Está en la página 1de 36

ANSI/IEEE C37.20.

1-1987

metal-enclosed low-voltage
power circuit-breaker switchgear

June 29. 1987 SHlo&A7


ANSI / IEEE C37.20.1-1987

An American National Standard


IEEE Standard for
Metal-Enclosed Low-Voltage
Power Circuit-Breaker Switchgear

Sponsor
Switchgear Committee of the
IEEE Power Engineering Society

Secretariat
Institute of Electrical and Electronics Engineers
National Electrical Manufacturers Association

Approved September 22, 1983


IEEE Standards Board

Approved August 7, 1986


American National Standards Institute

@ Copyright 1987 by

The Institute of Electrical and Electronics Engineers, Inc


345 East 47th Street, New York, NY 10017, USA
---
No part of this publication m a y be reproduced in a n y form,
in a n electronic retrieval system or otherwise,
without the prior written permission of the publisher.
IEEE Standards documents are developed within the Technical Com- .
mittees of the IEEE Societies, and the Standards Coordinating Committees
of the IEEE Standards Board. Members of the committees serve volun-
tarily and without compensation. They are not necessarily members of the
Institute. The standards developed within IEXE represent a consensus of
the broad expertise on the subject within the Institute as well as those
activities outside of IEEE which have expressed an interest in participating
in the development of the standard.
Use of an IEEE Standard is wholly voluntary. The existence of an IEEE
Standard does not imply that there are no other ways to produce, test,
measure, purchase, market, or provide other goods and services related
to the scope of the IEEE Standard. Furthermore, the viewpoint expressed
at the time a standard is approved and issued is subject to change brought
about through developments in the state of the art and comments received
from users of the standard. Every IEEE Standard is subjected to review
at least once every five years for revision or reaffirmation. When a doc-
ument is more than five years old, and has not been reaffirmed, it is
reasonable to conclude that its contents, although still of some value, do
not wholly reflect the present state of the art. Users are cautioned to
check to determine that they have the latest edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any in-
terested party, regardless of membership affiliation with IEEE. Sugges-
tions for changes in documents should be in the form of a proposed change
of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the mean-
ing of portions of standards as they relate to specific applications. When
the need for interpretations is brought to the attention of IEEE, the
Institute will initiate action to prepare appropriate responses. Since IEEE
Standards represent a consensus of all concerned interests, it is important
to ensure that any interpretation has also received the concurrence of a
balance of interests. For this reason IEEE and the members of its technical
committees are not able to provide an instant response to interpretation
requests except in those cases where the matter has previously received
formal consideration.
Comments on standards and requests for interpretations should be ad-
dressed to:
Secretary, IEEE Standards Board
345 East 47th Street
New York, NY 10017
USA
Foreword
("his Foreword is not a part of ANSI/IEEE C37.20.1-1987,
IEEE Standard for Metal-Enclosed Low-Voltage Power Circuit
Breaker Switchgear.)

This standard includes only the requirements for metalenclosed low-voltage power circuit-breaker
switchgear. These requirements were previously a part of ANSI / IEEE C37.20-1969 (R 19811, IEEE
Standard for Switchgear Assemblies Including Metal-Enclosed Bus (1974 Consolidated Edition). Other
types of equipment previously included in ANSI / IEEE C37.20-1969 (R 1981), will now be incorporated
in separate publications.
ANSI / IEEE C37.20 has for many years covered all switchgear assemblies including metal-enclosed
bus. Standards committees of IEEE Switchgear Assemblies Subcommittee and NEMA Power Switch-
gear Assemblies Technical Committee recommended that the document be further developed and,
where appropriate, the various sections be identified with their own standards. This approach also
identifies with the Conformance Test Procedure Standards.
This edition was prepared by the Power Switchgear Assemblies Technical Committee, National
Electrical Manufacturers Association (NEMA). NEMA is responsible for Section 4, Ratings and Section
6, Construction.
The Switchgear Assemblies Subcommittee of the IEEE Switchgear Committee is responsible for
Section 2, Definitions, Section 3, Service Conditions; Section 5, Tests; Section 7, General Application
Conditions; and Section 8, Handling, Storage, and Installation.
A working group of the NEMA Power Switchgear Assemblies Technical Committee revised ANSI /
IEEE C37.23-1970, IEEE Guide for Calculating Losses in Isolated-Phase Bus, to include Section 8 of
ANSI / IEEE C37.20, Metal-Enclosed Bus. The document updates the material for metalenclosed
conductors including cable bus. The IEEE Switchgear Assemblies Subcommittee refined and expanded
the document.
The following documents were developed for each product type based on ANSI / IEEE C37-20 (see
Fig A).
C37.20.1 Metal-Enclosed Low-Voltage Power Circuit-Breaker Switchgear (lo00 V and Below)
C37.20.2 Metal-Clad and Station-Type Cubicle Switchgear (Above 1000 V)
C37.20.3 Metal-Enclosed Interrupter Switchgear (Above 1000 V)
C37.21 Control Switchboards
C37.23 Metal-Enclosed Bus and Guide for Calculating Losses in Isolated Phase Bus
Through this joint effort over the many years, the switchgear assemblies standards have been of
extreme value to the industry and further suggestions for improvement gained in the use of this
standard will be welcomed.
The Standards Committee on Power Switchgear, C37, which reviewed and approved this standard
had the following personnel at the time of approval:
W.E. Laubach, Chairman Charles H. White, Secretary

W.N. Rothenbuhler, Executive Vice-chairman of High-Voltage Switchgear Standards


S. H. Telender, Executive Vice-chairman of Low- Voltage Switchgear Standards
D. L. Swindler, Executive Vice-chairman of IEC Activities
Organization Represented Name of Representative
Association of American Railroads.. ................................................... Vacant
Association of Iron and Steel Engineers.. .............................................. J. M.Tillman
Electric Light and Power Group ....................................................... D. 0. Craghead
R. L. Capra (AW
D. A. Ditzler (Alt)
K. D. Hendrk
David E. Soffrin (Alt)
T.D. Weston
J. H. Provanzana (A2t)
Organization Represented Name of Representative

Institute of Electrical and Electronics Engineers. ........... ........................ H. W. Mikulecky


M. J. Beachy (Alt)
G. R. Hanks
R. P. Jackson (Alt)
E. W. Schmunk
C. A. Schwalbe
C. E. Zanzie
National Electrical Manufacturers kssociation.. ........................................ G. A. Wilson
R. 0. D. Whitt
T. L. Fromm
R. A. McMaster
Tennessee Valley Authority.. ......................................................... Robert C. St. Clair
Testing Laboratory Group.. ........................................................... L. Frier
W. T. OGrady
R. W. Seelbach (Alt)
US Department ofthe Army .......................................................... H. K. Snyder
US Department of the Interior, Bureau of Reclamation ................................. R. H. Auerbach
US Department of Defense, Defense Communications Agency.. .......................... Vacant
US Department of the Navy, Naval Construction Battalion Center.. ..................... R. L. Clark
Western Area Power Authority.. ...................................................... G. D.Birney

The Switchgear Assemblies Subcommittee of the IEEE Switchgear Committee that prepared and
approved this standard had the following personnel:

S. C. Atkinson, Chairman
A. Alsaker H. G. Frus J. Rule
C. Burland J. Joannou J. C. Scott
A. P. Colaiaw A. J. Kalvaitis J. F. Sellers
J. J. Dravis W.E. Laubach S.D. Smith
R. P. Ehas J. J. Mikw E. M. Spencer
F. C. Farrell M. Olender S. H. Telander
G. 0. Perkins

The Power Switchgear Assemblies Technical Committee of the NEMA Switchgear Section that
prepared and approved this standard had the following personnel:

S. H. Telender, Chairman C. White, Secretary


M. Boyle J. Laughlin
E. Dvorak R. K. Leidy
K. Hanke M. Shepnew
H. Hornhorst D. Swindler
W. E. Laubach C. L. Welter
h
The following persons were on the balloting committee that approved this document for submission
to the IEEE Standards Board.
A. K. A l d e r G. R. Hanks D.C. Mills
J. G. Angelis W. E. Harper G. 0. Perkins
R. H. Arndt K. D.Hendrix C. A. Popeck
J. E. Atkinson E. J. Huber J. C. W. Ransom
J. E. Beehler W. C. Heuning A. B. Rishworth
F. L. Cameron W. B. Kelly H. C. Ross
L. V. Chabala P. L: Kolarik W. N. Rothenbuhler
A. P. Colaiaco S.R. Lambert G. G. Schockelt
J. J. Dravis D.M. Larson C. A. Schwalbe
J. L. Drown W. E. Laubach J. C. Scott
C. J. Dvorak T. S.Lauber E. M. Spencer
R. P. Ehas G. N.Lester H. Swanson
F. C. Farrell E. L. Luehring G. H. Taylor
J. D.Finley P. c. Lyons S.H. Telender
R. E. Friedrich M. J. Maier F. C. Teufel
G. B. Fritz J. A. Maneatis J . R. Truitt
H. G. Frus J. R. Marek C. L. Wagner
G. Genest L. V. McCall G. A. Wilson
W. F. Giles W. C. McKay W. R. Wilson
G. P. Gill R. A. McMaster B. F. Wirtz
R. D.Hambrick H. W. Mikulecky C. E. Zanzie

When the IEEE Standards Board approved this standard on September 22,1983, it had the following
membership:

James H. Beall, Chairman Edward Chelotti, Vice Chairman


Sava I. Sherr, Secretary
J . J. Archambault Donald N.Heirman John P. Riganati
John T. Boettger Irvin N. Howell Frank L. Rose
J. V. Bonucchi Joseph L. Koepfinger* Robert W. Seelbach
Rene Castenschiold Irving Kolodny Jay A. Stewart
Edward J. &hen George Konomos Clifford 0. Swanson
Len S.Coreyt R. F. Lawrence Robert E. Weiler
Donald C. Fleckenstein John E. May W. B.Wilkens
Jay Forster Donald T. Michael. Charles J. Wylie

Member emeritus
t Deceased
SWITCHGEAR ASSEMBLIES
1
~

I
----
I 1 1
I

,
METAL-ENCLOS ED
POWER SWITCHGEAR
METAL:!iOSED
1 CONTROL
SWITCH BOARDS
C37.21 1
LOW-VOLTAG E POWER NONSEGREGATED
CIRCUIT BREAKER (LV) PHASE
C37.20.1
VERTICAL
SEGREGATED (OPEN OR
PHASE

I
METAL-CLAD (MC) ENCLOSED)
C37.20.2
I------
ISOLATED PHASE
REQUIREMENTS AND
I DUAL
STAT1ON-TYPE CUB ICLE (SC)
C37.20.2
GUIDE FOR
CALCULATING LOSSES
I DUPLEX

CONTROL
METAL-ENCLOSED
INTERRUPTER (MEI)
C37.20.3
BENCHBOARD

BENCHBOARD

DUPLEX
BENCHBOARD

FIXED RACK
CABINET

SWING RACK
CAB1N ET

Fig A
Types of Switchgear Assemblies
Contents
.-
SECTION PAGE

1. Scope and References ................................................................................. 9


1.1 Scope ............................................................................................ 9
1.2 References ...................................................................................... 9
2. Definitions .............................................................................................. 10
2.1 Types of Switchgear Assemblies ............................................................. 10
2.2 Qualifying Terms .............................................................................. 11
2.3 Common or Related Terms ................................................................... 11
3. Service Conditions ..................................................................................... 12
4. Ratings ................................................................................................. 12
4.1 General.......................................................................................... 12
4.2 Voltage and Insulation Levels ............................................................... 13
4.3 Rated Frequency ............................................................................... 13
4.4 Rated Current .................................................................................. 13
4.5 Temperature Limitations ..................................................................... 14
4.6 Current Transformer Ratings ................................................................ 15
4.7 Current Transformer Accuracies ............................................................ 15
5. Tests .................................................................................................... 16
5.1 General.......................................................................................... 16
5.2 Design Tests .................................................................................... 16
5.2.1 Dielectric Tests ......................................................................... 16
5.2.2 Rated Continuous Current Tests ..................................................... 17
. 5.2.3 Short-Time Current Withstand Tests ................................................ 17
5.2.4 Short-circuit Current Withstand Test .............................................. 18
5.2.5 Mechanical Endurance Tests .......... .............................................. 19
5.2.6 Flame Resistance Tests ................. .............................................. 19
5.2.7 Rod Entry Test .......................... .............................................. 19
5.2.8 Paint Qualification Test ................ .............................................. 19
5.2.9 Rain Test for Outdoor LV Switchgear .............................................. 20
5.3 Production Tests ................................ .............................................. 20
5.3.1 Dielectric Tests ......................................................................... 20
5.3.2 Mechanical Operation Tests .......................................................... 21
5.3.3 Grounding of Instrument Transformer Case Test .................................. 21
5.3.4 Electrical Operation and Control-Wiring Tests ..................................... 21
5.4 Conformance Tests. ............................................................................ 21
5.5 Field Dielectric Tests .......................................................................... 21
6. Construction ........................................................................................... 21
6.1 General Requirements ........................................................................ 21
6.1.1 Buses and Primary Connections ...................................................... 21
6.1.2 Grounding ............................................................................... 22
6.1.3 Control and Secondary Circuits and Devices........................................ 22
6.1.4 Miscellaneous ........................................................................... 24
6.2 Materials and Finish .......................................................................... 25
6.3 Barriers ......................................................................................... 25
6.4 Buses and Connections ........................................................................ 25
6.5 Access Doors and Covers ...................................................................... 25
6.6 Closing and Tripping .......................................................................... 25
. 6.7 Indoor LV Switchgear ......................................................................... 25
6.8 Outdoor LV Switchgear ....................................................................... 26
6.9 Pull Box ......................................................................................... 26
SJXTION PAGE

