Está en la página 1de 5

BONDING

6
concepts were introduced
and many existing practices
were expanded or enhanced -
one of those being
supplementary equipotential
bonding. To a great extent,
the 15th Edition was based
on CENELEC harmonised
documents (HDs) (more so
now with the introduction of
the 17th Edition).

HD 384.4.41 was the basis for


Chapter 41 of the 15th
Supplementary Edition - Protection against
electric shock, which had

equipotential bonding

Courtesy of Yorkshire Water


requirements for
supplementary equipotential
bonding in Regulation 413-7,
by Mark Coles reproduced here:

413-7 Within the zone formed


Questions relating to the *Earthing and bonding Main protective bonding by the main equipotential
requirements for are two separate concepts conductor Used to connect bonding, local
supplementary extraneous-conductive-parts, supplementary equipotential
equipotential bonding are Earthing such as a metallic water bonding connections shall be
frequently asked; a very Connection of the exposed- pipe, to the main earthing made to metal parts, to
common one is where conductive-parts of an terminal. maintain the equipotential
should it be installed. installation to the main zone, where those parts -
This article looks at the earthing terminal of that Supplementary (i) are extraneous conductive
requirements for installation. equipotential bonding parts, and
supplementary equipotential An example of earthing is conductors Used to (ii) are simultaneously
bonding in BS 7671:2008, where the metallic outer-case supplement to fault accessible with exposed
where supplementary of a class I appliance is protection by maintaining conductive parts or other
equipotential bonding connected by the circuit various exposed conductive- extraneous conductive parts,
should be installed and protective conductor to the parts and extraneous- and
offers help on the process of means of earthing conductive-parts at (iii) are not electrically
evaluation. providing a safe path substantially the same connected to the main
for fault or high potential, such as the equipotential bonding by
TERMINOLOGY leakage/high protective connection of all exposed- permanent and reliable
Firstly, it is important that conductor currents. conductive-parts and metal-to-metal joints of
the terminology is correct. extraneous-conductive-parts negligible impedance.
Earthing and bonding are Equipotential that can be touched by NOTE - Where local
two different concepts yet the bonding livestock in an agricultural equipotential bonding is
terms are often used together. Electrical connection installation. provided in accordance with
Once we have established maintaining various Regulation 413-7, metalwork
that "earth-bonding"* is exposed-conductive-parts HISTORY which may be required to be
a nonsensical expression and and extraneous-conductive- The change from the 14th to bonded includes baths and
should never be used, we parts at substantially the 15th Edition of the IEE exposed metal pipes, sinks,
can look at the requirements the same potential. Wiring Regulations in 1981 taps, tanks, and radiators
of supplementary There are two types of created a big upheaval in the and, where practicable,
equipotential bonding in equipotential bonding electrical installation accessible structural
BS 7671:2008. conductor: industry as many new metalwork

IET Wiring Matters | Summer 08 | www.theiet.org


The
toughest
jobs need
the
Those far reaching changes, (ii) Double or reinforced
toughest
issued on 31st March 1981, insulation (Section 412) labels...
are still being felt today (iii) Electrical separation for
with designers and the supply to one item of
specifiers still current-using equipment
implementing the (Section 413)
requirements for (iv) Extra-low voltage (SELV
supplementary and PELV) (Section 414).
equipotential bonding from
the 15th Edition. Much of A note at the end of this
the confusion can be Regulation acknowledges
attributed to the note of that, in electrical
Regulation 413-7 which installations, the most
required the bonding of all commonly used protective
metallic items, essentially, measure is automatic
those within the designated disconnection of
equipotential zone. This led supply. PT-1260
to the installation of
supplementary DISCONNECTION TIMES
equipotential bonding of Regulation 411.3.2.6 states
general metallic items such that where automatic
as baths, ceiling grids, hand disconnection cannot be
rails, kitchen sinks, achieved in the required
PT-7600
radiators, pipework at time, supplementary
boilers, etc. Thankfully, we equipotential bonding shall
have moved on from this be provided.

