The modal system analysis allows for a damping strategy the residues chart
much deeper analysis by not only in- shows the location(s) for a power sys-
terpreting the eigenvalues, but by also tem stabilizer (PSS). In this example,
analyzing the eigenvectors of a system. other devices that were studied for
The latter are automatically calculated comparison include a static Var com-
during the modal analysis: pensator (SVC), and a thyristor-
controlled static compensator (TCSC).
The right eigenvector gives infor-
mation about the observability of
oscillations
The left eigenvector gives infor-
mation about the controllability
Figure 5: Results of the eigenvalue analysis
The combination of the right and Figure 3: Eigenvectors of an inter-area mode (Details: Documentation of specific values)
left eigenvectors (residues) indi-
cates the location of the damping- Application example
controllers Figures 4 to 7 show the results of an
The damping of inter-area oscillations Eigenvalue calculation/modal analysis
is very important. The oscillations can for the ENTSO-E CGMES 1-machine
be damped when extra energy is in- benchmark network with or without
jected into the system, which instan- stabilizer (PSS).
taneously decelerates the system,
and/or vice-versa when extra energy is
consumed in the system.