Está en la página 1de 1

SITE TEST REPORT Date : 3-7-2017

Customer:
Contractor’s name: NCC
SEC-EOA
SEC – EOA Contract No. :
380/230 kV JUAYMAH BSP 4400002933
AUXILIARY CONTACTORS Page 1 of 1
Panel No: Equip. : Dwg. Ref.: Record No.:
1. GENERAL DATA AND INFORMATION:
Panel No: A805 Designation: K805_3
Manufacturer: SEIMENS Rated Voltage: 125 Vdc
Main Unit Order No: 3RH -1BG40 No. of Contacts (Main Unit): NO___ + NC___
Auxiliary Unit Order No: 3RH1911-1GA No. of Contacts (Aux. Unit): NO___ + NC___

2. MECHANICAL CHECKS AND VISUAL INSPECTION:

ITEM DESCRIPTION CHECKED


1 Inspect for physical damage / defects. ok

2 Verify connections as per approved drawings. ok

3 Check tightness of all connections. ok

4 Check Ferrules. ok

5 Check apparatus lists. ok

3. ELECTRICAL TESTS:
a) FUNCTION TEST:
ITEM DESCRIPTION CHECKED
1 All contacts checked. ok
2 All output contacts resistance measured. ok

b) OPERATE AND RESET VOLTAGE MEASUREMENT TEST:


Main Unit Operating Latching Unit Reset
Voltage (V) Current (mA) Voltage (V) Current (mA)
66.3 13.12 69 16.81
Operating Range: 0.8 to 1.1 Uc

c) PICK UP & DROP OFF TIME TEST (At rated voltage):


Contact No. Main Unit Pick Up (ms) Contact No. Latching Unit Pick Up (ms)
53-54 27 53-54 35
Limits: Not Available

d) RELAY BURDEN TEST (At rated voltage):


Applied Voltage Main Unit Operating Latching Unit Reset
Current (mA) Burden (W) Current (mA) Burden (W)
125 Vdc
Limits: 3.2W approximately
EQUIPMENT USED
>SVERKER 760
>FLUKE MULTIMETER
DATE:
TESTING ENGINEER (XERVON) CSD- Engineer

Signature: ________________ Signature: ________________


Name : Name : ________________