PT-9600
general concept. In this instance, if
disconnection will not occur
THE REQUIREMENTS FOR in the required 0.4 s, for
SUPPLEMENTARY example, supplementary
EQUIPOTENTIAL BONDING equipotential bonding is
from 59.99
el prices l.
ctronic lab
We'll look at the used to hold various exposed- of materia
six layers
Ele io n co m prising of to 180C
requirements for conductive-parts and nstruct from -80C
a unique co peratures
tapes have resist tem
Brother TZ e labels can
supplementary equipotential extraneous-conductive-parts ensely dura bl
These imm
bonding then at instances at substantially the same
where it would be required. potential to limit the risk of
Initially, the scene is set a dangerous electric shock - s use
g machine
d us tr ial labellin try level
by Regulation 410.3.7 which this clears the confusion professio
nal in th e en
th er yo u choose
A ll B ro so whe ther u ill be
w
requires that if the created by Regulation 413-7 TZ tapes, T-9600 yo
our tough top o f th e range P th e extreme.
conditions of a protective of the 15th Edition. P or the een tested
to
PT-1260V ha ve b
labels that
measure cannot be met, Do bear in mind that producing
supplementary provisions supplementary equipotential
shall be applied to achieve bonding need not be For full product information phone 0845 606 0626
the same degree of safety. physically carried out by the quoting ref. WM0608. To buy a Brother labelling
installation of single-core printer visit your preferred electrical wholesaler.
What is a protective green-and-yellow conductors
measure? in every instance. There may
There are four protective be a situation where, for
measures generally permitted example, two simultaneously www.brother.co.uk
by BS 7671:2008, given in accessible metallic parts are
Regulation 410.3.3: in reliable contact and the Brother UK, Shepley Street, Audenshaw, Manchester, M34 5JD. www.brother.co.uk

(i) Automatic disconnection resistance between the two


of supply (Section 411) parts is sufficiently low.
BONDING

8
Where doubt exists breaker, rated at 32 A. First
regarding the effectiveness we must establish the
of supplementary current causing operation of
equipotential bonding, the circuit-breaker by
Regulation 415.2.2 requires referring to the correct
that the resistance, R, time/current
between simultaneously characteristics graph in
accessible exposed- Appendix 3 of BS 7671.
conductive-parts and Therefore, looking at fig. 1
extraneous-conductive-parts (extract from fig.3.4 of
fulfils the following BS 7671:2008), we can
condition: establish that the current
causing operation of the
In a.c. systems R 50 V circuit breaker is 160 A.
Figure 1: Time/current characteristics of circuit-breakers to
Ia BS EN 60898 Type B and BS EN 61009-1
R 50 V
Where: Ia continuity test be made not forming part of the
Ia is the operating current with a recommendation that electrical installation
in amperes of either: R 50 V the test instrument has a becoming live due to
 the protective device for 160 no-load voltage of between damage to a cable, then the

R 0.31
RCDs, In. 4 V and 24 V, d.c. or a.c. and protection of that cable is
 overcurrent devices, the a short-circuit current of paramount and must form
current causing not less than 200 mA. part of the design. Simply

resistance of 0.31 will


automatic operation in 5 s Therefore, a maximum installing supplementary
WORKING STANDARDS equipotential bonding as a
Example 1 ensure there is sufficient The installation of means of omitting
Let's take the scenario that current to operate the supplementary mechanical protection will
the protective device is an circuit breaker within five equipotential bonding does just result in more metallic
RCD rated at 30 mA: seconds. not mean that a lower parts becoming live in the
Note that in fig. 1 the standard of work is event of damage to a cable.
R 50 V current causing operation of permitted, nor the
Ia the device between 0.1 and requirements for fault SIZING OF SUPPLEMENTARY
5 s is the same; this will not protection or the need to EQUIPOTENTIAL
R 50 V be the case for fuses. If many disconnect the supply for CONDUCTORS
0.03 circuits are present in a other reasons, such as BS 7671:2008 has

