Está en la página 1de 5

2013 International Conference on Renewable Energy and Sustainable Energy [ICRESE’13]

Impact of Distributed Generation on


Protective Relays
Sujo P George Ashok S M N Bandyopadhyay
Department o Electrical Engineering Department o Electrical Engineering Director
NIT Calicut NIT Calicut NIT Calicut
Kerala, India Kerala, India Kerala, India
sujop709@gmail.com ashoks@nitc.ac.in director@nitc.ac.in

Abstract— The current power system is working under quality problems, degradation in system reliability, reduction in
sustaining energy shortages. The distributed generation (DG) can the efficiency, over voltages and safety issues, increase in short
be a solution for the energy shortage. Distributed generation circuit level, co-ordination problems in relays, poor voltage
refers to generation of power using a set of small sized generators regulation, sag and swells, harmonics, voltage flicker, voltage
that produces power at low voltage levels. The distributed
dips, sustained interruptions and voltage unbalance. The change
generators are mainly designed to be connected directly to the
distribution network near load centres. The distributed in fault current level (FCL) can in turn alter device
generation have some negative impacts in the power grid. DG is discrimination; reduce reach of over current relays and distance
connected to the grid through power converters. These power relays, cause sympathetic tripping, force unintentional islanding
converters results in power quality problems. The power quality etc.
problems include frequency fluctuation and harmonics which The correct behavior of protective relays is important to
results in maloperation of relays. Many of the DG sources like assure three main functions 1.) Prevent possible failures,
wind, solar etc are intermittent in nature. The source impedance reducing economical losses resulting from equipment
is varying in nature due to these intermittencies. The fault current destruction. 2.) Mitigate the destructive consequences of
characteristics are changing in the presence of distributed
generation. Existing relay settings will not sense these change,
possible failures (faults) and avoiding its propagation.
which leads to maloperation of relays. The adaptive relaying can 3.) Prevent relay maloperation which cause unnecessary
be a solution for the malfunction of relays. Adaptive relaying disconnection of the healthy parts of the network and could
means the relay has to adapt to the changing environment. The potentially lead to system instability. [5]
decision making capability is to be incorporated with existing
relays. The intelligence capability must be added to the relays. II.ISSUES ON POWER QUALITY DUE TO DISTRIBUTED
GENERATION
Index Terms—: Distributed Generation (DG), Power Quality, The protective relays are affected by power quality
Adaptive Relaying and Fault Current.
problems because of poor wave quality. The main steady-state
I. INTRODUCTION disturbances that can affect the performance of protective
relays are frequency variation and harmonics. [5] - [7]
The earliest electric power systems were distributed
Frequency Variation: The relay magnitude measurement
generation (DG) systems intended to cater to the requirements
is based on input signal sampling. The input module takes a
of local areas. [1] Subsequent technology developments resulted
predefined number of samples in each cycle of fundamental
in the development of large centralized grids connecting up
frequency. In case of 12 samples per cycle, sampling period is
entire regions and countries. The design and operating
equal to Ti = 20 ms/12 = 1.66 ms. If an increase of frequency
philosophies of power systems have emerged with a focus on
takes place but the sampling period is fixed (1.66 ms, in this
centralized generation. Centralized generation alone is not
case) the resulting RMS value will be erroneous. The error
necessary to meet the power requirement. To avoid sustaining
appears in this case due to the fact that the RMS value
energy shortage, distributed generation (DG) can be a solution
calculated on the basis of 12 samples takes into account more
method. DG can be defined as the installation and operation of
than one cycle of the waveform. When power system
electric power generation units connected directly to the
frequency differs from 50Hz, the calculated current RMS value
distribution network or connected to the network on the
is erroneous, resulting in magnitude fluctuations. Due to these
customer site. The various types of distributed generation
fluctuations, the RMS value measured by the relay is not
includes wind power, solar power, biomass power generation,
constant, oscillating around the mean value which is close to
fuel cell, micro turbine etc. Promotion of energy conservation
the actual value. This behavior can potentially lead to incorrect
and increased use of renewable energy sources are the twin
operation of the relay. Thus, if the fluctuation magnitude
planks of a sustainable energy supply. [2]
exceeds the relay over current setting, the relay maloperate,
The various issues associated with the incorporation of resulting in an incorrect trip. The solution method suggested is
distributed generation in existing network are summarised in [3] the adaptiveness of relay sampling frequency.
and [4]. The addition of generation could influence power