6.10 Arrangements with Stationary Circuit Breakers .......................................... 26


6.11 Arrangements with Drawout Circuit Breakers ............................................ 26
6.12 Padlocking ...................................................................................... 27
6.13 Primary Cable Space .......................................................................... 27
6.14 Precautionary Labels .......................................................................... 27
6.15 Handling Devices .............................................................................. 27
7. Application Guide for LV Switchgear .............................................................. 27
7.1 Unusual Service Conditions .................................................................. 27
7.1.1 Ambient Air Temperature Above 40 "C.............................................. 28
7.1.2 Ambient Air Temperature Below -30 "C ........................................... 28
7.1.3 Application at Unusual Altitudes .................................................... 28
7.1.4 Modification of Equipment for Unusual Environment ............................ 28
7.2 System Characteristics-Voltage and Frequency .......................................... 30
7.3 Overvoltage Considerations-Insulation Levels ............................................ 30
7.4 Continuous Current Rating and Overload Capability ..................................... 30
7.5 Short-circuit Considerations.................................................................. 31
7.6 Nuclear Power Plant Application............................................................ 31
7.7 Associated Devices Often Used In LV Switchgear ......................................... 31
7.8 Protection and Isolation of Switchgear Connected to Other
Circuit Protective Equipment ................................................................ 32
7.9 Overcurrent Protection ....................................................................... 32
8. Guide for Handling. Storage. and Installation ..................................................... 32
8.1 General.......................................................................................... 32
8.2 Handling ........................................................................................ 33
8.3 Preoperation Check ............................................................................ 34
8.4 Removable Elements .......................................................................... 34 ..
8.5 Interlocks ....................................................................................... 34
8.6 Energization .................................................................................... 34
9. Bibliography ........................................................................................... 34
TABLES
Table 1 Voltage and Insulation Levels. AC LV Switchgear..................................... 13
Table 2 Voltage and Insulation Levels. DC LV Switchgear ..................................... 13
Table 3 Temperature Limits for Insulating Materials As Used In
Switchgear Assemblies....................................................................... 14
Table 4 Temperature Limits for Buses and Connections As Used In
Switchgear Assemblies....................................................................... 15
Table 5 Standard Accuracy Class Rating-Current Transformers in AC LV Switchgear... 16
Table 6 Copper Conductors for Use in Continuous Current Tests ............................... 18
Table 7 Copper Conductors for Use in Continuous Current Tests ............................... 18
Table 8 Control Power Transformer ShortCircuit Protection .................................... 24
Table 9 Minimum Areas for Multiple Cable Connections......................................... 27
Table 10 Altitude Correction Factors ................................................................. 28
Table 11 Circuit-Breaker Loads ....................................................................... 31

.
An American National Standard
IEEE Standard for
,Metal-EnclosedLow-Voltage
Power Circuit-Breaker Switchgear

1. Scope and References [3] ANSI C37.51-1979, American National Stan-


dard Conformance Testing of Metal-Enclosed
1.1 Scope. This standard covers metalenclosed Low-Voltage AC Power Circuit Breaker Switch-
low-voltage power circuit-breaker switchgear as- gear Assemblies.
semblies containing but not limited to such de-
vices as low-voltage power circuit breakers [4] ANSI 235.1-1972, American National Stan-
(fused or unfused), other interrupting devices, dard Specifications for Accident Prevention
switches, control, instrumentation and meter- Signs.
ing, protective, and regulating equipment. [5] ANSI 255.1-1967 (R 1973), American Na-
This standard is concerned with enclosed, tional Standard Gray Finishes for Industrial
rather than open, switchgear assemblies. It in- Apparatus and Equipment.
-- cludes equipments that are part of secondary
unit substations. It does not apply to equipment [6] ANSI / IEEE C37.09-1979, IEEE Standard
covered by industrial control standards, com- Test Procedure for AC High-Voltage Circuit
munication switchboards, communication Breakers Rated on a Symmetrical Current
switching equipment, switchboards for use on Basis.3
board ships, or deadfront distribution switch- [7] ANSI / IEEE C37.2-1979, IEEE Standard
boards. Electrical Power System Device Function Num-
In this standard, metal-enclosed low-voltage bers.
power circuit-breaker switchgear shall be called
LV switchgear. For ac LV switchgear the volt- [8] ANSI / IEEE C37.13-1981, IEEE Standard for
age shall be 1000 V or below and for dc LV Low-Voltage AC Power Circuit Breakers Used
switchgear, the voltage shall be 3200 V or below. in Enclosures.
[9] ANSI / IEEE C37.14-1979, IEEE Standard for
1.2 References Low-Voltage DC Power Circuit Breakers Used
[11 ANSI C2-1987, American National Standard in Enclosures.
National Electrical Safety Code.' [lo] ANSI/IEEE C37.241971 (R 1984), IEEE
Guide for Evaluating the Effect of Solar Radia-
[2] ANSI C37.16-1980, American National Stan-
tion on Outdoor Metal-Clad Switchgear.
dard Related Requirements and Application
Recommendations for Low-Voltage Power Cir- [ l l ] ANSIIIEEE C37.26-1972 (R 1976), IEEE
cuit Breakers and AC Power Circuit Protectors, Standard Guide for Methods of Power-Factor
Preferred Ratings.' Measurement for Low-Voltage Inductive Test
Circuits.
This publication is available from the sales Department, [12] ANSI / IEEE C37.100-1981, IEEE Standard
American National Standards Institute, 1430 Broadway,
New York. NY 10018 or from the IEEE Service Center. 445 Definitions for O' we' Switchgear.
- Hoes Lane, PO Box 1331, F'iscataway, NJ 088551331.'
ANSI publications are available from the Sales Deparb ANSI/ IEEE publications are available from the Institute
ment, American National Standards Institute, 1430 Broad- of Electrical and Electronics Engineers, Service Center, 445
way, New York, NY 10018. Hoes Lane, Po Box 1331, Piscataway, NJ 088551331.

9
ANSI / IEEE
C37.20.1-1987 IEEE STANDARD FOR METALENCLOSED LOW-VOLTAGE

[13] ANSIIIEEE C57.13-1978 (R 1986), IEEE [26] ASTM D229-82, Standard Method of Test- .-
Standard Requirements for Instrument Trans- ing Rigid Sheet and Plate Materials Used for
formers. Electrical Insulation.
[14] ANSIIIEEE Std 1-1986, IEEE Standard [27] ASTM D71456 (R 1981>,Standard Method
General Principles for Temperature Limits in of Evaluating Degree of Blistering of Paints.
the Rating of Electric Equipment and for the
[28] ASTM D1535-80, Standard Method of Spec-
Evaluation of Electrical Insulation.
ifying Color by the Munsell System.
[15] ANSI/IEEE Std 41978, IEEE Standard
[29] ASTM D165479 (R 1984), Standard Eval-
Techniques for High-Voltage Testing.
uation of Painted or Coated SpecimensSubjected
[16] ANSIIIEEE Std 100-1984, IEEE Standard to Corrosive Environments.
Dictionary of Electrical and Electronics Terms.
[30] ASTM G21-70 (R 1980), Standard Practice
[17] ANSIIIEEE Std 141-1986, IEEE Recom- for Determining Resistance of Synthetic Poly-
mended Practice for Electric Power Distribution meric Materials to Fungi.
for Industrial Plants.
[31] NEMA CC 1-1975, Electric Power Connec-
[18] ANSIIIEEE Std 142-1982, IEEE Recom- tors for S~bstations.~
mended Practice for Grounding of Industrial
[32] NEMA WC5-1973,Thermoplastic-Insulated
and Commercial Power Systems.
Wire and Cable for the Transmission and Dis-
[19] ANSIIIEEE Std 241-1983, IEEE Recom- tribution of Electrical Energy (ICEA S61-402).
mended Practice for Electric Power Systems in
[33] NEMA WC7-1971 (R 19761, Cross-Linked-
Commercial Buildings.
Thermosetting Polyethylene-Insulated Wire and
[20] ANSI/IEEE Std 242-1986, IEEE Recom- Cable for the Transmission and Distribution of
mended Practice for Protection and Coordina- Electrical Energy (ICEA S-66-524).
tion of Industrial and Commercial Power
[34] NEMA Bulletin No 77-1973 (R 19751, Guide
Systems.
Lines for Warning Labels.
[21] ANSIIIEEE Std 3441975, IEEE Recom-
mended Practices for Seismic Qualification of
Class 1E Equipment for Nuclear Power Gener-
ating Stations. 2. Definitions
[22] ANSIIIEEE Std 446-1987, IEEE Recom-
The definitions of terms contained in this stan-
mended Practice for Emergency and Standby dard, or in other standards referred to in this
Power Systems for Industrial and Commercial standard, are not intended to embrace all legit-
Applications.
imate meanings of the terms. They are appli-
[23] ANSI I NFPA 70-1987, National Electrical cable only to the subject treated in this standard.
Code.4 If a term is not defined in this standard, the
definition in ANSI/IEEE C37.100-1981[12]* a p
[24] ANSI I UL 486A-1982, Wire Connectors and plies. An asterisk (*) following a definition in-
Soldering Lugs for Use With Copper Conduc- dicates that the definition in this standard is
tors.' not contained in ANSIIIEEE C37.100-1981[12]
[25] ASTM B117-85, Standard Method of Salt while a dagger (t)indicates the definition differs
Spray (Fog) Testing? from that in ANSIIIEEE C37.100-1981 [12].
'The National Electrical code is published by the Na-
tional Fire Protection Association, Batterymarch Park, 2.1 switchgear. A general term covering
Quincy, MA 02269. Copies are also available from the Sales switching and interrupting devices and their
Department, American National Standards Institute, 1430
Broadway, New York, NY 10018.
combination with associated control, instru-
ANSI / UL publications are available from Underwriters
Laboratories Inc, Publication Stock, 333 Pfiigsten Road, 'NEMA publications are available from the National
Northbrook, IL 60062. Electrical Manufacturers Association, 2101 L Street, N W ,
ASTM publications are available from American Society Washington, DC 20037.
for Testing and Materials, 1916 Race St, Philadelphia, PA The numbers in brackets correspond to those of the ref-
19103. erences in 1.2.

10
ANSI / IEEE
POWER CJRCUIT-BREAKER SWITCHGEAR C37.20.1-1987

ments, metering, protective and regulating de- enclosed ventilated apparatus


vices, also assemblies of these devices with insulated
associated interconnections, accessories, and insulating
supporting structures used primarily in connec- isolated
tion with the generation, transmission, distri- manual
bution, and conversion of electric power. ventilated
2.1.1 switchgear assembly (seeFig A).An as- (2)The following qualifying terms are defined
sembled equipment (indoor or outdoor) includ- in ANSI/IEEE C37.100-1981 [12]and the user
ing, but not lirpited to, one or more of the is referred to the definitions given therein:
following categories: switching, interrupting, electrical
control, instrumentation, metering, protective enclosure
and regulating devices, together with their s u p flame-resistant
porting structures, enclosures, conductors, elec- general-purpose enclosure
trical interconnections, and accessories. indoor
2.1.2 metal-enclosed power switchgear. A metal-enclosed
switchgear assembly completely enclosed on all outdoor
sides and top with sheet metal (except for ven- resistant (used as a suffix)
tilating openings and inspection windows) con- secondary (used as an adjective)
taining primary powercircuit switching or ventilated enclosure
interrupting devices, or both, with buses and
connections. The assembly may include control 2.3 common or related terms. The following
and auxiliary devices. Access to the interior of common or related terms are defined in ANSI/
the enclosure is provided by doors or removable IEEE C37.100-1981[12]and the user is referred
covers, or both.j- to the definitions given therein:
metal-enclosed low-voltage power circuit- asymmetrical
breaker switchgear. LV switchgear of multiple auxiliary switches
A
or individual enclosures, including the following barrier
equipment as required: bus
(1)Low-voltage power circuit breakers (fused connected position (of a switchgear assem-
or unfused) in accordance with ANSI/IEEE bly removable element)
C37.13-1981[8]. continuous current tests
(2)Bare bus and connections current limiting fuse
(3)Instrument and control power trans- disconnected position (of a switchgear as-
formers sembly removable element)
(4) Instruments, meters, and relays drawoutcmounted device
(5) Control wiring and accessory devices ground bus
The low-voltage power circuit breakers are live parts
contained in individual grounded metal com- main (primary) switchgear connections
partments and controlled either remotely or mimic bus
from the front of the enclosure. The circuit primary disconnecting devices (of a
breakers may be stationary or removable switchgear assembly)
(drawout) type; when of removable type, removable element (of a switchgearassem-
mechanical interlocks are provided for proper bly)
operating sequence. secondary and control wiring (small wir-
ing)
2.2 qualifying terms. (relating to types of en- secondary disconnecting contacts
closures, ventilation methods, etc) silver surfaced or equivalent
(1)The following qualifying terms are defined stationary-mounted device
in ANSI/IEEE Std 100-1984 [16]and the user symmetrical
is referred to the definitions given therein: terminal (terminal connector)
accessible (as applied to equipment) terminal block (terminal board)
alive (live) test position
automatic 2.3.1 ambient air temperature. The temper-
dead front ature of the surrounding air that comes in con-
enclosed (inclosed) tact with equipment.*
ANSI / IEEE
C37.20.1-1987 IEEE STANDARD FOR METAL-ENCLOSED LOW-VOLTAGE

NOTE: Ambient air temperature, as applied to enclosed conductors and secondary control connection de-
switchgear assemblies, is the average temperature of the
surrounding air that comes in contact with the enclosure.* vices including current transformers.
(See 5.2.2.3for method of measurement.) 2.3.8 auxiliary compartment. That portion
of the switchgear assembly that is assigned to
2.3.2 design tests. Tests made by the manu- the housing of auxiliary equipment, such as po-
facturer to determine the adequacy of the design tential transformers, control power trans-
of a particular type, style, or model of equipment formers, or other miscellaneous devices.
or its component parts to meet its assigned rat-
ings and to operate satisfactorily under normal
service conditions or under special conditions if
specified, and may be used to demonstrate com-
pliance with applicable standards of the indus- 3. Service Conditions
try.?
NOTES: (1) Design tests are made on representative appa-
American National Standards for the design
ratus or prototypes to verify the validity of design analysis and performance of LV switchgear are based on
and calculation methods and to substantiate the ratings as- usual service conditions as described below. The
signed to all other apparatus of basically the same design. selection of equipment for a particular appli-
These tests are not intended to be made on every design
variation or to be used as part of normal production. The cation can be based on the construction and rat-
applicable portion of these design tests may also be used to ings as defined in this standard provided that
evaluate modifcations of a previous design and to ensure these usual service conditions exist.
that performance has not been adversely affected. These
data from previous similar designs may also be used for (1) The temperature of the cooling air (am-
current designs, where appropriate. Once made, the tests bient air temperature) surrounding the enclo-
need not be repeated unless the design is changed so as to sure of the LV switchgear is within the limits
modify performance.
(2)Design tests are sometimes called type tests. of - 30 "C and +40 "C.
(2) The altitude of the installation does not
2.3.3 production tests. Tests made for qual- exceed 6600 ft (2000 m).
ity control by the manufacturer on every device (3) The effect of solar radiation is not signif-
or representative samples, or on parts or ma- icant. (The principles stated in ANSI/IEEE
terials as required to verify during production C37.24-1971 (R 1984) [lo] may be used for guid-
that the products meets the design specifications ance.)
and applicable standards.t (4) Unusual service conditions such as out-
NOTES: (1) Certain quality assurance tests on identified lined in 7.1 do not prevail.
critical parts of repetitive high-production devices may be
tested on a planned statistical sampling basis.
(2)Production tests are sometimes called routine tests.

