paso = 25 cm
contrapaso = 17.3 cm
DISEÑO TRAMO 1
L= 1.77 m
L/20 = 8.85 cm 7.97 cm
promedio
L/25 = 7.08 cm 10 cm
Hallamos el ángulo
METRADO DE CARGAS
Tramo Inclinado
QD
peso propio = 291.86 kg/m
peso de los escalones = 207.60 kg/m
eso de piso terminado = 100 kg/m
QD = 599.46 kg/m
Q𝑢=1.4Q𝑑+1.7Q𝑙 = Q𝑢=1.4Q𝑑+1.7Q𝑙 = 1179.24 kg/m
QL
s/c = 200 kg/m
QL = 200 kg/m
Descanso
QD
peso propio = 240.00 kg/m
eso de piso terminado = 100 kg/m
QD = 340.00 kg/m
Q𝑢=1.4Q𝑑+1.7Q𝑙 = Q𝑢=1.4Q𝑑+1.7Q𝑙 = 816.00 kg/m
QL
s/c = 200 kg/m
QL = 200 kg/m
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
MOMENTOS 816.00
DISEÑO TRAMO 2
L= 1.92 m
L/20 = 9.60 cm 8.64 cm
promedio
L/25 = 7.68 cm 10 cm
Hallamos el ángulo
METRADO DE CARGAS
Tramo Inclinado
QD
peso propio = 291.86 kg/m
peso de los escalones = 207.60 kg/m
eso de piso terminado = 100 kg/m
QD = 599.46 kg/m
Q𝑢=1.4Q𝑑+1.7Q𝑙 = Q𝑢=1.4Q𝑑+1.7Q𝑙 =
1179.24 kg/m
QL
s/c = 200 kg/m
QL = 200 kg/m
Descanso
QD
peso propio = 240.00 kg/m
eso de piso terminado = 100 kg/m
QD = 340.00 kg/m
Q𝑢=1.4Q𝑑+1.7Q𝑙 = Q𝑢=1.4Q𝑑+1.7Q𝑙 =
816.00 kg/m
QL
s/c = 200 kg/m
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
QL = 200 kg/m
MOMENTOS 816.00
DISEÑO TRAMO 3
L= 1.37 m
L/20 = 6.85 cm 6.17 cm
promedio
L/25 = 5.48 cm 10 cm
Hallamos el ángulo
METRADO DE CARGAS
Tramo Inclinado
QD
peso propio = 291.86 kg/m
peso de los escalones = 207.60 kg/m
eso de piso terminado = 100 kg/m
QD = 599.46 kg/m P = QD + QL
Q𝑢=1.4Q𝑑+1.7Q𝑙 = 799.46 kg/m
1179.24 kg/m
QL
s/c = 200 kg/m
QL = 200 kg/m
Descanso
QD
peso propio = 240.00 kg/m
eso de piso terminado = 100 kg/m
QD = 340.00 kg/m P = QD + QL
Q𝑢=1.4Q𝑑+1.7Q𝑙 = 540.00 kg/m
816.00 kg/m
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
QL
s/c = 200 kg/m
QL = 200 kg/m
MOMENTOS 816.00
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
PREDIMENSIONAMIENTO
1. LOSA ALIGERADA
e = L/25 = 6.9
= 0.276
25
TOMAMOS = 0.30
0.40
0.40
METRADO DE CARGAS
UNIVERSIDAD PRIVADA DEL NORTE
0.40
METRADO DE CARGAS
AREAS DE INFLUENCIA
AREA - SOBRECARGAS
C21 3.4846 m2
METRADO DE CARGAS
DATOS GENERALES
muro de soga 0.15 m Área C1 0.0625 m²
P. especifico C. Armado 2400 kg/m³ Área C2 0.09 m²
P. especifico albañilería 1800 kg/m³ Área C3 0.1426 m²
Piso Terminado 100 kg/m² Altura piso a techo 2.4 m
Sobrecarga 200 kg/m² Nº de pisos 5
Tabiqueria movil 90 kg/m²
Peso Espesor de losa 300 kg/m²
hf= 1.7 m
Altura total = Err:509 m
Aligerado
P.P. aligerado 300 kg/m²
P. terminado 100 kg/m²
D= 400 kg/m²
COLUMNA 1
VIGAS:
VA-101 .30 *.30 *1*2400 = 0.00 kg
VP-101 .30* .45 *1*2400 = 4636.80 kg
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
D= Err:509 kg/m
