CUADRO DE CARGAS

VIVIENDA MULTIFAMILIAR

CARGA POT FACTOR MAXIMA MAXIMA


TABLERO UNIT. INST. DE DEMANDA DEMANDA
PISO DESCRIPCION CANT.
(Ubicación) (W) (Kw) DEMANDA (Kw) (1) (Kw) (2)
(TG-1) (TD-3)
Circuito (C-1) - Luminarias circulares TD-1 13.00 32.00 0.42 1.00 0.42
Circuito (C-2) - Luminarias circulares TD-1 10.00 32.00 0.32 1.00 0.32
Circuito (C-1) - Dicroicas TD-1 3.00 70.00 0.21 1.00 0.21
Circuito (C-2) - Dicroicas TD-1 2.00 70.00 0.14 1.00 0.14
Circuito (C-3) - Tomacorrientes normales TD-1 9.00 300.00 2.70 0.40 1.08
Circuito (C-4) - Tomacorrientes normales TD-1 11.00 300.00 3.30 0.40 1.32
1ER PISO Y
AZOTEA (TG-1 -- Circuito (C-5) - Cocina Electrica TD-1 1.00 400.00 0.40 0.35 0.14
TD-1 -- TD-2) Cicuito (C-6) - Lavadora TD-1 1.00 400.00 0.40 0.35 0.14
Circuito (C-7) - Electrobomba TD-1 1.00 750.00 0.75 0.35 0.26
Circuito (C-1) - Luminarias circulares TD-2 11.00 32.00 0.35 1.00 0.35
Circuito (C-2) - Luminarias circulares TD-2 10.00 32.00 0.32 1.00 0.32
Circuito (C-3) - Tomacorrientes normales TD-2 10.00 300.00 3.00 0.35 1.05
Cicuito (C-4) - Lavadora TD-2 1.00 400.00 0.40 0.35 0.14
Circuito (C-1) - Luminarias circulares TD-3 16.00 32.00 0.51 1.00 0.51
Circuito (C-1) - Dicroicas TD-3 1.00 70.00 0.07 1.00 0.07
Circuito (C-2) - Tomacorrientes normales TD-3 9.00 300.00 2.70 0.40 1.08
2DO PISO (TD-3)
Circuito (C-3) - Tomacorrientes normales TD-3 12.00 300.00 3.60 0.40 1.44
Circuito (C-4) - Cocina Electrica TD-3 1.00 400.00 0.40 0.35 0.14
Circuito (C-5) - Lavadora TD-3 1.00 400.00 0.40 0.35 0.14
Circuito (C-1) - Luminarias circulares TD-4 17.00 32.00 0.54 1.00
Circuito (C-2) - Tomacorrientes normales TD-4 11.00 300.00 3.30 0.40
3ER PISO (TD-4) Circuito (C-3) - Tomacorrientes normales TD-4 10.00 300.00 3.00 0.40
Circuito (C-4) - Cocina Electrica TD-4 1.00 400.00 0.40 0.35
Circuito (C-5) - Lavadora TD-4 1.00 400.00 0.40 0.35
Tablero de llegada de acometida
MAXIMA MAXIMA
DEMANDA DEMANDA
(Kw) (3) (Kw)
(TD-4)

5.89

3.38

0.54
1.32
1.20 3.34
0.14
0.14
12.62