2.3.4 conformance tests. Conformance tests


demonstrate compliance with the applicable 4. Ratings
standards. The test specimen is normally sub-
jected to all planned production tests prior to 4.1 General. The ratings of a switchgear assem-
initiation of the conformance test program.? bly are designations of operating limits under
specified conditions of ambient temperature,
NOTE: The conformance tests may, or may not, be similar temperature rise, etc. Where the switchgear as-
to certain design tests. Demonstration of margin (capabili- sembly comprises a combination of primary and
ties) beyond the standards is not required.
secondary circuits, each may be given ratings.
2.3.5 field tests. Tests made after the switch- LV Switchgear shall have the following rat-
gear assembly has been installed at its place of ings:
uti1ization.t (1) Rated maximum voltage
2.3.6 vertical section. That portion of the (2) Rated frequency
switchgear assembly between two successive (3) Rated insulation level
vertical delineations and may contain one or (4) Rated continuous current
more circuit breakers, auxiliary compartments, (5) Rated short-time current
and associated primary conductors.* (6) Rated shortcircuit current
2.3.7 circuibbreaker compartment. That The designated ratings in this standard are
portion of a switchgear assembly that contains preferred but are not considered to be restric-
one circuit breaker and the associated primary tive.

12
ANSI I IEEE
POWER CIRCUIT-BREAKER SWITCHGEAR C37.20.1-1987

Table 1
Voltage and Insulation Levels, AC LV Switchgear
Rated Insulation Levels (kV)
Maximum Low-Frequency Reference*
Voltage Withstand dc (kV)
(ITIS) (rms) Withstand

2.2 3.1
* The column headed “dc Withstand” is given as a reference only for those using dc tests
to verify the integrity of connected cable installations without disconnecting the cables
from the switchgear. It represents values believed to be appropriate and approximately
equivalent to the corresponding power frequency withstand test values specified for each
voltage class of switchgear. The presence of this column in no way implies any requirement
for a dc withstand test on ac equipment or that a dc withstand test represents an acceptable
alternative to the low-frequency withstand tests specified in this standard, either for design
tests, production tests,conformance tests, or field tests.When making dc tests, the voltage
should be raised to the test value in discrete steps and held for a period of one minute.

Table 2 4.4 Rated Current


Voltage and Insulation Levels. 4.4.1 Rated Continuous Current. The rated
6 C LV Switchgear continuous current of a LV switchgear is the
Insulation Levels (kW maximum current in root mean square (rms)
Rated Low-Frequency Reference amperes at rated frequency, or direct current,
Maximum Withstand dc (kV) which can be carried continuously by the pri-
Voltage (rms) Withstand mary circuit components, including buses and
300 I325 2.2 3.1 connections, without causing temperatures in
800 3.7 5.2 excess of specified limits for
- 1200
1600
4.6
5.4
6.5
7.6 (1)Any primary or secondary circuit compo-
3200 8.8 12.4 nent
(2) Any insulating medium, or structural or
enclosing member
The specified temperature limits applicable to
4.2 Voltage and Insulation Levels switchgear assemblies are given in 4.5.1 through
4.2.1 Rated Maximum Voltage. The rated 4.5.6.
maximum voltage of LV switchgear is the high- 4.4.2 Continuous Current Ratings. The con-
est rms voltage for which the equipment is de- tinuous current ratings of the main bus in
signed, and is the upper limit for operation. ac LV switchgear are 600A, 800A, 1200A,
4.2.2 Rated Insulation Level. The rated in- 1600 A, 2000 A, 3000 A, 3200 A, or 4000 A and
sulation level of LV switchgear is equal to the in dc LV switchgear are 1600A, 2000A,
low-frequency one-minute withstand voltage. 2500 A, 4000 A, 5000 A, 6000 A, 8000 A,
4.2.3 Voltage and Insulation Levels for 10 000 A, and 12 000 A.
AC LV Switchgear. The rated maximum volt- The continuous current rating of the vertical
ages and corresponding insulation levels for section bus riser shall be equal to the frame size
ac LV switchgear are listed in Table 1. of the ac LV power circuit breaker used (see
ANSI C37.16-1980 [2]) except as modified by the
4.2.4 Voltage and Insulation Level for allowable cumulative loading of multiple ac cir-
DC LV Switchgear. The rated maximum volt- cuit breakers in the same section (see Table 11)
ages and corresponding insulation levels for or by lower continuous current ratings for cur-
dc LV switchgear are listed in Table 2, which rent transformers, but in no case does it need
is based on ANSI/IEEE C37.14-1979 [9]. to be greater than the rating of the main bus.
4.4.3 Rated Short-Time Current. The rated
4.3 Rated Frequency. The rated frequency of short-time current of a LV switchgear assembly
a device, or an assembly, is the frequency of the is the designated limit of available (prospective)
circuit at which it is designed to perform. (Rat- current at which it shall be required to with-
ings for ac equipment are based on a frequency stand its short-time current duty cycle (two pe-
of 60 Hz) riods of one-half second current flow, separated

13
ANSI/ IEEE
-7.20.1-1987 IEEE STANDARD FOR METALENCLOSED LOW-VOLTAGE

by a 15 s interval of zero current) at rated max- DC LV switchgear shall meet the ratings
imum voltage under the prescribed test condi- and test parameters required for LV dc power
tions. This current is expressed in rms circuit breakers as covered in ANSI/IEEE
symmetrical amperes and is measured from the C37.141979 [9] and ANSI C37.16-1980 [2].
envelope of the available current wave at a time
one-half cycle after current is established. This
current also demonstrates the dc short-time cur- 4.5 Temperature Limitations
rent ratings. 4.5.1 Limiting Temperature. The limiting
LV switchgear assemblies shall be capable of temperature for LV switchgear is the maximum
withstanding the short-time current duty cycle temperature permitted
with all degrees of current asymmetry produced (1) For any component, such as insulation,
by three-phase or single-phase circuits having a buses, instrument transformers, and switching
short-circuit power factor of 15% or greater and interrupting devices
( X / R ratio 6.6 or less). LV switchgear assemblies (2) For air in cable termination compartments
shall have preferred short-time current ratings (3) For any noncurrent-carrying structural
equal to the short-time current rating of the parts
smallest frame size circuit breaker used in the (4) For air surrounding devices
assembly as listed in ANSI C37.16-1980[2]. 4.5.2 Temperature Limits for Insulating
4.4.4 Rated Short-Circuit Current. The Materials. The total temperature to which in-
rated short-circuit current of an ac assembly is sulating materials are subjected shall not exceed
the designated limit of available (prospective) the values listed in Table 3 for the various
current at rated maximum voltage which it shall classes of insulating materials.
be required to withstand for a period of no less 4.5.3 Temperature Limits for Buses and
than 4 cycles on a 60 Hz basis under the pre- Connections. The total temperature of buses
scribed test conditions. This current is expressed and connections shall not exceed the values
in rms symmetrical amperes and is measured listed in Table 4.
from the envelope of the available current wave 4.5.4 Temperature Limitations for Air
at a time one-half cycle after current is estab- Surrounding Devices Within An Enclosed
lished. Assembly. The temperature of the air sur-
AC LV switchgear assemblies shall have pre- rounding all devices within an enclosed assem-
ferred short-circuit current ratings equal to the bly, considered in conjunction with their rating
short-circuit current rating of the smallest and loading as used, shall not cause these devices
frame size circuit breaker used in the assembly to operate outside their rated temperature range
as covered in ANSI C37.16-1980 [2]. Use power when the enclosure of the assembly is sur-
factor ( X / R ratio) identical to that of 4.4.3 for rounded by air within an ambient temperature
this test. range of -30 “C to +40 “C.

Table 3
Temperature Limits for Insulating Materials
As Used in Switchgear Assemblies*
Class of Limit of HottestrSpot Limit of HottestSpot
Insulating Temperature Rise Total Temperature
Material (“C) (“C)
Class 90 50 90
Class 105 65 105
Class 130 90 130
Class 155 115 155
Class 180 140 180
Class 220 180 220
’These temperature limits for insulating materials may not apply
to insulation in circuit breakers or other devices. For temperature
limitations on devices, refer to the appropriate standards for the
devices. See also 4.5.4.

14
ANSI / IEEE
POWER CIRCUIT-BREAKER SWITCHGEAR C37.20.1-1987

Table 4
Temperature Limits for Buses and
Connectio& as Used in Switchgear Assemblies
Limit of Limit of
Hottest-Spot Hottest-Spot
Type of Bus or Temperature Rise Total Temperature
Connection CC) ("0
Buses and connectionswith unplated copper
to copper connecting joints 30 70
Buses and connections silver surfaced, tin
surfaced, or equivalent connecting joints 65 105
Connection to insulated cables unplated c o p
per to copper 30 70
Connections to insulated cables silver sur-
faced, tin surfaced or equivalent 45 85
NOTE: All aluminum bus shall have silver surfaced, tin surfaced, or equivalent connecting
joints.
Welded bus connections are not considered connecting joints.

4.5.5 Temperature Limitations for Air which the associated circuit interrupting devices
Surrounding Insulated Power Cables. The are applied. When the primary circuit is pro-
temperature of the air surrounding insulated tected by current-limiting fuses, the current
power cables within any compartment of an en- transformers shall successfully withstand the
closed assembly shall not exceed 65 "C when the maximum letithrough current of the fuses. Un-
assembly is less specifically limited to a shorter time by the
(1)Equipped with devices having maximum associated protective equipment, the duration of
A
current rating for which the assembly is de- the short-circuit shall be considered as being
signed four cycles.
(2) Carrying rated continuous current at 4.6.2 Current Transformer Thermal Rat-
rated voltage and at rated frequency or direct ings. The thermal ratings of current trans-
current, whichever applies formers shall be such that they will successfully
(3) In an ambient air temperature of 40 "C. withstand the short-circuit current for which the
NOTE: This temperature limitation is based on the use of
associated circuit interrupting devices are a p
90 "C insulated power cables. Use of lower temperature rated plied. When the primary circuit is protected by
cables requires special consideration. current-limiting fuses, the current transformers
shall successfully withstand the maximum 12t of
4.5.6 Temperature Limitations for Parts the fuses. Unless specifically limited to a shorter
Subject to Contact by Personnel. (1) Parts time by the associated protective equipment, the
handled by the operator in the normal course of duration of the short-circuit shall be considered
his duties shall have no higher total tempera- as being one second.
ture than 50°C. 4.6.3 Current Transformer Ambient Tem-
(2) External surfaces accessible to an operator perature. Current transformers for use in
in the normal course of his duties shall have no switchgear assemblies shall be rated on the basis
higher total temperature than 70°C. of at least 55 "C ambient temperature in accord-
(3) External surfaces not accessible to an o p ance with ANSI / IEEE C57.13-1978 (R 1986)[13],
erator in the normal course of his duties shall 3.1.1.2.
have no higher total temperature than 110 "C.
NOTE: For additional information on temperature limits 4.7 Current Transformer Accuracies. Accu-
~ e ANSI/IEEE
e SM 1-1986 [14]. racies tabulated hereafter are the minimum
which shall be supplied. The manufacturer
4.6 Current Transformer Ratings should be consulted if higher accuracies are re-
4.6.1 Current Transformer Mechanical quired by the purchaser. It should be recognized
Ratings. The mechanical ratings of current that current transformers with higher accura-
transformers shall be such that they will suc- cies may not meet the requirements of 4.6.1 and
cessfully withstand the short-circuit current for 4.6.2.

15
ANSI / IEEE
C37.20.1-1987 IEEE STANDARD FOR METAL-ENCLOSED LOW-VOLTAGE

Table 5 zero to the required test value within 5 s to


Standard Accuracy Class Rating* 10 s and shall be held at that value for 1 min.
Current Transformers in The ac test voltages shall be essentially si-
AC LV Switchgear nusoidal and applied with a minimum crest
Ratio B 0.1 B 0.2 value equal to 1.414 times the specified values.
1W5 1.2 2.47 The frequency of the test voltage shall be within
150:5 1.2 2.4t f 20% of the rated frequency of the LV switch-
2W5 1.2 1.2 gear being tested. If a test transformer of less
3W5 0.6 0.6
4m5 0.6 0.6 than 500 VA is used, a suitable voltmeter shall
m 5 0.6 0.6 be provided to measure the applied output po-
m 5 0.3 0.3 tential directly. The applicable test voltage in
1200:5 0.3 0.3
15W5 0.3 0.3 accordance with Tables 1 and 2,shall be applied
2000:5 0.3 0.3 for a period of 1 min to the primary circuit of
3000:5 0.3 0.3 the LV switchgear in the following manner:
4000:5 0.3 0.3
5000:5 0.3 0.3 (1)For equipment with stationary devices and
6000:5 0.3 0.3 for equipment with drawout mounted devices
See ANSI/IEEE C57.13-1978 (R 1986) [13]. with the removable elements in the connected
t Not in ANSIIIEEE C57.13-1978 (R 1986) [13]. position, apply the test voltage between primary
circuits and ground:
(a) With the circuit-breaker contacts closed,
between each phase of the switchgear assembly
For installation in ac LV switchgear, the with the frame and the other phases and the
standard current transformer accuracies for me- neutral bus grounded.
tering are listed in Table 5. (b) With the circuit-breaker contacts open,
between each terminal of the switchgear assem-
bly with the frame and all other terminals
5. Tests grounded.
(2)With the drawout circuit breaker in the
5.1 General. This section establishes physical test position and closed, apply the test voltage
and electrical conditions for tests and methods to primary terminals:
of determining temperatures and test values. All (a) Simultaneously to all the incoming ter-
apparatus and devices in the power circuit shall minals of the switchgear assembly with the
be mounted in their normal locations during frame and outgoing terminals grounded. Repeat
tests. No statement in this section is to be con- tests by applying the test voltage to the outgoing
strued as modifying the test requirements for terminals with the frame and incoming termi-
devices included in switchgear assemblies. nals grounded.
Tests are classified as design tests, production (b) Simultaneously between all incoming
tests, conformance tests, and field tests. These and outgoing terminals of the switchgear assem-
are generally defined in 2.3.2 to 2.3.5. bly. This test shall be made with a value of volt-
age 10% higher than that specified in Tables 1
NOTE: Except for the main switching or interrupting de-
vice, other devices, such as voltage transformers that are and 2.
mounted in the switchgear assemblies, may be disconnected
during the dielectric test. Such devices are individually
tested in accordance with standards applying to them. NOTES (1) For the test across the open gap at 10% higher
voltage, an intermediate point of the voltage source may, if
practicable, be connected to ground and to the frame of the
5.2 Design Tests. Design Tests as applicable assembly 80 that the voltage between any live part and the
shall be made in accordance with 5.2.1 through frame will not exceed that specified in Table 1. If this is not
practicable, the frame may be insulated from ground.
5.2.7. (2) Successful completion of these tests does not neces-
5.2.1 Dielectric Tests. Low-frequency with- sarily provide assurance that with the circuit breaker in the
stand tests on LV switchgear shall be performed test position, it will always flashover to ground instead of
across the gap between line and load terminals. Switchgear
to demonstrate the ability of the insulation sys- insulation does not provide surge protection for the open
tem to withstand the voltages in accordance with gap. Where surge protection of the gap is required, suitable
Tables 1 and 2. All voltages shall be measured protective devices must be applied.
(3) Apply test voltage between neutral and ground, except
in accordance with ANSI / IEEE Std 4-1978[15]. at 1800 V instead of 2200 V (not applicable to dc LV switch-
The potential is to be increased gradually from gear).

