0020 X Certified Design or Type Test Certificate of Compliance with ANSI-C 57 by Independent Third
Party as per 14-SAMSS 531.
0030 X Welding Procedure Specification (WPS) and Procedure Company approval required.
Qualification Records (PQR)
0020
0010
*** X
In process inspection & test requirement
Welders certification
Specification Details / Notes:
0020 X Construction As per approved drawings & Per 14-SAMSS-531 Section 5.0
0030
0010
*** Final inspection & test requirements
Electrical Requirements:
Specification Details / Notes:
0030 X X Routine Tests Per 14-SAMSS-531. For 2500 KVA OA and less, witness only
one randomly selected transformer for each line item. Above
2500 KVA OA, all transformers to be witnessed.
0040 X Zero-Phase-Sequence Impedance Voltage For 5 MVA & above as per 14-SAMSS-531 section 9.17.
IR140500 Continued...
INSPECTION & TESTING REQUIREMENTS REVISION: 01/31/2011 CODE NUMBER: PAGE:
SAUDI ARAMCO FORM-175 REPLACES: 04/25/2006 IR140500 2 of 2
(1) VISUAL INSPECTION WITNESSING BY INSPECTOR (Note 1)
(2) CERTIFICATES / RECORDS TO BE CHECKED BY INSPECTOR
(3) CERTIFICATES / DATA TO BE PROVIDED BY VENDOR / SUPPLIER / MANUFACTURER
0050 X Paint Check paint color and thickness per 14-SAMSS-531 Sec VI
0060 X X Noise Level Test is required for only one randomly selected transformer for
each line item. Witness for 2.5 MVA and above. Certify below
2.5 MVA. Per 14-SAMSS-531 Sec VI.
0070 X Temperature Rise Test is required for only one randomly selected transformer for
each line item of 2.5 MVA and above. Per 14-SAMSS-531 Data
schedule-1
Notes:
(1) May only be waived by the responsible Saudi Aramco, ASC, or AOC Inspection Offices.
(2) See form SA175 000003 for instructions on using this form.
End of IR140500