978-1-4799-2075-4/13/$31.00 ©2013 IEEE 157


Harmonic Distortion: Harmonic distortion causes the remainder of the power system, yet continues to be energized
working of relay incorrectly. Depending on the characteristics by DG connected to the isolated subsystem. Distribution
of the measured signal, in practice four types of harmonics can networks with DG are presently not designed to operate in
be found, quasi-stationary harmonics, fluctuating harmonics, island mode. If unplanned islanding occurs it presents a
rapidly changing harmonics and inter harmonics, apart from number of hazards and thus need to be avoided.
other spurious components. For protective relays rapidly Protection Coordination: Faults are eliminated in the
changing harmonics have the worst effect. When the harmonic smallest possible time, isolating the smallest part of the system
level is less than 20% the correct operation of relay is not containing the cause of the fault. The presence of distributed
affected. Harmonics can distort or degrade the operating generation may cause coordination problem, such that more
characteristics of protective relays depending on the design area will be isolated.
features and principles of operation. Due to increase in non Blinding of Protection: Blinding of protection is also
linear loads, total harmonic distortion (THD) level more than called protection under reach. The distributed generation is
20% is expected. Over current relays have to operate with supplying energy locally to load. As a result the fault current
current transformers (CT) which may saturate and distort the seen by the relay is reduced. The result is that the relay fails to
current waveform causing a malfunction in over current relays. trip.
Voltage fluctuations or Flicker: Variation in power Sympathetic Tripping: Sympathetic tripping is an
generation of distributed generators based on irregular primary expression given to the case at which one of the protection
sources like wind turbines, photo voltaic etc cause voltage devices trips instead of the other. This tripping occurs due to
fluctuation or flicker. All relays in the power system have fixed one device detecting the fault while it is out of its local
operating voltage. The variation in the voltage causes protection area and tripping before the required tripping device.
maloperation of relays. The protective device operates unnecessary for faults in
Voltage sag and Voltage swell: A sag is a decrease to another protection zone. As a result the healthy feeder gets
between 0.1 and 0.9 pu in rms voltage or current at the power tripped.
frequency for durations from 0.5 cycles to 1 minute. A swell is The approaches based on adaptive relaying are proposed in
an increase to between 1.1 and 1.8 pu in rms voltage or current [9]–[10] is used to face the above situations. Adaptive relaying
at the power frequency for durations from 0.5 cycle to 1 is defined as a protection philosophy which permits and seeks
minute. Both sag and swell causes the deviation of voltage to make adjustments to various protection functions in order to
from the actual relay setting voltage level which results in make them more attuned to prevailing power system conditions
malfunction of relays. in [10]
III.PROBLEMS DUE TO INTERMITTENT NATURE OF IV.SIMULATIONS AND RESULTS
DISTRIBUTED GENERATION IN PROTECTION LEVEL
The following are the different problems due to intermittent The IEEE 14 bus test system is used to demonstrate the
nature of distributed generation in protection level. [8] impact of distributed generation on protective relays. The
Fault Level: The connection of a DG to a distribution
network will inevitably result in some local changes to the
characteristics of the network. Connecting a generator to a
distribution network has the effect of increasing the fault levels
in the network close to the point of connection. The connection
of distributed generation to the network could cause a
distribution network, which happens to be close to its fault
level limit, to exceed it. The risks when fault levels are
exceeded will cause damage and failure of the plant, with
consequent risk of injury to personnel and interruption to
supplies. The new fault current and setting should be calculated
for the protection equipment in the system.
Reverse Power Flow: Radial distribution networks are
usually designed for unidirectional power flow, from the in
feed downstream to the loads. This assumption is reflected in
standard protection schemes with directional over current
relays. The load flow situation may change with a generation
on the distribution feeder. If the local production exceeds the
local consumption, the power flow will change the direction.
Reverse power flow is problematic if it is not considered in the Fig.1. IEEE 14 bus system
protection system design.
Islanding: Islanding occurs when a portion of the Electrical transient and analysis program (ETAP) software is
distribution system becomes electrically isolated from the taken for simulation purpose.

978-1-4799-2075-4/13/$31.00 ©2013 IEEE 158


The IEEE 14 bus test system has 2 generators, 3 synchronous indicated for LLG and LG faults in figures 2 and 3
condensers and 9 load buses. The system has 20 transmission respectively.
lines. The details of IEEE 14 bus system is given in [11]. Increase in fault level with increase in DG penetration - LLG fault
77.85
. The capacity of wind turbine generator is set to be 10 MW.
The three phase short circuit fault is inserted to bus number
77.8
4.The two over current relays are connected in between bus 2
to 3 and 3 to 4.The two over current relays are made such that
77.75
it is supposed to with stand the fault. Due to non availability of