16
ANSI / IEEE
POWER CIRCUPT-BREAKERSWITCHGEAR C37.20.1-1987

- 5.2.2 Rated Continuous Current Tests. To thermocouples shall be located a t the junction
determine compliance with continuous current of the conductor and its insulation.
ratings, it is necessary to determine that tem- Thermocouples shall be held in intimate
peratures of the various components of the contact with the conductor surface by such
switchgear assembly are within the limits set methods as welding, drilling, and peening or ce-
forth in 4.4.1through 4.4.7.Temperature mea- menting.
surements shall be made in accordance with The thermocouples on a design test shall be
5.2.2.1 through 5.2.2.6. located in a manner so as to measure the hottest
5.2.2.1 Test Area Conditions. Tempera- spot, even though it may involve drilling holes
ture tests shall be conducted indoors in a test that destroy some parts. It is recognized that
room that is reasonably free from drafts. thermocouples cannot be located in the actual
5.2.2.2 Ambient Air Temperature Lim- contact point of line or point contacts without
its. Tests may be made at any ambient air tem- destroying the effectiveness of such line or point
perature between 10 "C and 40 "C. contacts.
5.2.2.3 Measurement of Ambient Air Measurements shall be made a t junction
Temperature. Indoor ambient air temperatures points of insulation and conducting parts to en-
shall be determined by taking the average of the sure against exceeding temperature limits of the
readings of three temperature-measuring d e insulation.
vices, such as thermometers or thermocouples, 5.2.2.5 Duration of Tests. The continuous
placed as follows: current test shall be made for such a period of
(1)One level with the top of the structure time that the temperature rise of any monitored
(2)One 12 in (305 mm) above the bottom of point in the assembly has not increased by more
the structure than 1.0"Cduring each of two successive 30 min
(3)One midway between the two positions (1) intervals as indicated by three successive read-
and (2) ings. If the temperature rise at the end of the
All temperature-measuring devices shall be second interval is equal to the established limits
- placed 12 in (305 mm) from the structure, not and if the temperature rise has increased since
in front of ventilators, and in locations unaf- the previous reading, the test shall be continued
fected by drafts caused by the structure or a p until the temperature rise is constant.
preciable radiation from the equipment. When 5.2.2.6 Frequency of Test Current. The
the ambient air temperature is subject to vari- frequency of the test current shall not be less
ations that might result in errors in measuring than the rated frequency of the assembly tested.
the temperature rise, the temperature-measur- A sine-wave shape is recommended. The test
ing devices should be immersed in a suitable shall be made with alternating current having
liquid, such as oil in a suitable container, or a crest value equal to 1.414 times the rms test
reliably attached to a suitable mass of metal. current. Directcurrent assemblies should be
tested using a dc power supply with an rms am-
NOTE: A convenient form for such a container consists of
a metal cylinder with a hole drilled partly through it. This peres output equal to the continuous current
is filled with liquid and the temperaturemeasuring device rating.
is placed therein. A glass bottle may also be used as a con- 5.2.2.7 Copper Conductors for Use in
tainer. The size of the container should be at least 1 in
(25.4 mm) in diameter and 2 in (50.8mm) high. Continuous Current Tests.Bus bars are to be
used for the connections to the main bus per
5.2.2.4 Method of Measuring. Temperu- Table 6 and cables or bus per Table 7 for con-
ture-Thermocouples, when used for measuring nection to the circuit-breaker unit outgoing ter-
the temperature of insulation, shall be located minals. If test arrangement internal bus sizes
on the currentcarrying member or other metal are different than Tables 6 and 7,then external
part at a point as close as practical to the ac- bus sizes equal to internal bus sizes may be sub-
cessible junction of the insulation and the cur- stituted at the option of the manufacturer.
rent-carrying member or other metal part. The conductors connected to the terminals
Thermocouples used for measuring the temper- shall be a minimum of 4 ft (1.2m) long.
ature of the circuit-breaker separable primary 5.2.3 Short-Time Current Withstand Tests.
contacts shall be located approximately 0.5 in Short-time current withstand tests shall be
(13 mm) from the contacts on the current- made to demonstrate the electrical and thermal
carrying member. For cable terminations, the adequacy of buses and connections in switchgear

17
ANSI / IEEE
C37.20.1-1987 IEEE STANDARD FOR METAL-ENCLOSEDLOW-VOLTAGE

Table 6* h

Copper Conductors for Use in Continuous Current Tests


Main Bus Rating Copper Bus per Terminal?
(Amperes) Quantity Size,in (mm)
1600 2 x
* 3 (6.35 76.2)
2000
3000/ 3200
2
3 x
-
% * 4 (6.35 101.6)
* 5 (6.35 127.0)
4000 4 2 * 5 (6.35 * 127.0)
* Larger main buses and circuit-breaker frame sizes are required in dc LV switchgear
and ANSI/IEEE C37.141979 [9] and ANSI C37.161980 [2] shall be utilized for guidance
in testing.
t Where multiple bus bars are used, they are to be spaced % in (6.35 mm) apart. The
4000 A group is to be two sets of two bars with not more than 4 in (101.6 mm) between
pair centers.
Vertical or horizontal configuration shall be the option of the manufacturer.

Table 7*
Copper Conductors for Use in Continuous Current Tests
size of CoDDer Conductor
~ ~~

Circuit Breaker AWG or Bus per Terminal?


Frame Size Circular Mi4 Quantity Size,in (mm)
225 1-4/0
600 2-350M
800 2-500M
1600 4-600M
2000 5-600M
3000 / 3200 3 . 5 (6.35 . 127)
4000 4 % . 5 (6.35 . 127)
* Larger main buses and circuit breaker frame sizes are required in dc LV switchgear
and ANSI/IEEE (37.141979 [9] and ANSI C37.161980 [2] shall be utilized for guidance
in testing.
?Where multiple bus bars are used,they are to be spaced 2 in (6.35 mm) apart. The
4000 A group is to be two sets of two bars with not more than 4 in (101.6 mm) between
pair centers.
Vertical or horizontal confwration shall be the option of the manufacturer.
8 Tests based on cross-sectional area, not cable insulation classification.

assemblies to withstand the rated short-time assembly is properly applied on systems when
current of the assembly without physical dam- the available shortcircuit current is equal to the
age. The prospective current shall be the rms short-circuit current rating of the circuit break-
value calculated in accordance with ANSI/ ers in the LV switchgear.
IEEE C37.09-1979[6]and shall continue for two The duration of current flow during the short-
periods of one-half second separated by a 1 5 s circuit current withstand test shall be for no less
interval of zero current. Single-phase testing is than 4 cycles on a 60 Hz basis (0.067 s), unless
permitted. For short-time tests the alternating the bus is protected by a current-limiting device,
component of the current at the end of one-half in which case the duration shall be for the time
second shall be no less than 80% of the alter- permitted by that device.
nating component measured at one-half cycle
after initiation of the current. NOTE: Four cycles is the maximum duration of short circuit
5.2.4 Short-Circuit Current Withstand expected on 600 V ac systems on which this equipment is
Tests. Short-circuit current withstand tests applied.
shall be made to demonstrate the mechanical
adequacy of the structure, buses, and connec- "he three-phase rms symmetrical value of cur-
tions to withstand the maximum short-circuit rent that verifies the short-circuit current rating
stresses which could occur when the switchgear shall be determined by calibrating the test cir-

18
ANSI / IEEE
POWER CIRCUIT-BREAKER SWITCHGEAR C37.20.1-1987

cuit with the LV switchgear omitted and shall and test positions, for each frame size and type
be measured one-half cycle after the inception of circuit breaker to demonstrate proper se-
of the current flow in the test circuit. This cur- quential operation and to establish satisfactory
rent in each phase shall be calculated in ac- function of the following elements. All primary
cordance with ANSI / IEEE C37.09-1979 [6]. For power should be disconnected during these
three-phase circuits the symmetrical current mechanical tests.
value shall be the average of the phase current. (1) Separable primary contacts
The power factor of the test circuit shall be (2) Separable control contacts
15% lagging or less ( X / R ratio of 6.6 or greater) (3) Circuit breaker removable element posi-
with X and R in series connection. The power tion interlocks (every tenth operation to with-
factor shall be determined in accordance with drawn position)
ANSI/IEEE C37.26-1972 (1976) [ll](power fac- (4) Stored energy mechanism interlocks, as
tor minus 20% or less, X / R ratio of 5 or greater applicable (every tenth operation to withdrawn
for fused circuit-breaker equipment). position)
The rms value of the alternating component (5) Housing mounted breaker position
of the current at the end of 3 cycles shall be no switches
less than 90% of the value measured at one-half 5.2.6 Flame Resistance Tests. Sheet, molded
cycle after initiation of the current. or cast insulating material used in a switchgear
The current shall be initiated in the test cir- assembly shall not be classed as flame resistant
cuit in such a manner to ensure that the peak unless they have a minimum average ignition
current available is no less than 2.3 times the time of 6 0 s and a maximum average burning
single-phase rms symmetrical value for the sin- time of 100s when tested in accordance with
gle-phase test and 2.3 times the three-phase rms ASTM D229-82 [26], Method 11.
symmetrical value in one phase for three-phase 5.2.7 Rod Entry Test
tests (peak current 2.16 times for fused circuit 5.2.7.1. Method. Ventilated Enclosures-
breakers). This test shall prevent the insertion of a straight
The frequency of the test circuit shall be rod having a diameter of 0.500 in (12.7 mm) into
60 Hz k 20%. the opening, except that, if the distance between
The testcircuit voltage prior to the inception the openings and the nearest live part is greater
of current flow shall be no less than the rated than 4 in (101.6 mm), a rod having a diameter
maximum voltage. greater than 0.500 in (12.7 mm) shall be per-
Individual single-phase tests are also to be mitted to enter the opening, but a rod having a
made to prove the strength of the ground bus diameter greater than 0.750 in (19 mm) shall
and the neutral conductor design with respect not be permitted to enter the opening.
to the nearest phase bus during the test. Line- 5.2.7.2 Evaluation. The enclosure is con-
to-neutral voltage is to be applied between the sidered to have met the requirements of this test
neutral and the nearest phase bus during the if the appropriate rod cannot enter the enclo-
test. Line-to-line voltage is to be applied between sure.
the ground bus and the nearest phase bus during
the test. 5.2.8 Paint Qualification Test. The paint
The LV switchgear shall be considered as hav- qualification test applies to all enclosures incor-
ing passed this test if there is no breakage of porating external ferrous parts. Nonferrous en-
closures with no external ferrous parts need not
the bus supports and the repeat of the dielectric
requirements of 5.2.1have been met. Permanent be tested.
The paint qualification test shall be performed
deformation of bus bars and supports that is
insufficient to prevent dielectric requirements to ensure the adequacy of finishes to inhibit the
buildup of rust on ferrous metal materials used
from being met is permissible. Permanent de-
for enclosures. The following methods are used.
formation of bus and bus supports shall not im-
5.2.8.1. Test Specimens. Representative
pair mechanical performance as specified in
test panels of a 3 in by 6 in minimum size that
5.2.5.
can be accommodated by the test chamber shall
5.2.5 Mechanical Endurance Tests. LV be provided. Each specimen shall be uniformly
. switchgear with drawout circuit breakers shall processed in the standard production paint-fin-
have mechanical endurance test cycles consist- ishing system. At least four panels shall be se-
ing of at least 100 operations between connected lected for the test. All the test specimens shall