L= 5894.54 kg/m
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA C2
VIGAS:
VA-101 .30 * .25 *1*2400 2169.6 kg
VP-101 .30* .45*1*2400 4636.8 kg
VP-102 .30* .20 *1*2400 0 kg
D= Err:509 kg
L= 7766.06 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA C3
VIGAS:
VA-102 .30 * .25 *1*2400 0.00 kg/m²
VP-102 .30* . 0.20*1*2400 0.00 kg/m²
D= Err:509 kg
L= 1893.41 kg
P=D+L P= Err:509 kg
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
COLUMNA C4
VIGAS:
VA-102 .30 * .25 *1*2400 0 kg/m²
VP-103 .30* .25 *1*2400 0 kg/m²
D= Err:509 kg
L= 4532.70 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA C5
VIGAS:
VA-101 .30 * . 0.25*1*2400 2169.6 kg/m²
VP-101 .30* .45 *1*2400 4636.8 kg/m²
D= Err:509 kg
L= 8102.00 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA C6
VIGAS:
VP-103 .30 * .25 *1*2400 0 kg/m²
VP-101 .30* .45 *1*2400 4636.8 kg/m²
VP-104 .30* .25 *1*2400 0 kg/m²
VA-101 .30* .25 *1*2400 2169.6 kg/m²
CONCRETO ARMADO 2
QD
UNIVERSIDAD PRIVADA DEL NORTE
D= Err:509 kg
L= 22651.03 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA C7
VIGAS:
VA-103 .30 * .30 *1*2400 0 kg/m²
VP-101 .30* .45 *1*2400 4636.8 kg/m²
D= Err:509 kg
L= 7761.27 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 8
VIGAS:
VP-104 .30 * .50*1*2400 0 kg/m²
VP-101 .30 * .50*1*2401 4636.8 kg/m²
VP-105 .30 * .50*1*2402 0 kg/m²
VA-103 .30* .35 *1*2400 0 kg/m²
CONCRETO ARMADO 2
QD UNIVERSIDAD PRIVADA DEL NORTE
D= Err:509 kg
L= 26433.50 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 9
VIGAS:
VP-105 .30 * .45*1*2400 0 kg/m²
VA-103 .30* .35 *1*2400 0 kg/m²
D= Err:509 kg
L= 8107.68 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 10
VIGAS:
VP-106 .30 * .30*1*2400 Err:509 kg/m²
VA-103 .30* .30 *1*2400 0 kg/m²
D= Err:509 kg
L= 7761.13 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
COLUMNA 11
VIGAS:
VP-106 .30 * .30*1*2400 Err:509 kg/m²
VP-107 .30 * .20*1*2401 0 kg/m²
VP-108 .30 * .50*1*2402 0 kg/m²
D= Err:509 kg
L= 1334.00 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 12
VIGAS:
VP-105 .30 * .45*1*2400 0 kg/m²
VP-107 .30 * .20*1*2400 0 kg/m²
VA-103 .30* .30 *1*2400 0 kg/m²
D= Err:509 kg
L= 25633.39 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 13
VIGAS:
VP-105 .30 * .50*1*2400 0 kg/m²
VA-103 .30* .35 *1*2400 0 kg/m²
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
D= Err:509 kg
L= 10088.38 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 14
VIGAS:
VP-106 .30 * .50*1*2400 Err:509 kg/m²
VA-105 .30* .35 *1*2400 0 kg/m²
D= Err:509 kg
L= 8692.03 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 15
VIGAS:
VP-106 .30 * .50*1*2400 Err:509 kg/m²
