bus via conduit seals. (To be field
• Adjustable circuit breaker handle stops poured). All hardware used to mount the
shall be provided to ensure full operation enclosures shall be stainless steel.
of the circuit breaker and to prevent
handle overthrow that could damage the
circuit breaker toggle.

616 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
Switch Rack Assemblies 7C

Lighting Panelboards: Conduit Boxes, Outlet Wiring:


Class I, Division 1: Boxes, Device Boxes: • Standard wire shall be copper only,
• Panelboards shall be Eaton's Crouse- • Conduit boxes, outlet boxes, and device 600 volt, 75°C minimum rating, UL
Hinds type, factory-sealed EXD or EPL boxes shall be Eaton's Crouse-Hinds listed.
as specified and shall meet the following Condulet® fittings. • No power wire less than 12AWG
electrical ratings: shall be used.
Seals:
EPL – 1, 2 or 3 pole, 240 volt maximum, • Seals will be standard Eaton's Crouse- • Control wire shall be 14AWG
100 amp maximum branch trip rating, Hinds type Condulet EYS. (Eaton's minimum, 7 strands, THW
10,000 AIC. Crouse-Hinds Condulet EYD drains to minimum.
EXD – 1, 2 or 3 pole, 600 volt be specified as required.) • Wiring shall be sized in accordance
maximum, 100 amp maximum branch with the NEC requirements.
Unions:
trip rating.
• Unions will be Eaton's Crouse-Hinds
Class I, Division 2: UNY. Drawings:
• Lighting panelboard shall be Eaton's • Standard drawings supplied for
Breathers and Drains:
Crouse-Hinds type D2L factory-sealed, customer approval shall include
120 / 240 volt panelboards and be • Breathers and drains shall be Eaton's

7C
Crouse-Hinds ECD. complete rack wiring diagram,
provided with single-pole, two-pole, or component data, nominal weight of
three-pole branch circuit breakers with the rack, and overall rack
up to 100 amp trip rating; main breaker dimensions.
ranging to 225 amp. Similarly, lighting
panelboard shall be type D2PB factory-
sealed, 120 / 240 volt panelboards and
be provided with single-pole or two-pole
factory sealed circuit breakers with 15,
20 or 30 amp trip ratings and maximum
10,000 AIC. Power panelboards type
D2D factory-sealed, up to 600 volt are
provided with single-pole, two-pole, or
three-pole branch circuit breakers with
up to 100 amp trip ratings; main breaker
rating to 225 amp.

NEMA 4X Option:
• All bus boxes, control enclosures and
lighting panelboards will be made of
KRYDON® material to meet NEMA 4X
requirements.

Fittings:
• All fittings shall be made and provided
by the manufacturer. Seals and unions
will be provided for each incoming and
outgoing conduit as required. All
interconnections between components
shall be done by the manufacturer with
galvanized rigid conduit, and conduit
fittings as required to meet the
hazardous classification. Interconnecting
conduits to be provided with conduit
seals as required. All incoming and
outgoing rack conduit entrances shall
include conduit seals as required by the
hazardous location specified. Such seals
will be provided by the manufacturer and
will not be filled where field wiring is to
be introduced.

www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business 617
7C Bus Duct (Termination Box) NEMA 3R
Up to 600 Volts
Assemblies

Applications: Features:
• Eaton's Crouse-Hinds is now offering NEMA 3R, UL Listed Bus • UL Listed.
Duct (Termination Box) Assemblies as standard product. Up to • NEMA 3R.
600V, three-phase, 3 or 4 wire, 400Amp or 600Amp service with • Maximum voltage rating 600V.
short circuit ratings of 25K or 50K.
• 400 Amp or 600 Amp @ 25KAIC or 50KAIC.
• Bus ducts or termination boxes provide a means of tapping feeder
circuits for power distribution on outdoor switchrack assemblies • External flange on bus duct enclosure and lip on covers prevents
or indoor wall-mounted applications. water leakage and allows covers to hang freely for ease of
installation and maintenance.
• Typical application is primarily for bus replacements on existing
switchrack installations. New applications may include on-site • 3 degree pitch at top, for water run-off, on all flush mounted
construction of switchracks or indoor feeder distribution points bottom entry designs.
due to space confinements making local installation more • Chorosulfonated polyethlene (Hypalon®) gasket material at all bus
practical. box section joints, covers and end plates.
• Standoff (Glastic) insulators molded of (UL) recognized flame-
resistant fiberglass-reinforced thermoset polyester molding
compound.
7C

• Bus bar sizing and bracing complies to UL857 requirements.


• All welded construction - sheet aluminum, sheet steel (galvanized),
or stainless steel.
• Stainless steel hardware throughout.
• Two hole compression lugs at all power phase connectors
attatched with stainless steel hardware.
• One (1) drain is standard per bus duct section (typical 4 foot
sections).
• Solid copper bus bars (tin, silver plated and/or insulated – optional
per customer request).
• Solid copper ground bar – standard.
• Incoming main lugs – supplied size and location specified with
customer.
• Space heaters – optional per customer request.
• Pre-drilled copper bars (when specified by customer).
• Conduit entries for Myers hubs – optional per customer request.

618 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
Bus Duct (Termination Box) 7C
Catalog Numbering System

7C

For pricing and lead times, contact Eaton's Crouse-Hinds Customer Service at 866-764-5454 or fax to 315-477-5179.

www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business 619
7C Switch Rack Assemblies Cl. I, Div. 1 & 2, Groups B, C, D Explosionproof
Cl. II, Div. 1, Groups E, F, G Dust-Ignitionproof
Cl. II, Div. 2, Groups F, G Raintight
Cl. III Wet Locations
Selection Guide NEMA 3, 4X, 7BCD, 9EFG, 12 Watertight
7C

620 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business
Switch Rack Assemblies Cl. I, Div. 1 & 2, Groups B, C, D Explosionproof 7C
Cl. II, Div. 1, Groups E, F, G Dust-Ignitionproof
Cl. II, Div. 2, Groups F, G Raintight
Cl. III Wet Locations
Selection Guide NEMA 3, 4X, 7BCD, 9EFG, 12 Watertight

7C

‡ Not available with D2PB panelboards.

www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business 621
7C Switch Rack Assemblies Cl. I, Div. 1 & 2, Groups B, C, D Explosionproof
Cl. II, Div. 1, Groups E, F, G Dust-Ignitionproof
Cl. II, Div. 2, Groups F, G Raintight
Cl. III Wet Locations
Selection Guide NEMA 3, 4X, 7BCD, 9EFG, 12 Watertight
7C

622 www.crouse-hinds.com US: 1-866-764-5454 CAN: 1-800-265-0502 Copyright© 2013 Eaton’s Crouse-Hinds Business