19
ANSI / IEEE
(37.20.1-1987 IEEE STANDARD FOR METAGENCLOSED LOW-VOLTAGE

be of standard gauge ferrous metal equivalent uniform spray over the entire surface or surfaces
to that used for the enclosure. The specimen under test. The various vertical surfaces of a n
shall be allowed to age for a minimum of seven enclosure may be tested separately or collec-
days before being tested. tively, provided that a uniform spray is simul-
5.2.8.2 Test Apparatus. The test appara- taneously applied to both (1) and (2) as follows:
tus shall consist of a fog chamber, salt-solution (1) The roof surface, from nozzles located at a
reservoir, compressed-air supply, provisions for suitable height
heating, and means of control. The conditions (2) The floor outside the enclosure for a dis-
in the saltrspray chamber including the posi- tance of approximately 3 ft (1 m) in front of the
tioning of the specimens, content of the salt so- surface under test with the enclosure located at
lution, and temperature and pressure to be floor level.
maintained, shall be as defined in ASTM-B117- The nozzles used for this test shall deliver a
85 [25]. square-shaped spray pattern with uniform spray
5.2.8.3 Preparation of Test Specimens. distribution and shall have a capacity of at
Two of the test panels shall be suitably scribed least 7.1 gal/min (450 cm3/s) at a pressure of
for testing in accordance with ASTM D-165479 60 lbf/in2 (41.4 N/cm2), and a spray angle of
(R 1984) [29]. approximately 75". The centerline of the nozzles
5.2.8.4 Exposure of Test Specimens. All shall be inclined downward so that the top of
test specimens shall be tested in the salt-spray the spray is horizontal as it is directed toward
chamber for a period of 200 h continuously ex- the vertical and roof surfaces being tested.
cept for the short daily interruptions necessary The pressure at the nozzles shall be a mini-
to inspect the test specimen or replenish the mum of 60 lbf/in2 (41.4 N/cm2) under flow con-
solution in the reservoir. ditions. (Thisis approximately equivalent to rain
5.2.8.5 Procedure. After completion of the driven by a 65 mi / h (29 m / s) wind.) The quan-
exposure period, the scribed specimens shall be tity of water applied to each surface under test
processed in accordance with ASTM D165479 shall be at least 0.2 in (0.5 cm) per unit surface
(R 1984) [29], either Method A (tape)or Method per minute, and each surface so tested shall re-
B (scraper). ceive this rate of artificial precipitation for a
5.2.8.6 Evaluation. The scribed specimens duration of 5 min. The spray nozzle shall not be
shall then be evaluated for creepage from the more than 10 ft (3 m) from the nearest vertical
scribe mark in accordance with ASTM D1654- surface under test.
79 (R1984) [29], Rating Schedule No 1. The non- After the test is completed, an inspection shall
scribed specimen shall be evaluated for degree be made promptly to determine if the enclosure
of blistering in accordance with ASTM D71456 meets the requirements of outdoor construction.
(1981) [27]. More specifically, the equipment shall have sat-
5.2.8.7 Performance. The scribed speci- isfactorily met the requirements of this test if
mens shall be judged to have met the require- the visible inspection indicates
ments of the test if their rating number is 5 or (1) No water on primary or secondary insu-
higher as determined by ASTM D1654-79 (1984) lation
[29]. The nonscribed specimens shall be judged (2) No water on any electrical components or
to have met the requirements of the test if their mechanisms of the assembly
blistering size is No 6 or higher, and their fre- (2) No significant accumulation of water re-
quency designation is F or M as determined by tained by the structure or other noninsulating
ASTM D714-56 (1981) [27]. parts (to minimize corrosion).
5.2.9 Rain Test for Outdoor LV Switch-
gear, The enclosure to be tested shall be 5.3 Production Tests. Production tests for LV
equipped and complete with typical appur- switchgear shall be low-frequency dielectric
tenances, and placed in the area to be supplied tests, mechanical tests, grounding of instrument
with artificial precipitation. For multiple unit transformer case tests, and electrical operation
construction a minimum of two units shall be and control wiring check. Drawout circuit break-
used to test the joints between units. A roof joint ers need not be tested in the assembly if they
shall be included. are tested spearately.
The artificial precipitation shall be supplied 5.3.1 Dielectric Tests. Low-frequency with-
by a sufficient number of nozzles to produce a stand tests shall be made on each LV switchgear

20
ANSI / IEEE
POWER CIRCUIT-BREAKER SWITCHGEAR C37.20.1-1987

in accordance with the general requirements of This sequence test need not include remote
5.2.1, with the exception that tests across the equipment controlled by the switchgear assem-
open gap are not required. Tests shall be made bly. However, this equipment may be simulated
between each phase and ground with the other where necessary.
phases grounded.
Apply a test voltage of 1800 V between neutral 5.4 Conformance Tests. Conformance test pro-
and ground. cedures for LV switchgear are given in ANSI
5.3.2 Mechanical Operation Tests. Mechan- C37.51-1979[3].
ical tests shall be performed to ensure the proper
functioning of mechanical interlocks, etc. These 5.5 Field Dielectric Tests. When low-fre-
tests shall ensure the interchangeability of re- quency withstand tests are to be made on LV
movable elements designed to be interchange- switchgear after installation in the field the
able. switchgear shall not be tested at greater than
5.3.3 Grounding of Instrument Trans- 75% of the test values given in Tables 1 and 2.
former Case Test. The effectiveness of ground- NOTE Field tests are recommended when new units are
ing of each instrument transformer case or added to an existing installation or after major field modi-
frame shall be checked by a low potential source, fications. The equipment should be put in good condition
such as 10 V or less, using bells, buzzers, or prior to the field test. It is not expected that equipment shall
be subjected to these tests after it has been stored for long
lights. This test is required only when instru- periods of time or has accumulated a large amount of dust,
ment transformers are of metalcase design. dirt, moisture, or other contaminants without first being
5.3.4 Electrical Operation and Control- restored to good condition.
Wiring Tests
5.3.4.1 Control-Wiring Continuity. The
correctness of the control wiring of a switchgear 6. Construction
assembly shall be verified by either
(1) Actual electrical operation of the compo- 6.1 General Requirements
nent control devices or 6.1.1 Buses and Primary Connections.
(2) Individual circuit continuity checks by Buses and primary connections shall be of cop-
electrical circuit testers or per or aluminum, or both. For bus ratings see
(3) Both (1) and (2) 4.4.2.
5.3.4.2 Control-Wiring Dielectric Test. A 6.1.1.1 Phase or Polarity Arrangements.
60 Hz test voltage, 1500 V to ground, shall be (1) The phase arrangement on three-phase as-
applied for 1 min after all circuit grounds have sembled switchgear buses and primary connec-
been disconnected and all circuits are wired to- tions shall be 1, 2, 3, (or A, B, C) from front to
gether with small, bare copper wire to short- back, top to bottom, or left to right, as viewed
circuit coil windings. The duration of the test from the front of the switchgear. Certain types
may be 1 s if a voltage of 1800 V is applied. At of equipment may require other phasing ar-
the option of the manufacturer switchgear rangements and a neutral conductor. In these
mounted devices that have been individually cases the phasing shall be suitably indicated.
tested may be disconnected during the test. (2) Polarities on directcurrent assembled
5.3.4.3 Polarity Verification. Tests or in- switchgear buses and connections shall be pos-
spections shall be made to ensure that connec- itive, neutral, negative, front to back, top to bot-
tions between instrument transformers and tom, or left to right, as viewed from the front of
meters or relays, etc, are correctly connected the switchgear. Certain types of equipment may
with proper polarities in accordance with circuit require other polarity arrangements. In these
diagrams. Instruments shall be tested to ensure cases the polarity shall be suitably indicated.
that pointers move in proper direction. This does (3) Panel-mounted devices shall be mounted
not require tests using primary voltage and cur- in the same arrangement as described in (1) and
rent. (2), as viewed from the front of the panel.
5.3.4.4 Sequence Tests. LV switchgear in- 6.1.1.2 Phase Sequence. The phase se-
volving the sequential operation of devices shall quence on connection diagrams shall be such
be tested to ensure that the devices in the that, when considering voltages to neutral on a
sequence function properly and in the order polyphase system with respect to the element of
intended. time, the voltage of Phase 1will reach a maxi-
ANSI / IEEE
C37.20.1-1987 IEEE STANDARD FOR METAL-ENCLOSED LOW-VOLTAGE

mum ahead of the voltage of Phase 2, Phase 3, 6.1.3 Control and Secondary Circuits and
etc. This sequence shall be designated as phase Devices
sequence in the order 1, 2, 3, etc. 6.1.3.1 Control and Secondary Wiring.
6.1.1.3 Cable Terminations. The LV Flameresistant, 600 V insulated copper wire,
switchgear shall provide space for the devices with a cross-sectional area not less than AWG
used for making electric and mechanical con- No 14 stranded (4110nominal cmil) shall be used
nections to incoming and outgoing cables. Each on small wiring between component devices or
cable terminal connection point shall meet the parts of switchgear assemblies. Where wire is
bolt hole requirements of NEMA CC 1-1975[30], connected across a hinge, flexible (41 or more
paragraph CC14.05, Electric Power Connectors strands) wire shall be used.
for Substations. The insulated wire shall be type TBS, or SIS
6.1.1.4 Bushings, Potheads, or Other as listed in ANSI/NFPA 70-1987 [23] or an
Terminators. These devices are not ordinarily equivalent .
used in LV switchgear. The insulated wire shall meet the require-
6.1.1.5 Main Bus Splicers. When bolts, ments of the following standards publications as
nuts, and washers are provided for connecting applicable:
through buses to other sections, the length of (1)Type TBS. NEMA WC5-1973 [32] (ICEA
the bolts shall be such that the dielectric integ- s61-402)
rity is not impaired. (2) Type SIS. NEMA WC7-1971 (1976) [33]
6.1.2 Grounding. A ground bus shall be in- (ICEA 566-5241.
cluded which will electrically connect together For wiring from supervisory and annunciator
the structures in a switchgear assembly in or devices to terminal blocks, smaller wire may be
on which primary equipment or devices are used provided it is adequately supported and will
mounted. meet the voltage and current requirements of
At all points of connection between the ground the circuit. Smaller wire, when used, shall not
bus and the assembly, any nonconductive coat-
ings, such as paint, shall be removed or pene-
run in the same wire packs with other control
and secondary wiring.
-
trated to ensure good electrical contact. Bushings, grommets, or other mechanical pro-
The ground bus for each group of vertical sec- tection shall be provided for the wiring where
tions shall have facilities for connection to a control or secondary wiring is run through a
station ground bus by suitable conductors. metal sheet, barrier, or raceway.
Circuit connections to the ground bus shall be The internal wiring of component devices or
made so that it is not necessary to open circuit parts shall be in accordance with the applicable
the ground bus to remove any connection made industry standards.
to the ground bus. 6.1.3.2 Secondary-Wiring Terminals.
Ground connections shall be provided for all Stranded control wire shall have solderless ter-
removable elements to ensure that they are minals of the type wherein the body of the ter-
grounded until the primary is disconnected and minal is crimped or indented onto the conductor
the removable element is moved a safe distance where the wire is formed into an eye and con-
(see ANSI/IEEE C37.100-1981 [12], test posi- fined within a crimp and flat washer assembly.
tion. Solderless terminals are not required for con-
When mounted on metal switchgear struc- nection to devices that have integral pressure
tures, cases of instruments, instrument trans- terminal connectors.4 The wire may be soldered
formers, meters, relays, and similar devices shall into terminals or, where desirable, directly to
be considered as being adequately grounded devices, such as secondary disconnecting con-
when secured to these structures by metal tacts, or to soldered terminals on supervisory
mounting hardware with adequate provision for control and annunciator equipment.
penetrating the paint film (see 5.3.3). 6.1.3.3 Terminal Blocks. Terminal blocks
The ground bus shall be capable of carrying incorporating screw or stud-and-nut-type ter-
the rated short-time current of the LV switch- minals shall accommodate wire lugs or similar
gear for 0.5 s. devices affixed to stranded wire. Screw or stud-
,---
EXCEPTION: LV switchgear having single polarity directi
current circuits, rated above 250 V, shall be ungrounded. It 'In the absence within this standard of definitive per-
is recommended that they be connected to ground only by formance requirements, compliance with this clause can be
protective or indicating devices of relatively high resistance. assessed by referencing ANSI / UL 486A-1982 [24].

22
ANSI / IEEE
POWER CIRCUIT-BREAKER SWITCHGEAR C37.20.1-1987

and-nubtype terminals intended for use with of the circuit breaker shall be designated for the
stranded wire shall be such that all strands of contacts. As examples:
the conductor are confined. Terminal blocks in-
52MOC Open when circuit breaker is
corporating pressure connectors shall not dam-
a open
ageg the wire and, when terminating stranded
conductors, all strands shall be clamped within
the connector. 52MOC Close when circuit breaker is
Terminal blocks for external connections shall b open
be suitable to accept AWG No 10 (10 380 nom- If several auxiliary switches and contacts are
inal cmil) stranded wire. The use of solid wire present on the same device, they shall be des-
is not recommended. ignated numerically 1,2,3, etc, when necessary.
NOTE: Where long connections to the control battery are On diagrams of all types, contacts and
necessary the cable should be large enough to prevent ex- switches shall be shown in the de-energized po-
cessive voltage drop.
sition of the device.
6.1.3.4 Designation ofAuxiliary Switches 6.1.3.5 Device Function Numbers. Device
and Contacts. The operation of auxiliary function numbers shall be in accordance with
switches and contacts for circuit interrupting ANSI / IEEE C37.2-1979 [7].
and switching devices shall be designated as 6.1.3.6 Voltage Limits of Instrument and
follows: Control Circuits. Voltage and current trans-
a Open when the device is in the de- formers shall be used for all instruments, me-
energized or nonoperated position ters, and relays connected to alternatingcurrent
circuits over 240 V so as to reduce the voltage
b Closed when the device is in the de- on instrument wiring which must necessarily be
energized or nonoperated position closely grouped.
Directcurrent instruments, meters, and re-
aa Open when the operating mechanism lays may be used directly on circuits up to
of the main device is in the deenergized 750 V if their cases are grounded to the switch-
or nonoperated position gear structures in accordance with 6.1.2.
Directcurrent instruments, meters, and re-
bb Closed when the operating mechanism lays together with their associated wiring and
of the main device is in the deenergized accessories, when used on circuits over 750 V,
or nonoperated position shall be connected through isolating trans-
ducers.
Special contacts and auxiliary switches EXCEFTION (1): Instruments, meters, and relays along
with their associated wiring and accessories may be con-
other than a, b, aa, or bb nected directly to circuits over 750 V dc when the instru-
k ment, meter, or relay and its associated wiring and
Auxiliary switches mounted on the stationary accessories are isolated from other instruments, meters, r e
lays, and their associated wiring and accessories and where
housing used to indicate the connected position the cases of such devices are left ungrounded and are pro-
of the removable element shall have a suffix vided with suitable protective barriers, insulated covers, or
TOC (circuit-breaker truck-operated cell switch). guards.
The position of the removable element in which EXCEPTION (2): Ground detectors may be connected di-
the contacts are closed or open shall be desig- rectly to circuits up to 600 V ac, if connected to ground
through voltage dividing resistors. The resistors should not
nated. As examples: be mounted on the instrument panel and the wires should
be isolated from other control wiring.
52TOC Open when the circuit breaker
a is not in the connected position 6.1.3.7 Polarity of Direct-Current Con-
Closed when the circuit breaker nections to Device Coils. Where coils on de-
52TOC
vices used in LV switchgear are connected to a
b is not in the connected position
directcurrent supply and when de-energized,
Auxiliary switches mounted on the stationary are not disconnected from both the positive and
housing operated by the circuit breaker to in- negative supply leads, such coils shall be so con-
dicate circuit-breaker openclosed position shall nected that, when deenergized, they will be left
have a suffix MOC (circuit-breaker mechanism- connected to the negative supply lead to mini-
operated cell switch). The openclosed position mize the possibility of corrosion.