VP-108 .30* .35 *1*2400 0 kg/m²
VP-109 .30* .35 *1*2400 0 kg/m²
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
QD
Peso de la columna Err:509 kg/m
Peso muro ladrillo eje B-B tramo 4-5 0.00 kg/m
Peso muro ladrillo eje 4-4 tramo A-B 0.00 kg/m
Peso muro ladrillo eje 4-4 tramo B-D 0.00 kg/m
QL Sobrecarga 9960.775 kg/m
D= Err:509 kg
L= 9960.78 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 16
VIGAS:
VP-109 .30 * .25*1*2400 0 kg/m²
VP-110 .30* .35 *1*2400 0 kg/m²
VP-111 .30* .40 *1*2400 Err:509 kg/m²
D= Err:509 kg
L= 12917.62 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 17
VIGAS:
VP-110 .30 * .35*1*2400 0 kg/m²
VP-112 .30* .50 *1*2400 Err:509 kg/m²
VA-104 .30* .35 *1*2400 0 kg/m²
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
QD
D= Err:509 kg
L= 15680.93 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 18
VIGAS:
VP-113 .30 * .60*1*2400 Err:509 kg/m²
VA-105 .30* .25 *1*2400 0 kg/m²
D= Err:509 kg
L= 13664.80 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 19
VIGAS:
VP-111 .30 * .60*1*2400 Err:509 kg/m²
VP-113 .30 * .60*1*2400 Err:509 kg/m²
VP-114 .30* .15*1*2400 Err:509 kg/m²
CONCRETO ARMADO 2
UNIVERSIDAD PRIVADA DEL NORTE
D= Err:509 kg
L= 15585.62 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 20
VIGAS:
VP-114 .30 * .15*1*2400 Err:509 kg/m²
VP-115 .30* .20 *1*2400 0 kg/m²
D= Err:509 kg
L= 2511.69 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
COLUMNA 21
VIGAS:
VP-112 .30 * .50*1*2400 Err:509 kg/m²
VP-115 .30* .20 *1*2400 0.00 kg/m²
D= Err:509 kg
L= 5252.67 kg
P=D+L P= Err:509 kg
PU= 1.4D+1.7L = Err:509 kg Err:509 Tn
CONCRETO ARMADO 2
ZAPATAS AISLADAS
DATOS
f'c = 210 kg/cm² ht = 1.2 m
fy = 4200 kg/m² ɣc = 2400 kg/m³
σt = 1 kg/cm² hc = 0.5 m (asumida)
S/Cg = 250 kg/m² recub. 0.075 cm
ɣm = 1750 kg/m³ Φ= 0.85
f'cz = 175 kg/cm² λ= 1
Nº pisos = 4 Bₒ = 1
PREDIMENSIONAMIENTO
Losa aligerada
e = L/25 0.146 m
e= 14.6 cm 20 cm
Viga Principal
e = L/10 0.45 m
e= 45 cm 45 cm
Viga Amarre 30 cm
e = L/14 0.261 m
e= 26 cm 30 cm
Aligerado
P.P. aligerado e = 0.20 m 300 kg/m²
P. terminado 100 kg/m²
D= 400 kg/m²
Vigas
VP-101 324 kg/m²
VA 216 kg/m²
S/C 65425.5 kg
D 31963.20 kg
L 65425.5 kg
P 97388.70 kg
ZAPATAS AISLADAS
U 1.4*D + 1.7*L 155971.83 kg
Peso Zapata
Pz = 10% P 9738.87 kg
A=B= 4.08 m
A= 4.10 m
m= A - 0.3/2 1.89 m
Actuante Resistente
12.11 < 13.55 OK
Actuante Resistente
3.19 < 6.53 OK
Verificación de Aplastamiento
ZAPATAS AISLADAS
A₁ = A₂ b y t = lados de columna
A₁ = b*t 0.09 m²
Actuante Resistente
108.21 < 124.95 OK
usamos 3/4"
n= As/a 17.32 17
1
7
4.10 m Φ
3
/
4
"
@ 17 Φ 3/4" @ 0.24
0 4.10 m
.
2
4