F a u lt L e v e l in k A
wind, the wind generator capacity is changed to OFF mode. In
77.7
that case the circuit breaker in line connecting the buses 2 and
3 is tripped. (Fig.3) The wind turbine generator capacity is
changed to 20 MW due to good availability of wind. When
77.65

there is a fault in bus number 4 the circuit breaker connected


in line between the buses 3 and 4 will trip. Therefore the
77.6

existing relays malfunctions in the presence of distributed


generation. Due to intermittent nature of wind we cannot 5 7 9 11 13 15 17 19 21 23 25
Increase in DG penetration
provide an ideal setting for the relays. Table I gives the
increase in fault level with increase in DG penetration for three Fig. 2 Increment of fault level with increase in DG
penetration –LLG fault
phase short circuit fault and the variation is graphically
Increase in fault level with increase in DG penetration - LLG fault
TABLE I. INCREAMENT OF FAULT LEVEL WITH INCREASING DG 71.98

DG 10 15 20
0 MW 5 MW
71.96

Capacity MW MW MW
71.94

Bus No Increase in Fault Ampere


F a u lt L e v e l in k A

71.92

1 206.1 208 210 211.9 214 71.9

71.88
2 205.7 207.7 209.7 211.6 213.6
71.86
3 201.8 203.8 205.8 207.8 209.8
71.84
5 7 9 11 13 15 17 19 21 23 25
4 204.3 206.3 208.2 210.2 212.1 Increase in DG penetration

5 204.2 206.2 208.1 210 212


Fig. 3 Increment of fault level with increase in DG penetration –LG
fault
6 84.81 84.91 85.01 85.11 85.21
V. ADAPTIVE RELAYING
7 85 85.11 85.21 85.31 85.41
Adaptive protection concepts were introduced in 1980s to
8 83.39 83.49 85.59 83.69 83.78 fulfil the requirement of absolute selectivity, high sensitivity
and adequate severity. Adaptive Relaying means protective
9 85.47 85.57 85.68 85.78 85.88 settings should be automatically adjusted to make the
protective relays more attuned to prevailing system conditions.
10 85.1 85.21 85.31 85.41 85.51 There are different types of adaptive protection like adaptive
distance protection, adaptive current differential protection
11 84.62 84.72 84.82 84.92 85.02
and adaptive power differential protection. Recently
increasingly more distributed generators (DGs), being
12 83.59 83.69 83.79 83.89 83.98
connected to the grid. The implementation of DG can create
difficulties for the existing power system protection schemes
13 84.48 84.58 84.68 84.78 84.88
and cause protection devices to operate incorrectly. Adaptive
14 84.32 84.43 84.53 84.63 84.72 relaying can be a solution to these problems. [9]

CAPACITY – THREE PHASE SHORT CIRCUIT FAULT

978-1-4799-2075-4/13/$31.00 ©2013 IEEE 159


Fig.4. IEEE 14 bus with a DG on third bus and a three phase short circuit fault on fourth bus

Relays are used to protect electric power systems in a whether the relay settings should be changed or not. If it
predetermined manner. The relay settings are selected after decides to change the settings, it calculates them and conveys
studying most of the critical power system conditions. It is them to the relays via the station control computers. The relays
difficult and impossible to identify and analyze all operating implement the new settings and send confirmation messages to
conditions of concern in advance and to determine relay settings the central computer via the station computers. If the central
that would the optimum for all normal and abnormal operating computer decides not to change the settings, the decision is
conditions. The scenario has been changed with the communicated to the relays for sharing information and
development of microprocessor-based relays, because they can confirming that communication facilities are working properly.
collect information, handle complex logic and communicate Adaptive relaying provides lower relay operating times and
with other relays and control devices. It is possible to maintains proper relay coordination. A change of system
continuously monitor the state of a power system, analyze it in configuration affects the selectivity adversely unless relay
real-time, and change the relay settings to most appropriate at settings are changed. The adaptive relaying is a key
that time. Microprocessor based relays forms an adaptive requirement for smart grid operation which includes distributed
approach which reduces the relay operating times and provides generation. [12]-[15]
proper relay coordination at all operating conditions. [12]
The architecture of adaptive relaying is given in Fig.5. The Central Computer
relays sample bus voltages and line currents via voltage and
current transducers, auxiliary transformers, analog to digital
converters and multiplexers. Each relay processes quantized Substation Control
samples and calculates voltage and current phasors. During Computer
normal operating conditions, each relay provides phasor
measurements to its station control computer at regular
intervals. The relays check the status of local isolators and
circuit breakers and provide the information to the station Relay
computers. In addition to communicating with the relays, the
station computers pass on the collected information to the
central computer which estimates the system state and decides Substation