23
ANSI/ IEEE
C37.20.1-1987 IEEE STANDARD FOR METAL-ENCLOSED LOW-VOLTAGE

6.1.3.8 Voltage Circuit Protection. All NOTE. Voltage and control power transformer primary
fuses are intended for use as a protective function only and
voltage circuits used for control, relaying, or me- are not intended to be used as disconnect devices. When a
tering shall be protected within the LV switch- primary disconnect meam is required, a dead-front design
gear as follows: switch or fuse pullout should be used with these trans-
formers.
(1)All circuits supplied from external sources
(ac or dc) shall have short-circuit protection 6.1.3.9 Current Transformer Secondary
within the control source incoming section. This Circuit Protection. Overcurrent protection of
may be provided by a single set of short-circuit current transformer secondary circuits shall not
protective devices. be provided.
(2) All circuits supplied from internal sources 6.1.4 Miscellaneous
(ac or dc) shall have short-circuit protection 6.1.4.1 Nameplate Marking. The follow-
within the same section as the supply source. If ing minimum information shall be given on
these circuits are supplied by a control power switchgear assemblies nameplates:
transformer, this protection may be in the pri- (1) Manufacturer’s name and address
mary circuit only. (2)Manufacturer’s type designation (optional)
Overcurrent protection of voltage circuits may (3)Manufacturer’s identification reference
be provided in addition to the required short- (4)Rated maximum voltage (where applica-
circuit protection. ble)
Voltage transformers are required whenever (5) Rated frequency (where applicable)
the nominal primary voltage is greater than 6.1.4.2 Wiring Devices. Lighting fixtures
240 V ac. provided in outdoor switchgear shall be of a type
Other circuits supplying loads, such as heat- and shall be so located that lamps may be safely
ers, receptacles, or lights shall have overload replaced without deenergizing the primary
and short-circuit protection. equipment. Convenience outlets shall be of the
two-pole, threewire grounding type and pro-
6.1.3.8.1 Control Power Transformers. tected by a ground-fault interrupter.
Short-circuit protection of control power trans- 6.1.4.3 Ventilation Openings and Vent
formers shall be provided in accordance with Outlets. Openings for pressure relief or venti-
Table 8. lation shall be so arranged that the gas or vapor
6.1.3.8.2 Voltage Transformers. Volt- escaping during normal operation will not en-
age transformers shall be protected in the pri- danger personnel operating the switchgear.
mary circuit with currenblimiting fuses not 6.1.4.4 Service Disconnecting Means.
larger thhn 10 A. Switchear assemblies designated as the service
6.1.3.8.3 Isolation. Switches, fuse pull- disconnecting means shall be designed so that
outs, and molded-case circuit breakers used to they can be installed in accordance with the
disconnect devices from the primary circuits applicable provisions of ANSI/NFPA 70-1987
shall be of a dead-front design. [23], Section 230.

Table 8
Control Power Transformer Short-circuit Protection
Primary Maximum Current-LimitingFuses for Control
Single Phase Power Transformers(A)
OCVA) 240 V 48OV 6OOV
Upto lkVA 10 * 10 *6
2 20 10 * 10
3 30 15 15
5 50 25 20
7.5 80 40 30
10 100 50 40
15 150 80 60
Due to inrush current certain types of current-limitingfuses may require larger ratings
than those shown, but shall not exceed 20 A.

24
ANSI / IEEE
POWER CIRCUIT-BREAKER SWITCHGEAR C37.20.1-1987

6.2 Materials and Finish provided in the bus compartments. Where buses
6.2.1 Materials. The materials for LV switch- and connections penetrate internal barriers,
gear assemblies shall be sheet metal suitably suitable insulation or clearance shall be pro-
supported. Barriers between compartments as vided.
listed in 6.3 shall not be less than MSG No 11
(nominal thickness 0.1196 in or 3 mm). All other 6.4 Buses and Connections.The bus and con-
covers, barriers, panels, and doors shall not be nections shall be bare except where close clear-
less than MSG No 14 (nominal thickness ances may make insulation necessary. The buses
0.0747 in or 1.9 mm). shall be mounted on Class 105 or higher insu-
The minimum thickness of sheet metal used lation. See Table 3.
for LV switchgear is based on the use of steel.
Where other metals are used the thickness shall 6.5 Access Doors and Covers. A hinged door
be modified to provide equivalent strength and shall be furnished on the front of the structure
deflection." to cover each breaker compartment. Removable
Doors or panels used to support devices shall top and back plates shall also be provided in
be increased in thickness or otherwise strength- sufficient number to permit access to the bus
ened as necessary to support the devices. and connection compartments. For stationary
6.2.2 Finishes and Color. All steel surfaces equipment a bolted cover may be used in the
to be painted shall receive a phosphatizing treat- front of the breaker compartment.
ment or equivalent prior to application of paint. For ease in handling, cover plates that are
External and internal surfaces shall be coated intended to provide access for inspecting and
with at least one coat of corrosion-resisting maintenance shall not exceed 12 ft2 (1.12 m2)in
paint. The finish paint system shall comply with area or 60 lb (27 kg) unless they are equipped
the requirement of 5.2.8. with lifting means or hinges.
The under-surfaces of outdoor assemblies To prevent access to energized fuses in power-
shall additionally receive either a corrosion- circuit protectors, means shall be provided to
resistant undercoating or an additional thick- interlock the door, cover, or barrier so that it
ness of corrosion-resistant paint. cannot be opened unless the circuit breaker or
The preferred color for the finish on switch- switch is in the open position.
gear assemblies shall be light gray No 61 per
ASTM D1535-80 [28], (MUNSELL NOTATION 6.6 Closing and Tripping. Mechanical means
8.3 G6.10/0.54). for closing and tripping manually operated
breakers and for manually tripping electrically
NOTES (1) See ANSI 255.1-1967 (R 1973) [5].
(2) Internal detail parts may have metallic plating or operated breakers shall be provided and shall
equivalent in lieu of paint finish. be accessible without exposing the operator to
(3) For conformance testing a recognized organic coating live parts. See ANSI/IEEE C37.13-1981 [8] for
system that has been investigated and found suitable for
use as protection against atmospheric corrosion of electrical limitations on manually operated breakers.
equipment steel enclosures for outdoor use may be utilized.
6.7 Indoor LV Switchgear. LV switchgear for
6.3 Barriers. Each circuit breaker shall be indoor applications shall be ventilated enclo-
mounted in a separate metalenclosed compart- sures (NEMA Type 1) intended primarily to pro-
ment ventilated as necessary. Ventilation open- vide a degree of protection against contact with
ings between compartments within the low- the enclosed equipment.
voltage switchgear shall be such that the gases 6.7.1 Requirements. When completely and
produced by circuit-breaker interruption shall properly installed, these enclosures
not impair the operation of adjacent compart- (1) Shall provide a degree of protection
ments. When a bus sectionalizing breaker (or against limited amounts of falling dirt; however,
breakers) is included, barriers shall be provided they will not prevent the entry of dust or liquids.
in the bus compartment to segregate the sepa- (2) Shall prevent the insertion of the end por-
rate bus sections from each other. If no bus sec- tion of a straight rod of the specified diameter
tionalizing breaker is involved, no barriers are into the equipment cavity of the enclosure.
(3) Shall not rust when subjected to the paint
"For example, if aluminum alloy sheet, having a yield qualification test for 200 h.
strength of 20 OOO lbf / in2,is used in the place of sheet steel,
to provide equivalent strength and deflection, it is required 6.7.2 Design Tests.The enclosures shall be
that the thickness specified above be increased by 50%. tested and evaluated by

25
ANSI / IEEE
C37.20.1-1987 IEEE STANDARD FOR METAL-ENCLOSED LOW-VOLTAGE

(1) Rod entry test of 5.2.7 (1) To prevent moving the circuit breaker to h

(2) Paint qualification test of 5.2.8 or from the connected position when the circuit
breaker is in the closed position.
6.8 Outdoor LV Switchgear. LV switchgear (2) To prevent closing the circuit breaker un-
for outdoor applications shall be housed in ven- less the primary disconnectingdevices are in full
tilated enclosures (NEMA Type 3R) intended contact or are separated by a safe distance.
primarily to provide a degree of protection (3) Circuit breakers equipped with stored en-
against falling rain, sleet, and external ice for- ergy mechanisms shall be designed to prevent
mations. the release of the stored energy unless the mech-
When completely and properly installed, these anism has been fully charged. Operators and
enclosures service personnel shall be protected from the
(1) Shall not permit water to enter the equip effects of accidental discharge of the stored en-
ment cavity at a level higher than the lowest ergy by any of the following means:
live part except if constructed to divert water (a) Interlocks provided in the housing to
from live parts, insulation, wiring, and shall prevent the complete withdrawal of the circuit
have provisions for drainage. breaker from the housing when stored energy
(2) Shall require the use of a tool to gain access mechanism is charged.
to the equipment cavity or have provision for (b) A suitable device provided to prevent the
locking. complete withdrawal of the circuit breaker until
(3) Shall have doors that are equipped with the closing function is blocked.
latches and stops to hold the doors in the open (c) A mechanism is provided to automati-
position. cally discharge the stored energy during the
(4) Shall prevent the insertion of the end por- process of withdrawing the circuit breaker from
tion of a straight rod of the specsled diameter the housing.
into the equipment cavity of the enclosure. (d) Mechanisms as described above are not
(5) Shall not rust when subjected to the paint
qualifkation test for 200 h.
required provided the stored energy mechanism
and contact assembly are isolated within the -
(6) Shall have heaters or other effective breaker element and service is not possible.
means to minimize internal condensation. 6.11.2 CircuibBreaker Retention. Means
shall be provided for positively holding the cir-
Design Tests.The enclosures shall be tested and cuit breaker in place in the housing when the
evaluated by removable element is in the connected or test
(1) Rod entry test of 5.2.7 position. When breakers are left in the housing
(2) Paint qualification test of 5.2.8 in the disconnected position, they shall be se-
(3) Rain test of 5.2.9 curely held in that position by suitable mechan-
ical means.
NOTE: External icing tests are not required because LV
switchgear has no external cavities to trap water when 6.11.3 Fuse Accessibility. Where the remov-
mounted in the normal position. able element consists of a fused circuit breaker,
the fuses shall be accessible only when the re-
6.9 Pull Box. A pull box for cables is not in- movable element is withdrawn to the test, dis-
cluded in the standard equipment, but it may connected, or withdrawn position.
be furnished as an option. 6.1 1.4 Removable Element Interchange-
ability. All removable elements of the same type
6.10 Arrangements with Stationary Circuit and rating on a given assembly shall be physi-
Breakers. Circuit breakers may be stationary cally interchangeable in the corresponding sta-
mounted with or without disconnecting tionary housings. This need not include
switches. electrical interchangeability of secondary con-
trol circuits.
6.11 Arrangements with Drawout Circuit 6.11.5 Fuses on Separate Removable Ele-
Breakers. Drawout circuit breakers shall be ments. Current-limiting fuses may be mounted
equipped with self-coupling disconnecting de- on separate removable elements. The require
vices and have the following categories: ments of 6.11.4 apply to these elements, and in ,---
6.11.1 Interlocks. Mechanical interlocks addition these elements must be only used in
shall be provided in LV switchgear as follows: series with circuit breakers or switches.

26
ANSI / IEEE
P O m R CIRCUIT-BREAKERSWITCHGEAR C37.20.1-1987

Table 9
Minimum Areas for Multiple Cable Connections
Minimum Areas Required for Multiple Cables, in2
(Based on Factor of 2.5)
Size of Cable Two Three Four Five Six Seven
AWG* or Cables Cables Cables Cables Cables Cables
1 (8.7)1.35 (13.1)2.03 (17.4)2.70 (21.8) 3.38 (26.2) 4.05 (30.5) 4.73
0 (10.0)1.55 (15.1)2.33 (20.0)3.10 (25.0) 3.88 (30.0) 4.65 (35.0) 5.43
00 (11.6)1.80 (17.5)2.70 (23.20.60 (29.0) 4.50 (34.8) 5.40 (40.5) 6.30
OOO (13.5)2.10 (20.4)3.15 (27.1M.20 (33.9) 5.25 (40.5) 6.30 (47.4) 7.35
oooo (15.5)2.40 (23.2)3.60 (31.0M.80 (38.7) 6.00 (46.5) 7.20 54.1) 8.40
250 mcmil (19.0)2.95 (28.6M.42 (38.2)5.90 (47.5) 7.36 (57.0) 8.85 (66.6U0.32
350 mcmil (24.513.80 (36.8F.70 (49.217.60 (61.4) 9.50 (73.5111.40 (85.8)13.30
600 mcmil (31.7M.90 (47.4)7.35 (63.4B.80 (79.0)12.25 (95.U14.70 (110.6U7.15
'AWG = American Wire Gage mcmil = thousands of circular mils
NOTE: Numbers in parentheses are in cm2 and are approximate

