Está en la página 1de 6

DeltaV Product Data Sheet

August 2010 – Page 1 DeltaV SD Plus Controller

DeltaV SD Plus Controller

The DeltaV SD Plus Controller and the DeltaV I/O subsystem make rapid installation easy

 Scalable controllers Introduction


 Quick Assembly The DeltaV S-Series controllers provide
communication and control functions and integrate
field devices and the other nodes on the control
 Easy to use network. The SX and SD Plus controllers provide a
choice to match the controller capacity to the
 Field Proven architecture requirements of the process. They also provide new
ease of use features that eliminate mounting screws
 Designed for Digital Marshalling and accelerate cabinet assembly.
Control strategies and system configurations created
 Advanced Controls
on earlier DeltaV systems can be used with this
controller. The SD Plus Controller provides all the
features and functions of the M-Series controllers
with the added support for CHARM based Digital
Marshalling.
The control languages executed in the controllers
are described in the Control Software product data
sheet.

www.EmersonProcess.com/DeltaV
DeltaV Product Data Sheet
August 2010 – Page 2 DeltaV SD Plus Controller
Benefits  Hardware redundancy is automatically detected with
zero configuration effort.
Scalable controllers. The SD Plus controller
complements the SX controller by providing a smaller Field Proven Architecture. The S-Series controllers
controller platform at a reduced price for those small to are an evolution of DeltaV M-Series hardware. The new
moderate applications: design delivers installation and robustness enhancement
while still using the same processor and OS that has
 Speed. The SD Plus controller supports all the proven itself in the field. All S-series I/O cards run the
features you’ve come to expect from the DeltaV latest software enhancements of corresponding M-Series
system: self-addressing, automatic I/O detection. All I/O cards and deliver the same field proven, reliable
these features are designed to make your projects operation.
execute faster—just plug and play!

 Redundant architecture. The SD Plus controller


supports 1:1 redundancy for increased availability.
Redundant SD Plus controllers can be upgraded to
SX controllers online—robust!

 Late Changes. You can easily upgrade an SD Plus


controller to an SX to handle project scope changes
late in the project. Simply replace the SD Plus with
the SX and all existing configuration, documentation
and hardware design remain the same —forgiving.

Quick Assembly. The S-Series hardware has been


redesigned for speed of project execution. Carriers snap
to standard DIN rails and controllers and S-series IO snap
into position without the use of retaining screws.

Easy to use. Controllers are also easy to configure.


Simply connect the SD Plus to the DeltaV network and
Auto-Sense it from DeltaV Explorer. Add the controller
and all its IO interfaces to the system database and all
components are automatically addressed and
communicating. There are no dip switches or jumpers to
set.
The SD Plus Controller
 Control strategies are developed using IEC-61131
programming techniques: Function Blocks, Sequential Designed for Digital Marshalling. The S-Series
Function Charts and Structured Text. controllers have highly distributable I/O capabilities with
CHARMS based Electronic Marshalling. Electronic
 Automatic diagnostic and event reporting with time Marshalling I/O can be mounted anywhere, facilitating
stamps applied in the controller system design and expansion while reducing overall
system footprint over traditional marshalled I/O
 Set control execution to match process dynamics and Subsystems.
controller scheduling adjusts automatically.
Advanced Controls. The SD Plus controller supports
 Reference any parameter by its module name, all the advanced control features that are expected in a
regardless of its location in the system. world class Digital Control System:

 Synchronized system clock for consistent time based  Batch Software


event driven actions across the system.
 Model Predictive Control
 Online expandable IO carriers allow new cards to be
added online, with autosense capability, for modular  Neural Networks
system growth
DeltaV Product Data Sheet
August 2010 – Page 3 DeltaV SD Plus Controller
Product Description The WirelessHART I/O card provides redundant
communication for up to 100 WirelessHART devices,
The SD Plus controller executes control logic based on the providing high availability and reliability of wireless data.
process signals derived from the I/O subsystem and Up to 16 Wireless HART I/O cards can communicate to a
provides communication to the rest of the DeltaV control single controller.
system for operator interaction and data collection.
Control modules are automatically scheduled by the
Each controller node can be installed as a simplex or controller, based on their assigned scan rates. This allows
redundant node. Redundancy is provided by adding a each control function to be optimized based on the
second controller and power supply mounted adjacent to process dynamics. Modules scan times can be set as fast
the primary controller. The controllers are connected to as 100 ms, and as slow as 60 seconds. The number of
the I/O carriers, which are mounted to the right of the control modules that can be assigned to a controller
controller carriers. Up to 8 carriers with 8 cards each can depends on the complexity and scan rate of each module,
be connected to the local bus I/O, for a total of 64 and the available CPU and memory. The SD Plus
traditional I/O cards. In addition to the 8 local I/O carriers, controller should be used for small to medium applications
each controller can communicate with an additional 16 with a maximum of 750 individual I/O signals.
Remote I/O units hosting traditional card based I/O.
The SD Plus controller is designed for harsh environments
In addition to traditional I/O cards, the local bus supports and is rated for G3 corrosive environments, with an
field bus technologies, including Foundation fieldbus, operating temperature range from -40 to 70 ºC. It is
Profibus DP, DeviceNet and AS-I protocols. The I/O ideally suited for remote installation, close to the process
subsystem also supports Serial interface cards as well as equipment. For more traditional installations with central
the Ethernet I/O interface. These various I/O products marshalling cabinets, CHARMS I/O cards can be mounted
provide a wide range of interfaces to meet the needs of in standard I/O cabinets providing Electronic Marshalling.
your control application. CHARMS I/O Cards can also be used for highly distributed
I/O applications.
The SD Plus also supports CHARMS and WirelessHART
IO cards. The CHARMS I/O card (CIOC) connects via the
redundant Ethernet ports of the controller and provide a
highly distributed and flexible I/O solution called Electronic
Marshalling. Up to 16 CIOC’s can communicate with one
controller, each providing up to 96 individually configurable
signal types.