Fig.5. Adaptive Relaying Architecture

978-1-4799-2075-4/13/$31.00 ©2013 IEEE 160


VI. CONCLUSIONS International Journal of Electrical Power & Energy Systems,
Volume 43, Issue 1,December2012, Pages1460-1466
The protective relays in the power system malfunctions [10] S.H. Horowitz, A.G. Phadke and J.S. Thorp, “Adaptive
in the presence of distributed generation due to power Transmission System Relaying”, IEEE Transactions on
quality issues and intermittent nature of wind power, solar Power Delivery, Vol.3, no4,October 1988, pp.1436-45.
power etc. The IEEE 14 bus system is taken as test system [11] M A Pai “Computer Techniques in Power System
and proved that malfunction of relays takes place due to Analysis” Tata McGraw- Hill Publishing Company Limited,
intermittent nature of distributed generation. The fault level 2006, ISBN: 0070593639
is getting increased with increase in DG penetration. The
solution method suggested is adaptive relaying and [12] Sachdev. M.S. , Chattopadhyay. B. , Sidhu, T.S. ― “ A
multiagent system in which relay has to adapt to the new approach to distribution system protection-adaptive
changing environment. The existing relays are to be changed relaying” Fifth International Conference on Develpments in
into adaptive relays. Power System System Protection,1993. Publication Year
1993,Pages 165 – 168
REFERENCES [13] “Application of adaptive theory in distribution network
[1] Rangan Banerjee ― "Comparison of options for protective relaying” Technical Session. International
distributed generation in India” Energy Policy, Volume 34, Conference on Electricity Distribution, 2008. CICED 2008.
Issue 1, January 2006, Pages 101-111. China Publication Year: 2008 , Page(s): 1- 4
[2] Ashwani Kumar, Kapil Kumarb, Naresh Kaushik, [14] Hui Wan , LiK. K., Wong. K.P. ―An Adaptive
Satyawati Sharma, Saroj Mishra ― “Renewable energy in Multiagent Approach to Protection relay coordination with
India: Current status and future potentials” Renewable and distributed generators in industrial power distribution
Sustainable Energy Reviews Volume 14, Issue 8, October system IEEE Transactions on Industry Applications
2010, Pages 2434–2442. Volume: 46, Issue: 5 Publication Years: 2010 ,
Page(s):2118-2124
[3] Hussain B. , Sharkh S.M., Hussain S. ― “Impact
studies of distributed generation on power quality and [15] Hui Wan , LiK. K., Wong. K.P. ―An Multiagent
protection setup of an existing distribution network” Approach to Protection relay coordination with distributed
International Symposium on Power Electronics Electrical generators in industrial power distribution system Industry
Drives Automation and Motion (SPEEDAM). Publication Applications Conference, 2005. Fortieth IAS Annual
Year: 2010, Page(s): 1243 - 1246 Meeting. Conference Record of the 2005, Volume: 2,
Publication Year: 2005, Page(s): 830 - 836 Vol. 2.
[4] Olatoke, A., Darwish, M.K. ― “A study of the impact of
Distributed Generation on power quality” 47th International
Universities Power Engineering Conference (UPEC), 2012
Publication Year: 2012 , Page(s): 1- 5
[5] Zamora, I. , Mazon, A.J. , Valverde, V., Martin, J.I.San ,
Buigues, G., Dysko, A. ― “Influence of power quality on
the performance of digital protection relays” IEEE Russia,
Power Tech, 2005, Publication Year: 2005 , Page(s): 1 – 7
[6] Tin, H. , Abu-Siada, A. , Masoum, M.S. ― “Impact of
harmonics on the performance of over-current relays” 21st
Australasian Universities Power Engineering Conference
(AUPEC). Publication Year 2011, Page(s): 1-4.
[7] Abu-Siada, A., Tin. H. Masoum. M.S, Qian, Y. ―
“Improving the performance of smart grid over-current
protection relays”Innovative Smart Grid Technologies Asia
(ISGT), 2011 IEEE PES. Publication Year: 2011, Page(s):1-
5
[8] Wan. H. , Wong. K.P., Chung. C.Y. ― “Multi- agent
application in protection coordination of power system with
distributed generations” IEEE Power and Energy Society
General Meeting - Conversion and Delivery of Electrical
Energy in the 21st Century,2008PublicationYear:2008
,Page(s):1-6
[9] Jing Ma, Xi Wang, Yagang Zhang, Qixun Yang, A.G.
Phadke ― “A novel adaptive current protection scheme for
distribution systems with distributed generation”

978-1-4799-2075-4/13/$31.00 ©2013 IEEE 161

También podría gustarte