To prevent access to energized fuses on these 6.13 Primary Cable Space. The clear cabling
removable elements, means shall be provided to space independent of all projections, obstruc-
interlock the door or cover so that it cannot be tions, or interference from moving parts, shall
opened unless the associated circuit breaker or not be less in total area than 250% of the total
switch is in the open position. cross-sectional area of the maximum number of
If the fuses are located on the line side of the cables which may be used in such space.
---. Table 9 gives the minimum area for the more
associated circuit breaker interlocking of the
breaker shall be provided to prevent connection common multiplecable connections.
or disconnection under load.
6.11.6 Secondary Disconnect Devices. Con- 6.14 Precautionary Labels. Each LV switch-
trol wiring connections between stationary gear should be provided with appropriate pre-
structure and the removable element shall be cautionary labels to call the user's attention to
provided with automatic (selfcoupling) contacts potential hazards that are inherent to the equip
or manual plug and receptacle for disconnection. ment and which cannot be eliminated by design.
"he manual control connector shall be either See ANSI 235.1-1972[4]and NEMA Bulletin No
interlocked or inaccessible to prevent connection 77-1973(R 1975)[34]for recommendations.
or disconnection of the control circuits when the
removable element is in the connected position 6.15 Handling Devices. Handling devices may
and the removable element shall be prevented be provided to facilitate the insertion or removal
from being installed in the connected position of drawout circuit breakers from their individ-
unless the manual control connector is con- ual compartments and consist generally of a
nected. wheeled hoist device or an overhead lift device
With the manual arrangement, all connec- attached to the switchgear itself.
tions shall be group connectable simultaneously
with the male contacts on the removable ele-
ment and the female receptacles on the station-
ary structure. 7. Application Guide for LV
Switchgear
NOTE: The intent of this requirement is to ensure that the
control connection is always made to the circuit breaker
when the circuit breaker is in the connected pwition. 7.1 Unusual Service Conditions. It is strongly
recommended that the usual service conditions,
6.12 Padlocking. Means shall be provided for as described in Section 3, be provided for LV
padlocking circuit breakers in the disconnect po- switchgear applications if practical (artificially,
sition. if necessary). However, if unusual conditions ex-

27
ANSI / IEEE
C37.20.1-1987 IEEE STANDARD FOR ME'TAL-ENCLOSED LOW-VOLTAGE

Table 10
Altitude Correction Factors
Altitude
(ft) Voltarre Current
6600 (2000 m) (and below) 1.00 1.00
8500 (2600 m) 0.95 0.99
13 0oO (3900m) 0.80 0.96
NOTE3 (1) Intermediate values may be obtained by interpolation.
(2) For devices used in switchgear assemblies, standardscovering the spe-
cific devices should be used to determine the specific altitude correction
factors.

ist and cannot be eliminated, the following con- eral construction modifications which will mit-
siderations apply. igate the effects of these environments may be
7.1.1 Ambient Air Temperature Above made in accordance with 7.1.4.1through 7.1.4.6,
40 "C.When LV switchgear is applied where the but the emphasis should be on eliminating such
ambient air temperature is higher than 40 "C conditions if at all possible. However, if these
its performance may be affected and special con- undesirable conditions cannot be eliminated,
sideration should be given to these applications. more frequent maintenance may be required.
The total temperature limits for parts and ma- 7.1.4.1 Exposure to Damaging Fumes,
terials as given in 4.5 should not be exceeded. Vapors Steam,Salt Air,and Oil Vapors. In-
Therefore, for the higher ambients, the equip door and outdoor equipment should be provided
ment should be derated to a continuous current with the following modifications:
value that maintains the total temperature lim- (1)Minimum of two coats of paint, one of
its. which should be a corrosion or rust-resisting
7.1.2 Ambient Air Temperature Below primer, on all structural parts.
-30 "C. Special consideration is also required (2) All steel parts that are not painted or
when LV switchgear is applied where the am- plated should be covered with protective grease.
bient air temperature is less than -30 "C. Space (3) All current-carrying joints should be cov-
heating and thermal insulation to minimize the ered with a coating of nonoxidizing grease.
effects of exposure should be considered. If this Greasing of nonarcing contacts should only be
is not possible, the effect of low temperatures done on recommendations of the manufacturer.
on the functional performance of such materials (4)All coils should be impregnated with in-
as oils, plastic insulation on primary and sec- sulating compound and covered with an appro-
ondary circuits, control wire insulation, and lu- priate protective coating.
bricants should be considered. (5) Heaters, in quantity and rating sufficient
7.1.3 Application at Unusual Altitudes. to minimize condensation in all compartments,
Switchgear assemblies that depend on air for an should be furnished.
insulating and cooling medium will have a 7.1.4.2 Exposure to Excessive Dust,
higher temperature rise and a lower dielectric Abrasive Dust, and Magnetic or Metallic
withstand capability when operated at altitudes Dust. Indoor or outdoor equipment should be
above values specified in Section 3. For appli- provided with the following modifications: To-
cations at higher altitudes, the rated one-minute tally enclosed nonventilated equipment should
power-frequency withstand voltage and contin- be furnished with a current rating of 70% of the
uous current rating of the assemblies should be ventilated rating or as specified by the manu-
multiplied by the correction factors in Table 10 facturer. Condensation could be a problem and
to obtain the modified ratings. should be evaluated.
7.1.4 Modification of Equipment for Unu- Ventilation filters for outdoors assemblies: For
sual Environment. Successful performance of outdoor assemblies ventilated enclosures may be
standard LV switchgear may be extended to un- furnished with the ventilating openings
usual environments by special considerations equipped with dust filters. The requirements for
when developing equipment specifications. Sev- these filters vary over such a range that stan-

28
ANSI / IEEE
POWER CIRCUIT-BREAKERS W l " G E A R C37.20.1-1987

- dard specifications for their application are not


practicable. Filters are available in both the
70 (R 1980) [30].Materials to be classified as
fungus-resistant should have a rating not
washable type and the disposable type. Where greater than 1.
used, they must be cleaned or replaced at inter- (7)Materials that are made fungus-resistant
vals, depending upon the amount of dust in the by means of a coating should have the coating
air. Filters that are not cleaned or changed when reapplied at periodic intervals.
required can c a w excessive equipment tem- 7.1.4.4 Exposure to Explosive Mixtures
perature or condensation. of Dust or Gases. Application of LV switchgear
The type of filter used should be selected based for explosion-proof requirements is not recom-
on the size of dust particles encountered and the mended.
extent to which dust is to be excluded. Where 7.1.4.5 Exposure to Abnormal Vibration,
very fine dust particles are to be excluded, dis- Shocks, or Tilting. Indoor and outdoor equip
posable filters soaked in oil should be used. ment is designed for mounting on level struc-
These must be changed at frequent intervals. tures free from vibration, shocks, or tilting.
Forced ventilation may be required depending Since these conditions vary so widely, it is
upon the volume of air required for ventilation recommended that the manufacturer be con-
and the severity of the environment. When fur- sulted for each specific application where vibra-
nished due to environment, the blower and filter tion, shocks, or tilting are to be encountered.
should be installed on the intake to minimize It is important that the full nature of the ab-
the possibility of drawing dust or other foreign normal motion be specified. The magnitude and
matter into and throughout the switchgear as- frequency range of the dynamic motion is re-
sembly. quired so that resonances may be investigated.
7.1.4.3 Exposure to Hot and Humid Cli- This is usually specified by means of an accel-
mate. Indoor and outdoor equipment intended eration response spectrum curve for the mount-
for exposure to hot and humid climates should ing surface on which the LV switchgear is to be
be made fungus-resistant by the following mod- installed. The response spectrum is a plot of the
ifications: maximum response of single-degree-of-freedom
(1) Heaters in quantity and rating sufficient bodies, at a damping value expressed as a per-
to minimize condensation in all compartments cent of critical damping of different natural fre-
should be furnished. quencies, when these bodies are rigidly mounted
(2) Secondary wiring that is not inherently on the surface of interest (that is, on the ground
fungus-resistant should have fungus-resistant for the ground response spectrum or on the floor
coating applied. Secondary wiring that has fun- for the floor response spectrum) when that sur-
gus-resistant insulation should not require fur- face is subjected to a given abnormal motion as
ther treatment. modified by any intervening structures. The re-
(3) All impregnated coils should be given an sponse spectrum is useful in designing a test or
external treatment with fungus-resistant coat- in making an analysis of the performance of the
ing. Encapsulated coils that are inherently fun- LV switchgear equipment mounted on the same
gus-resistant should not require further surface and subjected to the same motion.
treatment. In the case of tilting it is also important that
(4) Paintssuch as alkyd enamels having a fun- the maximum angles of tilt, both transverse and
gus and rust-resistant property should be used. longitudinal, be specified. The exact perform-
(5) Insulation that is not inherently fungus- ance requirements should also be defined. It
resistant should have fungus-resistant coating should be recognized that equipment that is spe-
applied. Insulation in switchgear assemblies cifically designed for a usual installation on a
that is inherently fungus-resistant should not substantially level surface free from excessive
require further treatment. Fungus-resistant vibration, shock, or tilting may be damaged and
coatings should not be applied where they will may not be able to function properly when sub-
interfere with proper operation of apparatus. In jected to excessive motion and displacement.
such cases,the part should be inherently fungus- Hence, the application should be carefully ana-
resistant. These coatings should not reduce the lyzed and the essential performance require-
- flame-resistant properties. ments should be precisely defined.
(6) The fungus-resistance of materials should 7.1.4.6 Exposure to Seismic Shock. Be-
be determined in accordance with ASTM G21- cause of the importance of adequate perform-

29
ANSI / IEEE
C37.20.1-1987 IEEE STANDARD FOR METAL-ENCLOSED LOW-VOLTAGE

ance of equipment when applied as Class 1E perature, the following considerations are in
equipment in a nuclear power generating sta- order:
tion, ANSI/IEEE SM 3441975 [21]was devel- (1)It is permissible to exceed rated current
oped for this application. for short periods, such as in the starting of mo-
tors or synchronous condensers, or when ener-
7.2 System Characteristics-Voltage and gizing cold loads. Generally, the short duration
Frequency. LV switchgear is designed for use of this type of current increase does not raise
on threephase, 60 Hz, grounded or ungrounded temperatures significantly.
ac systems. Application on other types of sys- (2) When several switchgear compartments
tems, such as are included in the same vertical section, con-
sideration must be given to the allowable cu-
(1) dc
(2) Three phase, 4-wire with insulated neutral mulative loading of the section (see 7.4.1).
(3)! b o phase 7.4.1 Load Current-Carrying Capability of
(4)Frequency other than 60 Hz AC LV Switchgear. For ac LV switchgear,
should be reviewed with the manufacturer. which may include one to four compartments in
LV switchgear is intended for application on a single vertical section, the followingguidelines
systems where the maximum operating voltage are recommended for estimating the allowable
of the system does not exceed the rated maxi- cumulative loading.
mum voltage for which the equipment is d e 7.4.1.1 Determination of Main Bus Load
signed. The voltages for various types of LV Current-Carrying Capability. The ampacity
switchgear are listed in Tables 1 and 2. for the main bus is usually a function of the
main circuit breaker frame size or the current
output of the supply transformer. The ampacity
7.3 Overvoltage Considerations - Insula- of the main bus is based on the temperature
tion Levels. The insulation levels to which LV limitations as described in 4.5.
switchgear is designed are also listed in Tables 7.4.1.2 Determination of Vertical Sec-
1 and 2. tion Load CurrentcCarrying Capability. The
load currenkarrying capability of a vertical sec-
7.4 Continuous Current Rating and Over- tion consisting of one, two, three, or four circuit
load Capability. LV switchgear assemblies are breakers should be determined by the lesser of
designed for normal application where the sus- the following two considerations:
tained load current does not exceed the rated (1)The main bus continuous current rating.
continuous current, the altitude above sea level (2)The allowable cumulative circuit-breaker
does not exceed 6600 ft (2000 m), the ambient loading.
air temperature does not exceed 40°C,and the 7.4.1.3 The Cumulative Circuit-Breaker
effects of solar radiation can be neglected. For Load -AC LV Switchgear. The cumulative
unusual altitudes, derating factors should be ap- circuibbreaker loading is the total current that
plied in accordance with 7.1.3.If solar radiation all circuit breakers within a vertical section can
is significant, continuous current capability is carry simultaneously without exceeding the
limited and one should refer to ANSI/IEEE temperature limits in 4.5.The preferred values
C37.241971 (R 1984)[lo]. for allowable cumulative circuibbreaker loading
The rated continuous current is based on not are as given in Table 11.
exceeding the limits of the hottest-spot total tem-
perature of the various parts of the switchgear NOTE: The values of allowable cumulative load can be
based on equal loading (as a percentage of rating) of all
assembly when this value of current is sustained compartments in the same vertical section. If equal loading
in an ambient air temperature of 40°C. When is not practical, the load distribution should be such that
the ambient air temperature is greater than the heavier loads are connected to the lowest circuibbreaker
compartment. Typically, a section with four equally rated
40 "C,the current should be reduced to less than circuit-breaker compartments should be loaded as follows:
rated continuous current to keep the total tem- (1) Bottom compartment 100% of compartment rating
(2) Second compartment 75% of compartment rating
perature of these parts within allowable limits. (3)Third Compartment 60% of compartment rating
The application of switchgear assemblies should (4) Top compartment 50% of compartment rating
be based on avoiding operation at current higher The cumulative load should be checked against Table 11. h

This type of arrangement provides optimum heating distri-


than the rated continuous current of the assem- bution in a section. If other arrangements are required, it
bly. However, since the criterion is total tem- is recommended that the manufacturer be COnSUlted.