S-series controller hardware dimensions


DeltaV Product Data Sheet
August 2010 – Page 4 DeltaV SD Plus Controller
Hardware Specifications
Specifications for the SD Plus Controller
DST Limit 750
SCADA tags 3200
Max data values sent 2000/second
Max data values received 250/second
Max unsolicited client nodes 64
Module Execution rates 100ms, 200ms, 500ms, 1s, 2s, 5s, 10s, 30s, 60s
User Memory 48 MB
Fuse protection (internal) 3.0 A, non-replaceable fuses
Power dissipation 5.0 W typical, 7.0 W maximum
Environmental specifications:
Operating temperature -40 to 70 C (-40 to 158 F)
Storage temperature -40 to 85 C (-40 to 185 F)
Relative humidity 5 to 95%, non-condensing
Protection rating IP 20, NEMA 12
Airborne contaminants ISA-S71.04-1985 Airborne Contaminants Class G3
Conformal coating
Shock (normal operating 10 g ½-sine wave for 11 ms
conditions)
Vibration (operative limit) 1 mm peak-to-peak from 5 Hz to 16 Hz, 0.5 g from 16 Hz to 150 Hz
LED Indicators:
Green – Power Indicates DC power is applied.
Red – Error Indicates an error condition.
Green – Active Indicates that the controller is operating as the primary controller.
Green – Standby Indicates that the controller is operating as a backup controller
Yellow flashing – Pri. CN Indicates valid primary control network communication.
Yellow, flashing – Sec. CN Indicates valid secondary control network communication.
External connections:
Primary Control Network 8-pin RJ-45 connector
Secondary Control Network 8-pin RJ-45 connector
DeltaV Product Data Sheet
August 2010 – Page 5 DeltaV SD Plus Controller
Certifications The following certifications have been submitted for
Hazardous Locations and for Marine applications. Please
verify with the appropriate certifying agency for a specific
The following certifications are available on the SD Plus list of approved components
controller.
 CENELEC Zone 2 ATEX/IEC EX
 CE:
EN 60079-15:2005
- EMC- EN 61326-1:2006 Certifying agency: Nemko
- LVD- EN 61010-1:2001 Certificate Number: TBD

 CSA: Refer to document TBD


"DeltaV ™ Scalable Process System Zone 2
- CLASS 2252 05 - PROCESS CONTROL Installation Instructions"
EQUIPMENT:

CAN/CSA-C22.2 No. O-M91 General Requirements-  FM Approval


Canadian Electrical Code, Part II
CAN/CSA-C22.2 No. 61010-1-04 Safety Class 1 Division 2 Hazardous Locations
Requirements for Electrical Equipment for
Measurement, Control, and Laboratory Use,
Part 1: General Requirements Certifying agency: FM Approvals
Certificate Number: TBD

Refer to document TBD


Complies with NAMUR NE21 per DeltaV Digital
"DeltaV ™ Scalable Process System Class 1
Automation System NAMUR NE21 Installation Instructions
12P2822. Division 2 installation Instructions”

 Marine Certifications:

IACS E10:2006 Rev.5 Control, protection &


Safety

- ABS Certificate of Design Assessment


- Bureau Veritas Certificate
- DNV Marine Certificate
- Lloyds Register

 GOST Hazardous Area certification Zone 2


(Russian)

Other country specific certifications may also be available.


Verify with your local Emerson sales office to confirm any
certification requirements not listed here.

.
DeltaV Product Data Sheet
August 2010 – Page 6 DeltaV SD Plus Controller
Ordering Information
Description Model Number
SD Plus Controller SE3006

Prerequisites
 For each controller you will need a Power/Controller carrier. Please refer to the S-series I/O Carrier product data sheet for
details.

 Each controller requires a dedicated system power supply. Please refer to the S-series Power Supplies product data
sheet for details.

To locate a sales office near you, visit our website at: For large power, water, and wastewater applications
www.EasyDeltaV.com/reach contact Power and Water Solutions at:
Or call us at: www.EmersonProcess-powerwater.com
Asia Pacific: 65.777.8211 Or call us at:
Europe, Middle East: 41.41.768.6111 Asia Pacific: 65.777.8211
North America, Latin America: +1 800.833.8314 or Europe, Middle East, Africa: 48.22.630.2443
+1 512.832.3774 North America, Latin America: +1 412.963.4000

© Emerson Process Management 2009. All rights reserved. For Emerson Process Management trademarks and service marks, go to:
http://www.emersonprocess.com/home/news/resources/marks.pdf.

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not to be
construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed
by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time
without notice.

www.EmersonProcess.com/DeltaV

También podría gustarte