R 1666
particular area and are protection against fire, requirements for the sizing
protected by different thermal stresses in of supplementary
protective devices/types, etc., equipment, etc., can be equipotential bonding

resistance of 1666 will


Therefore, a maximum the worst case characteristic omitted. conductors in Regulation
should be used. Regulation 522.6.1 544.2, the table shown
ensure there is sufficient The IET publication, requires that the correct overleaf, fig. 2, will aid with
current to operate the RCD. Guidance Note 3, with the wiring system is selected for the choice of conductor.
Note that the touch voltage latest edition due for the application to minimize
may rise above 50 v; the imminent publication, the risk of damage arising WHERE SUPPLEMENTARY
value of 50 v is used as a advises that the resistance from mechanical stress, e.g. EQUIPOTENTIAL BONDING
constant in the formula to of supplementary by impact, abrasion, IS REQUIRED
ensure sufficient current is equipotential bonding penetration, tension or Ultimately, responsibility is

more than 0.05 . When


flowing to operate the RCD. conductors should be no compression during with the designer of the
installation, use or installation, who is a
Example 2 verifying supplementary maintenance. competent person, fully
Let's take the scenario that equipotential bonding Fundamentally, this aware of the installation
the protective device is a conductors, Regulation means that if there is a conditions and will use
BS EN 60898 Type B circuit- 612.2.1 requires that a danger of a metallic part their skill and engineering

IET Wiring Matters | Summer 08 | www.theiet.org


BONDING

10
Minimum cross-sectional area of supplementary bonding conductors appliance, designed to be protection by means of a
Size of
CPC Exposed-conductive- Exposed-conductive- Extraneous-conductive- connected to the means of 30 mA RCD
part to extraneous- part to exposed- part to extraneous- earthing at all times of (iii) All extraneous-
mm conductive-part conductive-part (1)
conductive-part
operation conductive-parts of the
mechanically mechanically mechanically mechanically mechanically mechanically location are effectively
protected protected protected protected protected protected
mm mm mm mm mm mm Extraneous-conductive-part connected to the protective
1.0 1.0 4.0 1.0 4.0 2.5 4.0 A conductive part liable to equipotential bonding
1.5 1.0 4.0 1.5 4.0 2.5 4.0 introduce a potential,
generally Earth potential, Section 702 - Swimming
2.5 1.5 4.0 2.5 4.0 2.5 4.0
and not forming part of the Pools and Other Basins
4.0 2.5 4.0 4.0 4.0 2.5 4.0
electrical installation. Supplementary
6.0 4.0 4.0 6.0 6.0 2.5 4.0
An example of an equipotential bonding will
10.0 6.0 6.0 10.0 10.0 2.5 4.0
extraneous-conductive-part is connect all extraneous-
16.0 10.0 10.0 16.0 16.0 2.5 4.0 a metallic water pipe which conductive-parts in zones 0,
is buried in the ground 1 and 2 to the protective
Figure 2: Minimum cross-sectional area of supplementary
equipotential bonding and subsequently enters conductors of exposed-
a building conductive-parts of
equipment situated in these
To generalise, as stated zones, in Regulation
earlier, supplementary 702.411.3.3.
equipotential bonding is Regulation 702.522.21
required where a requires that in zones 0, 1
disconnection time can not and 2, any metallic sheath
be met or where a Special or metallic covering of a
Installation or Location, i.e. wiring system shall be
those in Part 7 of connected to the
BS 7671:2008, has an supplementary
increased risk of electric equipotential bonding. The
shock. The following note at the end of this
Sections of Part 7 directly Regulation states that cables
reference supplementary should preferably be
equipotential bonding - note installed in conduits made
that other measures will be of insulating material. This
necessary to meet the is a relaxation from the
requirements of 16th Edition as Regulation
BS 7671:2008. 602-06-01 states that in zones
Figure 3: Application of supplementary equipotential bonding
A and B, a surface wiring
Section 701 - Locations system shall not employ
judgement to design the equipment and all containing a Bath or metallic conduit or metallic
installation accordingly. extraneous-conductive- Shower trunking or an exposed
parts. Section 701 now has a metallic cable sheath or an
Where supplementary relaxed requirement for exposed earthing or
equipotential bonding is Exposed-conductive-part supplementary bonding conductor.
required, it may involve the Conductive part of equipotential bonding when Regulation 702.55.1
entire installation, a part of equipment which can be the following three permits the installation of
the installation, an item of touched and which is not conditions of Regulation an electric heating unit
equipment or a location, etc. normally live, but which can 701.415.2 are met; embedded in the floor,
Where supplementary become live when basic (i) All final circuits of the provided that it
equipotential bonding is insulation fails. location comply with the incorporates an earthed
installed, it should include An example of an exposed- requirements for automatic metallic sheath, is covered
all simultaneously conductive-part is the disconnection by an embedded earthed
accessible exposed- metallic outer case of an (ii) All final circuits of the metallic grid and connected
conductive-parts of fixed electrical class I location have additional to the supplementary