30
ANSI / IEEE
POWER CIRCUIT-BREAKER SWITCHGEAR C37.20.1-1987

- Table 11 (3) All other equipment must be properly co-


CircuibBreaker Loads ordinated, including the protective equipment
Circuit Breaker Number of Allowable on the high-voltage side of power transformers,
Frame Size Circuit-Breakers Cumulative Load and also short-time ratings of current trans-
(A) Carrying Load (A) formers, series reactors, cables, and buses. For
600 1 600 further information on selective tripping, see
600 2 loo0
600 3 1400 ANSI/IEEE Std 141-1986 [17].
600 4 1700 7.5.2 Application of Circuit Breakers in
800 1 800 Cascade. Application of circuit breakers in cas-
800 2 1300 cade (above their short-circuit current ratings)
800 3 1800
800 4 2200 is not recommended.
1600 1 1600
1600 2 2600 7.6 Nuclear Power Plant Application. LV
1600 3 3600
16OC 4 4500 switchgear applied in nuclear power generating
2ooG 1 2000
stations and particularly as Class 1E equipment
2000 2 3200 should meet the requirements of pertinent stan-
3000 1 3000 dards that have been developed for such appli-
3Ooo 2 4800 cations.
4Ooo 1 4Ooo
7.7 Associated Devices Often Used in LV
Switchgear
7.7.1 Current Transformers. Current trans-
formers included in LV switchgear are in ac-
7.4.1.4 Conductor Temperature. Cables cordance with 4.6 and 4.7. The accuracies listed
- connected to LV switchgear should be capable in 4.7 are the minimum supplied in the usual
of withstanding the 65 "C ambient temperature design of this equipment, and are adequate for
to whidh they may be subjected. most applications. If an application requires
7.4.1.5 Conductor Terminations. Consid- higher accuracies, it should be specified by the
eration should be given to the use of suitable user. It should be recognized that current trans-
connectors that are designed for use with the formers with higher accuracies than those listed
outgoing conductors and terminals in the switch- in 4.7 may not meet the requirements of 4.6. The
gear units. manufacturer should be consulted for possible
solutions to the problem of obtaining required
7.5 Short-circuit Considerations. LV switch- accuracy without compromising on other re-
gear should have short-circuit capability equal quirements.
to or greater than the short-circuit capability of 7.7.2 Surge Protective Devices
the system on which it is applied. The short- 7.7.2.1 Rotating Equipment. Capacitors
circuit capability of the LV switchgear is equal or surge arresters, or both, used to protect the
to that of the smallest frame size circuit breaker insulation of rotating machines, should be
utilized. housed in a suitable enclosure adjacent to the
7.5.1 Selective Trip Arrangement. Low- machine and connected without fuses or discon-
voltage power circuit breakers are suitable for necting devices. Cable connections to these de-
selective tripping arrangements when the fol- vices should be able to withstand possible short-
lowing precautions are taken: circuit current, both thermally and mechani-
(1) All the requirements of ANSI/IEEE cally.
C37.13-1981 [8] should be met. 7.7.2.2 Exposed Circuits. Protection
(2) Selective tripping is usually accomplished against lightning surges should be considered for
with circuit breakers utilizing direct-acting all switchgear assemblies having exposed cir-
series-tripping devices integral with the circuit cuits. Exposed circuits are those outside of build-
breaker. Relay tripping may be used provided ings or those that do not have adequate surge
- the total time to clear the circuit (including protection connected to limit voltages to less
relay, shunt trip, and circuit breaker time) does than the withstand level of the switchgear.
not exceed the short-time rating of any of the 7.7.2.3 Surge Arresters in Switchgear
circuit breakers. Assemblies. Surge arresters used in switchgear

31
ANSI / IEEE
C37.20.1-1987 IEEE STANDARD FOR METAGENCLOSED LOW-VOLTAGE

assemblies should have adequate discharge ca- 7.8 Protection and Isolation of Switchgear -
pability and be voltage limiting to keep voltage C o ~ e ~ t e to
d Other Circuit Protective
surges below the insulation level of the protected Equipment. When LV switchgear is electrically
equipment. Special consideration should be connected to other power switching and circuit
given to the use of coordinated surge arresters protective equipment, tie circuit protective
for LV switchgear installed at high altitudes. equipment should be provided in the connection
7.7.3 Ground Detectors. The following between the two so that a fault in one assembly
methods are recommended for ground detectors will not result in the loss of the other assembly.
furnished on power switchgear assemblies.
NOTE: Where both assemblies supply power to an entire
NOTE: These ground detectors are useful only on normally integral unit process, 80 that the shutdown of one part n e
ungrounded circuits. ceasitates the shutdown of the entire process, tie circuit
protective equipment is not required. For additional infor-
(1) Application to nominal voltages up to and mation and further study of switching arrangements see
Industrial and Commercial Power Systems Standards
including 240 V alternating current. Lamps or ANSI/IEEE Std 141-1986[17],ANSI/IEEE Std 142-1982
voltmeters connected from the power conductors [18],ANSI/IEEE Std 241-1983[19],ANSI/IEEE Std 242-
to ground without the use of transformers. 1986 [20], and ANSIIIEEE Std 4461987 [22].
(2) Application to nominal voltages above
240 V
(a) Transformers Connected Wye-Wye: For 7.9 Overcurrent Protection. For alternating-
three-phase systems, use 3 transformers rated current applications, overcurrent protection is
for line-to-line voltage connected wye-wye with usually provided for each ungrounded phase
primary neutral grounded and lamps or volt- conductor. However, alternately, the twu-phase
meters connected across the secondaries of the overcurrent, residual ground arrangement is ac-
transformers. ceptable protection.
The primary neutral of the transformers
should be stabilized by either connecting resis-
tors in parallel with the lamps or voltmeters
across the transformer secondaries, or connect-
ing a resistor between the primary neutral of
the transformers and ground. 8. Guide for Handling, Storage, and
(b) l’!ransformers Connected Wye-Broken Installation
Delta: Eor three-phase systems, use 3 trans-
formers rated for line-to-line voltage connected 8.1 General. This section is a guide for the han-
wyedelta with neutral of primary wye-grounded dling, storage and installation of LV switchgear,
and with a voltage relay, to give indication of and emphasizes safety aspects and other consid-
ground, connected in the brokendelta corner of erations when working with this type of equip
the 3 transformer secondaries. ment. It supplements, but does not replace, the
The primary neutral of the transformers manufacturer’s detail instructions on these sub-
should be stabilized by either connecting a re- jects. The objective is to furnish additional guide-
sistor in parallel with the voltage relay across lines to promote and enhance a reliable
the brokendelta corner of the 3 transformer sec- installation.
ondaries or connecting a resistor between the The manufacturers of LV switchgear include
primary neutral of the transformers and ground. instruction books and drawings with their equip
The relay should have a minimum voltage rating ment, containing detailed recommendations for
of 1.73 times the nominal secondary line-to-line storage, handling, installation, operation, and
voltage of the transformers. maintenance.
(c) Lamps or voltmeters may be used for Personnel responsible for these functions
nominal voltages up to 600 V if connected to should review these recommendations before
ground through voltage dividing resistors that handling the equipment. Particular attention
will limit the voltage applied to a lamp recep should be given to recommendations for prepa-
tacle (with bulb removed) or to a voltmeter dur- ration of foundation and forms on which the
ing ground conditions to 240 V. switchgear is to be mounted. One set of manu-
facturer’s instruction books should remain with
NOTE: Due to variations in brilliance between lamps, volt- the LV switchgear when in storage or at the
meters are preferred for ground indication. installation site.

32
ANSI / IEEE
C37.20.1-1987
POWER CIRCUIT-BREAKER SWJ!I’CHGEAR

8.2 Handling 8.2.4 Installation. When installing LV


8.2.1 Receiving. LV switchgear should be switchgear
carefully inspected and packed before leaving (1) Protect workers adequately from live parts
the factory. Immediately upon receipt, the with barriers, screens, etc.
equipment should be examined for damage that (2) ANSI (32-1987 [l], Part 1, Rule 124 for
may have been sustained during transit. If dam- guarding live parts shall be observed.
age is evident or indications of rough handling 8.2.5 Removal of Shipping Members. Be-
are visible, the carrier (transportation company) fore installation of LV switchgear a careful
and the manufacturer should be notified check should be made to ensure that all mem-
promptly. bers included for shipping purposes, have been
Only authorized personnel should be permit- removed.
ted to handle the equipment. Care should be 8.2.6 Connections
exercised in handling each piece of equipment 8.2.6.1 Bus Connections. When the LV
(even if crated) because parts may be damaged. switchgear consists of several shipping sections,
8.2.2 Rigging. Instructions for lifting and the main bus is necessarily disconnected before
handling of the equipment are contained in the shipping. The main bus should be reconnected
manufacturer’s instruction books and drawings. with particular attention to the cleanliness of
The rigging should be adequate for the size and and pressure between the contact surfaces. It is
weight of the equipment. essential that the connections be securely bolted
8.2.3 Storage. Indoor switchgear that cannot because the conductivity of the joints is depen-
be installed immediately should be stored in a dent on the applied pressure. Refer to the man-
dry, clean location and should remain protected ufacturer’s torque instructions and any other
during the storage period. The longer the period special instructions.
of storage, the greater the care required for pro- 8.2.6.2 Cable Connections. Before making
tection of the equipment. During storage, the up the cable connections, the phasing of each
LV switchgear should be placed on a level sur-
-. face to prevent unnecessary strain and possible
cable should be determined in accordance with
the connection diagram and the cables tagged
distortion. During the construction period, pro- accordingly. The cable manufacturer’s instruc-
tection should be provided against dust, dirt, fall- tions should be followed when forming cable ter-
ing objects, dripping water, excessive water, minations and during the installation of the
excessive moisture, and other possible causes of cable. It is essential that the connections be
damage to the equipment. Any temporary cov- clean and securely bolted, since the conductivity
ering should not restrict ventilation and should of the joints is proportional to the applied pres-
not be removed until the equipment is ready for sure. The terminating devices (where required)
installation. It is preferable to store indoor should be installed pursuant to the terminator
equipment within a heated building. If this is manufacturer’s instructions.
not possible, special precaution should be taken 8.2.6.3 Control Connections. Control
to keep the equipment sufficiently warm with wires between shipping sections should be re-
adequate ventilation to prevent condensation connected as marked by the manufacturer. Con-
during the storage period. If necessary, tempo- nections which are to be connected to terminals
rary heating should be installed in the equip in apparatus remote from the switchgear should
ment. be carefully checked against the connection dia-
If outdoor switchgear cannot be installed and gram. When making connections to terminals,
energized, temporary power must be provided care should be exercised to ensure that the con-
for the operation of the space heaters provided nections are properly made.
so as to prevent condensation of moisture within 8.2.6.4 Grounding. Sections of ground bus
the housing. previously disconnected at shipping sections
must be reconnected when the units are in-
WARNING Disconnect normal supply stalled. Make sure that all secondary wiring is
source to prevent backfeed. connected to the switchgear ground bus as in-
dicated on the drawings. The ground bus should
be connected to the system ground with as direct
Ventilation openings in LV switchgear should a connection as possible and should not be run
be left open to permit proper circulation of air. in metal conduit unless the conduit is ade-

33
ANSI / IEEE
C37.20.1-1987 IEEE STANDARD FQR METAL-ENCLOSED LOW-VOLTAGE

quately bonded to the circuit. The grounding final check for phase rotation/sequence before _-
conductor should be capable of carrying the the switchgear is finally energized for service.
maximum line-*ground shortcircuit current
for the duration of a fault. A reliable ground 8.4 Removable Elements. All circuit breakers
connection is necessary for every switchgear in- should be inspected for damaged parts and any
stallation. It should be of sufficient ampacity to loose connections pursuant to the manufactur-
handle any abnormal condition that might occur er’s instructions. Check manual operation with
on the system and should be independent of the the manual closing lever or with the mainte-
grounds used for other apparatus. A permanent nance closing handle on the larger size circuit-
low-resistance ground is essential for adequate breaker elements. Trip each circuit breaker by
protection and safety. operating the manual trip device. Operation
with maintenance handle and slow closing
should be done outside the breaker cubicle.
8.3 Preoperation Check. Care must be exer- Power-operated circuit breakers should be
cised to prevent the LV switchgear from being checked for proper operation while in the switch-
energized from the power system while prelim- gear cubicle test position, for both closing and
inary tests are being conducted. If disconnecting tripping at the normal control voltage.
means is not available, line leads should be dis-
connected. All internal connections should be 8.5 Interlocks. Interlocks should be checked for
examined to ensure that they have not been proper operation before power is applied to the
loosened or damaged during shipment or in- switchgear. Check interlock between removable
stallation and all bolted connections and joints element and housing to see that
should be tightened to ensure good contact. If (1) The element cannot be moved to or from
spring washers are used under bolt heads and the connected position when the circuit breaker
nuts, they should be tightened in accordance is in the closed position
with manufacturer’s instructions. All wiring (2) The circuit breakers cannot be closed un-
less it is in the fully connected position or in the ---
connections should be checked for tightness, in-
cluding those at instrument transformers and test position
all terminal blocks. Remove current trans- So as to maintain the integrity of key interlock
former shorting devices on all active circuits. systems, duplicate keys should be destroyed or
Remove all ties and blocking from the relay retained in a place accessible only to authorized
armatures or discs before the control energy is personnel.
applied.
Protective relays, overcurrent trip devices, 8.6 Ehergization. After the removable circuit-
and breaker attachments included with the LV breaker elements and interlocks have been
switchgear should be tested for correct connec- tested satisfactorily,the circuit breakers may be
tions and operation at the factory. However, the moved to the connected position. Each compart-
protective device settings for current, voltage, ment door should be closed and latched before
or other quantities must be made by the user in energizing the circuit.
accordance with his operating practices. The
manufacturer’s instruction books should be
studied carefully before setting the protective
devices.
It is recommended that the integrity of control 9. Bibliography
buses be checked with an ohmmeter to ensure
against short circuits in the control wiring. Con- @31] ANSI C37.17-1979, American National
trol wiring should be given a high-potential test Standard Trip Devices for AC and General Pur-
or be insulation-resistancetested and power cir- pose DC Low-Voltage Power Circuit Breakers.
cuits, such as buses and circuit breakers should
be given a low-frequency withstand test as de- [B2]ANSI/IEEE C37.181979, IEEE Standard
scribed in 5.2.1 and 5.5. After LV switchgear has Requirements for Enclosed Field Discharge Cir-
been installed and all interconnections com- cuit Breakers for Rotating Electric Machinery. -
pleted, any control schemes should be opera- [B3] ANSIIIEEE C37.23-1970, IEEE Guide for
tionally tested and power connections given a Calculating Losses in Isolated-Phase Bus.

34
ANSI / IEEE
POWER CIRCUIT-BREAKER SWITCHGEAR C37.20.1-1987

[B4] ANSI / IEEE C37.27-1972, American Na- [B7] ANSI/IEEE Std 308-1980, IEEE Standard
tional Standard Application Guide for Low-Volt- Criteria for Class 1E Power Systems for Nuclear
age AC Non-Integrally. Power Generating Stations.
[B5] ANSI / IEEE C37.29-1981, American Na- [BSI ANSI / IEEE Std 323-1983, IEEE Standard
tional Standard Low-Voltage AC Power Circuit Qualifying Class 1E Equipment for Nuclear
Protectors Used in Enclosures. Power Generating Stations.
[B9] NEMA SG5-1981, Power Switchgear As-
[B6] ANSI C37.52-1974 (R 1980), American Na- semblies.
tional Standard Test Procedures for Low-Volt-
age AC Power Circuit Protectors Used in [BlO] NFPA 70B-1983, Recommended Practice
Enclosures. for Electrical Equipment Maintenance.

-.

35

También podría gustarte