IET Wiring Matters | Summer 08 | www.theiet.org


BONDING
11
equipotential bonding of conductive-parts of fixed
the location (other equipment and the
requirements are also conductive parts of the
necessary). location where automatic
disconnection of the supply
Section 705 - Agricultural is the protective measure.
and Horticultural Premises Part e) of this Regulation
Supplementary requires that where the
equipotential bonding is protective measure is PELV,
required to connect all equipotential bonding is
exposed-conductive-parts provided between all
and extraneous-conductive- exposed-conductive-parts,
parts that can be touched by all extraneous-conductive-
livestock, the metal grid laid parts inside the conducting
in the floor, concrete location with restricted
reinforcement in general or movement, and the
reinforcement of cellars for connection of the PELV
liquid manure (other system to Earth.
requirements are also
necessary), in Regulation Section 740 - Temporary
705.415.2.1. Electrical Installations for
Regulation 705.544.2 Structures, Amusement
requires that Devices and Booths at
supplementary Fairgrounds, Amusement
equipotential bonding Parks and Circuses
conductors are protected Regulation 740.415.2.1
against mechanical damage reiterates the requirements
and corrosion and chosen to of 705.415.2.1, shown above Figure 4: Application of supplementary equipotential bonding in
avoid electrolytic effects, under Agricultural and a Special Location
with examples given as: Horticultural Premises.
(i) Hot-dip galvanized steel 411.3.2.6 and 415.2. Other Seventeenth Edition
strip with dimensions of at CONCLUSION installations, such as those Guidance Note 3 -
least 30 mm 3 mm To summarise, of hazardous locations, will Inspection and Testing
(ii) Hot-dip galvanized supplementary have further requirements  PD CLC/TR 50404:2003
round steel of at least 8 mm equipotential bonding is for supplementary Electrostatics Code of
diameter required where a equipotential bonding to practice for the avoidance
(iii) Copper conductor disconnection time can not reduce the risks of sparking of hazards due to static
having a minimum cross- be met or where a Special due to the build up of static electricity
sectional area of 4 mm2. Installation or Location, i.e. electricity, for example. In  BS EN 60079 Electrical
Other suitable materials those in Part 7 of such installations, the apparatus for explosive
may be used. BS 7671:2008, has an requirements of BS 7671 gas atmospheres (suite of
increased risk of electric will be supplemented by the standards)
Section 706 - Conducting shock. Confusion created by requirements or  BS EN 6007914:2003
Locations with Restricted Regulation 413-7 of the 15th recommendations of other Electrical apparatus for
Movement Edition of the IEE Wiring British Standards or by the explosive gas
In a conducting location Regulations, which requirements of the person atmospheres - Part 14:
with restricted movement, effectively required ordering the work. Electrical installations in
Regulation 706.410.3.10 supplementary hazardous areas (other
requires that a supply to equipotential bonding to FURTHER INFORMATION than mines) 
fixed equipment shall connect all accessible  BS 7671:2008
incorporate supplementary metallic parts within the Requirements for Thanks to Richard Rennie
equipotential bonding is equipotential zone, has been Electrical Installations, of Yorkshire Water for the
used to connect exposed- clarified by Regulations IEE Wiring Regulations, image used.

IET Wiring Matters | Summer 08 | www.theiet.org

También podría gustarte